Bulletin Number 825-P
Bulletin 825-P
Modular Protection System
The Bulletin 825-P Modular Protection System for motors
offers a compact, modular design that uniquely allows an
installer to configure a devices functional capabilities to
match the application requirements. Flexibility is also afforded
by accommodating future expansion of the system as the
application requirements grow. Ease of installation is
provided through pluggable options and accessories. Finally,
this next generation design offers greater capabilities with
the option of full metering for line voltage and power
monitoring in addition to expanded RTD monitoring.
Product Profile
System Overview
Basic Unit
0.5 ... 5000A Current Range
Suitable for Low- and Medium-Voltage Applications
Built-in Keypad and Backlit 2-Line LCD
Test / Reset Button
Status LEDs
Front accessible RS 232 port
Wide Supply Voltage Range (110...240V AC/DC)
Three Output Relays
Two Configurable Inputs
PTC thermistor Input
Core Balance Current Transformer Input
Fiber Optic Port for Remote RTD Scanner
Three option card slots
NEMA 12 (IP65) Housing
Converter Modules
Compact Three-Phase current transformer modules
Provides electrical isolation
Six current ranges
0.5 ... 2.5 A
2.5 ... 20 A
20 ... 180 A
160 ... 630 A
Compatibility with MCS PLUS Bulletin 100-D contactors
Core Balance Current Transformer
Sensitive, low level ground fault detection
100:1 ratio
110 mm window opening
Note: The 825-P is compatible with core balance current
transformer ratios of 1:1 to 2000:1.
RTD Scanner Module
12-channel inputs
Compatible with 100 Platinum, 100 Nickel, 120 Nickel,
and 10 Copper type RTDs
Can be remote mounted near the motor, simplifying wiring
Class 1, Division 2, Group T4A rated
Noise immune fiber optic connection to the Basic Unit
Channels are individually configurable for RTD type and
location (winding, bearing, ambient, or other).
Option Cards
Voltage Input
Input terminations for VA, VB, VC and VN
Enables voltage and power measurement and related
protection functions
Accommodates potential transformers for levels
exceeding 250V AC
DeviceNet or Modbus Communications
Direct network access for control and monitoring
DeviceNet communications card features DeviceLogix
component technology for enhanced control capability
DeviceNet communication card provides compatibility with
the IntelliCENTER software
Expansion I/O
Three Configurable Inputs
Four Auxiliary Relay Outputs
4 ... 20mA Isolated Analog Output
The 825-P Modular Protection System
is a key component to Bulletin 1500
medium voltage controllers.
Comprehensive Protection
The 825-P Modular Protection System offers in-depth motor protection coverage by monitoring the critical elements of motor current, line
voltage and temperature. High resolution settings allow the installer to configure a precise envelope of protection to achieve maximum
motor utilization while avoiding damage and downtime.
ANSII No.
Current Elements
51
46
50G/51G
37
48
50
47
81
86
Voltage Elements
27
59
47
81
Function
Thermal Overload
Current Imbalance / Phase Loss
Ground Fault
Undercurrent (Load Loss)
Overcurrent (Load Jam)
Short Circuit
Phase Reversal
Frequency
Overload Lockout
Undervoltage
Overvoltage
Phase Reversal
Frequency
ANSII No.
Function
Temperature Elements
49
PTC Thermistor
49
Stator STD
38
Bearing RTD
Ambient and Other RTD
Power Elements
37
Underpower
55/78
Power Factor
Reactive Power
Motor Starting Elements
66
Starts / Hour
Start Time Monitoring
14
Speed Switch Monitoring
19
Reduced Voltage Starting
48
Incomplete Start
Note: Voltage and Power elements are only available with the installation of the Voltage Input option card.
Full Function Metering
The 825-P Modular Protection System offers in-depth motor protection coverage by monitoring the critical elements of motor current, line
voltage and temperature. High resolution settings allow the installer to configure a precise envelope of protection to achieve maximum
motor utilization while avoiding damage and downtime.
Current Elements
Voltage Elements
Power Elements
Thermal Elements
Phase Currents
Average Current
% Motor Load
Ground Fault Current
Line-Line Voltages
Avg. Line-Line Voltage
Line-Neutral Voltages
Voltage Imbalance
System Frequency
Real Power (kW)
Reactive Power (kVAR)
Power Factor
Phase Angle
% Thermal Capacity Utilization
RTD Values
Note: Voltage and Power elements are only available with the installation of the Voltage Input option card.
Statistical Values
The 825-P Modular Protection System provides the following valuable statistical values of motor operation:
Elapsed time of operation
Stopped time
Percent of time running
Number of starts
Number of emergency starts
Date and time of last trip reset
Historical Data
The 825-P Modular Protection System saves records for the five most recent trip events. Each trip event is summarized
with record of the following prior to trip data capture:
Event day and time recording
Trip and warning identification
Phase and ground current amplitude and angle values
Voltage amplitude and angle values
Ordering Information
Description
Cat. No.
Basic Unit
Converter Module
825-PD
0.5 ... 2.5A
2.5 ... 20A
20 ... 180A
160 ... 630A
825-MCM2
825-MCM20
825-MCM180
825-MCM630N
825-CBCT
825-PR12D
Core Balance Current Transformer (100:1)
RTD Scanner Module
Option Cards
Voltage Input
Expansion I/O (120V Inputs)
Expansion I/O (24V Inputs)
DeviceNet Communications
Modbus Communications
825-PVS
825-PIOD
825-PIOR
825-PDN
825-PMB
MPS Explorer Sofware
Operation Instructions
Quick Start Guide
Basic Unit User Manual
DeviceNet Card
825-QS001_-EN-P
825-UM004_-EN-P
825-UM005_-EN-P
A basic system requires a basic unit plus one converter module.
Please contact your local Allen-Bradley distributor.
Detailed operation instructions ship separately from the product. Please contact your local Allen-Bradley distributor to obtain printed copies.
Function Overview
Trip Level
Setting Range
Trip Delay
Setting Range
Warning Level
Setting Range
Motor FLA (le)
0.5...5000A
Locked Rotor Current
2.5...12 x le
50...100% TCU
Locked Rotor Time
1...600 sec
Short Circuit
4...12 x le
0.00...5.00 sec
4...12 x le
0.1...1.0 x le
0.00...5.00 sec
0.1...1.0 x le
0.01...25A
0.00...5.00 sec
0.01....25A
Jam
1.0....6.0 x le
0.00...5.00 sec
1.0...6.0 x le
Undercurrent
0.1...1.0 x le
0.0...120.0 sec
0.1...1.0 x le
5...80%
0....240 sec
5...80%
1....240 sec
0...250 C
Disable, Enable
Undervoltage
0.60...1.00 x Vnom
0...120 sec
0.6...1.0 x Vnom
Overvoltage
1.00...1.20 x Vnom
0...120 sec
1.00...1.20 x Vnom
Underpower
1...25,000 kW
0...240 sec
1...25,000 kW
Power Factor
0.05...0.99
0...240 sec
0.05...0.99
1...25,000 kVAR
0...240 sec
1...25,000 kVAR
45...55 / 55...65 Hz
0...240 sec
45...55 / 55...65 Hz
1...15
0.240 sec
Description
Ground Fault (Residual)
Ground Fault (Core Balance)
Current Imbalance
Start Monitoring
RTD Temp
Phase Reversal
VAR
Frequency
Start Inhibit (Starts/Hr)
Speed Switch
0...250 C
Main Circuits
825-MCM Converter Modules
Rated Operating
Voltage Ue
IEC
CSA/UL
Rated Impulse
Strength Uimp
Operating Current
Range (A)
825-MCM2
825-MCM5
400V AC
240V AC
2.5kV
825-MCM180
825-MCM420
825-MCM630N
1,000V AC
600C AC
8kV
825-MCM20
690V AC
600V AC
6kV
825-MCM2
825-MCM5
825-MCM20
825-MCM180
825-MCM420
825-MCM630N
0.5-2.5
3
1-5
6
2.5-20
24
20-180
216
160-420
504
160-630
756
30
60
240
1350
3400
4600
Rated Continuous
Thermal Current (A)
Rated Saturation
Current
Rated Frequency
50/60 Hz 3 Hz
Voltage Input Option Card
Inputs
Rated Operating Voltage (Ue)
250V AC max
Operating Range
0.80 ... 1.1 Ue
Rated Continuous Voltage
300V AC
Rated Insulation Voltage (Ui)
300V AC
Rated Impulse Strength (Uimp)
4kV
Rated Frequency
50/60 Hz (5 Hz)
Control Circuits
Supply
Supply Rated Supply Voltage (Us) 110 ... 240V AC
110 ... 250V DC
Operating Range
0.80 ... 1.1 Us
Rated Frequency (V AC)
50/60 Hz (5 Hz)
Max. Power Consumption
AC: 15VA, DC: 15 W
Output Relays
Type of Contacts
Trip
Aux1 ... Aux 6
Form C SPDT
Form A SPST - NO
Rated Operating Voltage (Ue)
IN1 and IN2
24V AC/DC
IN3, IN4 and IN5
120V AC/DC
Operating Range
0.80 ... 1.1 Ue
Rated Insulation Voltage (Ui)
300V AC
Rated Impulse Strength (Uimp)
4kV
Rated Frequency (AC)
50/60 Hz (5 Hz)
On-State Voltage
15V
79V
On-State Current (turn-on)
2mA
2mA
Steady State Current (max)
15mA
15mA
Off-State Voltage
5V
20V
Off-State Current
0.5 mA
1 mA
Transition Voltage
5...15V
20...79V
PTC Thermistor Input
Type of Control Unit
Mark A
Max. No. of Sensors in Series
Max. Cold Resistance of PTC
Sensor Chain
1500
Trip Resistance
3400 150
Reset Resistance
1500 ... 1650
Short Circuit Trip Resistance
25 10
Rated Insulation Voltage (Ui)
300V AC
Rated Operating Voltage (Ue)
240V AC
Rated Impulse Strength (Uimp)
4kV
Mechanical Ratings
Rated Thermal Current (Ithe)
5A
Environmental
Rated Operating Current (Ie)
120V AC
240V AC
3A
1.5A
Contact Rating Designation
B300
Utilization Category
AC15
Contact Reliability
5 mA @ 17V
Ambient Temperature Storage
Operating (open)
-40...+85C (-40...+185F)
-20...+60C (-4...+140F)
Humidity (Operating)
5...95% Non-condensing
Maximum Altitude
2000 m
Vibration (per IEC 68-2-6)
3G
Shock (per IEC 68-2-27)
30G
Pollution Degree
Protection Class
825-P
825-MCM
IP65
IP40
Electromagnetic Compatibility
Control Terminals
Terminal Screw
M3
Cross Section (Stranded/Solid)
1 x 0.14...2.5 mm2
1 x 26...12 AWG
Torque
0.79 Nm/7 lb-in
Degree of Protection
IP20
Electrostatic Discharge Immunity
Test Level
Performance Criteria
RF Immunity
Test Level
RTD Scanner Module
8kV Air Discharge
Performance Criteria
10V/m
1
Supply
Rated Supply Voltage (Us)
110/240V AC
Operating Range
0.80 ... 1.2 Us
Rated Frequency
50/60 Hz (5 Hz)
Max. Power Consumption
5 VA
Rated Insulation Voltage (Ui)
300V AC
Rated Impulse Strength (Uimp)
4kV
Surge Immunity
Ambient Temperature Storage
-40...+85C (-40...+185F)
Performance Criteria
Operating (open)
-20...+60C (-4...+140F)
Emissions
Humidity (Operating)
5...95%, Non-condensing
Radiated Emissions
Class A
Maximum Altitude
2000 m
Conducted Emissions
Class A
Vibration (per IEC 68-2-6)
3G
Shock (per IEC 68-2-27)
30G
Pollution Degree
Protection Class
IP 40
Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria
Test Level
Environmental
Environment 2.
12
Standards
Type
3-wire
CSA C22.2 No. 14
Compatibility
CU10
NI100
NI120
PT100 (per IEC 60751: 1983)
EN 60947-4-1
Accuracy
Open Circuit Detection
> 250C
Short Circuit Detection
< -50C
Degree of Protection
IP20
2kV L-E
1kV L-L
1
degradation or loss of performance.
Number of input channels
-50...250 C
2C
Performance criteria 1 requires the DUT to experience no
Inputs
Range
4kV (Power)
2kV (Control and Comms)
EN 60947-5-1
UL 508
Basic Connection Diagram
GROUND CT
L1
M
3
L2
L3
5
3
MCM
L1
L2
L3
MCM
RTD SCANNER
T1
T2
S1
S2
VOLTAGE INPUT OPTION
BK
VBU CAN_L
DNET
OPTION SH DRAIN
WH CAN_H
RD
V+
33
AUX 3
34
43
EXPANSION
I/O
OPTION
AUX 4
44
53
1
2
MOD3
BUS
OPTION 4
5
AUX 5
54
63
+TX
-TX
+RX
-RX
SH
A1 +
A2
825-P
MODULAR
PROTECTION
SYSTEM
RELAY
ANALOG
OUTPUT
I+
COM IN3
IN4
Y2-
Y22
96
98
13
14
IN5
IN1
I-
120/240V AC/DC
95
TRIP
AUX1/
ALARM
AUX 6
64
COM
23
IN2
AUX2
Y24 Y26
Rx
Y12
Y1-
Y14
24
500m MAX
FIBER OPTION
RTD1
5
RTD2
10 11 12 13 14 15 16 17 18
RTD3
RTD4
RTD5
RTD6
23
120V AC
24
825-P RTD SCANNER
RTD7
RTD8
RTD9
27 28 29 30 31 32 33 34 35
RTD10
25
RTD11
RTD12
240V AC
26
36 37 38 39 40 41 42 43 44
[Link]
Corporate Headquarters
Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201
Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Headquarters for Dodge and Reliance Electric Products
Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433
Europe/Middle East/Africa: Rockwell Automation, Herman-Heinrich-Gossen-Strasse 3, 50858 Kln, Germany, Tel: 49 (0) 2234 379410, Fax: 49 (0) 2234 3794164
Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 6356 9077, Fax: (65) 6356 9011
Publication 825-PP011B -EN-P March 2005
Supercedes Publication 825-PP011A-EN-P April 2003
Copyright 2004 Rockwell Automation, Inc. All rights reserved. Printed in USA.