KOMP Simetris PDF
KOMP Simetris PDF
1 & 2
Presented at the
27th Annual
HANDS ON RELAY SCHOOL
March 15 - 19, 2010
Washington State University
Pullman, Washington
Introduction
The electrical power system normally operates in a balanced three-phase sinusoidal steady-state
mode. However, there are certain situations that can cause unbalanced operations. The most
severe of these would be a fault or short circuit. Examples may include a tree in contact with a
conductor, a lightning strike, or downed power line.
In 1918, Dr. C. L. Fortescue wrote a paper entitled Method of Symmetrical Coordinates
Applied to the Solution of Polyphase Networks. In the paper Dr. Fortescue described how
arbitrary unbalanced 3-phase voltages (or currents) could be transformed into 3 sets of balanced
3-phase components, Fig I.1. He called these components symmetrical components. In the
paper it is shown that unbalanced problems can be solved by the resolution of the currents and
voltages into certain symmetrical relations.
Fig I.1
By the method of symmetrical coordinates, a set of unbalanced voltages (or currents) may be
resolved into systems of balanced voltages (or currents) equal in number to the number of phases
involved. The symmetrical component method reduces the complexity in solving for electrical
quantities during power system disturbances. These sequence components are known as
positive, negative and zero sequence components, Fig I.2
Fig I.2
The purpose of this paper is to explain symmetrical components and review complex algebra in
order to manipulate the components. Knowledge of symmetrical components is important in
performing mathematical calculations and understanding system faults. It is also valuable in
analyzing faults and how they apply to relay operations.
1. Complex Numbers
The method of symmetrical components uses the commonly used mathematical solutions applied
in ordinary alternating current problems. A working knowledge of the fundamentals of algebra
of complex numbers is essential. Consequently this subject will be reviewed first.
Any complex number, such as a + jb , may be represented by a single point p, plotted on a
Cartesian coordinates, in which a is the abscissa on the x axis of real quantities and b the
ordinate on the y axis of imaginary quantities. This is illustrated in Fig. 1.1
Fig. 1.1
Referring to Fig. 1.1, let r represent the length of the line connecting the point p to the origin
and the angle measured from the x-axis to the line r. It can be observed that
a = r cos
b = r sin
(1.1)
(1.2)
2. Properties of Phasors
A vector is a mathematical quantity that has both a magnitude and direction. Many quantities in
the power industry are vector quantities. The term phasor is used within the steady state
alternating linear system. It is used to avoid confusion with spatial vectors: the angular position
of the phasor represents position in time, not space. In this document, phasors will be used to
document various ac voltages, currents and impedances.
A phasor quantity or phasor, provides information about not only the magnitude but also the
direction or angle of the quantity. When using a compass and giving directions to a house, from
a given location, a distance and direction must be provided. For example one could say that a
house is 10 miles at an angle of 75 degrees (rotated in a clockwise direction from North) from
where I am standing. Just as we dont say the other house is -10 miles away, the magnitude of
the phasor is always a positive, or rather the absolute value of the length of the phasor.
Therefore giving directions in the opposite direction, one could say that a house is 10 miles at an
angle of 255 degrees. The quantity could be a potential, current, watts, etc.
Phasors are written in polar form as
Y = Y
(2.1)
= Y cos + j Y sin
(2.2)
where Y is the phasor, Y is the amplitude, magnitude or absolute value and is the phase angle
or argument. Polar numbers are written with the magnitude followed by the symbol to
indicate angle, followed by the phase angle expressed in degrees. For example Z = 11090o .
This would be read as 110 at an angle of 90 degrees. The rectangular form is easily produced by
applying Eq. (2.2)
The phasor can be represented graphically as we have demonstrated in Fig. 1.1, with the real
components coinciding with the x axis.
When multiplying two phasors it is best to have the phasor written in the polar form. The
magnitudes are multiplied together and the phase angles are added together. Division, which is
the inverse of multiplication, can be accomplished in a similar manner. In division the
magnitudes are divided and the phase angle in the denominator is subtracted from the phase
angle in the numerator.
Example 2.1
Multiply A B where A = 535o and B = 345o .
Solution
A B = 535o 345o = (5 3) 35o + 45o
= 1580o
Example 2.2
Solve
C
where C = 1535o and D = 350o .
D
Solution
C 1535o 15
= 35o 50o
=
o
D 350
3
o
= 5 15
j 3 = 1270o = j
j = 1 90o
Example 3.1
Compute jA where A = 1060o .
Solution
jA = 190o (1060o )
= 10150o
Notice that multiplication by the j operator rotated the Phasor A by 90o , but did not change the
magnitude. Refer to Fig. 3.1
(a) A
jA
(b) j A
Fig. 3.1. j effects
In a similar manner the a operator is defined as unit vector at an angle of 120o, written as
a = 1120o . The operator a2, is also a unit vector at an angle of 240o, written a 2 = 1240o .
Example 3.2
Compute aA where A = 1060o .
Solution
aA = 1120o (1060o )
= 10180o
(a) A
aA
(b) j A
Fig. 3.2. a effects
Table 3.2 - Properties of the vector a
1 = 1.0 + j 0.0
a = 1120o
a 2 = 1240o
a 3 = 1360o = 10o
1 + a2 + a = 0
a + a 2 = 1
1 + a = 330o
1 + a 2 = 3 30o
a a2 = j 3
a2 a = j 3
1 a = 3 30o
1 a 2 = 330o
Fig. 4.1
VLL = 3VLN
(4.1)
(4.2)
I L = I
In a Delta connected system the voltage measured from line to line equals the phase voltage. See
Fig. 4.2 and Eq. (4.3). The line current will equal the square root of three, 3 , times the phase
current, see Eq. (4.4)
IL
I
VLL
Fig. 4.2
VLL = V
(4.3)
I L = 3I
(4.4)
(4.5a)
P = 3VLL I L cos
(4.5b)
Q = 3VLL I L sin
(4.5c)
where S is the apparent power or complex power in volt-amperes (VA). P is the real power in
Watts (W, kW, MW). Q is the reactive power in VARS (Vars, kVars, MVars).
Device parameters tend to fall into a relatively narrow range, making erroneous values
conspicuous.
Using this method all quantities are expressed as ratios of some base value or values.
The per-unit equivalent impedance of any transformer is the same when referred to either
the primary or the secondary side.
The per-unit impedance of a transformer in a three-phase system is the same regardless of
the type of winding connections (wye-delta, delta-wye, wye-wye, or delta-delta).
The per-unit method is independent of voltage changes and phase shifts through
transformers where the base voltages in the winding are proportional to the number of
turns in the windings.
The per-unit system is simply a scaling method. The basic per-unit scaling equation is
per unit =
actual _ value
base _ value
(5.1)
The base value always has the same units as the actual value, forcing the per-unit value to be
dimensionless. The base value is always a real number, whereas the actual value may be
complex. The subscript pu will indicate a per-unit value. The subscript base will indicate a
base value, and no subscript will indicate an actual value such as Amperes, Ohms, or Volts.
The first step in using per-unit is to select the base(s) for the system.
Sbase = power base, in VA. Although in principle Sbase may be selected arbitrarily, in practice it is
typically chosen to be 100 MVA.
Vbase = voltage base in V. Although in principle Vbase is also arbitrary, in practice Vbase is equal
to the nominal line-to-line voltage. The term nominal means the value at which the system was
designed to operate under normal balanced conditions.
From Eq. (4.5) it follows that the base power equation for a three-phase system is:
S3base = 3Vbase I base
(5.2)
S 3base
3Vbase
Because S3base can be written as kVA or MVA and voltage is usually expressed in kilo-volts, or
kV, current can be written as:
kVAbase
amperes
3kVbase
Solving for base impedance:
I base =
(5.3)
Z base =
2
Vbase Vbase
=
I base Sbase
Z base =
2
kVbase
x1000
ohms
kVAbase
(5.4a)
Z base =
2
kVbase
ohms
MVAbase
(5.4b)
or
Given the base values, and the actual values: V = IZ , then dividing by the base we are able to
calculate the pu values
V
IZ
=
V pu = I pu Z pu
Vbase I base Z base
After the base values have been selected or calculated, then the per-unit impedance values for
system components can be calculated using Eq. (5.4b)
Z pu =
Z () MVAbase
Z ()
=
2
Z base kVbase
(5.5a)
or
kVAbase
Z ()
Z pu =
2
1000 kVbase
(5.5b)
per unit =
percent _ value
100
(5.6)
It is frequently necessary, particularly for impedance values, to convert from one (old) base to
another (new) base. The conversion is accomplished by two successive application of Eq. (5.1),
producing:
old
new
old Z base
new
= Z pu
Z pu
Z base
old
new
Substituting for Z base
and Z base
and re-arranging the new impedance in per-unit equals:
new
pu
=Z
old
pu
old
new
kVAbase
kVbase
new
old
kVA
kV
base
base
(5.7)
In most cases the turns ratio of the transformer is equivalent to the system voltages, and the
equipment rated voltages are the same as the system voltages. This means that the voltagesquared ratio is unity. Then Eq. (5.9) reduces to
new
new
old MVAbase
Z pu
= Z pu
old
MVAbase
(5.8)
Example 5.1
A system has Sbase = 100 MVA, calculate the base current for
a) Vbase = 230 kV
b) Vbase = 500 kV
Solution
kVAbase
Using Eq. (5.3) I base =
amperes
3kVbase
1000 100
amperes = 251A
a) I base =
3 230
b) I base =
1000 100
amperes = 115.5 A
3 500
Example 5.2
A 900 MVA 525/241.5 autotransformer has a nameplate impedance of 10.14%
a) Determine the impedance in ohms, referenced to the 525 kV side.
b) Determine the impedance in ohms, referenced to the 241.5 kV side
Solution
First convert from % to pu.
Z%
= 0.1014
Zpu =
100
2
kVbase
; therefore
MVAbase
a) Z 525kV = 0.1014
= 31.05
5252
900
b) Z 241.5 kV = 0.1014
= 6.57
241.52
900
A check can be made to see if the high-side impedance to the low-side impedance equals
the turns ratio squared.
31.05
= 4.726
6.57
525
= 4.726
241.5
10
6. Sequence Networks
Refer to the basic three-phase system as shown in Fig. 6.1. There are four conductors to be
considered: a, b, c and neutral n.
Network A
Ia
Ib
Ic
Network B
In
Fig. 6.1
The phase voltages, V p , for the balanced 3 case with a phase sequence abc are
Van = Va = V p 0o
(6.1a)
Vbn = Vb = V p 120
(6.1b)
(6.1c)
(6.2a)
Vbc = Vb Vc = VLL 90
Vca = Vc Va = VLL 150
(6.2b)
(6.2c)
Equation (6.1) and (6.2) can be shown in phasor form in Fig. 6.2.
Fig. 6.2
11
There are two balanced configurations of impedance connections within a power system. For the
wye case, as shown in Fig. 4.1, and with an impedance connection of Z , the current can be
calculated as
Ia =
V
V
= P 0o
ZY ZY
(6.3)
Where is between 90o and + 90o . For greater than zero degrees the load would be
inductive ( I a lags Va ). For less than zero degrees the load would be capacitive ( I a leads Va ).
The phase currents in the balanced three-phase case are
I a = I p 0 o
(6.4a)
I b = I p 120o
(6.4b)
I c = I p 240o
(6.4c)
Fig. 7.1
12
Consider the symmetrical system of phasors in Fig. 7.2. Being balanced, the phasors have equal
amplitudes and are displaced 120o relative to each other. By the definition of symmetrical
components, V b1 always lags V a1 by a fixed angle of 120o and always has the same magnitude
as V a1 . Similarly V c1 leads V a1 by 120o. It follows then that
Va1 = Va1
(7.1a)
(7.1b)
(7.1c)
Where the subscript (1) designates the positive sequence component. The system of phasors is
called positive sequence because the order of the sequence of their maxima occur abc.
Similarly, in the negative and zero sequence components, we deduce
Va 2 = Va 2
(7.2a)
(7.2b)
Vc 2 = (1240 )Va 2 = a Va 2
(7.2c)
Va 0 = Va 0
Vb 0 = Va 0
Vc 0 = Va 0
(7.3a)
(7.3b)
(7.3c)
Where the subscript (2) designates the negative sequence component and subscript (0) designates
zero sequence components. For the negative sequence phasors the order of sequence of the
maxima occur cba, which is opposite to that of the positive sequence. The maxima of the
instantaneous values for zero sequence occur simultaneously.
Fig.7.2
In all three systems of the symmetrical components, the subscripts denote the components in the
different phases. The total voltage of any phase is then equal to the sum of the corresponding
components of the different sequences in that phase. It is now possible to write our symmetrical
13
components in terms of three, namely, those referred to the a phase (refer to section 3 for a
refresher on the a operator).
Va = Va 0 + Va1 + Va 2
Vb = Vb 0 + Vb1 + Vb 2
Vc = Vc 0 + Vc1 + Vc 2
(7.4a)
(7.4b)
(7.4c)
(7.5a)
(7.5b)
(7.5c)
(7.6a)
Vb = V0 + a V1 + aV2
(7.6b)
Vc = V0 + aV1 + a 2V2
(7.6c)
V0 =
(7.7a)
(7.7b)
(7.7c)
(7.8a)
I b = I 0 + a 2 I1 + aI 2
(7.8b)
I c = I 0 + aI1 + a 2 I 2
(7.8c)
(7.9a)
(7.9b)
(7.9c)
14
The unbalanced system is therefore defined in terms of three balanced systems. Eq. (7.6) may be
used to convert phase voltages (or currents) to symmetrical component voltages (or currents) and
vice versa [Eq. (7.7)].
Example 7.1
Given Va = 553o , Vb = 7 164 o , Vc = 7105o , find the symmetrical components. The
phase components are shown in the phasor form in Fig. 7.3
Vc
Va
105o
53o
-164o
Unbalanced condition
Vb
Fig. 7.3
Solution
Using Eq. (7.7)
Solve for the zero sequence component:
1
Va 0 = (Va + Vb + Vc )
3
1
= 553o + 7 164o + 7105o
3
= 3.5122o
) (
15
))
) (
))
Va2
Vc2
Vb2
Negative Sequence
Va1
Vb1
Va0
Vb0
Vc0
Zero Sequence
Positive Sequence
Fig. 7.4
Using Eq. (7.6) the phase voltages can be reconstructed from the sequence components.
Example 7.2
Given V0 = 3.5122o , V1 = 5.0 10o , V2 = 1.992o , find the phase sequence
components. Shown in the phasor form in Fig. 7.4
Solution
Using Eq. (7.6)
16
Vc1
Vc2
Va
Va0
Va2
Vb
Va1
Vb0
Vb1
Vb2
Fig. 7.5
Notice in Fig. 7.5 that by adding up the phasors from Fig. 7.4, that the original phase, Fig. 7.3
quantities are reconstructed.
17
Given a system, represented in Fig. 8.1, we can construct general sequence equivalent
circuits for the system. Such circuits are indicated in Fig. 8.2.
Fig. 8.1
Z0
Z1
I0
+
V0
10 o
V1
V2
-
I2
+
Z2
I1
Fig. 8.2
Each of the individual sequence may be considered independently. Since each of the sequence
networks involves symmetrical currents, voltages and impedances in the three phases, each of
the sequence networks may be solved by the single-phase method. After converting the power
system to the sequence networks, the next step is to determine the type of fault desired and the
connection of the impedance sequence network for that fault. The network connections are listed
in Table 8.1
The system shown in Fig. 8.1 and simplified to the sequence network in Fig. 8.2 and will be used
throughout this section.
18
Example 8.1
Given Z 0 = 0.19990o pu , Z1 = 0.17590o pu ,
Z0
I0
+
V0
-
Z1
I1
+
V1
10o
Z2
10o
I1 =
j 0.175
= j 5.71
I2
+
V2
Fig 8.3
I a = 0 j 5.71 + 0 = 5.71 90 pu
o
Calculating the voltage drop, and referring to Fig. 8.3, the sequence voltages are
V0 = V2 = 0
Ib
V1 = 10 Z1I1
V1 = 1 j 0.175( j 5.71) = 0.0
= 0.0 pu
Ic
Vc
Vb Va
Ia
Fig 8.4
19
The per-unit value for the current and voltage would now be converted to actual values
using Eq. (5.6b) and knowing the base power and voltage for the given system.
The currents and voltages can be shown in phasor form in Fig. 8.4
Example 8.2
Given Z 0 = 0.19990o pu , Z1 = 0.17590o pu , Z 2 = 0.17590o pu , compute the fault
current and voltages for a Single line-to-ground fault. Note that the sequence impedances
are in per-unit. This means that the results for current and
voltage will be in per-unit.
Solution
Z0
I0
The sequence networks are interconnected in series, as
shown in Fig. 8.5
+
V0
-
Z1
I1
+
10o
I0 =
( j 0.199 + j 0.175 + j 0.175)
10o
V1
= j1.82 pu
Z2
I2
+
V2
I a = I 0 + I 0 + I 0 = 3I 0
I b = I 0 + a 2 I 0 + aI 0 = 0
I c = I 0 + aI 0 + a 2 I 0 = 0
Fig 8.5
20
Calculating the voltage drop, and referring to Fig. 8.5, the sequence voltages are
V0 = Z 0 I 0
V1 = V Z1I1
V2 = Z 2 I 2
Vc
Va
The phase voltages are converted from the sequence value using
Eq. (7.6).
Vb
Ia
Fig 8.6
Z0
I0
+
V0
-
Example 8.3
Given Z 0 = 0.19990o pu , Z1 = 0.17590o pu ,
Z1
I1
+
10 o
V1
-
Z2
V2
-
Fig 8.7
21
I2
I1 =
I 2 = + j 2.86 pu
I0 = 0
The phase current is converted from the sequence value using Eq. (7.8).
I a = 0 j 2.86 + j 2.86 = 0 pu
I b = 0 + a 2 ( j 2.86) + a( j 2.86) = 4.95 pu
I c = 0 + a( j 2.86) + a 2 ( j 2.86) = 4.95 pu
Calculating the voltage drop, and referring to Fig. 8.7, the sequence voltages are
V1 = V2
V2 = Z 2 I 2
= ( j1.75)( j 2.86)
= 0.5 pu
V0 = 0
The phase voltages are converted from the sequence value using Eq. (7.6).
Va = 0.0 + 0.5 + 0.5 = 1.0 pu
Vb = 0.0 + a 2 (0.5) + a(0.5) = 0.5 pu
Vc = 0.0 + a(0.5) + a 2 (0.5) = 0.5 pu
The per-unit value for the current and voltage
would now be converted to actual values using
Eq. (5.6b) and knowing the base power and
voltage for the given system.
Vc
Ic
Ib
Va
Vb
22
Fig 8.8
Example 8.4
Given Z 0 = 0.19990o pu , Z1 = 0.17590o pu , Z 2 = 0.17590o pu , compute the fault
current and voltages for a Double Line-to-Ground fault. Note that the sequence
impedances are in per-unit. This means that the solution for current and voltage will be
in per-unit.
Solution
The sequence networks are interconnected, as shown in Fig. 8.9
I1 = ( I 0 + I 2 )
I0
+
V0
-
Z1
V1
ZZ
Z1 + 0 2
Z0 + Z2
I1
+
10o
V1
Z2
I2
I1 = j 3.73 pu
Z2
+
I0 =
I1
(Z 0 + Z 2 )
V2
= + j1.75
Z0
I2 =
I1
(Z0 + Z 2 )
Fig 8.9
= + j1.99
The phase current is converted from the sequence value using Eq. (7.8).
23
Calculating the voltage drop, and referring to Fig. 8.9, the sequence voltages are
V0 = V1 = V2
V0 = Z 0 I 0
= ( j1.75)( j 0.199)
= 0.348 pu
The phase voltages are converted from the sequence value using Eq. (7.6).
Va = 0.348 + 0.348 + 0.348 = 1.044 pu
Vb = 0.348 + a 2 (0.348) + a(0.348) = 0 pu
Vc = 0.348 + a(0.348) + a 2 (0.348) = 0 pu
24
IR
Ib
Ic
Va
Fig 8.10
Fig 9.1a
Fig 9.1b
Fig 9.1c
25
Fig 9.2a
Fig 9.2b
Fig 9.2c
26
Fig 9.3a
Fig 9.3b
Fig 9.3c
27
Fig 9.1a
Fig 9.4b
Fig 9.4c
28
Using a directional ground distance relay it will demonstrated how sequential components are
used in the line protection. To determine the direction of a fault, a directional relay requires a
reference against which the line current can be compared. This reference is known as the
polarizing quantity. Zero sequence line current can be referenced to either zero sequence current
or zero sequence voltage, or both may be used. The zero sequence line current is obtained by
summing the three-phase currents. See Fig. 10.1
(I a + I b + I c ) = 3I 0 = I r
(10.1)
Va
Vb
Vc
29
V0 =
(10.2a)
(10.2a)
Example 10.1
Using the values obtained from example 8.2, calculate 3V0 .
Solution
Va = 0
Vb = 1.022238o pu
Vc = 1.022122o pu
The zero sequence voltage is 3.25180o pu . By connecting the value in the reverse gives 3V0
which equals 3.250o pu . Plotting this, we can show in phasor form what the relay sees, Ia
lagging 3V0 by the line angle. In this case resistance is neglected, therefore Ia lags by 90o.
(see Fig 10.3).
30
References
Blackburn, J. L., Protective Relaying: Principles and Applications, Mercel Dekker, Inc., New
York, 1987
Gross, Charles A., Power System Analysis, John Wiley & Sons, Inc., 1986
ABB, Protective Relaying Theory and Applications, Mercel Dekker, Inc., New York, 2004
Wagner, C. F. and Evans, R. D., Symmetrical Components, Krieger Publishing Company,
Florida, 1933
Lantz, Martin J., Fault Calculations for Relay Engineers, Bonneville Power Administration, 1965
31
2/23/2010
Agenda
Introductions
y Schedule:
y
Course Format
2/23/2010
Introductions
Instructor: Daniel Goodrich, PE
y 1986-2010: Engineer at Salt River Project,
Ph
Phoenix,
i AZ
y March 2010 to Present: Planning Engineer at
Bonneville Power Administration,Vancouver
Washington
y 10 years in System Protection (Transmission,
Distribution, and some Generation)
y Active participant in IEEE Power System Relay
Committee, 2005-2009
y And you areName, Utility/Business Affiliation,
Experience with Distribution Protection
Course Format
Theory
y Examples
y Questions
y Takeaways (watch for the T) and
reference material
y
2/23/2010
Outline
Configurations
y Comparison of Distribution and
Transmission Systems
y Class Scope
y Load shedding
y Substation feeder breakers
y Reclosing
y Fuse saving/sacrificing
y Cold Load Pickup
y
Outline Continued
Line Reclosers
y Sectionalizers
y Distribution Automation
y Distributed Generation
y
2/23/2010
2/23/2010
Radial Feeds
Lowest cost; older systems
y Feeders isolated by geography
y Fault location is very difficult
y
Substation
Feeder
Open--Looped System
Open
Reduced outage time
y Switching flexibility for both planned
maintenance and unplanned outages
y
Normally Closed
Switch
Substation A
Normally Open
Switch
S b t ti B
Substation
2/23/2010
Open--Looped Example
Open
From
NREL
2/23/2010
RELAY RELIABILITY
DEPENDABILITY
SECURITY
2/23/2010
Scope of Class
Step--up
Step
Transformer
Transmission
230kV
Subtransmission
69kV
Distribution
12kV
Industrial./Commercial
Building
Distribution Substation
69/12kv
16
2/23/2010
Load Shedding
For transmission system stability
y Typically is employed at the distribution
level
y Three types, in order of speed:
y
Under--frequency Example
Under
Coordinated by NERC
Frequency
% of Total Load
59.5
5%
59.1
1.5%
58.9
5%
58.7
7.5%
58.5
7%
58 3
58.3
7%
Total
35%
2/23/2010
Voltage
Time Delay
% Load Shed
50% of nominal
2 Seconds
5%
70%
80%
90%
10
10
2/23/2010
Under--voltage Restoration
Under
Automatic
y In stages; example:
y
Breakers
11
2/23/2010
Newer configurations
All functions in one relay
May add under
under-voltage
voltage, under
under-frequency
frequency, back
block/trip, breaker failure
12
2/23/2010
Distribution Coordination
Principles
1.
2
2.
3.
13
2/23/2010
Substation A
Substation A
Normally Open
Switch
New feeder
segment
Normally Open
Switch
Normally Closed
Switch
Substation B
Substation B
2.
3.
4.
14
2/23/2010
COLLIER
69.kV 15544
36.9P-2
1153P123
1563P-57
Collier 3
12.47kV 3
0.0P-169
Sample
12.47kV
0.0P107
8651P93
0.88P-90
0.00P90
86 0P 8
8650P-87
410P122
UNDERGROUND DESIGN
(Primary)
CONDUCTOR
DESCRIPTION
PRIMARY CONDUCTORS
R (/mile)
Xa (/mile)
397 A.A.
0.259
0.4587
477 A.A.
0.216
0.447
795 A.A.
0.131
0.4146
0.386
0.4895
0.613
0.5177
0.973
0.5434
2 A.A. (7 strd)
1.55
0.5739
2/0 CU.
0.481
0.532
1 CU. (7 strd)
0.765
0.56
2 CU. (7 strd)
0.964
4 CU. (3 strd)
1.518
0.599
6 CU. (1 strd)
2.39
0.637
0.574
#2 ACSR
1.41
0.665
312 A.A.A.C.
0.417
0.479
0.2472
0.3807
0.264
0.2207
0.6354
350 MCM-AL **
0.2904
0.14784
0.1265
0.3965
600 CU.
0.432
0.0981
0.3968
0.689
2 AL (D.B.)
1.9628
0.11
0.3078
4/0 AL (DUCT)
0.6529
0.3458
500 CU.
0.15206
0.14098
0.625
0.2434
4/0 AL (D.B.)
15
2/23/2010
Fault levels
(1)
(2)
8700 A
9300 A
Substation
3000 A
2000 A
End of line
Time
(Seconds)
Current (Amperes)
16
2/23/2010
10
100
70
50
40
30
20
1000
700
500
400
300
200
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
.4
3
.3
.2
1
.7
.5
.4
3
.3
.2
.1
.07
.05
.04
.03
.02
.1
.07
.05
.04
.03
.02
.01
10
.01
@ Voltage By
10
100
70
50
40
30
20
Fuse blows
1. Pole Riser Fuse S&C 167-62-85
Total clear.
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
4
.4
.3
.2
1
.7
.5
4
.4
.3
.2
.1
.07
.05
.04
.03
.02
.01
1000
700
500
400
300
200
.1
.07
.05
.04
.03
.02
Fuse does
not blow
10
.01
@ Voltage By
N
17
2/23/2010
18
2/23/2010
Transformer
Damage Curve
POTENTIAL
DAMAGE
AREA
38
19
2/23/2010
Area of
Coordination
100
70
2
50 2. Main Normal OC Ph IEEE_EI TD=3.500
40
30 CTR=240 Pickup=6.5A No inst. TP@5=0.6484s
20
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
Upstream 1device
1
.7
.5
.4
.3
.2
.7
.5
.4
.3
.2
Downstream
device
.1
.07
.05
.04
.03
.02
.01
.1
.07
.05
.04
.03
.02
10
100
3
70
2
50 2. Main Normal OC Ph IEEE_EI TD=3.500
40
30 CTR=240 Pickup=6.5A No inst. TP@5=0.6484s
20
3. FDR Normal OC PH IEEE_EI TD=4.500
CTR=240 Pickup=2.5A No inst. TP@5=0.8336s
10
S
E7
C5
O4
N3
D2
S
1000
700
500
400
300
200
100
70
50
40
30
20
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
2
1
.7
.5
.4
.3
.2
2
.1
.07
.05
.04
.03
.02
.1
.07
.05
.04
.03
.02
10
.01
@ Voltage By
.01
1000
700
500
400
300
200
.01
@ Voltage By
N
20
2/23/2010
Coordination:
Fuse operates before feeder
breaker curve, before main
breaker curve, before
transformer damage curve
Fault at end of
line
Fault at
substation
Pickup
Coordination
Curve
Comparison
of Time Dials
Time Dial 15
Time Dial 0
0.55
55
42
21
2/23/2010
1000
700
500
400
300
10
200
Coordination
Curve
Comparison
of curve shape
100
70
50
40
30
20
100
70
50
40
30
20
1
3
10
7
5
4
3
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
Moderatelyy Inverse
.1
.07
.05
.04
.03
.02
.01
200
10
S
E7
C5
O4
N3
D2
S
1000
700
500
400
300
.1
.07
Very Inverse
.05
.04
.03
.02
Extremely Inverse
.01
@ Voltage By
43
Fuse
51
Relay
Fault
Load
22
2/23/2010
Fused Single
Single--Phase Transformer
23
2/23/2010
Fusing Cubicle
24
2/23/2010
Successful
Coordination
1000
700
500
400
300
200
10
1000
700
500
400
300
200
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
2. Xfmr fuse Lo BAY-0-NET065
Total clear.
Ia= 3006.8A T= 0.18s
.1
.07
.05
.04
.03
.02
.01
FAULT DESCRIPTION:
Bus Fault on:
0 Sample
10
.1
.07
.05
.04
.03
.02
12.47kV 3LG
.01
@ Voltage By
Automatic Reclosing
Why? ~70% of faults are temporary
y Improved customer service and reliability
y Survey Results:
y
Utility
First Reclosure
Second Reclosure
Instantaneous
20 seconds
25
15
N/A
N/A
N/A
Instantaneous
30
Instantaneous
15
25
2/23/2010
Reclosing Continued
A wide variety of practices
y The presence of underground feeders,
feeders
distributed generation and SCADA tend
to reduce reclosing
y
Fuse Sacrificing/Saving
Fuse sacrificing allows the fuse to blow
before an upstream device for fault
conditions
y Fuse saving allows the upstream device to
operate once before the fuse. If the fault
is temporary, the fuse might be saved.
y
26
2/23/2010
Fuse
Sacrificing
1000
700
500
400
300
200
10
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
2. Xfmr fuse Lo BAY-0-NET065
Total clear.
Ia= 3006.8A T= 0.18s
.1
.07
.05
.04
.03
.02
.01
FAULT DESCRIPTION:
Bus Fault on:
0 Sample
10
.1
.07
.05
.04
.03
.02
12.47kV 3LG
Fuse Saving
1000
700
500
400
300
200
10
1000
700
500
400
300
200
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
.1
.07
.05
.04
.03
.02
.01
.01
@ Voltage By
100
70
50
40
30
20
Addition of
instantaneous
element on relay
1000
700
500
400
300
200
FAULT DESCRIPTION:
Bus Fault on:
0 Sample
10
.1
.07
.05
.04
.03
.02
12.47kV 3LG
.01
@ Voltage By
N
27
2/23/2010
DC +
Trip Bus
60
NA
Enable
Lockout
NA
0.1
p
#2 Pickup
51P (3I>)
50P-1 (3I>>1)
50P-2 (3I>>2)
50P-3 (3I>>3)
#2 Open time (Seconds)
NA
Disable
Lockout
NA
15.0
28
2/23/2010
Fuse Saving
Coordination
Problem
1000
700
500
400
300
10
200
1000
700
500
400
300
200
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
Cannot predict
which element will
operate first
100
1. Xfmr fuse 150 kVA Lo BAY-0-NET015
70
Total clear.
50
Ia= 3006.8A T= 0.01s
40
2. FDR Normal OC PH IEEE_EI TD=4.500
30
CTR=240
CTR
240 Pickup=2
Pickup 2.5A
5A Inst=1500A
Inst 1500A TP@5=0
TP@5 0
20
Ia= 3006.8A (12.5 sec A) T= 0.83s
FAULT DESCRIPTION:
Bus Fault on:
0 Sample
10
7 3
12.47kV
5
4
3
2
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
.1
.07
.05
.04
.03
.02
.1
.07
.05
.04
.03
.02
.01
10
.01
@ Voltage By
29
2/23/2010
30
2/23/2010
From ee.Washington.edu
31
2/23/2010
~3,000
3 000 Amps
~600
600 Amps
32
2/23/2010
10
100
70
50
40
30
20
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
1
.7
.5
.4
.3
.2
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
.1
.07
.05
.04
.03
.02
.01
1000
700
500
400
300
200
.1
.07
.05
.04
.03
.02
10
.01
@ Voltage By
10
100
70
50
40
30
20
1000
700
500
400
300
200
100
1. FDR Normal Gnd OC IEEE_VI TD=5.00
70
CTR=240 Pickup=0.75A Inst=1560A TP@5=
50
40
2. FDR Cold Load Gnd IEEE_VI TD=10.00
30
CTR=240 Pickup=1.5A Inst=3000A TP@5=1
20
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
.1
.07
.05
.04
.03
.02
.1
.07
.05
.04
.03
.02
.01
10
.01
@ Voltage By
N
33
2/23/2010
Line Reclosers
Is a breaker on a stick: It can sense and
interrupt faults
y Typically has 3 or 4 automatic reclosures
y Commonly employs fuse saving
y Can be single or three-phase
y Are rated by:
y
Line Reclosers
34
2/23/2010
System Voltage
Maximum fault current at recloser
location
Maximum load current
Minimum fault current in the zone of
p
protection
Coordination with upstream and
downstream devices
Ground fault Sensing
From Electrical DistributionSystem
Protection, Cooper Power Systems
35
2/23/2010
10
200
20
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
.2
.1
.07
.05
.04
.03
.02
.02
.01
100
70
50
40
30
12.47kV 3LG
20
10
S
E7
C5
O4
N3
D2
S
.1
.07
.05
.04
.03
1.
2.
3
3.
4.
5.
200
100
70
50
40
30
1000
700
500
400
300
10
.01
@ Voltage By
For
No
FaultLevels:
Phase2,100Amps
Gnd 1,420 Amps
Gnd1,420Amps
3.45miles
Bkr
Substation
1245
R
Line
Recloser
Fault Levels:
FaultLevels:
5.54
miles
Phase970Amps
Gnd620Amps
End of line
36
2/23/2010
10
100
70
50
40
30
100
70
50
40
30
1
2
2. Recloser IEEE_VI TD=3.600
CTR=1000 Pickup=0.08A Inst=900A
20
10
S
E7
C5
O4
N3
D2
S
20
1
.7
5
.5
.4
.3
1000
700
500
400
300
200
10
7
5
4
3
2
1
.7
5
.5
.4
.3
.2
.2
.1
.07
.05
.04
.03
.02
.1
.07
.05
.04
.03
.02
.01
10
.01
@ Voltage By
N
Recloser-Recloser
RecloserRecloser--Breaker
Coordination
37
2/23/2010
Recloser Challenges
y
y
y
y
y
y
y
Sectionalizer
From IEEE 100:
A self
self-contained
contained circuit
circuit-opening
opening device that
automatically opens the main electrical
circuit through it after sensing and
responding to a predetermined number
of successive main current impulses equal
or greater to a predetermined magnitude
magnitude.
It opens while the main electrical circuit is
de-energized. It may also have a provision
to be manually operated to interrupt
loads.
38
2/23/2010
Secitionalizer Applications
Where fault duty is very high, and time
curves won
wontt coordinate (typically
between breaker or recloser curves and
fuse curves.
y Between two protective devices with
time curves that are too close together.
y
39
2/23/2010
1000
700
500
400
300
200
10
1000
700
500
400
300
200
100
70
50
40
30
20
10
S
E7
C5
O4
N3
D2
S
10
7
5
4
3
2
1
.7
.5
.4
.3
.2
1
.7
.5
.4
.3
.2
.1
.07
.05
.04
.03
.02
.01
Area of difficult
coordination
2. Xfmr fuse Lo BAY-0-NET065
Total clear.
Ia= 3006.8A T= 0.18s
FAULT DESCRIPTION:
Bus Fault on:
0 Sample
10
.1
.07
.05
.04
.03
.02
12.47kV 3LG
.01
@ Voltage By
N
Distribution Automation
Technique used to limit outage duration
and restore service to customer through
fault location identification and automatic
switching. Reconfiguring a feeder can also
be done to reduce losses, or eliminate
temporary overloading
40
2/23/2010
Basic Example
Fiber
Fiber
Substation
Substation
CLOSED
MID-POINT
Automatic Switch
OPEN
OPEN
Automatic Switch
CLOSED
MID-POINT
Automatic Switch
Basic Example
Fiber
Fiber
Substation
Substation
FAULT
OPEN
MID-POINT
Automatic Switch
CLOSE
OPEN
Automatic Switch
MID-POINT
Automatic Switch
41
2/23/2010
Distributed Generation
Distributed Resource (DR): A source
of electric power that is not directly
connected to the bulk power
transmission system. DR includes both
generators and energy storage
technologies
42
2/23/2010
Sample Controls
43
2/23/2010
44
2/23/2010
Residential Photovoltaic
Utility AC
Disconnect
Solar
S
System
PV non
billing Meter
Inverter
DC Disconnect
45
2/23/2010
Bicycle Power!
46
2/23/2010
47
2/23/2010
Types of Paralleling
Open-transitiononly needs to meet
NEC requirements
y Fast-transitiongenerators parallel for
0.1 seconds or less
y
Soft unloading
For larger loads where fast transition will not
work
Generator typically parallels for 2 to 20
seconds
48
2/23/2010
Island
A condition in which a portion of a area electric
power system
p
y
(the
(
utility)
y) is energized
g
solelyy byy
one or more local electric power systems (the
distributed generator)
y Is a possibility when the generator size is equal
to or greater than the minimum feeder load. At
SRP, this value is around 500 kW
y IEEE 1547: Unintended islandsgenerator
must be off line within 2 seconds
y Transfer tripping may be required, or voltage
sensing at the substation
Customer
Switchboard
SRP
Transformer
Customer
Generator
49
2/23/2010
CT
Customer
Switchboard
Customer
Generator
GFR
SLGF
Delta-wye xfmr
To SES
Theory of operation
Fault on delta side of xfmr has
no path to ground, relative to DG
Grounding bank (GB) provides
a path to ground
CT on neutral of GB provides an
operating quantity for DG GFP (Iop)
Or, use open delta VT connection
in conjunction with GB
Transfer switch
Distributed
Generator (DG)
~
m ww
Iop
Generator GFP
Alternate
configuration
(Open delta VT
connected
to delta primary still requires GB, but
VT provides relay
operating quantity)
Grounding bank
ww
Generator GFP
50
2/23/2010
Sympathetic Tripping
Transient pickup of relays or other healthy
feeders due to the conditions created byy
a fault on another feeder of the system.
(Othman, Mamdoh and Karnal)
References
The Art and Science of Protective Relaying, C.
Russell Mason
Electrical Distribution System Protection, Third
Edition, Cooper Power Systems
Protective Relaying Principles and Applications,
J. Lewis Blackburn
IEEE Standard for Interconnecting Distributed
Resources with Electric Power Systems
51
2/23/2010
Disturbance photos
52
2/23/2010
Failed Switch
Open CT
53
2/23/2010
4 kV Energized at 12 kV
54
2/23/2010
PT Fire
55
2/23/2010
Trampoline
56
DG Interconnection Protection
Protecting
Utility Distribution with Interconnecting
Distributed Generation Green Power, MicroGrids and
Smart Grids
Technical & Industry Practice Background
What IEEE Standard 1547 Doesnt Tell You
DG Interconnection Protection
Presentation Objectives
n
Protection Variables & Standards
Generator types: Synchronous, Induction, Asynchronous
Interconnection Transformer grounding makes a big difference!
Protection to meet interconnection challenges
Comparison of various power company and standards
including IEEE 1547
Distribution protection coordination issues
IEEE Distribution Survey Data - DG issues and impact on distribution systems
DG Interconnection Protection
DG Interconnection Protection
Interconnection
Transformer
Utility System
DG System
Interconnection
Relay
Utility System
DG System
Local Loads
Local Loads
Interconnection
Generator
DG Interconnection Protection
Outline
Dispersed Generator Interconnection Protection Areas
Detection of loss of parallel operation with utility
Fault backfeed detection
Detection of damaging system conditions
Abnormal power flow
Restoration
Tripping, Automatic Restoration and Automatic Reclosing on Utility System
Trip of generator or main incoming breaker to separate from utilityhow to
decide
Auto restoration strategies
Utility auto reclosinghow to protect your generator
Use of Digital Technology for DG Interconnection/Generator Protection
Advantages of the technology
User-selectable functionality
Self-diagnostics
Communications capability
Oscillographic capability
Software demo
DG Interconnection Protection
DG Interconnection Protection
Brief DG History
Until Public Utility Regulatory Policies Act (PURPA) in 1978, U.S. utilities
were not required to interconnect with small generators.
- Started DG
- Beckwith
B k ith gets
t into
i t the
th interconnection
i t
ti
protection
t ti
business
b i
- Hot until late 1980s when tax incentive terminated
DG Interconnection Protection
DG Interconnection Protection
Protection Objectives
UTILITY CONCERNS:
Protection of the system from
damage
DG OWNER CONCERNS:
Protection of the generator from
damage
Automated Reclosing:
shaft to torque on generator
Transient Overvoltage:
also affects generator
Transient Overvoltage:
during islanding, transformer
connections, ferroresonance
Power Quality:
affects load served from
generator bus
Power Quality:
during islanding voltage and
harmonics
DG Interconnection Protection
Large capacity plants owned & operated by non-utility entities (IPPs and
NUGs)
- Gas turbines & combined cycle plants
n
- Typically greater than 10MW
- Connected into utilitys transmission and subtransmission systems
Protection integrated into transmission and subtransmission systems
DG Interconnection Protection
DG Standards History
Published in 1985
DG Interconnection Protection
DG Standards History
Published in 1988
DG Interconnection Protection
DG Interconnection Protection
IEEE 1547 Says DGs Shall :
Not Cause Overvoltages or Loss of Utility Relay
Coordination
Disconnect When No Longer Operating in Parallel With
the Utility.
+ Only Discusses 81O/U and 27, 59
Not Energize the Utility when it is De-energized
Not Create an Unintentional Islands
Use Utility Grade Relays
Not Cause Objectionable Harmonics
Not Cause Loss of Synchronism That Results in
Objectionable Flicker
DG Interconnection Protection
Impact of size
- Intended to cover up to 10MW
Impact of Islanding
- Creation of unintentional islands must be detected and
eliminated as fast as possible
Local Disturbances
- Quality of service on the utility system should not be degraded
DG Interconnection Protection
1547.2:
1547
for
DG Interconnection Protection
DG Interconnection Protection
DG Interconnection Protection
10
DG Interconnection Protection
Peak Shaving
No electrical export
DG Interconnection Protection
Load Following
Load
Generation
Morning
Midday
Night
11
DG Interconnection Protection
DG Interconnection Protection
Not Green
- Burn conventional fuel
Gas
Diesel, oil, gasoline
Green
- Use renewable sources to reduce reliance of fossil fuels:
Solar
Methane (from decomposition)
Wind
Hydro
Diesels Powered by Syn Fuel
Biomass (burn it)
Tidal
12
DG Interconnection Protection
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
DG Interconnection Protection
Loads
Loads
Loads
Loads
Loads
Loads
Loads
Loads
n
Loads
Loads
Loads
Loads
Loads
Loads
DG can create its own island,
and synchronize to the utility
13
Loads
DG
DG Island
DG Interconnection Protection
Smart Grids
Full Integration of all Components of the Distribution System
Through By-Directional Communication
Communication.
+ Peer to Peer Relay Communication
+ Adaptive Relaying
DG Interconnection Protection
14
DG Interconnection Protection
DG Interconnection Protection
15
DG Interconnection Protection
DG Interconnection Protection
16
DG Interconnection Protection
DG Interconnection Protection
Sync
Interconnection
Transformer
DG
Point of
Common
Coupling
Loads
Loads
17
DG Interconnection Protection
Interconnection
Transformer
Point of
Common
Coupling
DG Interconnection
Protection
Sync
DG
Loads
Loads
DG Interconnection Protection
Point of
Common
Coupling
Interconnection
Transformer
DG Interconnection
Protection
Sy nc
Point of
Interconnection
DG
Loads
18
Loads
DG Interconnection Protection
Functional protection
- 81U/O, 27, 59, etc.
- Settings of some interconnection functions
Pick ups
Times (to clear faster than utility reclose)
DG Interconnection Protection
Types of Generators
Induction
Synchronous
Asynchronous (Static Power Converters)
19
DG Interconnection Protection
Induction Generator
VAr Source
Induction
Types of
- Excitation provided externally by system
Generators
VAr
VA drain
d i
- Less costly than synchronous machines
Wind Power
No excitation system or control
No sync equipment needed
- Limited in size to <=500 KVA
- May cause ferroresonance after disconnection from
utility (self-excitation from nearby caps)
DG Interconnection Protection
20
DG Interconnection Protection
DG Interconnection Protection
21
DG Interconnection Protection
DG Interconnection Protection
22
DG Interconnection Protection
DG Interconnection Protection
23
DG Interconnection Protection
DG Interconnection Protection
24
DG Interconnection Protection
FERRORESONANCE
NEW YORK FIELD TESTS 1989
FIELD TEST CIRCUIT
DG Interconnection Protection
Induction/Synchronous Generator:
Ferroresonance can also occur on synchronous
generators
25
DG Interconnection Protection
DG Interconnection Protection
Synchronous Generator
Types of Generators
Internal Combustion
Engines
Small Hydro
Synchronous
Gas Turbines
26
DG Interconnection Protection
Asynchronous Generator
VArs
Types of
Generators
Solar, PV
Fuel Cells
Wind
Asynchronous
- St
Static
ti P
Power C
Converter
t (SPC) converts
t generator
t frequency
f
to system frequency (dc-ac or ac-dc-as)
- Generator asynchronously connected to Power System
+ may be self-commutating (needs sync relay)
+ may be line-commutating (no sync relay needed)
-
DG Interconnection Protection
Asynchronous Generator:
Static Power Converter
S
Some
h
have built-in
b ilt i anti-islanding
ti i l di protection
t ti
- SPC tries to periodically change frequency
If grid is hot, SPC cannot change the frequency
If grid has tripped, the frequency moves and the controller
trips the machine
27
DG Interconnection Protection
DG Interconnection Protection
Typical Capacity
Photovoltaic (Solar)
Wind
10 s W to several 100s
10s
100 s W
100s W to a few MW
Geothermal
Hydro
100s kW to a few
n MW
100s W to a few MW
Reciprocating Engine
100s W to a few MW
Combustion Turbine
Combined Cycle
Microturbines
Fuel Cells
10s MW to 100s MW
A few 10s of MW to 100s MW
10s of kW to 100s kW
10s of kW to 10s of MW
28
Utility Interface
DC to AC Inverter
Induction and synchronous
generators, AC to AC
inverter
Synchronous generator
Induction or synchronous
generator
Induction or synchronous
generator
Synchronous generator
Synchronous generator
AC to AC Inverter
DC to AC Inverter
DG Interconnection Protection
DG Interconnection Protection
Backfeed to Utility
DG
n
DG Facility
a
Ground Fault
Van=Vag
ground
n=g
vag=0
Van= -Vng
Vbn=Vbg
Vbn=Vbg
Vcg
Vbg
n
Unfaulted
b
c
Vcn
29
Vbn
DG Interconnection Protection
n
DG Facility
59
N
Ground Fault
Van=Vag
ground
n=g
vag=0
Van= -Vng
Vbn=Vbg
Vbn=Vbg
Vcg
Vbg
n
Unfaulted
b
c
Vcn
Vbn
DG Interconnection Protection
59
N
27
N
DG Facility
a
Ground Fault
Van=Vag
ground
n=g
vag=0
Van= -Vng
Vbn=Vbg
Vbn=Vbg
Vcg
Vbg
n
Unfaulted
b
c
Vcn
30
Vbn
DG Interconnection Protection
DG Interconnection Protection
Low
Voltage
(SEC.)
High
Voltage
(PRI.)
DG
31
DG Interconnection Protection
Low
Voltage
(SEC.)
High
Voltage
(PRI.)
DG
DG Interconnection Protection
n
Advantages
Provide no ground
fault backfeed for
fault at F1 & F2
No ground current
from breaker A for a
fault at F3
Low
Voltage
(SEC.)
High
Voltage
(PRI.)
DG
32
DG Interconnection Protection
Low
Voltage
(SEC.)
High
Voltage
(PRI.)
DG
DG Interconnection Protection
Problems
Provides an unwanted
ground current for supply
circuit faults at F1 and F2
Low
Voltage
(SEC.)
DG
33
High
Voltage
(PRI.)
DG Interconnection Protection
Advantages
No g
ground current from
breaker A for faults at F3
(delta sec. only)
No overvoltage for ground
fault at F1
Low
Voltage
(SEC.)
High
Voltage
(PRI.)
DG
DG Interconnection Protection
Anti-Islanding
M-3410A Functional
Diagram
59
I
81
59
Note 1
47
27
51
V
60
FL
51
N
46
32
3Y
25
Waveform Capture
Sequence of Events
Communications
(Modbus)
LED Targets
User Interface
with PC
M t i
Metering
79
Programmable I/O
52
I
Note 2
BUS
52
G
Notes:
1) Supply VTs are not necessary if potential to relay terminals is <= 480 VAC
2) Bus VTs are not necessary if potential to relay terminals is <= 480 VAC
34
DG Interconnection Protection
59
I
81
51
N
59
Note 1
47
27
51
V
60
FL
46
Grounded
Primary
32
3Y
25
Waveform Capture
Sequence of Events
Communications
(Modbus)
LED Targets
User Interface
with PC
Metering
79
Programmable I/O
52
I
Note 2
BUS
Notes:
1) Supply VTs are not necessary if potential to relay terminals is <= 480 VAC
2) Bus VTs are not necessary if potential to relay terminals is <= 480 VAC
52
G
DG Interconnection Protection
UTILITY
M-3410A
M
3410A Functional
F nctional
Diagram
59
N
27
N
59
I
81
51
N
46
59
47
27
51
V
60
FL
n
32
Waveform Capture
Sequence of Events
Communications
(Modbus)
LED Targets
User Interface
with PC
Metering
79
Programmable I/O
3Y
52
I
Note 2
BUS
52
G
Ungrounded
Primary
Note 1
Notes:
1) Supply VTs are not neccessary if potential to relay terminals is <= 480 VAC
2) Bus VTs are not neccessary if potential to relay terminals is <= 480 VAC
35
DG Interconnection Protection
Abnormal Conditions
M-3410A Functional
Diagram
59
I
81
51
N
59
46
Note 1
47
27
51
V
60
FL
32
3Y
25
Waveform Capture
Sequence of Events
Communications
(Modbus)
LED Targets
User Interface
with PC
Metering
79
Programmable I/O
52
I
Abnormal Conditions
Unbalanced currents
- open conductor/single phase (46)
- phase reversal (47)
Not just for commissioning
Ferroresonance
instantaneous overvoltage (59I)
Fuse Loss
- Potential loss detection ((60FL))
Note 2
BUS
52
G
Notes:
1) Supply VTs are not necessary if potential to relay terminals is <= 480 VAC
2) Bus VTs are not necessary if potential to relay terminals is <= 480 VAC
DG Interconnection Protection
81
51
N
46
59
Note 1
47
27
51
V
60
FL
32
3Y
25
Waveform Capture
Sequence of Events
Communications
(Modbus)
LED Targets
User Interface
with PC
Metering
79
Programmable I/O
52
I
Note 2
BUS
52
G
Notes:
1) Supply VTs are not necessary if potential to relay terminals is <= 480 VAC
2) Bus VTs are not necessary if potential to relay terminals is <= 480 VAC
36
DG Interconnection Protection
DG Interconnection Protection
Load
Generation
Morning
Midday
Night
37
DG Interconnection Protection
Option
O
ti 1
- Use sensitive 32F relay, set at 0.01 pu (0.1%) of
interconnection transformer rating
Option 2
- Use 32R-U relay to guarantee import of at least 5%
of gross generator capacity
DG Interconnection Protection
VT
2 7 , 5 9 ,8 1 U /O ,
25
CT
32
Reverse -
Local
Load
38
DG Interconnection Protection
VT
Forward +
32
CT
Excitation
KW
Local
Load
DG Interconnection Protection
32
120/1
CT
Reverse (-)
480V
G1
Local
Load
G2
32R-U Relay pickup set to at least 5% (-0.05 p.u.) of total connected generator
rated KVA
32R-U Relay programmed to trip when imported power falls below the
pick-up level
39
DG Interconnection Protection
Th
These
elements
l
t can cause nuisance
i
tripping
t i i off the
th DG if
large load swings occur in the DG facility
DG Interconnection Protection
Feeder Loads
Local
Load
400 kVA
40
Pow er Import
5 kVA
DG
395 kVA
DG Interconnection Protection
Feeder Loads
Utility Source
Pow er Import
5 kVA
Generation adjusted to
match local load with
small bias
Part of load 40 kVA of
motors
Local
Load
40 kVA
360 kVA
DG
395 kVA
DG Interconnection Protection
Feeder Loads
Utility Source
Momentary
export
<= 35 kVA
Local
Load
DG
0 kVA
360 kVA
395 kVA
41
DG Interconnection Protection
DG Interconnection Protection
Special Situation:
Use of Rate-of-Change of Frequency 81R
42
DG Interconnection Protection
Special Situation:
Use of Out-of-Step 78- Reciprocating
Engines
DG Interconnection Protection
43
DG Interconnection Protection
1.
2.
Voltage may not go down enough for undervoltage protection to protect the pole slip
3.
OOS protection will detect the acceleration of the rotor and the resultant angle increase past 90 in the
case of a possible unstable swing
DG Interconnection Protection
44
DG Interconnection Protection
DG Interconnection Protection
45
DG Interconnection Protection
DG Interconnection Protection
Ungrounded Primary
UTILITY
M-3520 Relay
27
N
59
N
1 or 3
25
59
I
67
N
79
81
R
50
46
2 or 3
81
59
47
27
60
FL
67
51
V
32
21
3Y
Waveform Capture
LED Targets (opt)
Sequence of Events
Programmable I/O
User Interface with PC
Metering
HMI (optional)
IRIG-B Input
Communications (MODBUS or BECO 2200)
52
I
BUS
XX
= standard function
XX
= optional function
52
G
46
DG Interconnection Protection
Protection
25
n
Supervises "A"
Reclosing
Auto
Sync
Auto
Sync
Re-sync at breakers
B&C after utility
restoration
LOADS
DG Interconnection Protection
Protection
CLOSE
25
n
Supervises "A"
Reclosing
OPEN
Auto
Sync
S
Auto
Sync
S
Trips "A"
LOADS
When utility restores, 25 function (with , F, and V) supervises recloses A which is auto sync by switching
VT Sources as shown
47
DG Interconnection Protection
DG Interconnection Protection
10kW
Texas
1
3
50kW
500kW
1,000kW
2,000kW
2,500kW
10,000kW
32
81U
TT
IEEE
1547
Co
om Ed
Rule 21
Entergy
y
59N or 51N, 32
32
81U
TT
32
LFP
48
DG Interconnection Protection
Transformer Connections
Texas
- Not specified
Entergy
- Ygnd/delta or delta with zig-zig/Ygnd
Rule 21 (California)
- Not specified
Commonwealth Edison
- Delta/not specified
IEEE 1547
- Not specified
DG Interconnection Protection
Interconnection Transformer
IEEE Distribution Practices Survey 1/02
2002 Survey
- Grounded wye primary 58%
- Delta primary 9%
- Other 33%
1995 Survey
- Grounded
G
d d wye primary
i
33%
- Delta primary 33%
- Other 33%
49
DG Interconnection Protection
No effect 22%
DG Interconnection Protection
50
DG Interconnection Protection
DG Interconnection Protection
Summary
to be part
51
of
addresses
the overall
DG Interconnection Protection
Recommended Reading
of
DG Interconnection Protection
Recommended Reading
52
27th Annual
Table of Contents
1.0
2.0
2.1
3.0
4.0
4.1
5.0
Portions of this Power Quality presentation have been incorporated and reprinted with Permission from:
2
It would be difficult to
define the Quality of this
quantity in any
meaningful way.
Impulsive
Oscillatory
Short
Duration
Variations
Instantaneous
Momentary
root-meansquare
(rms)
Temporary
Typical
Duration
Typical
Voltage
Magnitude
Typical
Spectral
Content
Nanosecond
< 50 ns
5 ns rise
Microsecond
50 ns 1 ms
1 us rise
Millisecond
> 1 ms
< 5 kHz
Medium
Frequency
0 8 pu
5 500 kHz
High
Frequency
0 4 pu
0.5 - 5 MHz
Typical
Causes *(3)
Example of
Power
Conditioning
Solutions*(3)
Lightning,
Electrostatic
discharge, Load
switching,
Capacitor
switching
Surge Arresters,
Filters,
Isolation
Transformers
*(3)
Peak Magnitude,
Rise Time,
Duration
0.1 ms rise
0 4 pu a.
Low Frequency
Method of
Characterization
Waveshape,
Peak Magnitude,
Frequency
Components
Line/Cable
switching,
Capacitor
switching
Ferroresonant
Transformers,
Energy Storage
technologies,
UPS
Sags
Swells
0.5 - 30 cycles
0.5 - 30 cycles
0.1 0.9 pu
1.1 1.8 pu
Interruptions
Sags
Swells
0.5 cycles 3
s
30 cycles 3 s
30 cycles 3 s
< 0.1 pu
0.1 0.9 pu
1.1 - 1.4 pu
Interruptions
Sags
Swells
> 3 s 1 min.
> 3 s 1 min.
> 3 s 1 min.
< 0.1 pu
0.1 0.9 pu
1.1 1.2 pu
> 1 min
0.8 0.9 pu
Long
Duration
(rms)
Variations
Undervoltage
Overvoltage
> 1 min
1.1 1.2 pu
Imbalance
Voltage
steady state
0.5 2 %
Current
steady state
1 30%
RMS vs Time,
Magnitude,
Duration
Duration
rms vs time
Remote System
Faults,
System
Protection
(breakers),
Load Pick-up
Voltage
regulators,
Ferroresonant
transformers
Motor Start,
Load Pickup
Load Variations,
Capacitor bank
(in or out),
Transformer Tap
setting,
Voltage
Regulators,
Ferroresonant
transformers
Typical
Voltage
Magnitude
DC Offset
steady state
0 0.1%
Harmonics
*(1)(2)
steady state
Interharmonics
steady state
Notching
steady state
Noise
Voltage Fluctuations
(Flicker)
Categories
Waveform
Distortion
Typical
Spectral
Content
Method of
Characterization
*(3)
Typical
Causes *(3)
Example of
Power
Conditioning
Solutions *(3)
0 20%
0 50th
Harmonic
0 2%
0 9kHz
Harmonic
spectrum, Total
Harm. Distortion,
Statistics
Non-Linear
loads, System
resonance,
Transformer
saturation
Filters (active
or passive),
Transformers
(cancellation
or zerosequence
components)
steady state
0 1%
broadband
intermittent
0.1 7%
0.2 2 Pst b.
< 25 Hz
< 10 s
+ 0.10 Hz
Intermittent
loads, motor
start, Arc
Furnace
Static Var
systems
NoteThese terms and categories apply to power quality measurements and are not to be confused with similar terms defined in IEEE std 1366 and other
reliability-related standards, recommended practices, and guides.
a. The quantity 1.0 pu corresponds to 100%. The nominal condition is often considered to be 1.0 pu. In this table, the nominal peak value is used as the base for transients and
the nominal rms value is used as the base for rms variations.
b. Flicker severity index Pst as defined in IEC 61000-4-15:2003 and IEEE Std 1453-2004.
*Notes:
1)
Magnitudes, durations, spectral content are typical but may exceed listed values.
2)
PQ Monitors may only measure up to the 50th or 70th harmonic as determined by sampling rates, but harmonics up to the 100th can be generated.
3)
Data Source - EPRI 2007 PQ Seminar.
Duration 3 cycles
-5
Magnitude (50%)
-10
-Remote Fault9
The best way to Guarantee that Process Equipment is Compatible with its
Electrical Environment is to Require the Equipment to Comply with Voltage Sag
Standards
EPRI has shown that Machines can be Built to Comply with Voltage Sag
Standards, like SEMI F47, with almost no Difference in Cost
Information
Technology Industry
Council (ITIC) CBEMA
Curve
Not Actual
Events Meter
connection
changes.
12
Duration at 50 Hz
Duration at 60 Hz
50%
10 cycles
12 cycles
70%
25 cycles
30 cycles
80%
50 cycles
60 cycles
#1 Sag depth is expressed in percent of remaining nominal voltage. For example, during a 70% sag on a 200 volt nominal system, the voltage is reduced
during the sag to 140 volts (not 60 volts).
Duration at 50 Hz
Duration at 60 Hz
0%
1 cycle
1 cycle
80%
500 cycles
600 cycles
14
2009 Electric Power Research Institute, Inc. All rights reserved.
Sag generators are the ideal tool for testing and qualifying
OEM equipment for sag immunity and ride-through tolerances.
15
2009 Electric Power Research Institute, Inc. All rights reserved.
16
2009 Electric Power Research Institute, Inc. All rights reserved.
17
2009 Electric Power Research Institute, Inc. All rights reserved.
18
2009 Electric Power Research Institute, Inc. All rights reserved.
Embedded
Solution
Strategies
Utilize a combination of
both strategies
19
2009 Electric Power Research Institute, Inc. All rights reserved.
DYSC
CoilLock
Low Voltage
Ride Through
Module
Fast (<700s) transfer, off-line system develops little heat & fails to safety.
Able to withstand high inrush currents; no need to oversize as with UPSs & CVTs.
Accurate application control; adjustable ride through time & variable transfer level.
21
2009 Electric Power Research Institute, Inc. All rights reserved.
Islanded Motors
Common Sources:
24
Startup Transformer
Arrester Damage
26
27
One-Line Diagram
28
29
30
1 sec
31
3 sec
32
3 sec
33
Investigation:
34
35
Backfeed Condition
Only Occurs when a Main Generator is Off Line and Its Auxiliary Loads
(Motors) are Fed from the Startup Transformers
Large Capacitance from Long 230 kV Line (22 Mvar) Allows Induction
Motors to Self-Excite
Neutral Shift
Ungrounded Wye on 230 kV Side Acts Like Delta Winding - Allowing Full
Neutral Shift During Backfeeding
Lessons Learned
38
Problem:
Steam Plant Concern
over Damage to Other
Motors with Three
Reclosures for Each Fault
Consider Making it a
System Standard at 230 kV
When its Possible
(Like Reclose Blocking with
Transfer Trip at 500 kV)
39
3.0
41
Flicker severity
(Pst) is measured
over a 10 minute
observation period
Tst= 10 min.
1.0
Plt
0.8
compatibility levels are the upper limit . . . Plan for lower levels
Planning Levels
MV
HV-EHV
Pst
0.9
0.8
Plt
0.7
0.6
IEC 61000-3-3
42
Plt =
i =1
Psti3
12
Plt =
3
P
sti
i =1
12
Distributed Generation
Photovoltaic systems
Wind Turbines
ZSYS =
VSYS
ISC
Vsys
ISC
I LR = 3% VSYS
I LR = 3% ISC
44
Power factor is a measure of how effectively equipment can convert current, from the power
system, to power that actually performs work.
True power factor (TPF) the ratio of real power (kW) to apparent power (kVA) includes the
60hz component plus all the harmonics.
Displacement power factor (DPF) is for the fundamental 60 Hz component (linear circuits) only
and is a measure of the angle between the voltage and current COS.
PF= kW / kVA
kvar
kVA
kW
47
2009 Electric Power Research Institute, Inc. All rights reserved.
kVA = kW 2 + k var 2
% V =
k varcapacitor % Z transforme r
kVA transforme r
50
1. Transients Impulse
(capacitor switching)
Common
Sources:
Lightning
Capacitor
Switching
Switching
Electro-Static
Discharge
100000
50000
Volts
Load
MCMCAPS
Phase A Voltage
Wave Fault
150000
-50000
-100000
-150000
0
20
40
60
Time (mSeconds)
51
80
100
Electrotek
Zero crossing
causes
erroneous
relay operation
in ASDs
52
ASDs dc smoothing capacitor in the dc link can a have fairly narrow threshold
for dc overvoltages. Drives can be tripped for overvoltages as low as 1.17pu.
53
4.1 Harmonics
55
Volts
1
0
-1
-2
60hz Fundamental,
180hz 3rd h,
300hz 5th h
-3
-4
-5
-6
0
0.02
F
time
H3
H5
Voltage (V)
-2
-4
-6
0
0.01
0.02
0.03
time (s)
F+H3+H5
56
Distortion limits
in IEEE 519
57
58
The current drawn from the mains supply by the SMPS rectifier circuit occurs in
short pulses (dc capacitor charging) around the AC voltage peaks. These pulses
have significant high frequency energy which reduces the power factor.
As the dc capacitor charges, it will cause the voltage to drop at the peak of the
voltage waveform. This causes the peak to be flattened somewhat (a condition
known as flat-topping)
The input current of basic switched-mode power supplies have high harmonic
content and relatively low power factor.
Mains
Input
Inverter
Chopper
(Typ. 20kHz
Switching)
Output
Transformer
(High Frequency)
AC - DC Switched-Mode Power
Supply (SMPS)
Chopper
Controller
59
DC
Output
15000
10000
5000
0
0
0.005
0.01
0.015
0.02
0.025
0.03
0.035
0.04
-5000
-10000
-15000
U1
U2
U3
80
60
40
20
0
-20
PF1
PF2
PF3
-0.65
-0.92
-0.98
0.005
0.01
0.015
0.02
0.025
0.03
0.035
0.04
-40
-60
-80
I1
I2
I3
Note: Relatively high vars (reactive power) and high harmonic current distortion in Channel 1
resulting in low PF. High K factor is an indicator of what will be increased harmonic load
on transformers.
60
61
Harmonic Current
Content for Typical 6
Pulse Converter
N(6 1)
N =1
62
Frequency
(Hz)
Magnitude
(%)
60
100
300
17.5
420
11.0
11
660
4.5
13
780
2.9
Typical harmonic
current signatures
for common nonlinear loads
L1
120VAC
Switcher
and
Controls
63
DC
64
65
Amps
H=5th & 7th
H=17th & 19th
H=11th & 13th
Amps
66
Large refrigeration plant using 50Hp 150 Hp variable speed drive (VSD)
motors to run condensers for cooling/refrigeration.
Very high levels of harmonic currents causing thermal overloads in plant and
voltage distortion on utility distribution system I - THD 36.52%.
Higher frequency harmonics in this example could also cause interference with
communication circuits.
I THD =
I THD =
2
I
h
I 12
2
2
2
2
2
2
2
2
+
+
+
+
+
+
+
220
135
55
40
45
35
50
55
5
7
11
13
17
19
23
25
7702
I THD = 36.7%
67
THD =
68
n =2
Vfundamental
TDD =
2
h
I
n=2
2
h
*100%
69
Sequence
1st
2nd
3rd
4th
5th
6th
7th
8th
th
10th
th
11
12th
13th
etc
HV system
5
-5
5
-5
-2
-4
0
-6
-5
Flow of
harmonic current in
three phase transformers
72
The K-factor
K factor =
1
I 2R
2 2
I
hh
h =1
= K-factor = 0.97
Compare
(Recommended Practice for Establishing Liquid-Filled and Dry-Type Power and Distribution Transformer Capability
73
Common Sources:
Waveform Distortion
Steady State Variation
74
Nonlinear Loads
System Resonance
Transformer Saturation
M
Voltage
Regulator
SUBSTATION
End of Feeder
FEEDER
LTC
DG
Possible
Interactions
Ratio of DG Output
to Utility Fault Level
76
77
Problem 1
Problem 2
Combination of 69 kV system
impedances and up to 2Mvars cable
capacitance (varies with generation
level as turbines are on/off line
tuning capacitor effect)
79
Stiffness: The ability of the power system to resist voltage deviations caused by
distributed generation or loading.
Stiffness ratio (SR): The relative strength of the system, at the PCC, compared with
the DR.
SR =
SC kVA(SYS) + SC kVA( DR )
SC kVA( DR )
SR =
SC kVA(SYS)
SC kVA( DR )
+1
81
Parallel Resonance
Source reactance may be in the form of utility system sources and line
impedances, transformer impedance, or a combination of these.
High harmonic voltages drive high harmonic currents in the capacitor and
system inductive (source, line) reactance's.
Capacitor failure can occur if the voltage increase exceeds the capacitor
voltage rating.
82
83
[1]EPRI Power Quality Workbook for Utility and Industrial Applications
Series Resonance
When series resonance occurs a low impedance path is created for harmonic currents.
Series resonance tends to occur near the end of radial lines with capacitors near the end.
Radial lines frequently terminate on load serving transformers with power factor (PF) correction
capacitors and the combination can lead to series resonance between the transformer inductance
and PF capacitance.
The resultant harmonic voltage distortion can also lead to induced interference with parallel
communication circuits.
f =
1
2
LC
hr =
Xc
X sc
MVA sc
Mvar cap
kVAtx * 100
kvarcap * Ztx(%)
MVAsc= 35MVA
kVAT=
XT=
kVA
%X
MVAsc
MVA
35 MVA
hr =
1500 kvar
86
kvarcap= 1500kvar
hr = 4.8
XL
87
X
Hn
C
Hn
kV
Mvar
XC
XL
XL
XL
X
Hn
2
4.7
4.16kV
800kvar
Capacitor Impedance
XL = kV2
(Mvar)N2
=X
C
XL = XC = 21.63 = 0.9792
N2
(4.7)2
N2
Reactor Impedance
XL = 0.9792 ohms
88
89
Voltage regulation
The DR should not actively regulate the voltage at the PCC or
cause service voltages to go outside the requirements of ANSI
C84.1-1995, Range A.
ANSI C84.1 Maximum Utilization Voltage 72.5 kV
Manage flicker to
levels in IEEE 1453 &
IEC 6100-3-3
73
Voltage fluctuations at
the PCC < 5% of the
prevailing voltage level
of the Area EPS at the
PCC.
72
71
70
69
68
67
66
5.8kV = 8%
65
8/4/2009
0:00
8/5/2009
0:00
8/6/2009
0:00
90
8/7/2009
0:00
8/8/2009
0:00
8/9/2009
0:00
8/10/2009
0:00
8/11/2009
0:00
75
127
74
126
73
125
72
124
71
123
70
122
69
121
120
68
119
67
118
66
7/26/2009 0:00
7/31/2009 0:00
8/5/2009 0:00
8/10/2009 0:00
NC KV
CW KV
V 2 3 kV (2.2%)
91
8/15/2009 0:00
8/20/2009 0:00
76
74
72
70
68
66
64
7/26/2009 0:00
7/31/2009 0:00
8/5/2009 0:00
8/10/2009 0:00
CW KV
DM KV
92
8/15/2009 0:00
8/20/2009 0:00
93
2.
3.
95
MVAsc(69kV)
MVAsc(115kV)
Stiffness
Ratio
3.85
7.56
Inverters
Soft start (limited rate of change of power output at starting)
Synchronous machines
Use better voltage matching and phase angle synchronization at contact closure
Induction machines
Use good speed matching
Limit inrush by inserting impedance or reduced voltage start
96
2.
3.
Shared Responsibility
Certain power quality variations are unavoidable, and part of
operating a power system such as lightning transients and faultinduced sags. These are difficult to eliminate without assessing
unacceptably high costs that are ultimately borne by the
consumer.
98
Acknowledgements
EPRI 2007 Power Quality Seminar Incorporated w/Permission and Courtesy of:
Mark Stephens, PE
Manager Industrial Studies
Electric Power Research Institute
942 Corridor Park Blvd
Knoxville, Tennessee 37932
Phone 865.218.8022
[email protected]
Bonneville Power Administration Case Studies and Waveform Data courtesy of:
SPC Central Staff - TECS
5411 NE Highway 99
Vancouver, WA 98663
Rita Coppernoll Manager SPC Technical Services
Presenter:
Christine Goldsworthy, Electrical Engineer
Substation Maintenance & High Voltage Equipment Engineering
5411 NE Highway 99
Vancouver, WA 98663
99
References
100