Manual LSPS (ENG)
Manual LSPS (ENG)
Users manual
When the log screen disappeared, following starting screen appeared as follows.
Pull down menu includes, as above picture, File, Edit, View, Project, Option and Help Button. And most
of them exist in tool bar menu. Each menu has its items as follow.
File Menu
Content of file menu is similar to ordinary windows program. It has commands of New file, Open,
Save(as Save) and Print.
Edit Menu
Edit menu is same as ordinary windows program. It contains Undo, redo, cut, copy, paste and erase.
View Menu
Project menu has Step-by-step executive commands, of which program conducts four steps technical
calculation. First step is to input system topology and select/input the necessary data. Second step is to
perform SC calculation. Third step is to carry out CB automatic selection. Last step is to review protective
coordination.
Option Menu
DB Management: This software provides default database, users can add, delete and change data as
users need.
Characteristic value indication: its a command which could view and hide specific value indication
located in each component icon on the right side of the drawing screen.
-Help Menu
Help Menu consists of list and menu of LS Power Solution information. If you select it, you may open
users manual.
2) Basic command toolbar
This is the collection of the basic command icon, which is used in the other windows program. It consists
of file and edit icon same as pull down menu.
Detail
7) Navigator View
This is a picture showing Total drawing screen, to which system topology is applied. It could make users
move to specific spot quickly. Left picture is an initial screen, right is with system topology.
9) Drawing screen
It is a latticed type to draw the system topology with system component icon. Reversed box on the screen
is pointed with mouse. In this status, when system component icon is selected, new icon is located on the
reversed box.
The method of the drawing of power system component is as following figure. If you select a utility bus
component of toolbar menu, the selected component is created on the selected grid. The created
component appears the navigator and tree bar.
10
After Drawing
11
Size changing
If you drag the mouse where want the size change, the rectangular box of dotted line appears.
12
Size change(length)
It is an area indication of dotted line if you move a mouse to the position that you can can change size.
Size change(width)
13
Size change
14
2) Move of component
Move of single component
Before component move
Select the component that you want to move by a mouse.
Component moving
Move the selected component to a position that you want to move finally. An area of dotted line is
indicated to the area that a mouse moves.
15
3) Component deleting
Before component delete
Select a component to delete, and an area of selected component is indicated.
Component deleting
There are two methods of component delete. One is the erasure using "Delete" or "Cut" command
through mouse right click and the other is a method that erase using "Delete" key in keyboard. Following
picture is occasion to press mouse right button and select "Delete".
16
4) Component copy/paste
Before component copy
Select a component to copy. Area of selected component is indicated.
Component copying
There are two methods of component copy. One is the copy using "Copy" command through mouse right
click and the other is a method that copy using "Ctrl+C" key in keyboard. Following picture is a case to
press mouse right button and select "Copy".
17
Component paste
18
19
20
6) Component connection
Method 1
Before component connection
21
Method 2
Before component connection
Method 3
Before component connection
22
Component connection
23
After composing the example system in drawing screen each component data as follows input For data
input, user can use database or input directly and component of example system inputs directly. If data
entry is ended, a component name and main information are updated on the component left and right side
of drawing window, respectively.
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
In the case of single phase transformer, you should decide to omit because it is equal with three-phase
transformer except there is no selection of connection type.
40
41
42
Change of margin
Rate of margin is considered as the circuit breaker when choosed automatic. Software may choose
breaker that has suitable capacity to 10kA' fault current if it was established rate of margin by 100% and
the fault current of circuit breaker location was calculated by 10 kA. The other side, software may choose
breaker of capacity that is suitable to 15 kA' fault current if established rate of margin increases by 150%.
43
44
45
46
47
48
49
50
51
52
On the right of motor protection device establishment screen, the name of final selected devices is shown.
53
54
55
4. Skeleton Checking
If you achieve short circuit calculation clicking executable practice toolbar's 2nd die icon, the skeleton
checking (error search) is achieved before short circuit calculation.
Theres a method examining two errors. One is that user confirms the error information opening input
window and the other is that control dialog window directly in error information window. You must
choose with next picture If you want to open relevant component dialog window directly in error
information window.
56
If you double click the selected state by a mouse, the dialog window of relevant component with next
picture open.
57
If you calculate M1's rated current of load-side motor, the rated current of the motor becomes about 185A
because the voltage is 400V in 128.057kVA capacities. Therefore, the error message appears because
breaker CB4's rated current is smaller than the load-side motor.
If you raise CB4's rated current by 190A and achieve short circuit calculation again, you can see that the
number of error message is decreased.
Similarly, if you open relevant error message double clicking, breaker CB1's rated current is 400A and the
thermal capacity of cable W1 is 390A. Therefore, skeleton checking process informs user that the rated
current of circuit breaker is higher than the thermal capacity of load-side cable. Therefore, error message
doesnt appear if it heightens the thermal capacity of load-side cable by 400A and achieves short circuit
calculation again. The short circuit calculation result will be displayed on drawing screen as following.
Also, cross stripes in drawing state disappears.
58
59
60
Screen occurs following change on the whole if it finishes debugging through Skeleton checking and
achieves short circuit calculation.
If you open component input window in this state, there is following change. That is, the save button does
not permit any change that can affect in short circuit calculation.
61
User must return in again Step 1 as following if he wants change of input data.
In this case, change of input data is permitted because save button as following is activated if reopen
component inputs window.
62
Among all components, a circuit breaker is permitted to be changed after breakdown calculation. Like
following picture, the kind of circuit breaker can be changed after short circuit calculation.
63
64
6. CB Automatic Selection
If you execute practice toolbar's 3rd die button, CB automatic choice is achieved. In the case of practice
toolbar, Step 1(system drawing) and Step 4(protection coordination decision) are activated if progress in
Step 3 and second-stage become inactivation.
If you open the dialog window of chosen breaker, following screen appears. It is an occasion opened CB1
of example system. CB1 established a kind of breaker by ACB before achieve breaker automatic choice
and rated current established by 400A. Also, a short circuit current is calculated by about 42 kA. Also, it
is considered as 42 kA in breaker automatic choice because the rate of margin is 100%. The breaker
names(internal red-lined box) of following picture are candidates of ACB that satisfy all conditions of
singularity and the selection means the nearest breaker among them.
65
66
7. CB manual selection
The ways to change auto-selected CB manually are the same as follows.
Selection change using mouse
If users double click of mouse on one of the CB list and save it, the name of the CB located in the
drawing is updated as following picture.
67
68
69
70
71
Here, selecting combo button in the lower left-hand corner, a related T-C curve is displayed as follows.
Like above image, the red colored curve indicates a component selected by mouse and related rating and
value are displayed in the Tab setting. And also display of T-C curve is changeable according to the
variation of Tab setting value.
72
Users should click its Delete Curve button to remove any T-C curve in the display window.
73
If you want to add another T-C curve to the viewer, you may select a component and execute Add T-C
curve command by mouse right click during operation of T-C curve viewer.
74
Users should select the check button in the same way to see an added curve.
75
In order to print out the image of T-C curve, users click T-C curve image command button and then the
following viewer program to do printout jobs is shown.
76
77
9. Protective Coordination
Protective coordination of low voltage system may be widely divided to two sections, Cascading type and
Discrimination type and they are summarized as follows.
- Cascading: A protective device in the lower side (or load side) cannot interrupt all of the fault current
within its self-protective area and the other device in the upper side may be operated concurrently or more
quickly. It means for the latter device to be in charge of the obligation of removing fault of the lower device. It has
advantage to protect power system economically but makes reliability of power system operation declined.
- Discrimination: A protective device in the lower side (or load side) can interrupt all of the fault current
within its self-protective area and the other device in the upper side may not be operated at that time. It has
very high reliability of power system operation but is too much of an expense.
After Completing in CB selection, protective coordination is proceeding by performing the forth dice
button in the toolbar as follows.
And then users have to choose one of two kinds of protective coordination, explained above. C in the
picture indicates Cascading and D indicates Discrimination. First, Discrimination type is selected as
follows.
Next, users should choose two CBs (example CB2, CB5) to see coordination by mouse click in condition
of Shift key on. After selecting CBs, pop-up menu is shown up after you press mouse right button.
78
Selecting protective coordination analysis, the following message is displayed. Here, Coordination is
validate. means to make it coordinated based on the low voltage CB protective coordination standard of
LS industrial systems. And Select the other CBs? message asks users to replace one CB manually
among the coordination possible CB lists in the lower side without changing upper side CB.
79
If users select No, message in the screen will disappear and upper/lower side CB will change its color
into red and blue color respectively. Otherwise, selecting No message in the screen will disappear and
CB component input window will open in the screen. The CB list shows arranged lower side CBs
possible to coordinate with the upper side CB. Thus, users can change CB selection in the same way as
CB manual selection.
80
Protective coordination analysis on CB1 and CB2 appears in the screen as follows. This combination is
not found in the authorized table. means that there is no CB based on the low voltage CB protective
coordination standard of LS industrial systems and LS industrial systems can not assure protective
coordination on these CBs. In case of that, CB color will be changed into pink.
81
Protective coordination analysis on CB3 and CB6 appears in the screen as follows. Here, Coordination is
invalidate. means that these two CBs are impossible to coordinate but there are CBs based on the low
voltage CB protective coordination standard of LS industrial systems. In other words, LS industrial
systems can assure that the CBs do not coordinate each other. And also, In case of that, CB color will be
changed into pink.
82
83
10. REPORT
Users can see and print out the report after the fault calculation.
If a user clicks the Report button of toolbar in the above picture, the report manager is able to be
executed anytime after the fault calculation step as a following picture.
84
This image is to show Add All and Remove All functions of bus selection.
If a user clicks Add All Button, All buses will be displayed in the Selected buses list. And Remove
All button is using for removing all buses in the Selected buses list. The use of Add and Remove
functions is shown as below.
85
Add command button is activated when you select any bus of Selecting buses list and a selected bus of
the list is shown up in Selected buses list after clicking Add button. Also, remove command button is
used for removing a selected bus of Selected buses list. Users can select options of the fault calculation
using check button of the report manager and the output of the fault calculation is displayed in the report
form as the following image.
86
Users can convert the output of the fault calculation to the Excel file by Convert To Excel command
button in the upper-left corner of the report window shown above. The next image shows the excel file
converted from the output form of the S/W.
87
In order to zoom in power system drawing, users execute the drawing print command in the upper-left
corner of the report window and the output of the command is displayed as follow.
Command buttons such as print, zoom in/out and page move are deployed in the upper-left corner of the
report window.
88
11. DB management
This S/W is supporting DB management functions that users can add, edit and remove user defined data.
Components controlled by the DB management are generator, motor, line and transformer and users can
select DM management command in the option toolbar as follow.
Users also execute these functions using DB management button in each component input window.
The image as below shows each result of toolbar DB command case (left side) and component window
DB command case (right side).
89
The execution of input button on the lower corner of the DB management window shows user data input
window as follow.
90
If users input data and click button, the data will be added to DB and DB list of the window will
be updated.
91
Arrow buttons in the right corner of the window are used to change data order and it is for convenient use
as raising data order that users use frequently. The way to arrange data order using arrow buttons is shown
as following picture.
Data Edit and Remove functions are performed by and buttons respectively. The
following message box is shown in case of removing user defined data.
92
93
94
3) S/W Information
- Execution of LS Power Solution information command of pull-down help menu has the flowing
window displayed.
- Users can move to LS Industrial systems website (http://www.lsis.biz) and get technical data and
information on LSIS products.
95
96
Global Networks
Tokyo, Japan
LS Industrial Systems Tokyo Office
Dalian, China
Dalian LS Industrial Systems Co.,Ltd
Beijing, China
LS Industrial Systems Beijing Office
Qingdao, China
LS Industrial Systems Qingdao Office
Dubai, U.A.E.
LS Industrial Systems Dubai Rep. Office
Chengdu, China
LS Industrial Systems Chengdu Office
Hanoi, Vietnam
LS-VINA Industrial Systems Co.,Ltd
LS Industrial Systems Hanoi Office
Wuxi, China
LS Industrial Systems (Wuxi) Co., Ltd.
Shanghai, China
LS Industrial Trading (Shanghai) Co., Ltd
LS Industrial Systems Shanghai Office
Guangzhou, China
LS Industrial Systems Guangzhou Office
LS Industrial Systems International Trading (Shanghai) Co., Ltd. >> Shanghai, China
Address: Room 1705-1707, 17th Floor Xinda Commercial Building No 322,
Xian Xia Road Shanghai, China
Tel: 86-21-6278-4291 Fax: 86-21-6278-4372 e-mail: [email protected]