AMB AMC Machine Description
AMB AMC Machine Description
127,&(
The information in this document is subject to change without notice and should not be construed as a commitment by ABB.
ABB assumes no responsibility for any errors that may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising
from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software
or hardware described in this document.
This document and parts thereof must not be reproduced or copied without ABBs written permission, and the contents thereof
must not be imparted to a third party nor be used for any unauthorized purpose.
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
7DEOHRI&RQWHQWV
7DEOHRI&RQWHQWV
&KDSWHU%DVLFGHVLJQIHDWXUHV
1.1
1.2
General ..................................................................................................... 3
1.3
1.4
1.5
1.6
1.7
Design Standards.................................................................................... 12
1.7.1
1.7.2
1.7.3
1.7.4
&KDSWHU0RXQWLQJFRROLQJ SURWHFWLRQ
2.1
2.2
Methods of Ventilation............................................................................. 15
2.3
2.2.1
General .................................................................................... 15
2.2.2
2.3.2
2.3.3
2.3.4
2.3.5
2.3.6
2.3.7
2.3.8
2.3.9
2.3.10
2.3.11
2.3.12
&KDSWHU)UDPHVWDWRUFRUHDQGHQGVKLHOGV
3.1
Housing................................................................................................... 26
3.2
3.3
&KDSWHU%HDULQJVDQGOXEULFDWLRQ
4.1
3BSM900026, en
4.1.2
4.1.3
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
7DEOHRI&RQWHQWV
4.2
4.2.2
&KDSWHU6KDIWURWRUFRUHVKDIWH[WHQVLRQ
5.1
Shaft........................................................................................................ 43
5.2
5.3
Shaft Extension....................................................................................... 44
&KDSWHU:LQGLQJDQGLQVXODWLRQ
6.1
Stator Winding......................................................................................... 47
6.2
&KDSWHU3RZHUFRQQHFWLRQV
7.1
&KDSWHU1RLVHOHYHOV
&KDSWHU'LUHFWLRQRIURWDWLRQ
9.1
9.2
9.3
&KDSWHU5XQQLQJTXDOLW\
10.1 Balancing ................................................................................................ 56
10.2 Vibration Severity .................................................................................... 57
10.2.1
10.2.2
10.2.3
&KDSWHU$QWLFRUURVLRQSURWHFWLRQ
11.1 Standard paint system ............................................................................ 62
11.1.1
11.1.2
11.1.3
11.1.4
11.2.2
11.2.3
11.2.4
11.2.5
&KDSWHU2XWSXWVIRUGHYLDWLRQVIURPQRUPDOFRQGLWLRQV
12.1 Site Conditions........................................................................................ 67
3BSM900026, en
II
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
7DEOHRI&RQWHQWV
&KDSWHU7HPSHUDWXUHFODVV)
13.1 Formulas ................................................................................................. 70
13.2 Example .................................................................................................. 70
&KDSWHU%HKDYLRXUGXULQJVZLWFKLQJDQGFRQYHUWHUIHG
RSHUDWLRQ
14.1 Mechanical Behaviour During Switching Operations .............................. 72
14.2 Mechanical Behaviour During Converter-fed Operation ......................... 72
&KDSWHU5HPDUNVRQGHVLJQIRUFRQYHUWHUIHGPDFKLQHV
15.1 Insulation................................................................................................. 73
15.2 Bearings.................................................................................................. 73
15.3 Speed monitoring .................................................................................... 73
15.4 Separate ventilation ................................................................................ 73
15.5 Noise....................................................................................................... 74
15.6 Critical speed .......................................................................................... 74
15.7 Terminal connections for machines with two stator windings.................. 74
15.8 Oscillating Torques.................................................................................. 74
&KDSWHU0DFKLQHVIRUPDULQHDQGRIIVKRUHDSSOLFDWLRQV
16.1 Marine Application .................................................................................. 75
16.1.1
16.1.2
16.1.3
16.1.4
16.1.5
Accessories ............................................................................. 76
16.2.2
16.2.3
16.2.4
Accessories ............................................................................. 77
&KDSWHU7RUVLRQDOVSULQJFRQVWDQW,0
17.1 AMB 710 ................................................................................................. 78
17.2 AMC ........................................................................................................ 79
&KDSWHU7HVWV
18.1 Routine Tests .......................................................................................... 80
18.2 Type Tests............................................................................................... 80
18.3 Special Tests ........................................................................................... 81
3BSM900026, en
III
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
,QIRUPDWLRQRQVFRSHRIVXSSO\
The following information on scope of supply are valid for machine types AMB710 and
AMC800, 900, 1000 and 1120 delivered from ABB ATDM/M Vasteras factory.
3URGXFWVQRWDYDLODEOH
2-Pole Motors
2-Speed Motors
In some cases the above design are avialable from other factories within ABB, enquiries should
be sent to Vasteras for further distribution.
/LPLWDWLRQVRIVORZVSHHGPDFKLQHV
AMB710, AMC800 and AMC900 machines in combination with very high pole number
can only be manufactured after approval from factory.
7KHIROORZLQJFRPELQDWLRQVVKRXOGDOZD\VEHVHQWWRWKHIDFWRU\EHIRUH
TXRWDWLRQ
7HVWILHOGOLPLWDWLRQV
3BSM900026, en
Combined test with converter and motor or active load testing for VSD projects can not be
performed at ABB ATDM/M Vsters factory. The test must be discussed with the factory
before quoted. Combined tests can be performed close to and in cooperation with ABB
converter manufacturer.
The are limitations in test field power for heat run test according to the 2-frequency
method: <7kV maximum 1000A, 7<14kV maximum 500 A.
1-1
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
0DFKLQHVIRUKD]DUGRXVHQYLURQPHQWSHU([H([S([QDQG&ODVV,GHVLJQ
In general, Exp design is preferred in lieu of Exe design.
Exe is available in special cases up to a maximum rated voltage of 7.2 kV, IEC tolerance per
zone B. For higher voltages Exe design is not available.
Exn is available in special cases up to a maximum rated voltage of 11.5 kV, IEC tolerance per
zone A. For higher voltages Exn design is not available.
Class I division 2 is available in special cases up to a maximum rated voltage of 13.2 kV r 10%
as per NEMA MG1 20.5 20.14. For higher voltages Class I division 2 design is not available.
All inquires calling for Exe, Exn and Class I division 2 design shall be forwarded to the factory.
0DFKLQHVSHU$3,DQG6KHOO'(3VWDQGDUG
API 541 and Shell DEP machines are always studied case by case. All inquiries shall be
forwarded to the factory.
/RZYROWDJHPDFKLQHV
Enquiries including motors with voltage below 690 V or current above 2120 should always be
sent to factory for review.
3BSM900026, en
1-2
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
*HQHUDO
7KH$0%DQG$0&6HULHVLVFKDUDFWHUL]HGE\WKHIROORZLQJPDLQIHDWXUHV
Robust construction
High efficiency
According to speed and rotor weight only forced lubricated sleeve bearings may be
applicable (please see section Bearings and Lubrication for detailed information)
Degrees of protection IP23 to IP54 or WPI, WPII, TEAAC and TEWAC to NEMA MG1,
with corresponding attachments (ventilation unit, weather protection unit, air-water heat
exchanger, air-air heat exchanger, interfaces for ventilation ducts)
Ventilation:
All machines are self ventilated. Forced ventilated machines on request.
$0%
Horizontal four-pole machines have symmetrical (bilateral) ventilation, machines with a
higher number of poles have asymmetrical (unilateral) ventilation.
$0&
All machines are symmetrically ventilated.
Design standards: IEC 60034, IEC 60072A (interface dimensions), and those national
standards adapted to IEC, NEMA MG1
IM 1001: 2 endshield bearings, stator frame with feet, 1 shaft extensions, horizontal design.
IM 1002: 2 endshield bearings, stator frame with feet, 2 shaft extensions, horizontal design.
IM 4011: 2 endshield bearings, stator frame without feet, 1 shaft extensions with flange at
D-end, vertical design.
IM 1205: 1 endshield bearing, stator frame with feet, 1 shaft extensions with flange at D-end.
IM 7005: 1 pedestal bearing, stator frame with feet, 1 shaft extensions with flange at D-end.
3BSM900026, en
1-3
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
6WDQGDUG0DFKLQHV2YHUYLHZ
The following overview enables a check to be made whether or not the standard design covers
the specified requirements, or whether extra costs must be reckoned with due to deviations.
Ventilation:
Bearings:
Shaft extension:
$0%
One cylindrical, keyed shaft extension ISO-long (Diameter according to outline drawing).
$0&
One shrink fit stepped extension, ISO-short.
Fitting the coupling hub is not included as standard.
Degree of protection
IC611, IC81W, IC31:
IP54.
Terminal box:
Direction of rotation:
Installation:
Heat exchanger:
3BSM900026, en
1-4
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
3BSM900026, en
Monitoring:
Antifriction bearings:
Sleeve bearings:
Space heater:
1-5
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
2XWSXW5DQJHVRI$0%0DFKLQHV
127( VKDGHGFROXPQVRQUHTXHVWRWKHUYROWDJHVXSWRN9RQUHTXHVW
VHHWHFKQLFDOGDWDOLVWIRUGHWDLOV
7DEOH +],&,&:,0,02XWSXWVLQN:,(&PHWULF
1XPEHURISROHV
N9
N9
N9
N9
1)
2500 - 7100
2780 - 9600
2260 - 8500
,0
2000 - 7100
2250 - 7400
1600 - 6800
1600 - 5600
1650 - 5680
1250 - 5000
1120 - 5000
1410 - 4500
1080 - 4000
900 - 4000
960 - 3650
760 - 3080
630-2500
560-2240
560-2240
560-2000
500-2000
450-1800
630-1600
800-1400
,0
N9
N9
N9
N9
1)
2500 - 6300
2560 - 7800
1790 - 6800
,0
1800 - 6300
1850 - 6300
1450 - 5600
1400 - 4900
1475 - 4550
1310 - 4020
1000 - 4000
1050 - 3700
1050 - 3250
800 - 3350
830 - 2950
640 - 2540
560-2240
500-2000
500-1800
500-1800
450-1600
400-1600
560-1400
710-1250
,0
1)
3BSM900026, en
1-6
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
N9
N9
N9
1)
3000 - 9600
3430 - 9600
2630-8100
1920-6000
(IM1001)
2400 - 8500
2600 - 9000
1850-7900
1200-6000
(IM4011)
2400-60002)
2400 - 6000
1680-6000
1200-4800
1920 - 6720
1780 - 7000
1550-5900
2)
1360 - 6000
1530 - 5550
1280-4800
2)
1080 - 4800
1120 - 4500
820-3800
2)
755-3360
670-2680
670-2680
670-2400
600-2400
540-2160
755-1920
960-1680
N9
N9
N9
N9
1)
3000-7550
2980-7550
2400-6800
1680 - 5400
(IM1001)
2160-7550
2600-7550
1800-6600
1080 - 5400
(IM4011)
2160-54002)
2160-5400
1500-4800
1080 - 4250
1680-5850
1600-5400
1320-4720
2)
1200-4800
1480-4600
1020-3650
2)
850-3780
930-3520
710-2900
2)
670-2680
600-2400
600-2160
600-2160
540-1920
480-1920
670-1680
850-1500
1)
2)
3BSM900026, en
N9
1-7
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
N9
N9
N9
N9
1)
4020-12900
4600-12900
3530-10870
2580-8050
(IM1001)
3220-11400
3490-12070
2480-10600
1610-8050
(IM4011)
3220-80502)
3220-8050
2250-8050
1610-6440
2580-9010
2390-9400
2080-7910
2)
1820-8050
2050-7440
1720-6440
2)
1450-6430
1500-6040
1100-5100
2)
1010-4510
900-3590
900-3590
900-3220
800-3220
720-2900
1010-2580
1290-2250
N9
N9
N9
1)
4030 10130
4000 10130
3220 9130
2260 7250
(IM1001)
2900 10130
3490 10130
2420 8860
1450 7250
(IM4011)
2900 - 72502)
2900 7250
2010 6440
1450 7500
2250 7850
2150 7250
1770 6340
2)
1610 6440
1990 6170
1370 4900
2)
1140 5070
1250 4720
950 3890
2)
900 3600
800 3220
800 2900
800 2900
720 2580
640 2580
900 2250
1140 - 2010
1)
2)
3BSM900026, en
N9
1-8
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
2XWSXW5DQJHVRI$0&0DFKLQHV
127( VKDGHGFROXPQVRQUHTXHVWRWKHUYROWDJHVXSWRN9RQUHTXHVW
9HUWLFDOPRWRUVRQUHTXHVW
7DEOH +],&,3,3:,&:,02XWSXWVLQN:,(&PHWULF
1XPEHURISROHV
N9
N9
N9
N9
11200 - 14000
10000 - 18000
9000 - 18000
7100 - 16000
8000 - 16000
7100 - 16000
6300 - 14000
5600 - 12500
6300 - 14000
5000 - 12500
5600 - 11200
5000 - 10000
5000 - 14000
4500 - 12500
4500 - 9000
3550 - 8000
4000 - 14000
3150 - 10000
3150 - 7100
2500 - 6300
2800 - 12500
2500 - 7100
2500 - 10000
2240 - 7100
2000 - 10000
1600 - 5600
1400 - 7100
1600 - 6300
1250 - 6300
1800 - 4500
1000 - 5600
2500 - 5000
N9
N9
9000 - 10000
9000 - 11200
7100 - 12500
6300 - 12500
5600 - 11200
4500 - 10000
4500 - 12500
3550 - 11200
3550 - 12500
2800 - 9000
2500 - 11200
2240 - 6300
2240 -9000
2240 - 6300
1800 - 9000
1600 - 5000
1250 - 6300
1600 - 5600
1120 - 5600
1800 - 4000
900 - 5000
2240 - 4500
3BSM900026, en
N9
N9
1-9
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
N9
N9
N9
13050 - 16320
13050 - 16320
11560 - 14690
13050 - 26110
11560 - 22840
9140 - 20390
10270 - 20390
9140 - 19360
8160 - 16320
8160 - 16320
6530 - 16320
5790 - 13050
6800 - 13050
5780 - 11560
4080 - 10280
4570 - 11560
4080 - 8160
3640 - 9140
3640 - 10270
2940 - 10270
2610 - 9140
2040 - 9140
3260 - 10270
2040 - 10270
3260 - 7340
1470 - 9140
4080 - 8160
N9
N9
N9
12900 - 14480
11400 - 12900
9010 - 11400
11560 - 20390
9140 - 18360
8160 - 16320
8160 - 18360
7340 - 16320
5780 - 14680
7340 - 14680
5140 - 11560
4570 - 10270
5780 - 10270
4080 - 9140
3640 - 8160
4080 - 10270
3640 - 7340
3260 - 8160
3260 - 10270
2610 - 9140
2610 - 8160
1840 - 8160
2940 - 9140
1850 - 9140
3260 - 6530
1310 - 8160
3640 - 7340
3BSM900026, en
1-10
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
7\SH'HVLJQDWLRQ
Within the BU AC-machines the type designations have been standardized. The type
designation of the AMB- and AMC machines follows this standardization. The individual
symbols of the designation are explained below.
([DPSOH$0%/'%67)9
1.
$0
Standard for the BU, i.e., here $lternating Current 0achines. Two letters.
2.
3.
4.
5.
6.
'
7.
=
=
=
=
IC01/IP23(WP I)
IC01/IPW24(WP II)
IC11,21,31/IP23,54(55)
IC411/IP54(55)
8.
6
7)
3BSM900026, en
S = Sleeve
10. 9
V = Vertical
9.
L = IC81W/IP54(55)
A = IC611/IP54(55)
T = IC511/IP54(55)
H = Helsinki
V = Vsteras
M = Vittuone (Milan)
1-11
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
'HVLJQ6WDQGDUGV
%DVLFFDWDORJXHPDFKLQHVIURP+]OLVWRU+],(&PHWULFOLVW
The basic AMB 710- and AMC machines listed in the technical datalist fulfill the requirements
of the latest applicable IEC standards. The most important of these are:
67$1'$5'
68%-(&7
IEC 60027
Letter symbols
IEC 60034-1
IEC 60034-2
Determination of efficiency
IEC 60034-5
IEC 60034-6
IEC 60034-7
IEC 60034-8
IEC 60034-9
Noise limits
IEC 60034-14
Vibration severity
IEC 60034-15
IEC 60072-2
IEC 60085
NBN 7
Belgium
NFC 51-111
France
BS 4999/5000
United Kingdom
CEI 2-3
Italy
3BSM900026, en
NEN 3173
Netherlands
SEN 260101
Sweden
1-12
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
$FFRUGLQJO\WKHIROORZLQJSUHUHTXLVLWHVDUHDSSOLFDEOHWRWKHOLVWPRWRUVGHVLJQHGWR,(&
Site conditions:
+/- 20 %
+ 10 % of the losses
- (1-PF) / 6
(min. 0.02, max. 0.07)
- 10 %
- 15/+ 25 %
+ 20 %
Start-up:
approximately 50000
Starting times:
Efficiency:
$0%
Friction losses are calculated on four pole machines for sleeve
bearings, on other machines for antifriction bearings.
$0&
Friction losses always calculated for sleeve bearings.
3BSM900026, en
Direction of rotation:
Overspeed:
The overspeed value must not exceed 1.2 times rated speed.
1-13
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %DVLFGHVLJQIHDWXUHV
&DWDORJXHPDFKLQHVIURPWKH+]1(0$$PHULFDQXQLWVOLVW
The performance of the machine fulfills the requirements of
NEMA MG1 Part 1
Terminal Markings
ANSI C50.41
2WKHUVWDQGDUGV
AMB 710 - and AMC-machines may also be quoted to conform with other national or
indudstrial standards.
0DULQHDQGRIIVKRUH
AMB 710 - and AMC-machines can be quoted for marine and off-shore applications to meet the
requirements of any classified authority, e.g.:
ABS
BV
Bureau Veritas
DNV
GL
Germanischer Lloyd
LRS
URS
RINA
,QIRUPDWLRQRQORFDOUHTXLUHPHQWV
The regional sales offices are requested to continuously furnish information on such local
requirements which deviate essentially from the IEC standards or which are not considered to
be common knowledge. ABB factory has a standards collection which is updated continuously.
It will make the response time shorter if there is a ready-made deviation list available when an
inquiry calls for an exceptional standard.
3BSM900026, en
1-14
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
6WDQGDUG0RXQWLQJ$UUDQJHPHQWVLQDFFRUGDQFHZLWK,(&
+RUL]RQWDOPDFKLQHV
Code I: IM B3
Code II: IM 1001
Foot-mounted machine with
2 endshield bearings.
9HUWLFDOPDFKLQHV:
Code I: IM V10
Code II: IM4011
Flange-mounted machine with 2 endshield
bearings.The flange is an integral part of
the frame.
0HWKRGVRI9HQWLODWLRQ
*HQHUDO
All machines are self-ventilated.
In order to achieve a good efficiency the fans are designed with shaped blades and are therefore
unidirectional. Designs with straight blades (for both directions of rotation) result in a lower
efficiency and a possible reduction in rated output of up to approximately 7 % and in an increase
of noise.
Forced ventilated machines on request.
3BSM900026, en
2-15
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
2YHUYLHZRIPHWKRGVRIYHQWLODWLRQ
An overview is presented in the following table:
Standard methods of ventilation, number of internal fans
0: Symmetrical without fan (bidirectional, except IC 611)
2: Symmetrical with two fans (unidirectional, option bidirectional)
1: Asymmetrical with one fan on the D-end (unidirectional, option bidirectional)
Air-air cooled machines have one external fan in addition to the internal fans
7DEOH
0RXQWLQJ
7\SH
$0%$0&
1XPEHURI3ROHV
+RUL]RQWDO
9HUWLFDO
+RUL]RQWDO
+RUL]RQWDO
+RUL]RQWDO
+RUL]RQWDO
3BSM900026, en
2-16
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
)LJXUH 6\PPHWULFDOZLWKRXWIDQ
)LJXUH6\PPHWULFDOZLWKWZRIDQV
)LJXUH$V\PPHWULFDOZLWKRQHIDQDWWKH'HQG
3BSM900026, en
2-17
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
&RROLQJDQG3URWHFWLRQ
0DFKLQHVDFFRUGLQJWR,(&DQG1(0$0*
The standard for methods of cooling is IEC 60034-6 and the standard for degrees of protection
provided by enclosures is IEC 60034-5.
The following tables give an overview on standard design with corresponding IEC and NEMA
designation.
7DEOH
7\SHDFFRUGLQJWR,(&
7\SHDFFRUGLQJWR1(0$0*
IC01/IPW24
1.25.8.2, WPII
IC31/IP54
1.26.4, TEPV
IC611/IP54
1.26.8, TEAAC
IC81W/IP54
1.26.7, TEWAC
7DEOH$YDLODEOHRSWLRQVDUH
7\SHDFFRUGLQJWR,(&
7\SHDFFRUGLQJWR1(0$0*
3URWHFWLRQRI0DFKLQH3DUWV
The terminal boxes always have a protection of at least IP55. The bearings normally have the
protection IP54.
0DUNLQJVRQWKH5DWLQJ3ODWH
The degree of protection and the cooling method are indicated on the rating plate.
'HVLJQVIRUFRQYHUWHUIHGRSHUDWLRQ
On converter-fed drives, when a constant torque and a wide speed regulation range are needed,
the internal fan and/or the external fan have to be replaced by separately driven fan(s).
3BSM900026, en
2-18
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
AMC
Weather-protected machine acc. to IEC 60034-5. The machine is protected against splashing
water from any direction. The ingress of rain, snow and airborne particles into the electrical
parts is reduced. The air intake path with filters provides for an area of average velocity not
exceeding 3 m/s, enabling particles to settle. The air intake path also provides for three abrupt
90 changes in the direction of the air flow and at the discharge side the air path has two abrupt
changes. For symmetrically ventilated machines the air outlet is always located on the opposite
side of the terminal box.
6WDQGDUG
Inlet filter: synthetic material, washable, dedusting efficiency (Am according to EN779) 83 %,
dust holding capacity 500g/m2, filter frame of galvanized steel, filter monitoring with
differential pressure switch.
2SWLRQ
3BSM900026, en
Filter in stainless steel, dedusting efficiency 73%, dust holding capacity 500 g/m2.
2-19
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
AMC
AMC
Inlet and outlet pipe or duct using remote cooling air (Connecting faces on top). The machine is
dust protected and is also protected against splashing water from any direction.
2SWLRQV
,& (i.e. IC1A1), ,3 Inlet pipe or duct, using remote cooling air.
,& (i.e. IC2A1), ,3 Outlet pipe or duct, using surrounding air.
The machine may be operated at rated output without the need for a separate fan in the duct
system if the pressure drop in the ducts does not exceed the value given in the following table:
3BSM900026, en
2-20
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
7DEOH3HUPLVVLEOHSUHVVXUHGURSLQWKHYHQWLODWLRQGXFWVIRUFRROLQJPHWKRG,&DQG+]RSHUDWLRQ
)RU+]RSHUDWLRQPXOWLSO\WKHYDOXHVRISUHVVXUHGURSE\DQGWKRVHRIWKHDLUIORZUDWHVE\
3HUPLVVLEOHSUHVVXUHGURSLQ>3D@
DQGFRROLQJDLUIORZUDWHVLQ>PV@
1RRISROHV
0
0
;
;
220 (4.4)
120 (6.3)
480 (11.7)
280 (4.2)
90 (5.6)
130 (7.2)
200 (3.5)
70 (4.9)
130 (7.3)
130 (2.9)
80 (5.0)
80 (5.8)
70 (6.7)
95 (2.4)
110 (6.8)
70 (5.0)
60 (7.5)
90 (10.1)
40 (4.1)
60 (4.7)
60 (7.2)
80 (9.6)
40 (3.9)
40 (4.6)
40 (6.2)
50 (7.4)
30 (3.3)
30 (4.0)
30 (5.3)
50 (7.5)
20 (2.9)
20 (3.0)
30 (5.0)
30 (6.0)
20 (2.6)
20 (3.2)
20 (4.4)
30 (5.7)
20 (2.4)
20 (2.9)
20 (4.4)
30 (5.6)
3BSM900026, en
2-21
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
AMC
The machine is totally enclosed having a machine-mounted air-to-air heat exchanger. The
machine has a shaft-mounted external fan to convey the air in the external secondary cooling
circuit. The machine is dust protected and also protected against splashing water from any
direction.
Heat exchanger tube material in standard design: Aluminum alloy
Fan: Welded construction for four-pole machines and above.
2SWLRQV
3BSM900026, en
Resistance temperature detector (Pt100), 3 or 4-wire design, to monitor the cold and/or
warm air temperature
2-22
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
AMC
The machine is totally enclosed having a machine-mounted air-to-water heat exchanger. The
machine is dust protected and is also protected against splashing water from any direction.
6WDQGDUG
Design with one (AMB 710) or two (AMC) cooling elements for fresh water (salt content 1
g/dm3, sulphide 0.05 mg/dm3, ammonia 1.0 mg/dm3, suspended matter 100 mg/dm3,
oxygen ! 3 mg/dm3) with cooling tubes in copper and cooling fins in aluminum alloy. Tube
plates in steel, water chambers in steel with Rilsan coating, leakage water catch tray with drain.
Rigid water connection points with DIN or ANSI flanges.
3BSM900026, en
10 bar
27C
6K
2-23
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
2SWLRQV
Cooling element for saliferous to extremely saliferous water, or for other aggressive
secondary coolants according to a project water analysis.
Leakage detectors
Resistance temperature detector (PT100) 3- or 4-wire design to monitor the cold and/or
warm air temperature.
A water inlet temperature at 27C requires the following water flow rate
(according to a water temperature rise of 6 K)
0D[LPXPFRROLQJZDWHUIORZUDWHLQ>PK@DVDIXQFWLRQRISROH
QXPEHU
7\SH
31.9
26.2
23.0
20.3
17.7
17.7
17.7
17.7
17.7
17.7
17.7
42
34
34
34
24
24
24
18
18
18
18
64
48
48
48
30
30
30
24
24
24
24
42
38
38
38
38
38
38
38
50
50
40
40
40
40
40
3BSM900026, en
2-24
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0RXQWLQJFRROLQJ SURWHFWLRQ
7KHUPDOWLPHFRQVWDQWDWIXOOVSHHG
To estimate the temperature rise, caused by a temporary overload, the time constants given in
the next table, in dependence of method of cooling and pole number, can be used.
7DEOH7KHUPDO7LPH&RQVWDQWV
7\SH
&RROLQJ
710
710
1XPEHURISROHV
4
IC01, IC81W
25 min.
33 min.
35 min.
IC611
35 min.
45 min.
50 min.
800 1120
on request
3URWHFWLRQRIPDFKLQHSDUWV
The terminal boxes always have a protection of at least IP55. The bearings normally have the
protection IP54.
0DUNLQJVRQWKHUDWLQJSODWH
The degree of protection and the cooling method are indicated on the rating plate.
'HVLJQVIRUFRQYHUWHUIHGRSHUDWLRQ
On converter-fed drives, when a constant torque and a wide speed regulation range are needed,
the internal fan and/or the externel fan have to be replaced by separately driven fan(s).
3BSM900026, en
2-25
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU )UDPHVWDWRUFRUHDQGHQGVKLHOGV
&KDSWHU )UDPHVWDWRUFRUHDQGHQGVKLHOGV
+RXVLQJ
The housing is a torsionally rigid welded construction. The stator is fitted into two ribs within
the housing and doweled to safely withstand the short-circuit forces. The two end ribs are
provided with spigot seatings for the bearing endshields. Clearance holes for fastening the
machine to the foundation are located close to the bearing endshields in order to obtain
maximum possible flexural rigidity. Jacking bolts and angled faces for drilling the dowel holes
are provided in the feet to facilitate alignment and installation on site. There is an opening,
according to DIN 42962, at each side at the N-end for fitting a terminal box.
An earthing boss with a milled seat for the cable connection is provided at each side below the
terminal box opening. On horizontal machines the air inlet and outlet openings are on the top.
$0%
The laterally located lifting lugs protrude far enough to enable the machine to
be lifted on the crane even when the top-mounted attachments are fitted (heat
exchanger, ventilation or weather protection unit).
$0&
6WDWRU&RUH3DFN
The AMB-stator core is built up from single-piece annular laminations, the AMC-stator core is
built up from segmented laminations, both of varnish-insulated electrical sheet steel and is
subdivided into packages by radial ventilation ducts. The laminated core is pressed together in
both yoke and tooth regions by generously dimensioned press plates which are joined together
by welded tie bars. The core is rigidly secured into the housing in spigot seatings between the
press plates and the housing ribs.
%HDULQJ(QGVKLHOGV
The bearing endshields are of single piece design and are manufactured from steel plate. They
are located into concentric spigots in the housing end ribs to which they are securely bolted.
3BSM900026, en
3-26
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
+RUL]RQWDO0RXQWLQJ
5HFRPPHQGHG%HDULQJ$UUDQJHPHQW
$0%
The recommended bearing arrangement for AMB machines is shown inthe next table. All
sleeve bearings can be connected to a separate oil supply system when needed.
7DEOH $0%UHFRPPHQGHGEHDULQJDUUDQJHPHQWIRU7DPE &
7\SH
'LDPRI
6KDIWH[W
>PP@
6SHHG>UPLQ@
d
180
SF-A
SF-A
200
SF-A
SF-A
220
SF-A
A-OS
SF-A:
SS-O:
3BSM900026, en
4-27
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
$0&
Always sleeve bearings as standard.
7DEOH $0&UHFRPPHQGHGEHDULQJDUUDQJHPHQWIRU7DPE &6SHHG>UPP@
7\SH6SHHG
800
SF-A
SF-O
SS-O
SS-O
SS-O
900
SF-A
SF-A
SS-O
SS-O
SS-O
SF-O
SS-O
1000
SF-O
1120
SF-A:
SS-O:
SF-O:
Sleeve bearing forced lubric. / Option: Antifriction bearings, check lubrication interval
$QWLIULFWLRQ%HDULQJ
Each bearing is provided with a DIN grease nipple for relubrication, a grease regulator, and a
used grease chamber. Refer to the Maintenance Instructions for recommended lubricants.
Each bearing is also provided with a SPM nipple-thread.
On machines with IC611 cooling the N-end grease nipple is brought out for better accessibility.
3BSM900026, en
4-28
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
7DEOH 6WDQGDUGW\SHVRIDQWLIULFWLRQEHDULQJV
7\SH
'LDPRI
6KDIWH[W>PP@
'HQG
1HQG
220
NU248E.M1.C3 / 6048M.C3
NU238E.M1.C3
280/265
NU1060M1.C3 / 61960M.C3
NU1060M1.C3
300/285
NU1064M1.C3 / 61964M.C3
NU1064M1.C3
320/300
NU1068M1.C3 / 61968M.C3
NU1068M1.C3
340/320
NU2072E.M1.C3 / 61972M.C3
NU2072E.M1.C3
3HUPLVVLEOH$[LDO7KUXVW
The next table shows the maximum permissible axial thrust for the different machines. The
minimum calculated bearing life L10 (ISO 281/1) is 100000 operating hours.
7DEOH 3HUPLVVLEOHD[LDOWKUXVWIRUDQWLIULFWLRQEHDULQJV
7\SH
3HUPLVVLEOHD[LDOWKUXVWLQ>N1@DVDIXQFWLRQRIVSHHG>UPLQ@
5.8
6.1
6.5
6.6
7.1
10.3
11.0
11.4
12.1
12.2
13
13.9
14.9
14.9
15.4
16.5
17.5
11.7
12.4
12.5
13.3
14.2
14.7
15.2
15.8
16.8
17.9
12.8
13.5
14.4
14.9
15.5
16.0
17.1
18.2
14.0
14.9
15.5
16.1
16.6
17.7
18.8
3BSM900026, en
4-29
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
/XEULFDWLRQ
The next table shows the lubrication intervals, which are largely dependent on speed, as given
by the bearing manufacturer for a bearing operation temperature of 70C and for standard
lithium soap based greases.
7DEOH /XEULFDWLRQLQWHUYDOVDW&EHDULQJWHPSHUDWXUH
/XEULFDWLRQLQWHUYDOLQKRXUVDVDIXQFWLRQRIVSHHG>UPLQ@
7\SH
2400
2700
3500
3700
4500
5500
1400
1900
2000
2700
2900
3700
4600
5000
5900
6600
7800
9300
2000
2600
2700
3400
4300
4800
5500
6100
7400
8900
2500
3100
4000
4400
5200
5700
7000
8300
3000
3700
4300
4800
5300
6600
7900
To obtain the lubrication interval for the actual operation conditions the value from table 4-5 has
to be multiplied by the factor f.
f = f0 + f1 + k f2
f0
f1
f2
= (40 - -amb) / 30
(-amb : average ambient temperature in C at operating
location over a period of 3 months)
3BSM900026, en
4-30
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
7DEOH
)DFWRUIDVDIXQFWLRQRIVSHHG>UPLQ@
7\SH
0.75
0.37
0.47
0.55
0.73
0.77
1.0
1.0
1.0
1.0
1.0
0.40
0.60
0.60
0.87
0.87
1.0
1.0
1.0
1.0
1.0
0.53
0.73
0.87
0.93
1.0
1.0
1.0
1.0
0.60
0.77
0.87
1.0
1.0
1.0
0.43
0.87
0.90
0.97
1.0
The lubrication intervals for the four-pole and a part of the six-pole machines are relatively
short and lie below the values specified in some of the national standards (e.g. Germany:
Additional delivery requirements for high-voltage electrical motors for power stations: 4000
hours for four-pole machines). In cases where such requirements apply, sleeve bearings should
be provided.
6WDQGDUG
The antifriction bearings are always locked for transport (D- and N-End). This is indicated
by a warning label permanently attached to the machine
2SWLRQV
3BSM900026, en
Temperature monitoring on the two main bearings can be included when explicitly
requested. (Pt100 resistance temperature detector in 3 or 4-wire design to measure the
temperature of the outer ring)
The N-end bearing, or both if desired, can be insulated on request. The insulation would be
located in the bearing endshield between the inner and outer ring
4-31
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
6OHHYH%HDULQJV
The sleeve bearings are the flange-mounted type in accordance with DIN 31693. 4 pole AMCs
have center flange-mounted bearings acc. to DIN 31694 . 50 Hz machines have cylindrical
sleeve shells, 60 Hz machines have 4 lobe sleeve shells.
The bearing housing is manufactured in high grade cast iron and is designed for heavy duty
performance. The bearing shells are spherically seated in the housing.
The housing, seals and oil-ring are all in split design. This enables the bearing shells and seals to
be dismantled without uncoupling the machine. Both bearings have the same diameter.
AMC 4 pole with 4 lobe sleeve shells are without oilring!
Note: No emergency oil function on these bearings.
On the standard design, both bearings are non-locating (Bearing end float +/- 6.5 mm). It is
assumed that axial guidance of the shaft train is provided by the driven equipment or gearbox.
(Locating bearing see options.)
3BSM900026, en
4-32
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
7\SH
3ROHV
'LDPRI
6KDIW
H[W>PP@
'HQG
1HQG
200
FZLB 18-200
FZLQ 18-200
6...12
220
F*LB 18-225
F*LQ 18-225
4 / 50 Hz
250 / 235
MZLB 22-250
MZLQ 22-250
4 / 60 Hz
250 / 235
MZVB 22-250
MZVQ 22-250
6-24
280/265
F*LB 22-280
F*LQ 22-280
4 / 50 Hz
250 / 235
MZLB 22-250
MZLQ 22-250
4 / 60 Hz
250 / 235
MZVB 22-250
MZVQ 22-250
6-24
300/285
F*LB 22-300
F*LQ 22-300
10-24
320/300
F*LB 28-355
FNLQ 28-355
12-24
340/320
F*LB 28-355
FNLQ 28-355
3BSM900026, en
If sleeve bearings are to be used below 200 rpm, jacking oil is recommended.
4-33
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
VSHHG
>UPLQ@
,629*
T>OPLQ@
3>N:@
3600
3000
1800
1500
1200
1000
32
32
46
46
46
46
11
10
6
5
10
9
5.3
4.1
3.2
2.5
2.6
2
1800
1500
1200
1000
900
46
46
46
46
46
20
16
11
10
10
8.7
5.0
4.7
3.7
3.4
1500
1200
1000
900
750
46
46
46
46
46
16
13
12
11
9
6.1
5.4
4.3
3.7
2.9
720
46
18
5.4
600
46
17
4.7
3BSM900026, en
7\SH
VSHHG>UPLQ@XSWR
3HUPLVVLEOHD[LDOWKUXVW>N1@
1800
1800
12
720
14
600
14
4-34
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
In the event of failure of the lube oil system, lubrication will be provided by the built-in lube oil
rings, for operation at rated speed without inadmissible bearing temperature rise for the times
indicated in the following tables.
Note, that AMC 4-pole machine do not have emergancy oil ring.
7DEOH $SSUR[HPHUJHQF\UXQQLQJWLPHVLQFDVHRIIDLOXUHRIOXEHRLOVXSSO\V\VWHP
3HUPLVVLEOHHPHUJHQF\UXQQLQJWLPHVLQPLQ
UHODWHGWRIUDPHVL]HDQGUDWHGVSHHG>UPLQ@
7\SH
12
12
12
4 lobe
bearing *)
12
12
12
12
12
12
15
15
15
15
15
15
*) The AMC-machines with 4 lobe bearings have an emergency running time of 3 seconds. Make sure that in case of
failure of the oil supply system a backup system (second pump and for net independent power, or safety oil tank)
will start within 3 seconds.
([SHFWHGRLOILOPWHPSHUDWXUHVDW&DPELHQWZLWKRXWWKUXVWORDGV
QRQORFDWLQJEHDULQJDUUDQJHPHQWUHODWHGWRIUDPHVL]HDQGUDWHGVSHHG>UPLQ@
7\SH
62
60
65
62
53
64
63
60
58
64
63
60
58
84
78
77
71
66
87
85
78
73
89
81
75
92
85
88
51
95
56
57
90
55
102
55
98
3BSM900026, en
54
forced lubricated
self cooling
4 lobe bearing
89
4-35
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
6WDQGDUG
The standard degree of protection is IP54. An additional seal in split design is always
provided on the machine-side of the bearing in order to avoid the adverse effects of
possible low pressure or eddies in the air inside the machine.
The standard design includes an oil sight glass in the bearing housing, an inspection glass
to observe the oil-ring and temperature monitoring. (Pt 100 resistance temperature detector
in 3- or 4-wire design, at the bottom half of each shell).
Recommended lube oils are given in Table 4-8 and in the Maintenance Instructions.
The N-end bearing is always insulated. The insulating layer is located in the bearing
housing on the spherical seat for the shells.
When the machine is to be connected to a separate lube oil supply system, the standard
design will include an inlet pipe with a manometer, a throttle valve and a DIN or ANSI
flange, and oil according to Table 4-8 is assumed.
Before dispatch, the machine is provided with a rotor lock to protect the bearings from
being damaged during transport.
2SWLRQV
3BSM900026, en
The D-end bearing can be designed as a locating bearing (DIN 31693, Type K, i.e. with
lateral thrust faces) and the shaft journal designed to match. The permissible axial thrust is
given in Table 4-9. The manufacturer must be contacted for higher thrusts.
Special design sleeve bearings for connection to a jacking-oil system can also be supplied
on request.
4-36
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
9HUWLFDO0RXQWLQJ$0%
6WDQGDUG'HVLJQ
The vertical AMB 710 machines are equipped with grease lubricated antifriction bearings, as
standard.
3BSM900026, en
4-37
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
%HDULQJ7\SH
7DEOH 6WDQGDUG$QWLIULFWLRQ%HDULQJVYHUWLFDOGHVLJQ
7\SH
'LDPRI
6KDIWH[W
>PP@
'HQG
1HQG
220
6048 M.C3
2x 7330B.MP.UA
&DOFXODWHG%HDULQJ/LIHDQGSHUPLVVLEOH$[LDO7KUXVW
At the D-end the machines are provided with an axially-free and spring preloaded deep-groove
ball bearing (series 60).
The minimum calculated life L10 (ISO 281/1) of the D-end bearing is 100000 operating hours.
The axial thrust, downward only, of 100'000 and 50'000 operating hours, (rotor weight see
technical data sheet) is absorbed by angular-contact ball-bearings located at the N-end of the
machine.
7DEOH 5DWLQJOLIH/
KRXUV,62
7\SH
3HUPLVVLEOHD[LDOWKUXVW>N1@LQFOXGLQJURWRUZHLJKWDVDIXQFWLRQRIVSHHG>UPLQ@
60
62
66
70
74
80
88
96
3BSM900026, en
3HUPLVVLEOHD[LDOWKUXVW>N1@LQFOXGLQJURWRUZHLJKWDVDIXQFWLRQRIVSHHG>UPLQ@
72
76
82
88
94
102
110
120
4-38
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
/XEULFDWLRQ
The lubrication intervals for a bearing operation temperature of 70C and lithium soap base
grease are given in the next two tables. The grease nipples are brought out from the bearing to
an accessible point on the machine via a tube.
On the D-end bearing, excess and used grease is expelled by a grease valve through an opening
on the lower part of the bearing cover into a container.
On the N-end bearings, the excess and used grease is expelled, into a used grease container
lecated on the top part of the endshield outside of the machine. The used grease container is
oversized to contain more than the total quantity of grease required for greasing during the
whole bearing life.
7DEOH 'HQGEHDULQJV
/XEULFDWLRQLQWHUYDOLQKRXUVDVDIXQFWLRQRIVSHHG>UPLQ@
7\SH
%HDULQJ
VL]H
6048
3800
4700
5300
6000
6300
7800
8900
7DEOH 1HQGEHDULQJV
/XEULFDWLRQLQWHUYDOLQKRXUVDVDIXQFWLRQRIVSHHG>UPLQ@
%HDULQJ
VL]H
7330
3900
4600
5000
5800
6000
7200
8400
3BSM900026, en
4-39
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
6WDQGDUG
One SPM nipple at each bearing, brought out to the machine border for better accessibility,
is included as standard to monitor bearing condition.
The antifriction bearings are always locked for transport. This is indicated by a warning
label permanently attached to the machine.
2SWLRQV
Temperature monitoring on the two main bearings can be included when explicitly
requested. (Pt100 resistance temperature detector in 3 or 4-wire design to measure the
temperature of the outer ring).
The N-end bearing, or both if desired, can be insulated on request. The insulation would be
located in the bearing endshield between the inner and outer ring.
6SHFLDOGHVLJQ
In case of motors having to accept external axial thrust (with or without up-thrust), two
solutions are available on request for the N-end bearing:
3BSM900026, en
4-40
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
For the vertical sleeve bearing arrangement, all the sliding surfaces of the bearing are fully
submerged in a self-contained oil bath; the lubricating oil is normally cooled by a cooling coil.
If required the bearing can also be connected to a separate lube oil supply system.
The spherical roller thrust bearing arrangement is provided with an additional deep-groove ball
bearing to absorb radial load.
The spherical roller bearing is pre-loaded by springs and carries the main axial thrust only. The
bearings are oil lubricated in a self-contained and naturally or water cooled oil bath depending
on additional thrust and speed.
Connection for forced lubrication, or self lubrication and air cooling (e.g. for air-air cooled
machines) can also be delivered on request.
Two bearing sizes are available on request, depending on the customers requirements. Refer to
the next table:
7DEOH
7\SH
3BSM900026, en
7KUXVW
EHDULQJW\SH
0D[LPXP
6SHHG>UPLQ@
29336E
1200
29436E
900
4-41
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HDULQJVDQGOXEULFDWLRQ
The following two tablesshow the maximum axial thrust for a calculated bearing life L10 (ISO
281/1) of 100000 and 50000 operating hours.
7DEOH 5DWLQJOLIH/
KRXUV
7KUXVW
EHDULQJ
3HUPLVVLEOHD[LDOWKUXVW>N1@LQFOXGLQJURWRUZHLJKWDVDIXQFWLRQRIVSHHG>UPLQ@
7\SH
1200
1000
900
750
600
500
375
300
84
88
91
95
101
108
117
126
160
170
180
195
208
222
3HUPLVVLEOHD[LDOWKUXVW>N1@LQFOXGLQJURWRUZHLJKWDVDIXQFWLRQRIVSHHG>UPLQ@
7\SH
1200
1000
900
750
600
500
375
300
104
110
116
122
128
139
150
161
198
210
220
236
256
278
3BSM900026, en
4-42
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 6KDIWURWRUFRUHVKDIWH[WHQVLRQ
&KDSWHU 6KDIWURWRUFRUHVKDIWH[WHQVLRQ
6KDIW
The standard shaft materials are presented in table 5-1. All machines have a welded spider shaft.
7DEOH 6WDQGDUGVKDIWPDWHULDOVIRU$0%DQG$0&0DFKLQHV
0DFKLQH7\SH
2OG'HVLJQDWLRQRI
6KDIW0DWHULDO
1HZ'HVLJQDWLRQRI
6KDIW0DWHULDO
:1R
AMB 710
St52-3 / St442-5
S355J2G3 / 25CrMo4
1.0570 / 1.7218
AMC 800
St52-3 / St442-5
S355J2G3 / 25CrMo4
1.0570 / 1.7218
AMC 900
St52-3 / St442-5
S355J2G3 / 25CrMo4
1.0570 / 1.7218
AMC 1000
St52-3 / St442-5
S355J2G3 / 25CrMo4
1.0570 / 1.7218
AMC 1120
St52-3 / St442-5
S355J2G3 / 25CrMo4
1.0570 / 1.7218
5RWRU&RUH
$0%DQG$0&VPDOOHUWKDQ$0&SROH
The rotor core is built up from varnish-insulated, electrical sheet-steel circular laminations,
pressed together by solid end rings and shrunk onto the shaft.
$0&SROHDQGELJJHU
The rotor electrical sheet-steel is segmented.
3BSM900026, en
5-43
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 6KDIWURWRUFRUHVKDIWH[WHQVLRQ
6KDIW([WHQVLRQ
$0%
The motors are designed with an ISO shaft extension with one keyway and a
feather key.
$0&
2SWLRQV
3BSM900026, en
The machines can also be designed with a second shaft extension at the N-end. The
maximum permissible torque is given on the motor outline drawing.
AMB 710: If requested, or in cases when needed, a shrink-fit extension ISO-short can be
provided instead.
AMC: Motors with a key shaft extension ISO-long must have a low torque and are
available on request only.
5-44
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 6KDIWURWRUFRUHVKDIWH[WHQVLRQ
7DEOH $GPLVVLEOHWRUTXHVRIVKDIWHQGVDQGVKDIWKXEFRQQHFWRI$0%PDFKLQHV
0D[5DWHG7RUTXH
Type of Motor
Diam.
of
shaft
end
Shaft
material
[mm]
0D[%UHDN'RZQ7RUTXH
Shaft End
accord.
to
ISO/R775
Sleeve
bearing
design
with
key
Sleeve
bearing
design
with
shrink
fit
Antifricti
on
bearing
design
with
key
Antifricti
on
bearing
design
with
shrink
fit
Sleeve
bearing
design
with
key
Sleeve
bearing
design
with
shrink
fit
Antifricti
on
bearing
design
with
key
Antifricti
on
bearing
design
with
shrink
fit
[kNm]
[kNm]
[kNm]
[kNm]
[kNm]
[kNm]
[kNm]
[kNm]
[kNm]
AMB 710L4s
200
S355J2G3
61.5
59.2
59.2
59.2
59.2
123.2
179.3
123.2
134.6
AMB 710L4
200
25CrMo4
61.5
79.4
102.0
79.4
102.0
138.0
185.0
138.0
158.0
220
S355J2G3
82.5
78.9
78.9
78.9
78.9
160.9
228.9
160.9
176.7
220
25CrMo4
82.5
101.0
136.0
101.0
136.0
176.0
228.9
176.0
207.0
AMB
710L6-30s
AMB 710L6-30
1) The max. rated torque of the machine should not exceed the indicated value
2) The max. break down torque of the machine should not exceed the indicated value
s) Standard design
This table can only be used, if the standard shaft end design is used and standard boundary
conditions are applicable. Otherwise a recalculation considering the actual conditions is
necessary.
3BSM900026, en
5-45
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 6KDIWURWRUFRUHVKDIWH[WHQVLRQ
7DEOH $GPLVVLEOHWRUTXHVRIVKDIWHQGVDQGVKDIWKXEFRQQHFWRI$0&0DFKLQHV
0D[5DWHG7RUTXH
Type of Motor
Diam. of
shaft end
Shaft
material
[mm]
AMC800*4s
0D[%UHDN'RZQ7RUTXH
Shaft End
accord. to
ISO/R775
Sleeve bearing
design with key 3)
Sleeve bearing
design with
shrink fit 3)
Antifriction bearing
design with key 3)
Antifriction bearing
design with
shrink fit 3)
[kNm]
[kNm]
[kNm]
[kNm]
[kNm]
250
25CrMo4
118.0
203.4
280
S355J2G3
170.0
163.5
163.5
459.2
386.6
AMC800*6-24
280
25CrMo4
170.0
287.9
287.9
489.9
458.5
AMC900*4s
250
25CrMo4
118.0
203.4
AMC900*6-24s
300
S355J2G3
206.0
201.2
201.2
582.3
472.9
AMC800*6-24
300
25CrMo4
206.0
354.4
354.4
588.2
560.4
AMC1000*10-24s
320
S355J2G3
250.0
244.4
244.4
705.9
570.8
AMC1000*10-24
320
25CrMo4
250.0
430.6
430.6
705.9
676.5
AMC1120*12-24s
340
S355J2G3
300.0
293.4
293.4
898.7
681.3
AMC1120*12-24
340
25CrMo4
300.0
516.8
516.8
1041.9
807.5
AMC800*6-24
1)
2)
3)
s)
342.9
342.9
The max. rated torque of the machine should not exceed the indicated value
The max. break down torque of the machine should not exceed the indicated value
Key connection only on request
Standard design
This table can only be used, if the standard shaft end design is used and standard boundary
conditions are applicable. Otherwise a recalculation considering the actual conditions is
necessary.
3BSM900026, en
5-46
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU :LQGLQJDQGLQVXODWLRQ
&KDSWHU :LQGLQJDQGLQVXODWLRQ
6WDWRU:LQGLQJ
The insulation materials employed meet the requirements for Class F as defined by IEC
(maximum permissible temperature 155C).
The stator coils are wound from rectangular shaped wire. The insulation structure is the
Micadur-Compact system, now well established for almost thirty years, and by which the
coils are wrapped over their whole length with overlapped layers of glass-mica tape (refer also
to brochure 3BFP 001 980 R0101 REV A 12/98 Micadur-Compact Industry Insulation
System for Rotating Electrical Machines). The winding slots are closed with highly permeable,
powder composition wedges.
Irrespective of voltage, the finished wound stator is subjected to vacuum-pressure-impregnation
and cured in a hot air oven. The winding elements are then so rigid that they can withstand the
forces arising during system transfers and short-circuits without sustaining damage.
In addition to the final high-voltage test performed on the finished machine, dielectric tests with
a.c. voltage and impulse voltage with steep wave fronts are carried out during winding
production to ensure that the coil and turn to turn insulation meet the specified requirements
(surge withstand impulse strength in accordance with IEC 60034 - 15).
Remark: Experience made by many users and manufacturers has shown that occasionally surge
voltages can arise which subject the motors to more severe conditions than those specified by
IEC 60034-15. For rated voltages above 11 kV, overvoltage protection, consisting of surge
capacitors and ZnO voltage arresters, is provided close to the motor terminals. The purpose
would be to provide a reliable protection of the motors against switching surges with steep wave
fronts and high amplitudes, which can arise particularly with vacuum breakers at pre-ignition
and multiple restriking.
The standard design includes 6 resistance temperature detectors, 3 or 4-wire type Pt100, in the
winding slots to monitor the stator winding temperature (2 per phase). The leads are led to the
auxiliary terminal box.
2SWLRQV
Second vacuum impregnation for nuclear plants, extended exposure to steam, or extremely
dirty operating areas
5RWRU:LQGLQJ
The standard design incorporates a copper, deep-bar cage winding. The bars are hard-soldered
to the short-circuit rings by a long established and well proven technique. The bars are swaged
along their whole length to afford a tight fit to the slot walls. This prevents damaging bar
vibration. A reinforced high-strength shrink rings is needed for some motors with high
circumference speed.
2SWLRQV
3BSM900026, en
Bars and rings of special copper alloys for heavy starting conditions
6-47
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 3RZHUFRQQHFWLRQV
&KDSWHU 3RZHUFRQQHFWLRQV
6WDWRU7HUPLQDOV
The terminal box is a welded construction and is flange-mounted to the machine housing. The
degree of protection is IP55. A pressure relief flap is provided in the back wall, which would
open towards the machine in case of a short-circuit in the terminal box. The standard design is
for plastic insulated cables entering from below. It can be turned in steps of 90 in either
direction to afford cable entrance from the side or from above. The direction of cable entrance
should be known when placing the order because changes after manufacture are not always
possible.
The standard design includes a blank gland plate in order to accommodate the numerous
connection possibilities open. The table below shows the preferred number of cables entering
the terminal box for the different types of terminals.
7DEOH 1XPEHURIFDEOHVHQWHULQJWKHER[
7RWDOQXPEHURIFDEOHV
HQWHULQJWKHER[
0D[FDEOHGLDPHWHU
>PP@
Stud terminal
(Fig. 7.1)
1, 3
63
Bar terminal
(Fig. 7.2 and 7.3)
1, 3, 4
6
63
37
7\SHRIWHUPLQDO
The number of cables, type and diameter should be known latest when the motor outline
drawing is approved by the customer. Should it be necessary for the motor manufacturer to drill
the gland plate and provide cable glands this should be requested at the same time (extra
charge). It is recommended that the machine is delivered with fitted cable glands as this can
save considerable extra work on site.
The star point is not lead out in the standard design.
For voltages up to 4.2 kV and currents higher than 400 A, bar terminals are provided for the
connection of up to 4 cables per phase. For voltages up to 11 kV stud type terminals (to DIN
46264) are employed. For voltages above 11 kV the terminal connections are sealed with a
shrink-sleeve termination system (Fig. 7-4).
The terminal boxes are provided with internal and external grounding points.
3BSM900026, en
7-48
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 3RZHUFRQQHFWLRQV
7DEOH .LQGRIWHUPLQDODQGDGPLVVLEOHQXPEHURIFDEOHV
5DWHGYROWDJH>N9@
5DWHGFXUUHQW>$@
.LQGRIWHUPLQDO
1RRIFDEOHVSHU
SKDVH
0 ... 400
1 .... 4
0 ... 400
Stud (Fig.7.1)
1 .... 4
0 ... 400
3BSM900026, en
7-49
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 3RZHUFRQQHFWLRQV
)LJXUH6WXGW\SHWHUPLQDOV
)LJXUH%DUW\SHWHUPLQDOV
3BSM900026, en
7-50
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 3RZHUFRQQHFWLRQV
)LJXUH%DUWHUPLQDOVRQVWDQGRIILQVXODWRUV
)LJXUH6HDOHGWHUPLQDWLRQV
3BSM900026, en
7-51
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 3RZHUFRQQHFWLRQV
2SWLRQVH[WUDFKDUJHV
Star point in separate terminal box opposite to the machines main terminal box, with or
without current transformers
Star point in the same terminal box as the main terminals, with or without current
transformers.
Terminal box short-circuit proofed (Additional requirements for high voltage motors in
power stations). Rated voltages up to 11 kV and rated currents up to 2000 A. Heavy duty
terminals arranged in conformity with DIN 2962, parts 1 and 2. Short-circuit capacity 440
MVA at 6,6 kV or 730 MVA at 11 kV (short-circuit current: 38 kA for 0.25 1) ).
Terminal box short-circuit proofed, certified. Rated voltage up to 11 kV and rated currents
up to 2000 A. Heavy duty terminals. Short-circuit capacity 570 MVA at 6.6 kV or 950
MVA at 11 kV (short-circuit current: 50 kA for 0.3s *) )
Special terminal box for accepting surge capacitors, voltage arresters and current
transformers.
Terminal box with six bar terminals for converter-fed machines with two stator windings.
For further information about terminal boxes refer to the Accessories List.
*)
Note:
For rated durations (ts) longer than mentioned above the corresponding short-circuit current
(Is) can be obtained from the current (Is) and the time (ts) above from
Is =[Is2 (ts : ts)]0,5
$X[LOLDU\WHUPLQDOER[
The motors are equipped with one auxiliary terminal box for monitoring and one auxiliary
terminal box for space heaters and eventually instruments with high voltage. The box is
equipped with terminal blocks (max. 10 mm2, 750 V) and an earthing bar on the inside. The
degree of protection is IP65.
2SWLRQVH[WUDFKDUJHV
3BSM900026, en
7-52
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 1RLVHOHYHOV
&KDSWHU 1RLVHOHYHOV
The following tables show the surface sound pressure levels in dB(A) for 50 Hz, measured at
1m distance, at rated voltage and no-load, in conformity with ISO 1680. Guaranteed values lie
3 dB(A) higher. For details of designs with noise damping refer to the section Cooling and
protection. The values for full-load with air-water heat exchanger will be between 1 to 3 dB(A)
higher, the lower value being valid for machines with a no-load level above 82 dB(A) and the
higher value for those with a no-load level below 75 dB(A). The values at full load for all other
heat exchangers will be 1 dB (A) for all noise levels. Noise levels for 60 Hz will be 3 dB(A)
higher.
7DEOH 6XUIDFHVRXQGSUHVVXUHOHYHOVLQG%$IRU+]WRSROHPDFKLQHVXQLGLUHFWLRQDOIDQV
7KHYDOXHVLQSDUHQWKHVHVDUHYDOLGIRUVOHHYHEHDULQJGHVLJQV
(AMC: only for sleeve bearings)
Without:
With:
,3:
,&:
,&
7\SH
:LWKRXW
:LWK
:LWKRXW
:LWK
:LWKRXW
:LWK
(84)
86 (85)
78 (77)
74 (73)
73 (73)
(79)
83 (81)
76 (74)
72 (71)
71 (70)
(73)
80 (75)
74 (72)
71 (70)
71 (71)
(71)
80 (72)
74 (70)
71 (69)
70 (69)
(88)
86 (84)
78 (77)
74 (73)
73 (73)
(85)
84 (82)
76 (74)
72 (71)
71 (71)
Values for 12 pole machines are also valid for pole numbers above.
3BSM900026, en
8-53
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 1RLVHOHYHOV
3BSM900026, en
7\SH
,3:
,&:
,&
87
86
85
84
84
76
75
75
75
75
88
87
86
80
77
80
76
74
75
75
71
89
88
87
86
86
83
80
79
78
78
89
86
87
80
77
82
84
81
77
78
74
88
85
85
84
80
81
78
78
90
89
84
85
83
82
82
8-54
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 'LUHFWLRQRIURWDWLRQ
&KDSWHU 'LUHFWLRQRIURWDWLRQ
'LUHFWLRQRI5RWDWLRQ$FFRUGLQJWRWKH6WDQGDUG,(&
According to the standard IEC 60034-8 the direction of rotation is the one observed when facing
the shaft end (or main shaft end). The direction of rotation shall be clockwise when the
alphabetical sequence of the terminal letters of a phase group corresponds with the time
sequence of the terminal voltages.
For example the direction of rotation of an asynchronous motor shall be clockwise, when the
machine terminals U, V and W are connected to the lines L1, L2 and L3 in this alphabetical
sequence.
'LUHFWLRQRI5RWDWLRQ$FFRUGLQJWRWKH6WDQGDUG1(0$0*
According to 1(0$0* the terminal markings of polyphase induction machines are
not related to the direction of rotation.
'LUHFWLRQRI5RWDWLRQRI$0%DQG$0&0DFKLQHV
Machines manufactured to the standards IEC 60034 will have the direction of rotation in
accordance with IEC 60034-8. Standard direction is clockwise.
The direction of rotation of machines manufactured to the standard NEMA MG1 will normally,
if not otherwise agreed, be clockwise facing the shaft end when the machine terminals T1, T2
and T3 are connected to the lines L1, L2 and L3 in this alphabetical sequence.
3BSM900026, en
9-55
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5XQQLQJTXDOLW\
&KDSWHU 5XQQLQJTXDOLW\
%DODQFLQJ
All rotors are dynamically balanced at full speed, in the case of keyed shaft extensions with a
half key. The standard balance quality complies with ISO 1940-1: 1986, balance quality grade
G2.5. Other balance qualities are accessible on request (table 10-1)
7DEOH 3RVVLEOHEDODQFHTXDOLWLHVDFFRUGLQJWRGLIIHUHQWVWDQGDUGV
,62
%DODQFH4XDOLW\*UDGH*
,62
%DODQFH4XDOLW\*UDGH*
%DODQFH4XDOLW\DFFWR$3,
7KLUG(GLWLRQ
$%%IDFWRU\VWDQGDUG
on request
on request
3BSM900026, en
10-56
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5XQQLQJTXDOLW\
9LEUDWLRQ6HYHULW\
%HDULQJ+RXVLQJ
The standard running quality of the bearing housing complies with IEC 60034-14 second
edition, vibration grade R for speeds up to 1800 rpm, vibration grade N for speeds over 1800
rpm. Limits of other standards are accessible on request.
The following table gives an overview of accessible limits for the max. bearing housing
vibration according to different standards.
7DEOH /LPLWVIRUWKHPD[EHDULQJKRXVLQJYLEUDWLRQDFFRUGLQJWRGLIIHUHQWVWDQGDUGV
IRU0RXQWLQJ$UUDQJHPHQW,0KRUL]RQWDOPDFKLQHV
5HPDUN5RW
6SHHG>USP@
9LEUDWLRQ/LPLW
YUPV>PPV@
Qd
Q!
,(&
6HFRQG(GLWLRQ
vibration grade N
2.8
vibration grade R
1.8 1)
1(0$0*
5HYLVLRQ
standard mach.
n t1200
2.1 e) 1)
0.12
$3,
7KLUG(GLWLRQ
n t1200
1.8 e) 1)
0.1
$%%IDFWRU\
Qd
,(&
6HFRQG(GLWLRQ
vibration grade N
2.8
vibration grade R
1.8 2)
1(0$0*
5HYLVLRQ
standard machine
n t1200
2.1 e) 2)
0.12
$3,
7KLUG(GLWLRQ
n t1200
1.8 e) 2)
0.1
6WDQGDUG
$%%IDFWRU\
0RXQWLQJ
$UUDQJHPHQW
,0
+RUL]RQWDO
0DFKLQHV
0RXQWLQJ
$UUDQJHPHQW
,0
9HUWLFDO
0DFKLQHV
9LEUDWLRQOLPLW
Y>LQV@SHDN
1) For machines with a rot. speed > 1800 rpm (2p=2) on request
2) On request
e) Equivalent value
3BSM900026, en
10-57
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5XQQLQJTXDOLW\
5HODWLYH6KDIW9LEUDWLRQ
On four pole machines with sleeve bearings and shaft vibration monitoring system (e.g. Bently
Nevada), the ABB factory standard vibration limit complies with IEC 60034-14 and NEMA
MG-1. The limit of API 541 is accessible on request.
The following table presents different limits according to different standards.
7DEOH /LPLWVIRUWKHPD[LPXPVKDIWYLEUDWLRQDFFRUGLQJWRGLIIHUHQWVWDQGDUGV
6WDQGDUG
$%%IDFWRU\
,(&
6HFRQG(GLWLRQ
1(0$0*
5HYLVLRQ
$3,
7KLUG(GLWLRQ
5HPDUN5RW
6SHHG>USP@
0D[5HODWLYH6KDIW
'LVSODFHPHQW>P@SS
0D[5HODWLYH6KDIW
'LVSODFHPHQW>PLOV@SS
Qd
2.5
Q!
2.0
vibration grade R
n d1800
70
--
vibration grade R
n > 1800
50
--
special machines
d 1800
70
2.8
special machines
n t 1801
50
2.0
n d5000
38 1)
1.5
1) On request
3BSM900026, en
10-58
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5XQQLQJTXDOLW\
7RWDO5XQRXW0HDVXUHPHQW
On machines with sleeve bearings and a shaft vibration monitoring system the total electrical
and mechanical runout will be optionally measured during the manufacturing of the shaftsensing areas. The total runout will be measured again after the final assembly. The quality of
the runout complies with IEC 60034-14, NEMA MG-1 and API 541.
The following table presents the requirements of different standards.
7DEOH /LPLWVIRUWKHPD[FRPELQHGPHFKDQGHOUXQRXWDFFWRGLIIHUHQWVWDQGDUGV
6WDQGDUG
5HPDUN5RW
6SHHG>USP@
0D[5HODWLYH6KDIW
'LVSODFHPHQW>P@SS
0D[5HODWLYH6KDIW
'LVSODFHPHQW>PLOV@SS
$%%IDFWRU\
0.4
vibration grade R
n d1800
18.0
--
vibration grade R
n > 1800
12.5
--
special machines
n d 1800
17.5
0.7
special machines
n t 1801
12.5
0.5
n d5000
11.4
0.45
,(&
6HFRQG(GLWLRQ
1(0$0*
5HYLVLRQ
$3,
7KLUG(GLWLRQ
3BSM900026, en
10-59
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5XQQLQJTXDOLW\
/DWHUDO&ULWLFDO6SHHG
0RXQWLQJDUUDQJHPHQW,0KRUL]RQWDO
All machines with four or more poles run below the first critical speed.
The critical speeds are given in table 2. The reference values are valid for a stiff-stiff
foundation: Stiffness in horizontal and vertical direction of 5 MN/mm.
The critical speed are given in table 10-5. Table 10-6 presents separation margins according to
different standards.:
7DEOH /DWHUDOFULWLFDOVSHHGVIRU$0%DQG$0&0DFKLQHV
SROH
7\SH
6OHHYHEHDULQJV
+]
+]
$0%
1800 - 1900
2150 - 2400
$0&6
2000 - 2100
2100 - 2300
$0&0
1850 - 1900
$0&6
1800 - 1850
$0&0
1700 - 1800
Lower values for long cores, higher values for short cores.
7DEOH 6HSDUDWLRQPDUJLQVIRUODWHUDOFULWLFDOVSHHGVDFFRUGLQJWRGLIIHUHQWVWDQGDUGV
6HSDUDWLRQ
0DUJLQ>@
$%%IDFWRU\
,(&
6HF(GLWLRQ
1(0$0*
5HY
$3,
7KLUG(GLWLRQ
- 2)
- 2)
15
1) Recommended value
2) No requirement
3BSM900026, en
For lateral analysis contact ABB factory, this implies an additional cost.
10-60
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5XQQLQJTXDOLW\
0RXQWLQJDUUDQJHPHQW,0YHUWLFDO
All catalogue machines run below the first critical speed. In order to achieve a sufficient running
quality, it is recommended to keep a 25% separation margin.
The critical speeds are given in table 10-7. The reference values are valid for a weak-stiff
foundation: Stiffness in horizontal direction of 1 MN/mm, stiffness in vertical direction of 5
NM/mm.
7DEOH &ULWLFDO6SHHGDQGUHTXLUHGPLQLPXPQXPEHURISROHV
7\SH
3BSM900026, en
FULWLFDOVSHHG
Q>UPLQ@
0LQLPXPQXPEHURI
SROHVVSHHG>USP@
+]
+]
AMB 710M
AMB 710L
1500
1300
6/1000
6
6
8
AMC 800S
AMC 800M
AMC 800L
900
820
780
10
10
12
12
12
14
AMC 900M
AMC 900L
AMC 900X
850
760
680
10
12
12
12
14
16
AMC 1000L
AMC 1000X
700
600
12
14
14
16
AMC 1120L
AMC 1120X
660
550
14
16
16
18
10-61
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU $QWLFRUURVLRQSURWHFWLRQ
&KDSWHU $QWLFRUURVLRQSURWHFWLRQ
6WDQGDUGSDLQWV\VWHP
The painting system is discribed in ABB document 2065 4232.
$FFHSWDEOHHQYLURQPHQWDOFRQGLWLRQV
The described standard painting system is suitable for the ambient conditions corresponding to
C1-C2 according to ISO 12944-2.
Indoor installations.
The system is not suitable for areas with radioactivity, coastal areas (saliferous air), installations
below and top decks (splashing saliferous water), drilling platforms and ships.
After sandblasting, residual blast material will be removed and the parts will be cleaned and
dried.
6XUIDFHWUHDWPHQWSURFHGXUH
Welds are ground for removal of spatter and slag, if any, edges are rounded to at least 2 mm
radius and any surface defects are mended to preparation grade P3 according to ISO 8501-32.
All steel surfaces to be painted are degreased and blast cleaned to Sa 2 1/2 according to ISO
8501-1:19883. Edges and areas hard to reach with spraying are first primed using a brush, after
which primer is sprayed on all parts. When using zinc rich paint, immediately after drying the
zinc rich paint is covered with the intermediate coat in order to protect the surface from picking
up dirt. Surface preparation and painting are carried out indoors on dry goods of ambient
temperature. The temperature of the painting area is kept > 15 C and the relative humidity is
kept < 70 %.
After drying of the paint, the parts are transported to the machine shop and assembled to a
complete machine. Before application of further coats of paint the surfaces are ground, vacuum
cleaned and washed with a solvent to secure good adhesion between the paint layers. The
painting is then completed with another layer of primer/intermediate coat and the topcoat.
Each paint booth is well lighted, well ventilated and equipped with a lift, so that the painter can
easily reach all parts, also on the largest machines. High pressure spraying is performed using
two-component equipment, in which base and curing agents are mixed in the gun. The paint
materials are heated, which facilitates the use of high solid low solvent products. Before release,
the surfaces are visually inspected and the total dry film thickness measured using an
electromagnetic inductive device.
,623UHSDUDWLRQRIVWHHOVXEVWUDWHVEHIRUHDSSOLFDWLRQRISDLQWVDQGUHODWHGSURGXFWV9LVXDODVVHVVPHQWRIVXUIDFHFOHDQOLQHVV3DUW3UHSDUDWLRQ
JUDGHVRIZHOGVFXWHGJHVDQGRWKHUDUHDVZLWKVXUIDFHLPSHUIHFWLRQV
,623UHSDUDWLRQRIVWHHOVXEVWUDWHVEHIRUHDSSOLFDWLRQRISDLQWVDQGUHODWHGSURGXFWV9LVXDODVVHVVPHQWRIVXUIDFHFOHDQOLQHVV3DUW5XVW
JUDGHVDQGSUHSDUDWLRQJUDGHVRIXQFRDWHGVWHHOVXEVWUDWHVDEGVWHHOVXEVWUDWHVDIWHURYHUDOOUHPRYDORISUHYLRXVFRDWLQJVDOVRNQRZQDV66
3BSM900026, en
11-62
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU $QWLFRUURVLRQSURWHFWLRQ
3ULPHU
60 Pm oxirane ester primer or eqvivalent.
7RSFRDW
60 Pm oxirane ester top coat or eqvivalent.
3DLQWEXLOGXS
3ULPHUDQGWRSFRDWDUHEXLOGLQJXSDWRWDOWKLFNQHVVRIGU\FRYHULQJPP
The VOLGHLQVWDWRU, with the winding, will already be completely coated with the impregnating
resin from the vacuum impregnation process and is thus sufficiently protected. Therefore, this
internal component will QRW be primed.
The VWDWRUKRXVLQJDQGEXLOWRQFRPSRQHQWV will have been primed by the sub-suppliers. For
this reason priming will not be necessary for these parts.
Except for the seal and bearing surfaces on the shaft, all parts of the rotor, and fans when fitted,
will be primed. For some parts, this coating will be on top of an already applied primer. 1RWRS
FRDW will be applied.
For attachments, such as an DLUWRDLUFRROHU with its fan housing, of which the inner surfaces
come into contact with the ambient air, the complete paint system will be applied.
For fans, (blowers) the complete paint system will be applied.
5XVWLQKLELWRUVIRUEDUHVXUIDFHV
Spigot seatings, the undersides of the motor feet, and bare parts of machines, which can not be
protected with paint, will be protected with a 0.05 to 0.08 mm thick coating of a suitable rust
inhibitor.
6WDQGDUGFRORXUVRISDLQWIRUPRWRUVDQGDWWDFKPHQWV
3BSM900026, en
$0%
$0&
Motor:
Attachment:
11-63
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU $QWLFRUURVLRQSURWHFWLRQ
1RUPDWLYHUHIHUHQFHV
DIN 53167
ISO 7352
ISO 8501-1
ISO 8502-3
ISO 8503-1
ISO 8504-2
)RU2IIVKRUH$SSOLFDWLRQV
The painting system is discribed in ABB document 3BSM 007816-A
$FFHSWDEOHHQYLURQPHQWDOFRQGLWLRQV
The described painting system is a multi layer systerm for corrosive environment. e.g offshore
environment.
3DLQWDSSOLFDWLRQ
Castings and welded structures will be sandblasted and primed by the subsuppliers. The primed
surfaces will be degreased, and if necessary repaired and smoothed, before applying any further
coats.
6XUIDFHWUHDWPHQWSURFHGXUH
Welds are ground for removal of spatter and slag, if any, edges are rounded to at least 2 mm
radius and any surface defects are mended to preparation grade P3 according to ISO 8501-32.
All steel surfaces to be painted are degreased and blast cleaned to Sa 2 1/2 according to ISO
8501-1:19883. Edges and areas hard to reach with spraying are first primed using a brush, after
which primer is sprayed on all parts. When using zinc rich paint, immediately after drying the
zinc rich paint is covered with the intermediate coat in order to protect the surface from picking
up dirt. Surface preparation and painting are carried out indoors on dry goods of ambient
temperature. The temperature of the painting area is kept > 15 C and the relative humidity is
kept < 70 %.
3BSM900026, en
11-64
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU $QWLFRUURVLRQSURWHFWLRQ
After drying of the paint, the parts are transported to the machine shop and assembled to a
complete machine. Before application of further coats of
paint the surfaces are ground, vacuum cleaned and washed with a solvent to secure good
adhesion between the paint layers. The painting is then completed with another layer of
primer/intermediate coat and the topcoat.
Each paint booth is well lighted, well ventilated and equipped with a lift, so that the painter can
easily reach all parts, also on the largest machines. High pressure spraying is performed using
two-component equipment, in which base and curing agents are mixed in the gun. The paint
materials are heated, which facilitates the use of high solid low solvent products. Before release,
the surfaces are visually inspected and the total dry film thickness measured using an
electromagnetic inductive device.
,623UHSDUDWLRQRIVWHHOVXEVWUDWHVEHIRUHDSSOLFDWLRQRISDLQWVDQGUHODWHGSURGXFWV9LVXDODVVHVVPHQWRIVXUIDFHFOHDQOLQHVV3DUW3UHSDUDWLRQ
JUDGHVRIZHOGVFXWHGJHVDQGRWKHUDUHDVZLWKVXUIDFHLPSHUIHFWLRQV
,623UHSDUDWLRQRIVWHHOVXEVWUDWHVEHIRUHDSSOLFDWLRQRISDLQWVDQGUHODWHGSURGXFWV9LVXDODVVHVVPHQWRIVXUIDFHFOHDQOLQHVV3DUW5XVW
JUDGHVDQGSUHSDUDWLRQJUDGHVRIXQFRDWHGVWHHOVXEVWUDWHVDEGVWHHOVXEVWUDWHVDIWHURYHUDOOUHPRYDORISUHYLRXVFRDWLQJVDOVRNQRZQDV66
3ULPHU
50 Pm Interzink 52 or eqvivalent.
,QWHUPHGLDWH
250 Pm Duatar HM or eqvivalent.
7RSFRDW
50 Pm PU 110 or eqvivalent.
3DLQWEXLOGXS
3ULPHUDQGWRSFRDWDUHEXLOGLQJDWRWDOWKLFNQHVVRIGU\FRYHULQJPP
The VOLGHLQVWDWRU, with the winding, will already be completely coated with the impregnating
resin from the VPI process and is thus sufficiently protected. Therefore, this internal component
will QRW be primed.
The VWDWRUKRXVLQJDQGEXLOWRQFRPSRQHQWV will have been primed by the subsuppliers. For this
reason priming will not be necessary for these parts.
Except for the seal and bearing surfaces on the shaft, all parts of the rotor, and fans when fitted,
will be primed. For some parts, this coating will be on top of an already applied primer. 1RWRS
FRDW will be applied.
For attachments, such as an DLUWRDLUFRROHU with its fan housing, of which the inner surfaces
come into contact with the ambient air, the complete paint system will be applied.
For fans, (blowers) the complete paint system will be applied.
5XVWLQKLELWRUVIRUEDUHVXUIDFHV
Spigot seatings, the undersides of the motor feet, and bare parts of machines, which can not be
protected with paint, will be protected with a 0.05 to 0.08 mm thick coating of a suitable rust
inhibitor.
3BSM900026, en
11-65
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU $QWLFRUURVLRQSURWHFWLRQ
6WDQGDUGFRORXUVRISDLQWIRUPRWRUVDQGDWWDFKPHQWV
AMB:
AMC:
Motor:
Attachment:
1RUPDWLYHUHIHUHQFHV
3BSM900026, en
DIN 53167
ISO 7352
ISO 8501-1
ISO 8502-3
ISO 8503-1
ISO 8504-2
11-66
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 2XWSXWVIRUGHYLDWLRQVIURPQRUPDOFRQGLWLRQV
&KDSWHU 2XWSXWVIRUGHYLDWLRQVIURPQRUPDOFRQGLWLRQV
6LWH&RQGLWLRQV
Should the ambient temperature and/or the site altitude deviate from the normal conditions, the
rated output shown on the motor data sheet must be multiplied by the corresponding correction
factor given in the next table.
7DEOH 2XWSXWFRUUHFWLRQIDFWRUV
$PELHQW
7HPSHUDWXUH
2XWSXWFRUUHFWLRQIDFWRUVIRUGLIIHUHQWDOWLWXGHV>P@
>&@
1000
1500
2000
2500
3000
3500
4000
1.06
1.03
1.00
0.97
0.94
0.91
0.88
1.03
1.00
0.97
0.94
0.91
0.87
0.84
1.00
0.97
0.93
0.90
0.87
0.84
0.81
0.96
0.93
0.89
0.86
0.83
0.80
0.91
0.88
0.85
0.82
0.79
0.87
0.84
0.81
0.78
0.82
0.80
If, in case of cooling methods IC01, IC31 and IC611 for site altitudes 1000m to 4000m, no
information is given with regard to the ambient temperature, it will be assumed that the lower
cooling capacity is equalized by a lower ambient temperature. Therefore, assuming the values
of altitude and temperature shown in the table below the nominal rated output may remain
unchanged.
7DEOH $OWLWXGHVDQGDPELHQWWHPSHUDWXUHVIRUIXOOUDWHGRXWSXW
$OWLWXGH>P@
1000
1500
2000
2500
3000
3500
4000
7HPSHUDWXUH
>&@
40
36
32
28
24
20
16
3BSM900026, en
12-67
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 2XWSXWVIRUGHYLDWLRQVIURPQRUPDOFRQGLWLRQV
The rated output must be reduced by multiplying with the corresponding correction factor
given in the next table.
7DEOH 2XWSXWFRUUHFWLRQIDFWRUVIRU,&:
&RROLQJ
ZDWHULQOHW
WHPS
2XWSXWFRUUHFWLRQIDFWRUVIRUGLIIHUHQWDOWLWXGHV>P@
>&@
1000
1500
2000
2500
3000
3500
4000
1.00
0.97
0.93
0.90
0.87
0.84
0.81
0.98
0.95
0.91
0.88
0.95
0.92
0.88
0.93
0.9
0.91
'HYLDWLRQLQ6XSSO\9ROWDJH9DULDWLRQ
Continuous operation below 95% rated voltage necessitates a reduction in rated output in
accordance with Diagram 1. The manufacturer should be contacted in cases of voltages higher
than 105% of rated value.
Diagram 1
3BSM900026, en
12-68
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 2XWSXWVIRUGHYLDWLRQVIURPQRUPDOFRQGLWLRQV
3BSM900026, en
12-69
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 7HPSHUDWXUHFODVV)
&KDSWHU 7HPSHUDWXUHFODVV)
)RUPXODV
All the rating lists for AMB- and AMC-machines in PIF (Product Information File) are for
temperature rise B. When offering F-rise machines, take the data for the machine one step lower
than the required rated output. The data must be corrected (approximation only) according to the
following formulas:
Speed
= cosM B100
([DPSOH
$0%
A customer requires an offer for a 5600 kW motor IC81W (TEAWC) in temperature rise F (105
K), 6 kV, 50 Hz, 1000 rpm.
The data of the offered motor would be as follows:
Motor type
AMB 710L6
Rated output
Speed
Stator current
Torque
Efficiency
Power factor
cosM = 0.86
Current
Max torque
3BSM900026, en
13-70
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 7HPSHUDWXUHFODVV)
$0&
A customer requires an offer for a 11200 kW motor in temperature rise F (105 K), 6 kV, 50 Hz,
1000 rpm.
The data of the offered motor would be as follows:
Motor type
AMC 800 M6
Rated output
Speed
Stator current
Torque
Efficiency
Power factor
cosM = 0.88
Current
Max torque
3BSM900026, en
13-71
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU %HKDYLRXUGXULQJVZLWFKLQJDQGFRQYHUWHUIHGRSHUDWLRQ
&KDSWHU %HKDYLRXUGXULQJVZLWFKLQJDQGFRQYHUWHUIHG
RSHUDWLRQ
0HFKDQLFDO%HKDYLRXU'XULQJ6ZLWFKLQJ2SHUDWLRQV
Switching operations, as for instance reswitching following short voltage interruptions, can
produce torques inadmissible for the standard machines. If such are expected, a torsional
vibrational analysis should be performed. Should the motor manufacturer be contracted to carry
out these calculations he must be furnished with the necessary data on the shaft train
components and on the conditions of the power supply system.
0HFKDQLFDO%HKDYLRXU'XULQJ&RQYHUWHUIHG2SHUDWLRQ
Converter-fed operation leads to a reduction in the nominal output because of additional losses
resulting from non-sinusoidal voltages and currents. Furthermore, oscillating torques arise and
are superimposed to the constant driving torque. Should the exciting and resonant frequencies
coincide, these torques could lead to inadmissible stressing in the shaft train. Therefore, it is a
basic principle that for converter-fed operation a torsional vibration analysis must be performed
in order to check the mechanical stresses in the whole shaft train. The motor manufacturer is not
responsible for torsional analysis.
$&6
The integrated Sinus-filter reduces the effects of the converter to a negligible extent.
3BSM900026, en
14-72
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5HPDUNVRQGHVLJQIRUFRQYHUWHUIHGPDFKLQHV
&KDSWHU 5HPDUNVRQGHVLJQIRUFRQYHUWHUIHGPDFKLQHV
,QVXODWLRQ
Due to the voltage harmonics which arise during converter-fed operation the winding insulation
is laid out for at least double the rated motor voltage.
For $&6 with sinusoidal filter normal insulation for line fed machines can be applied.
For machines fed by a non-ABB converter, special information on insulation requirements have
to be provided.
%HDULQJV
Converter-fed operation causes additional shaft voltages which could result in bearing damage.
Depending on the converter type the following provisions are recommended:
ACS 6000 and Megastar: Independent of bearing type (antifriction, sleeve) both bearings
has to be insulated
Additionally careful grounding of the motor, right choice of the feeding cable and its correct
protective earthing contribute to a failure free operation of the motor.
In case of motors fed by ACS 600 a common mode filter should be provided.
To prevent bearing current paths, also the speed monitor has to be fully insulated against the
shaft.
6SHHGPRQLWRULQJ
As a rule, speed monitoring is necessary for machine control. Therefore, the N-end of the shaft
provides the possibility of mounting a speed monitor. The associated extra charge, including
that for the recommended speed monitors are to be extracted from the accessories price list.
6HSDUDWHYHQWLODWLRQ
3BSM900026, en
15-73
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 5HPDUNVRQGHVLJQIRUFRQYHUWHUIHGPDFKLQHV
Self-ventilation is sufficient for driven equipment with a load characteristic where the torque
varies to the square of the speed (e.g. pumps). If the torque is independent or only slightly
dependent on the speed, then self-ventilation is not sufficient to provide for an effective heat
transfer in the lower speed range. In such cases, the necessary air circulation must be provided
by separate ventilation. In air-air cooled machines this is true for both the primary and
secondary cooling circuit.
1RLVH
Current harmonics cause additional noise excitation. In general, the noise level is therefore
higher for converter-fed operation than for line operation. For machines which already have a
high noise level (high speed and air-air cooler) in direct online operation, the difference will
generally be about 6 dB(A). For machines with a relatively low noise level (e.g. air-water cooler
and low to medium speed), the difference can be up to 10 dB(A). Binding data should be
requested for each particular case.
Exception: For ACS 1000 the noise increase will only be 1,5 dB (A).
&ULWLFDOVSHHG
When selecting the machine it must be ensured that the first critical speed is at least 20% above
the operating speed range. In case of machines having an operating speed range between two
critical speeds, the critical speeds must have at least 20% margin to the specified speed range.
7HUPLQDOFRQQHFWLRQVIRUPDFKLQHVZLWKWZRVWDWRUZLQGLQJV
The 2 x 3 winding ends are brought out to 6 bar-type terminals in a common terminal box.
As an option two separate boxes with 3 terminals each can be supplied.
2VFLOODWLQJ7RUTXHV
The section Behaviour during switching and converter-fed operation is to be observed with
regard to the suitability of the shaft and the shaft train when subjected to the oscillating torques
which arise during converter-fed operation.
3BSM900026, en
15-74
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0DFKLQHVIRUPDULQHDQGRIIVKRUHDSSOLFDWLRQV
&KDSWHU 0DFKLQHVIRUPDULQHDQGRIIVKRUHDSSOLFDWLRQV
)RUVXFKDSSOLFDWLRQVWKHIROORZLQJGHYLDWLRQVIURPWKHVWDQGDUGGHVLJQZLOOEHWDNHQLQWR
DFFRXQWRSWLRQDOQRWLQFOXGHGLQEDVLFSULFH
0DULQH$SSOLFDWLRQ
$LUWRZDWHUKHDWH[FKDQJHU
Double tube design for fresh water cooling with inner tubes in Cu90/Ni10 and outer tubes
in Cu. (other materials for sea water)
Cable gland plate fitted with multi cable transit frame for cable entry. Sealing elements to
be supplied by the customer.
7HUPLQDOER[
$X[LOLDU\WHUPLQDOER[
9DULDEOHVSHHGPRWRUV
3BSM900026, en
A digital pulse encoder Leine & Linde 186, insulated against motor shaft, to avoid
interference of motor control.
Pt100 in 3- or 4-wire design for monitoring cold air of forced ventilated motors.
16-75
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0DFKLQHVIRUPDULQHDQGRIIVKRUHDSSOLFDWLRQV
$GGLWLRQDOO\WKHIROORZLQJGRFXPHQWVKDYHWREHGHOLYHUHGDQGWKHIROORZLQJWHVWVKDYHWR
EHSHUIRUPHGDFFRUGLQJWR'19
Material certificate 3.1C from shaft steel and cooler manufacturer (DNV attendance of
tests),
or
material certificate 3.1B from shaft steel supplier, plus stamping prior to separate material
from shaft, plus witnessing of material tests at ABB
Surface crack detection (NDT) on welds, and on shaft after machining (bearing sections,
coupling seat), not witnessed.
$FFHVVRULHV
3BSM900026, en
16-76
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 0DFKLQHVIRUPDULQHDQGRIIVKRUHDSSOLFDWLRQV
2II6KRUH$SSOLFDWLRQ
$LUWRZDWHUKHDWH[FKDQJHU
Double tube design for fresh water cooling with inner tubes in Cu90/Ni10 and outer tubes
in Cu. (other materials for sea water)
7HUPLQDOER[
$X[LOLDU\WHUPLQDOER[
Off-shore cables
$FFHVVRULHV
3BSM900026, en
16-77
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 7RUVLRQDOVSULQJFRQVWDQW,0
$0%
7DEOH 7RUVLRQDOVSULQJFRQVWDQWIRU$0%0DFKLQHV
.LQGRI
%HDULQJ
0RWRU
7\SH
1RRISROHV
6KDIWH[W
'LDPHWHU>PP@
6SULQJ&RQVWDQW
>01PUDG@
Antifriction
Bearings
710
220
29.5 38.3
8 to 20
220
30.4 41.7
Sleeve
Bearings
710
200
15.2 18.0
220
21.8 25.5
8 to 20
220
21.7 26.9
The values represent the shaft from shaft extension shoulder to 1/3 of the core length.
Deviations are in the range of 10%.
The spring constant values should only be used for investigations allowing for a single mass
presentation of the motor-rotor.
3BSM900026, en
Lower values:
Higher values:
17-78
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 7RUVLRQDOVSULQJFRQVWDQW,0
$0&
7DEOH 7RUVLRQDOVSULQJFRQVWDQWIRU$0&0DFKLQHV
.LQGRI
%HDULQJ
Antifriction
Bearings
0RWRU7\SH
1RRI3ROHV
6KDIW
([WHQVLRQ
>PP@
AMC 800
6 - 24
280/265
AMC 900
AMC 1000
Sleeve
Bearings
8 - 24
10 - 24
300/285
320-300
)UDPH
/HQJWK
6SULQJ
&RQVWDQW
>01PUDG@
90.8 93.1
88.2 90.4
130.6
124.2
117.2
106.9
156.6 163.2
149.4
AMC 1120
12 - 24
340/320
187.3 193.9
AMC 800
250/235
37.9 39.2
6 - 24
280/265
57.8 58.7
56.7 57.6
AMC 900
AMC 1000
AMC 1120
250/235
41.4 42.7
6 - 24
300/285
79.4
77.0
74.2
70.0
119.3 123.1
115.1
127.3 130.3
10 - 24
12 - 24
320/300
340/320
S = Short
M = Medium
L = Long
X = Extra Long
The values represent the shaft from the shaft extension shoulder to 1/3 of the core length.
Deviations are in the order of 10%.
The spring constant values should only be used for investigations allowing for a single mass
presentation of the motor-rotor.
3BSM900026, en
Lower values:
Higher values:
17-79
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 7HVWV
&KDSWHU 7HVWV
5RXWLQH7HVWV
In addition to the tests and inspections carried out during production, each machine is subjected
to the final tests as listed below:
1.
General Tests
Test of Accessory Parts
2.
3.
Winding-Resistance
4.
Direction of Rotation
5.
6.
7.
High-Voltage Test
8.
Bearing Vibration
9.
In principle, the test procedures were based on the IEC recommendations. For tests not covered
by the IEC recommendations, either the IEEE, NEMA, EN or DINVDE standards were drawn
upon, or the normal industrial testing practice and the corresponding ABB internal standards
were followed.
However, if the purchase order specifies a particular standard, then that standard is to be
followed.
7\SH7HVWV
The following type tests can also be carried out in addition to the routine tests against extra
charge:
Plotting of no load curve (iron and friction losses) up to 1.1 times rated voltage.
Plotting of short circuit characteristic at reduced voltage up to 1.3 times rated current.
The temperature rise test and efficiency determination will be performed at full load or with
equivalent load (two-frequency method, e.g. vertical motors, big AMC motors). Slip and current
will then be calculated, iron, friction and windage losses will be taken from the no-load test.
3BSM900026, en
18-80
0DFKLQH'HVFULSWLRQIRU$0%DQG$0&0DFKLQHV
&KDSWHU 7HVWV
6SHFLDO7HVWV
The following type tests can also be carried out against extra charge:
1.
2.
3.
Efficiency/Direct Measurement,
Power Factor
4.
5.
6.
Speed-Torque Curve
7.
Breakdown Torque
8.
9.
Overspeed Test
The Factory must be contacted for all special tests to confirm feasibility.
The test procedures were generally based on the IEC recommendations. Where a test was not
covered in these documents, the IEEE, NEMA, EN, API541or DINVDE standards were drawn
upon, or normal industrial testing practice and the corresponding ABB internal instructions
were used.
However, if the purchase order specifies a particular standard, then that standard is to be
followed.
3BSM900026, en
18-81
3BSM900026, en
2003-10-06