A Quantitative Approach To Selecting Nozzle Flow Rate and Stream
A Quantitative Approach To Selecting Nozzle Flow Rate and Stream
10/01/2010
Email
Print
12
Facebook
5
Twitter
1
LinkedIn
18
Share
The American fire service prides itself on a rapid, aggressive interior attack. In light of this philosophy, the time-critical
nature of applying the correct amount of water on the fire depends on understanding at what point in the development
of a fire firefighters typically arrive and enter a burning structure. The efficiency and speed with which todays
firefighters respond to occupied dwellings profoundly affect how precise the initial handline flow rate must be to deal
with modern heat-release rates and the potential for flashover. National response time standards suggest that the
initial arriving engine company typically making an offensive interior attack with just a single handline will often arrive
at approximately the same time as many fires are approaching the flashover stage.
NFPA 1221
The first-time component that we must understand is the time from when a fire is first reported to the time when firstalarm resources initiate their response. According to NFPA 1221, Standard for the Installation, Maintenance and Use
of Emergency Services Communications Systems, 2010 edition, an emergency communications center must answer
the call for a report of a fire within 15 to 40 seconds from when it is received.5 Correspondingly, the standard also
recommends that fire call processing and dispatching be completed within 60 to 80 seconds after the call has been
answered. (5) The worst-case scenario presents a situation in which 130 seconds (two minutes and 10 seconds)
have passed from the time the reporting party attempted to notify the fire department of the fire to when the initial
attack resources were notified.
NFPA 1710
This standard provides several first-alarm time and response standards for career fire departments. With respect to
response times, once an alarm is received, the recommended turnout time is one minute and 20 seconds. (5) NFPA
1710 subsequently recommends that from the time the response begins until the first engine arrives at the scene
should be four minutes maximum. (3) As a result, the first-arriving engine company that will begin the initial attack
should expect to arrive within six minutes of the receipt of the alarm.
NFPA 1410
This standard provides several standards for first-alarm fireground operations, including minimum flows from
handlines, supply lines, and master streams. Furthermore, NFPA 1410 provides time standards for various fireground
operations initial attack resources can expect to put into operation. For purposes of this discussion, NFPA 1710
recommends that the sum of the two first handlines placed into operation at a structure fire be a minimum of 300 gpm
and that the first handline flow be a minimum of 100 gpm. (3)
NFPA 1410 provides that the first two lines will be stretched, charged, and in operation with a water supply
established within three minutes of the first engine companys arrival. (2) An initial arriving engine company will likely
make an offensive interior attack without a backup line or water supply in place prior to entering the fire compartment
if occupants are trapped. Considering this, two minutes is a reasonable time for the first line to be placed into
operation within the structure from time of arrival. A two-minute time allowance would be expected from time of arrival
until water is applied into the main fire compartment. This accounts for the first-arriving officers providing an arrival
report, performing a thorough size-up, and providing proper direction to personnel prior to advancing the line into and
through the burning structure to the seat of the fire.
As the preceding NFPA standards exist as recommendations that many fire departments strive to meet, they provide
a reasonable estimate of the expected time frame within which an initial arriving engine company is likely to arrive at
the scene of a reported structure fire. These standards, when considered together, provide that the first nozzle team
will enter into the fire area in approximately eight minutes from the time the initial reporting call is made. What all
firefighters must consider is that during the response to and suppression of a structure fire, there is truly no way to
precisely determine how long the fire has been burning and the phase of development the fire is approaching.
The significance of the 2010 NIST report is that it provides true scale operational times using actual firefighters at a
true structure fire and provides data that can be accurately applied to approximate at what time in the fire
development curve firefighters most likely arrive on the scene, prepare to make entry, stretch lines to the fire
compartment, and initiate fire attack. This report also used response time standards from NFPA 1221 and 1710.
In the study, times for firefighters to begin their travel to the fire started at 312 minutes from when the fire started, and
response times were three and five minutes. (6, 31) These times placed the first-due engine arriving at 612 minutes
and 812 minutes from when the fire started.
The next timed parameter was Advance Attack Line Time, which was the time from when the first engine arrived
and stretched the first line and was in a position to initiate fire attack. (6, 38) The report states that a three-person
engine company took 3 minutes and 36 seconds, and a four-person engine company took 3 minutes and 2 seconds
to stretch the initial attack line to the fire. The time at which water was first applied to the room-and-contents fire area
(Time to Water) for the first-due engine company was 9 minutes and 15 seconds for the three-person company and
8 minutes and 41 seconds for the four-person companya 34-second or 6-percent difference. (6, 39)
Correspondingly, this recent research provides accurate evidence relative to the time the modern engine company
arrives at the scene of a typical residential structure fire and begins fire attack operations.
heat flux value at floor level of 20 kW/m2 can be expected, which can rapidly lead to flashover and full involvement of
the fire compartment, as well as rapid spread beyond the original compartment. (6, 46). However, not all fires burn at
the same speed, or rate. The peak HRR and rate of growth of any particular fire is greatly affected by physical and
chemical properties of the contents burning, including mass, surface area to volume ratios, and hydrocarbon content.
As an example, NIST states in this report that a typical upholstered chair burning at its peak would produce a 1-MW
fire, while a large sofa at its burning peak would produce roughly a 2-MW fire. (6, 46) With this in mind, the 2010
NIST residential fire study provided estimates of when the fire compartments, at slow, medium, and fast growth rates
used in their research, would reach peak HRR values of 1 and 2 MW, both producing peak HRRs that could lead to
flashover and total compartment involvement in the absence of suppression. (6, 46) The times reported for these
HRRs and respective growth rates are summarized below:
Firefighters understand there is no exact way of knowing during initial attack operations what the true target
compartment and upper-ceiling temperatures are and for exactly how long the contents of a room have been exposed
to radiant heat from ceiling gases that may be as high as 1,112F (minimum HRR of 1 MW). However, it is
understood that initial arriving engine companies typically make access into burning buildings at approximately the
same time that a burning room or an exposure room can flash over, as was demonstrated by bedroom fire tests NIST
conducted in 1985. They demonstrated that flashover in bedroom fires can occur as early as four minutes after
ignition with a HRR of 2 MW, depending on the surfaces used to line a rooms walls and ceiling.12
As an example of the potential heat firefighters must deal with following a flashover, when wood paneling was used in
the 1985 NIST test to line wall and ceiling surfaces, a post-flashover HRR of 7 MW was measured. (12, 19). This was
an enclosed room test with conditions comparable to a compartmentalized structure. Post-flashover heat flux values
(radiant heat at floor level) measured 130 to 220 kW/m2, much higher than the aforementioned materials that
experienced flashover when exposed to heat fluxes of 20 kW/m2. (12, 12) What firefighters must learn from this
research is that in enclosed structure fires, once preflashover ceiling gas temperatures and floor level radiant heating
starts, floor and wall coverings and typical furnishings can flash over in less than five minutes from the time of ignition
once the radiant heat at the floor level exceeds 20 kW/m2. (12, 13) When firefighters are in the room next to the one
that has just flashed over, preparing to make an attack, their position has now become a target of the radiant heat
produced, which can instantly be much greater than 20 kW/m2. Firefighters in such a position must be armed with the
firepower to deal with such worst-case, ceiling-level peak HRRs and extreme radiant heat at floor level to prevent
their location from flashing over next!
In March 2000, Andrew Fredericks discussed flashover research conducted by Vytemis Babruskas, Ph.D: The most
important factor in the speed with which a fire reaches flashover is the HRR .... If the HRR is high enough, flashover
will occur.13 Additionally, Fredericks referred to the Fire Protection Handbook, which states that the required HRR to
initiate a flashover can be as little as 1 MW. A very important factor to note with respect to initial attack flow rates is
that the Fire Protection Handbook further stated that a simple room-and-contents fire can rapidly produce
temperatures and radiant heat that can cause a room to flash over. (13, 122)
The Center for Fire Research studies conducted in 1985 examined the burning rates in open and enclosed rooms
with common furnishings and upholstery from that year. This report demonstrated the critical role that burning
surfaces covering ceilings and upper walls play in the flashover sequence. In the open-room tests (no walls), heat
output similar to that for flashover conditions of 1.2 MW occurred at approximately 660 to 720 seconds when the
furnishings in the room were well involved. (12, 13) However, for the enclosed-room tests, flashover occurred in as
little as 233 seconds with a HRR over 2 MW, which is the approximate time that the ceiling ignited. (12, 13)
To further investigate the effect walls have on flashover rates and temperatures, this research also analyzed the
effect of wall-surface linings in tests using noncombustible gypsum and combustible plywood wall and ceiling
coverings. For the room with gypsum-lined walls, the measured peak HRR was 2.5 MW; the measured peak HRR for
the plywood-lined wall room fires was 7 MW. (12, 11) Simply by adding combustible materials to the wall and ceiling
surfaces, the HRR increased by 4.5 MW. This report further found that when the ceiling surface ignited, the burning
rate of furnishings was significantly enhanced in all open-door room burn tests. (12, 19)
These full-scale fire tests measured the effects fire had on the standard furnishings in a typical United States Park
Service (USPS) bedroom that was 8 feet wide, 12 feet deep, and 8 feet high with a floor area of 96 square feet. (12,
4) Room furnishings consisted of plywood furniture and a wood-frame bed with synthetic bedding materials. There
were no televisions, radios, or other electronic devices. (12, 5) The fire load of this experimental room when lined with
plywood walls was 3.03 pounds per square foot (lb/ft2), almost two-thirds the fire load of the average recreational
room in a metropolitan Washington, DC, single-family home in 1985, reported as 4.71 lb/ft2. (12, 6)
With respect to the heat output of various materials commonly found in residential structures, wood, paper, cloth, and
cotton produce 7,000 to 8,000 British thermal units per pound (Btu/lb). Plastic furnishings using polyurethane produce
12,000 Btu/lb, and those using polystyrene plastics produce 18,000 Btu/lb.14 For each pound, plastics can yield
approximately twice as many Btus than materials and items composed primarily of wood and other natural organic
materials. As the fraction of hydrocarbon-based plastics in fire loads in modern construction materials and furniture
increases, and since the amount of electronics in typical homes has increased since 1985, firefighters should
anticipate the peak HRR in a room fire to be higher than the 7 MW recorded in the aforementioned bedroom fire
study in which there were no electronics. Because of this, along with the increased use of energy-efficient building
materials and windows engineered to contain heat, firefighters should expect a peak HRR greater than 7 MW, a
greater amount of radiant heat at floor level, and an increased likelihood of flashovers occurring in less than eight to
10 minutes following ignition. (13, 120)
The 1985 NIST studys open-room tests (the fire area had no walls to contain heat and products of combustion)
showed that the fire produced the minimum floor radiant heat level20 kW/m2needed for flashover. However, in
the closed-room tests, the measured floor heat flux was 130 to 220 kW/m2 when the fires were not extinguished early.
(12, 12) Firefighters making the initial interior attack will be operating in an enclosed environment that will have walls.
Therefore, they must expect radiant heat levels equal to or greater than 20 kW/m2 from adjacent fully involved
compartments to affect unignited contents in the room in which they are operating or from which they are directing a
stream.
This should sound an alarm for all firefighters: If a flashover of contents and materials at floor levels is initiated by a
radiant heat level of 20 kW/m2 in less than eight minutes, realize that flashover could very well occur in less than eight
minutes in enclosed fire compartments with a possible floor heat flux of up to 130 to 220 kW/m2 from upper surface
and upper/gas smoke layers. Clearly, it is possible for a flashover to occur in less than five minutes from ignition.
With rooms in residential structure fires having potential peak heat outputs of 7 MW or more, when such preflashover
conditions exist, there is little room for error, and the initial attack crew must select a stream that has the reach,
thermal penetration, and droplet size to reach not only the burning fuel base but also the primary radiant heat sources
that lead to flashoverthe ceiling gases and smoke, the burning ceiling, and the burning wall materials
simultaneously. This stream, at a minimum, must be capable of absorbing the maximum potential HRR at the ceiling.
At the same time, it also must have enough heat-absorbing capacity and mass so that a significant portion of the
stream will not turn to steam. These unevaporated droplets, if they are big enough, will then fall to the floor in droplet
form, suppressing the primary fuel source and preventing unignited combustibles from flashing over.
field value to help them roughly determine if their flow rates are in the ballpark of the flow rate needed to combat
worst-case scenario HRRs that can rapidly lead to a flashover when no backup line is in place.
An office-type fire burning at 100 percent efficiency produces a HRR per square meter of 0.25MW/m2.15 Converting
this HRR per-area value to square footage yields a value of 0.023 MW/ft2, which is the same value reported in the
NIST/USPS test for the gypsum-lined walls. Although most homes use gypsum-lined walls, the walls may have
combustible covers such as wainscoting, paints, wallpaper, pictures, paintings, and so on, so a value of 0.07 MW/ft2,
three times that of 0.023 MW/ft2, provides a reasonable safety margin in estimating possible HRRs. This value also
provides a margin of safety for those homes with high degrees of clutter, storage, and other fire hazards that so often
are found in residential structures in which fires occur.
The NIST Building and Fire Research Laboratory (BFRL) published Technical Note 1618, Fire Fighting Tactics Under
Wind-Driven Conditions: Laboratory Experiments, in January 2009. In this research, a full-scale apartment was
constructed in a fire test laboratory. It consisted of a bedroom, a living room, and a target room; all were connected by
a common hallway that opened to a corridor (similar to a center-hallway apartment). The bedroom, selected as the
fires point of origin, measured 16 feet wide 12 feet deep 8 feet tall and was 192 ft2. The fuel loading throughout
the apartment consisted of carpeting, carpet padding, a television and lamps, and furniture such as chairs and
mattresses; all were manufactured during 1998 and 1999. The walls and ceilings were latex-painted gypsum board.
The calculated combustible fuel load in the bedroom was 4.02 lb/ft2; in the living room, 2.5 lb/ft2; and in the hallway,
0.98 lb/ft2. (11) The fire was ignited in the bedroom in a trash can filled with paper positioned between an upholstered
chair and a bed. (11, 64)
and floors. These HRR values were obtained during the control portion of the NIST/DHS 2008 experiments (no wind
applied to the structure while it was burning). The post-flashover peak HRR value of 14 MW in this most recent NIST
test with gypsum-lined walls produced a HRR/ft2 similar to the post-flashover HRR/ft2 value from the 1985 NIST tests,
in which the walls and ceiling were lined with plywood. This comparison suggests that in the 2008 test with
noncombustible walls and a similar fuel load, a higher post-flashover peak HRR likely resulted from increased
combustibility of the modern furniture in the 2008 tests.
In 2004, NIST released the Cook County Administration Building Fire October 17, 2003: Heat Release Rate
Experiments and FDS Simulations. The researchers examined the factors that led to this fatal fire. This study
produced very precise heat-release rates for full-scale office fires, using building materials, office furniture, and
electronics collected from areas of the Cook County (IL) Administration Building that were not destroyed in 2003. In
previous office workstation fires, NIST discussed research that had produced a HRR/ft2 value of 0.169 MW/ft2, based
on a combustible fuel load of 18 lb/ft2.16 The 2003-2004 NIST full-scale office tests recreated burning conditions at the
Cook County Administration Building Fire and produced a HRR/ft2 value of 0.103 MW/ft2 using a fuel load of 17 lb/ft2.
(16)
Comparing the results from the 1985 NIST/USPS, the 2003-2004 NIST office fire studies with much higher fuel loads,
and the 2009 NIST/DHS Firefighting Tactics Under Wind-Driven Conditions suggests that a value of 0.07 MW/ft2 is an
accurate figure to use to estimate the possible worst-case HRR at residential structure fires. The value of 0.07 MW/ft2
for residential structures is consistent with real-scale fire test results over the past 20 years and correlates well
against HRRs produced in office fires using similarly aged combustibles. However, with higher fuel loadings and more
plastic electronic devices per square footi.e., a residential bedroom vs. an office workstationthese factors
suggest that this value provides a margin of safety when attempting to establish a field value to estimate single-room
peak HRR for contemporary furnishings and interior contents in residential structures based on the square footage of
a fire compartment.
As noted above, flashover can be initiated with a peak HRR as low as 1 to 3 MW and a heat flux of 20 kW/m 2
radiating from ceiling gases to floor level. As will be discussed in greater detail below, firefighters in full structural
personal protective equipment (PPE) can at best endure 500F temperatures and a heat flux of 20 kW/m2 for only 30
seconds. (11, 335) For a single stream operating from within a threatened compartment to be rapidly effective against
a possible flashover, that stream must be capable of absorbing the heat produced from the worst-case scenario HRR
for that particular compartment or an adjacent involved compartment within 30 seconds to provide the best chance
for the survival of firefighters operating within or occupants that may be trapped in that space. When preflashover or
rapid fire progression conditions are observed, firefighters committed to interior positions who cannot instantly exit the
threatened area must be able to reduce flashover-inducing HRRs and heat flux with a single stream in less than 30
seconds.
With decreased sensory awareness, firefighters have a reduced ability to accurately and quickly determine
environmental conditions and changes. In the most extreme cases of zero visibility, it is often difficult at best to
observe flames in the overhead or other visual clues. Since flashover can occur at approximately the same time as
the first hoseline is placed in operation in an offensive interior attack, firefighters may not have the thermal reference
history to be able to recognize subtle temperature fluctuations and interior environmental transitions that can occur in
a matter of seconds and initiate a flashover. This can cause firefighters to overcommit to an interior position so that if
a flashover were to occur and their handline flow rate does not have the heat-absorbing capability to prevent or stop
the fires progression, they are likely in a fatal situation. Even with the most modern PPE, they likely would not have
enough time to exit the structure without incurring serious thermal injury.
A given fire requires a specific amount of water to successfully absorb the heat produced in a relatively short time so
that a developing flashover can be effectively stopped and occupants not wearing structural PPE can be instantly
protected. With many modern residential structures having larger master bedrooms, family rooms, and kitchens,
firefighters must expect a HRR greater than that associated with an 8- 8-foot bedroom. The more floor space
available, the more combustible materials inhabitants are likely to accumulate. As discussed above, firefighters can
calculate field estimates of worst-case HRRs for residential, commercial, and office structure fires based on the
square footage of the area compartment involved.
An average value of 0.07 MW/ft2 is suggested for estimating the potential HRR from average residential bedroom fuel
loads. For example, a fire that has flashed over in a room 10 feet 10 feet, similar to that of a small bedroom fire, can
be estimated to produce a peak HRR at flashover of 7 MW. However, for a larger room, such as a living room that
measures 20 feet 20 feet, a peak HRR of 28 MW can be estimated. Many modern residential structures contain
master bedrooms, family rooms, or garages measuring at least 20 feet 20 feet. When operating in an interior
exposure position, firefighters who have advanced to an interior position close to the seat of the fire must be
concerned with the peak HRR from adjacent roomsopen doors, hallways, and uncompartmented areas. Once
flashed over, they can instantly expose adjacent exposure compartments to flashover-inducing HRRs and radiant
heat levels at the floor where firefighters are operating.
Table 1 lists various room dimensions and the estimated maximum HRRs for later comparison against the heatabsorbing capabilities of various flow rates and stream types.
The heat capacity of water and its latent heat of vaporization define the maximum potential HRR that a given amount
of water can absorb. The ceiling temperature needed to produce a flashover is 1,112F. At an initial temperature of
64F, the heat-absorbing capacity of water applied to a ceiling at 1,112F is 4.65MJ/kg, which converts to 0.3
MW/gpm. (15-23, 25) This ceiling temperature is used as the worst-case scenario where firefighters would direct their
stream at the ceiling should rollover or impending flashover conditions develop. As reported by Cliff Barnett, a New
Zealand civil and fire protection engineer, a fog stream at 1,112F has a heat-absorbing efficiency of 75 percent, and
a smooth bore stream has a heat-absorbing efficiency of 50 percent. (15, 26)
Based on the heat-absorbing capacities of fog and solid streams, Barnetts Fire Flow Formulae (Table 2) are used to
compare the heat-absorbing capacities for fog and solid streams when applied to the ceiling area with a temperature
of 1,112F just prior to a flashover.
When selecting a flow rate, firefighters must not only consider the specific streams heat-absorbing ability but also
understand the ability of the stream to reach, penetrate, and effectively cool ceiling-level smoke and fire gases at
1,112F. If the walls, ceiling, and floors are not effectively cooled because of an ineffective stream, it is possible that
these surfaces may retain enough heat to reignite, causing advancing firefighters to suffer radiant thermal burns and
combustible fire gases to ignite when they fall back within their respective flammable range.
One gallon of water can absorb only so much heat per second. If the heat-absorbing capability, or knockdown power,
of the flow rate is greater than the heat produced by the fire, the HRR, the fire will go out. William E. Clark refers to
this required flow rate as the critical flow rate.17 Conversely, if the HRR is greater than the heat-absorbing capability
of the applied stream when it reaches the ceiling, the fire will not go out in a timely fashion to adequately protect
interior operating nozzle teams and trapped occupants. In other words, the critical flow rate has not been delivered!
For example, if a fog stream produces a flow of 150 gpm, then the HRR that the stream can absorb is 35 MW at
1,112F. If a fire in a room is calculated to produce 20 MW, this flow rate will be effective in absorbing the heat
produced. However, if the same stream cannot reach or penetrate the 1,112F ceiling gases and smoke, or if the
HRR is 40 MW, then the stream would not be able to effectively control the fire in the time desired for firefighter or
occupant protection.
Considering this, when you commit to an interior attack, you select an initial attack flow rate at the exterior of the
structure. This gpm selection is based on exterior conditions from a distance, not on conditions inside the structure. If
a handline with a flow rate of less than 150 gpm is taken into the structure, the streams effective heat-absorbing
capacity and flashover-inhibiting power may not be sufficient to rapidly combat the HRR if the entire contents of a
room become involved.
The increasing use of lightweight building materials for initial construction as well as remodeling, repair, and
renovation projects; improved insulating materials; and energy-efficient windows indicate that as use of these
materials becomes more common, a greater percentage of fires will retain a greater amount of heat and combustible
smoke in the fire compartment as compared with the past. As exemplified in tests conducted by Underwriters
Laboratories, using ASTM Method E119, it has been demonstrated that modern lightweight building materials for
residential and commercial structures, such as wooden I-beams and OSB for flooring materials, can fail in as little as
six minutes on exposure to fire.18 Increased use of lightweight building materials underscores the need to select fire
streams that can do the following: (1) penetrate fire gases at the ceiling level and (2) immediately and effectively
absorb the total heat output that is actively attacking exposed flooring and materials at the ceiling. Not all flow rates
and stream types have the reach, momentum, or mass to penetrate fire and smoke gases rapidly approaching or at
1,112F, and not all flow rates possess the heat-absorbing capacity, using a single stream, to effectively suppress a
fire in an offensive interior attack in a relatively short time.
In the early 1980s, instructors at the National Fire Academy (NFA) examined the practicality of the Iowa formula for
normal operations, including use for an offensive interior attack initiated by a single engine company, concurrent
search operations, vertical and horizontal ventilation, and sequential support operations. (19, 3) The instructors then
surveyed a number of NFA students in simulated fire scenes, where the fire building was assumed to be 50 percent
involved, the fire attack initiated with a single interior attack line, and primary search and ventilation operations would
be achieved simultaneously with fire flow operations. (19, 3) The students provided their own assessment of needed
flows per line to operate such an interior attack. Based on their estimates, the instructors determined the
corresponding average flow rate based on square footage vs. the estimated flow rate. The corresponding formula is
(Area)/3.
Using the square footage NFPA 1710 provides for a two-story residential structure no more than 50 percent involved
in fire, the NFA flow formula calls for a rate of 666 gpm. This could include total involvement of the entire second floor,
totaling 1,000 ft2 for multiple compartments. It is highly unlikely that any single compartment on the second floor of a
typical residential structure would be 1,000 ft2. As discussed above, a room measuring 23 feet 23 feet, similar to
that of a two-car garage or a large family/bonus room, covers a square footage of just over 500 ft2. The corresponding
single-line flow rate for such an area using this formula would be 167 gpm.
Using the HRR/ft2 value of 0.07 MW/ft2 discussed above, if a two-story residential structure of 2,000 ft2 were 50
percent involved (1,000 ft2), a total HRR of all simultaneously involved compartments would be estimated to be 70
MW. Based on the heat-absorbing capabilities of a single fog or smooth bore handline listed above at manageable
nozzle reactions for a single person, more than one handline would be needed for this extent of involvement.
However, for a room of 500 ft2, an estimated peak HRR would be 35 MW, which would be much more likely to be
controlled by the heat-absorbing capabilities from a stream with a flow rate in the range of 150 to 185 gpm.
Over the past several years, there has been a great deal of discussion on verifying the actual flows from various
nozzles used for interior residential fire attack operations. Many of these discussions have highlighted the need for
firefighters to test their nozzles to determine what their actual flows are.
Lt. Jay Comella of the Oakland (CA) Fire Department discussed how flow rates and operating pressures were
examined after a fireground line-of-duty death. An initial attack handline flow rate of 150 to 185 gpm was suggested
following a Board of Inquiry investigation identifying the causal factors that led to a City of Oakland firefighter fatality.
(4) In another article, the authors suggested an initial attack flow rate of 180 gpm for a single handline based on
modern heat-release rates and to provide a safe margin of error in case of kinks, elevation changes, and other typical
fireground situations.22
KINK TESTS
In tests conducted at the Rockland County (NY) Fire Training Center, a series of common fireground kinks were
imposed in the middle of a 150-foot stretch of 1-inch fire hose. Nozzles tested included a 1516-inch smooth bore
(180 gpm at 50 psi), a 150-gpm variable fog nozzle (50 psi), and an automatic 150-gpm fog nozzle (100 psi). The
1516-inch smooth bore nozzle, at an initial flow rate of 180 gpm, maintained a higher average flow with kinks
imposed (150 gpm) than the other two 150-gpm nozzles that started at 50 psi (133 gpm) and 100 psi (111 gpm). The
double 180 kink flows were excluded from comparison for this report, since the authors experience has been that
this kink condition is most often encountered when a hosebed is not cleared prior to charging and is not that common
and is not used for fire attack operations.23
In August and September 2008, members of Sacramento (CA) Metropolitan Fire Departments Command Training
Center Hands-On Training Team flow-tested all of the departments handlines and nozzles, as well as a 1516-inch
smooth bore nozzle and a 50-psi, 150-gpm single-gallonage fog nozzle. The tests were to provide Metro Fire
members with accurate flow data for all interior attack lines using department standard fog and smooth bore nozzles.
All nozzles were operated and flow-tested at the manufacturers designed pressure of 50 psi (smooth bore) or 75 psi
(fog). As reported in previous studies, actual flows from fog nozzles were found to be less than the stated flow.
Conversely, from all smooth bore nozzles, flows either met or exceeded the flow rate for the specific tip diameter at
50 psi. Although 1.-, 1-, and 2-inch handlines were tested, only the results of the tests for the 1-inch handlines
are discussed in this article.
Another component of the Metro Fire tests included imposing the same kinks as was done in the Rockland County
research. Wooden templates were constructed to ensure that the exact same angles were imposed on each
repetitive test. In the Metro Fire tests, hose lengths of 200 feet were used, since most attack lines subjected to this
extent of kinking in this departments experience exceed 150 feet. (Metro Fire uses a single 150-foot preconnected
attack line; all other handline beds are dead/static loads of 400 feet or greater.) The first 50 feet and the last 50 feet of
hose were kept kink free; kinks were imposed on the middle two hose sections. The results of the Metro Fire flow
tests closely paralleled those of the Rockland County tests.
Table 3 provides the average flows with kinks imposed (excluding the double 180 kinks) from the Metro Fire tests.
Note that all standard Metro Fire fog nozzles use an integral smooth bore tip should an engine company officer elect
to use a smooth bore nozzle for fire attack operations. The standard Metro Fire fog nozzle used on 1-inch handlines
is an adjustable-gallonage fog nozzle rated to flow 30 to 200 gpm at 75 psi, tested at the 150-gpm setting with an
integral 78-inch tip rated to flow 160 gpm at 50 psi. The other nozzles tested were a 1516-inch smooth bore nozzle
and a single-gallonage fog nozzle rated to flow 150 gpm at 50 psi, with an integral 1516-inch tip rated to flow 185
gpm at 50 psi.
One of the more significant findings was the ability of the solid streams, at similar initial flows and at lower nozzle
pressures (50 psi), to maintain a higher average flow when kinks were imposed. Very similar results were produced in
the Rockland tests. One interesting finding for fog nozzles is that as the design nozzle pressure increased from 50 to
75 to 100 psi for the 150-gpm fog nozzles, the average flow with kinks decreased from 135 gpm (50 psi fog) for Metro
and 133 gpm for Rockland (50 psi fog) to 118 gpm for Metro (75 psi fog) and 111 gpm-Rockland (100 psi fog),
respectively. This indicates that as the required nozzle pressure increases, the ability to maintain a flow near 150 gpm
decreases when kinks are imposed on the hoselinein other words, as the required operating pressure for a fog
nozzle increases, it is more susceptible to flow reduction by kinks.
The flow that a nozzle team fights fire with must account for typical initial attack line problems such as kinks, car tires,
unsecured doors, narrow hallways, and so on. This is even more true of engine companies operating with only three
personnel, where two personnel are stretching and operating the handline with no additional assistance in the first
few critical minutes of an initial attack. For purposes of identifying target flow, the authors call this average flow that
takes into account reductions from standard kinks the fireground flow. Such kinks and flow-restricting conditions
may not be identified and removed until other crews arrive well after the first line is operating within a structure (for
instance a confirmed rescue/trapped occupant).
From Table 3, we see that the minimum initial target flow capable of providing an average minimum fireground flow
of 150 gpm is 185 gpm. However, when the authors experimented with a measured nozzle inlet pressure of 75 psi
with the 50 psi, 150-gpm fog nozzle, they measured a flow rate of 185 gpm. The calculated nozzle reaction was 81
pounds. Given that the goal of initial attack handlines is to select a nozzle reaction of less than 70 pounds so that the
nozzle can be managed effectively and safely by one person, this nozzle pressure and flow will be excluded.
FLOW-RATE EFFICIENCY
Table 4 presents flow rates and calculated nozzle reactions the authors determined during recent flow tests. During
initial attack operations, most engine companies in the United States are likely to select 1-inch handlines as the first
two lines. (1)Since NFPA 1710 recommends a total flow of 300 gpm from the first two handlines, a handline with an
initial minimum flow rate of 180 gpm, without kinks or flow restrictions, will be needed to ensure, with a good degree
of certainty, that each nozzle is delivering on average 150 gpm over the course of the fire attack.
Considering that an initial minimum flow rate of 180 gpm is needed if two like lines are to be used to ensure a total
fireground flow rate of at least 300 gpm, the nozzle reaction associated with this flow rate must be assessed to
determine the safest and most efficient way for a two-person nozzle team to meet this standard for safety and
effective fire attack operations.
In Table 4, the minimum nozzle reaction associated with a given nozzle capable of producing a flow (with kinks
averaged in) from two similar lines meeting the 300-gpm NFPA 1710 recommendation is 69 pounds. In these tests,
fireground flow rates produced by nozzles with nozzle reactions less than 69 pounds did not meet the NFPA 1710
recommendation. Conversely, although larger lines with flow rates approaching 300 gpm could be used, such as a
2-inch handline, the associated nozzle reaction would exceed the recognized safe single-firefighter maximum
nozzle reaction of 69 pounds. (13, 132).
A nozzles flow rate efficiency can be determined by comparing the nozzles flow rate against nozzle reaction. Table 4
reveals that when comparing flow rate against nozzle reaction, the minimum initial flow rate capable of meeting the
NFPA 1710 recommendation from two like lines must have an efficiency greater than or equal to 2.61 gpm per pound
of nozzle reaction. Of the nozzles evaluated, only two nozzles had reactions less than 69 pounds (single firefighter
maximum) with fireground flow rates that meet the NFPA 1710 recommendation: the two 1516-inch smooth-bore
nozzles with nozzle inlet pressures of 50 psi. All other streams evaluated in this test either had a nozzle reaction in
excess of 69 pounds or a fireground flow rate, inclusive of kinks, of less than 150 gpm per line. This indicates that two
like lines would not reliably meet or exceed the 300-gpm recommendation when typical hoseline management
problems are encountered during early initial attack operations.
The authors would like to thank the following for their assistance: Sacramento (CA) Metro Fire Department: Assistant
Chief Brian Rice, Battalion Chiefs Andoni Kastros and Ed Crawford; Captains Chris Greene, Randy Gross, and
Darren Taylor; Engineers Mike Welch, Dale Darnell, Ronni Sorgi, and Bryan Barthel; and Firefighters Bob Santee,
Mark Schreck, and Rich Turner. Special thanks also to Oakland (CA) Fire Department Lieutenants Jay Comella and
Darryl Liggins and Denver (CO) Fire Department District Chief David McGrail. The authors also acknowledge the
great contributions of the late Andrew Fredericks.
Endnotes
1. Coleman, John, Nozzle Settings, Fire Engineering, June 2006.
2. NFPA 1410, Standard on Training for Initial Emergency Scene Operations, 2010 edition. [Quincy, Mass.: National
Fire Protection Association (NFPA)].
3. NFPA 1710, Standard for the Organization and Deployment of Fire Suppression Operations, Emergency Medical
Operations, and Special Operations to the Public by Career Fire Departments, 2010 edition, NFPA.
4. Comella, Jay, Planning a Hose and Nozzle System for Effective Operations, Fire Engineering, April 2003.
5. NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services Communications
Systems, 2010 edition, NFPA.
6. Report on Residential Fireground Field Experiments National Institute of Standards and Technology (NIST)
Technical Note 1661, Gaithersburg, MD: U.S. Dept of Commerce, April 2010, 31.
7. Estimating Temperatures in Compartment Fires. In SFPE Handbook of Fire Protection Engineering, 3rd Edition,
DiNenno P, D Drysdale, CL Beyler, WD Walton, eds. 2002: 3, 171-188.
8. Kennedy, Kathryn C. and Patrick M Kennedy, Flashover and Fire Analysis: A Discussion of the Practical Use of
Flashover Analysis in Fire Investigations, Investigations Institute (Sarasota, FL: John A Kennedy and Associates, Inc,
2003).
9. Spearpoint, M, FW Mowrer, and K McGrattan, Simulation of a Compartment Flashover Fire Using Hand
Calculations, Zone Models, and a Field Model, International Conference on Fire Research and Engineering, Third
Proceedings. Oct 4-8, 1999, Chicago, IL. (Boston, Mass: Society of Fire Protection Engineers; 1999, 3-14).
10, Babrouskas, Vytenis, RD Peacock, and PA Reneke, Defining Flashover for Fire Hazard Calculations: Part II,
Fire Safety Journal, Elsevier Science Ltd.; 2003 (38).
11. Fire Fighting Tactics Under Wind-Driven Conditions: Laboratory Experiments, NIST Technical Note,
Gaithersburg, MD: U.S. Dept of Commerce, 2009.
12. Effect of Wall and Room Surfaces on the Rates of Heat, Smoke, and Carbon Monoxide Production in a Park
Lodging Bedroom Fire, National Bureau of Standards NBSIR-85-2998, Gaithersburg, MD., U.S. Dept. of Commerce,
1985, 13.
13. Fredericks, Andrew A, Little Drops of Water: 50 Years Later, Part II, Fire Engineering, March 2000, 12.
14. Dunn, Vincent. Strategy of Firefighting. [Tulsa, OK: Pennwell Corporation, 2007, 40].
15. Grimwood, Paul and C Barnett, Fire-Fighting Flow Rate, www.firetactics.com, Jan 2005, 38.
16. Cook County Administration Building Fire, Heat Release Rate Experiments and FDS Simulations. NIST Special
Publication SP-1021, Gaithersburg, MD: U.S. Dept of Commerce, 2004, 75.
17. Clark, William E. Firefighting Principles and Practices, 2nd Edition. (Saddle Brook, NJ: Fire Engineering Books
and Videos, 1991, 34).
18. Structural Stability of Engineered Lumber in Fire Conditions, Online Course. Underwriters Laboratories. U.S.
Department of Homeland Security; 2008. Available Online:
htttp://www.ul.com/global/eng/pages/offerings/industries/buildingmaterials/fire/structural/.
19. Burns, Edward and BW Phelps, Redefining Needed Fire Flow for Structure Firefighting, Fire Engineering, Nov
1994, 22.
20. Brunacini, Alan, telephone conversation, Jan 9, 2009.
21. Pumping Apparatus Operations, IFSTA, 186..
22. Flatley, Christopher, J Knapp, and T Pillsworth, Testing Your Target Flow, Fire Engineering, Oct 2006.
23. Leihbacher, Doug, C Flatley, J Knapp, and T Pillsworth, How Kinks Affect Your Fire Attack System, Fire
Engineering, Oct 2007.
JASON N. VESTAL has 14 years of experience as a career firefighter. He is a captain with the Sacramento
Metropolitan (CA) Fire Department, where he has worked since 2000. He has an A.S. in fire science from Allan
Hancock and a B.S. degree in environmental and resource sciences with an emphasis in hydrobiology from the
University of California at Davis.
ERIC A. BRIDGE has been a career firefighter for 17 years and is a battalion chief with the Sacramento Metropolitan
(CA) Fire Department, where he has worked since 1994. He has an A.S. in fire science and a B.S. in occupational
studies from California State University-Long Beach.
position and use the short-burst 3-D water-fog techniques to grab some vital seconds before they vacate their
position. (2, 9)
Based on this statement, the 3-D method is a means for advancing into a fire area, not an in-place survival technique
when a flashover is about to occur or is occurring. When situational awareness of fire conditions is limited or entirely
masked, flaming in the overhead is often not easily apparent and the signs that signal an imminent flashover can be
easily missed; firefighters in such a position will likely not have enough time to evacuate.
In an impending flashover, during an aggressive and committed interior attack, it will often take firefighters on the
interior of a working structural fire more than a few seconds to exit the structure. According to Fire Department of New
York (FDNY) Deputy Chief (Ret.) Vincent Dunn (a recognized subject matter expert on flashover incidents), time and
motion tests published in the Handbook of Fire Protection have shown that the average person moves two to five feet
per second when walking.3 The question Dunn poses is, How long can a firefighter take 1,000F to 1,500F
temperatures on the neck, ears, wrists, and any other exposed portions of the body? Dunn states that if there is a
1,000F flame in a burning room that has just flashed over, and a firefighter, who is five feet inside the room, crawls
back to the doorway at one-half foot per second, he will feel 1,000F to 1,500F temperatures on the portions of skin
not covered by fire gear for two seconds. Firefighters who are 10 feet inside the room when the room flashes over
and try to escape will experience 1,000F to 1,500F heat on the exposed portions of their bodies for four seconds.
(3) According to Dunn, the point of no return for firefighters in a room that is flashing over is five feet. Beyond five feet,
structural turnouts do not afford enough thermal protection during a flashover to provide a good chance of survival.
(3)
minute (cfm) of air to the fire compartment and also creates air currents that can carry superheated air, steam, and
smoke back to the nozzle.8 In comparison, the 180-gpm stream from a 1516-inch smooth bore tip was measured to
move only 500 to 710 cfm.9 These findings were the results of nozzle air flow tests that dramatically illustrated the
effect that nozzle choices can have on air movement and firefighter and occupant safety during interior attack
operations.
Dunn continues:
A solid stream does not reduce temperatures as well as a fog stream. The 1516-inch smooth-bore nozzle
reduces steam burns, and we do not manage flashover with hose streams in the real world. This is done in
flashover training only. In a typical apartment fire, if you direct a hose stream ahead, you will not be caught
in flashover. Firefighters searching without a line are caught in flashovers. A 1-inch hose with a 1516inch nozzle is an optimum hoseline for maneuverability, nozzle reaction, and discharge for one firefighter
assigned to the nozzle and a couple of backup firefighters. This 1-inch line is not used in commercial
building fires, high-rise fires, or as a backup line, which necessitate 2-inch lines. (6)
The NIST 2009 tests compared the performance of a fog stream vs. a solid stream in cooling and suppressing a fire
compartment with a room of origin that was 12- 16- 8 feet with a square footage of 192 ft2. In the first 30 seconds,
the fog stream actually increased temperatures from 400F to 1,000F, increased the HRR from 12 MW to 16 MW,
and took 30 seconds to reduce radiant heat levels in hallways (heat flux at three feet above the floor). The
temperature at the ceiling was still capable of producing enough radiant heat at floor level to cause flashover and
significant injury to firefighters after 30 seconds. The study compared the heat reduction results when an 80-gpm 30
fog stream (applied from outside the fire building through a window) was used and also when a 160-gpm solid stream
from a 1516-inch smooth-bore nozzle was directed from outside of a window and directed at the ceiling into the room
of origin with a temperature of 1,112F. (4, 60-61)
When the fog stream was directed into the bedroom window, temperatures increased at the highest levels of the
room and varied widely for the first 70 seconds. (4, 249) When heat flux values were measured for the living room
and center hallway areas downwind from the bedroom, the values in both areas increased to 100 kW/m2. The center
corridor heat flux took approximately 80 seconds to drop to 20 kW/m2, and the living room heat flux was still at 50
kW/m2 after 80 seconds. (4, 259) In the first 80 seconds after the stream was applied into the bedroom, the
temperatures between the ceiling and one foot from the floor in the bedroom increased to above 800F and to
approximately 500F in the hallway leading from the bedroom to the living room. The temperature decreased to no
less than 392F at three feet above floor level in the center hallway outside of the apartment entrance. (4, 253)
These observations are consistent with Laymans specific warning in 1952 that firefighters should not operate fog
nozzles from interior positions inside a burning building, especially if there is a possibility of trapped civilians in the fire
compartment. (8) As previously discussed, air flows from a 150- to 180-gpm fog stream have been measured to
introduce in excess of 2,000 cfm to the fire compartment. Such a large infusion of air can accelerate the fire growth
rate and associated HRR. (9)
Conversely, in the NIST 2009 wind-driven report, the 160-gpm smooth-bore stream, when swept across the ceiling of
the bedroom, instantly dropped ceiling temperatures in all rooms below 1,112F and to less than 500F in
approximately 30 to 50 seconds. The smooth-bore stream was also able to drop the HRR from 16 MW to 8 MW in the
bedroom in the first 30 seconds20 seconds faster than the fog stream. (4, 291) Again, as reported by Knapp,
Pillsworth, and Flatley, a 1516-inch solid stream at 180 gpm increased air flow by only 510 to 720 cfm into the fire
compartment, which was much less than the fog stream at the same gpm, and caused no movement of superheated
gases or steam back toward the nozzle team, thus allowing the aggressive interior fire attack to continue. (9)
In the NIST 2009 wind-driven fire report, the heat flux at three feet above the floor in the room of origin began to drop
instantlyfrom 90 kW/m2 to 20 kW/m2 in 1 minute, 40 seconds when the solid stream was used. Both the downwind
living room and the center hallway heat flux values decreased to 20 kW/m2 in the first 45 seconds. In the first 70
seconds from the solid streams being swept across the bedroom ceiling, the temperatures between the ceiling and
one foot from the floor decreased to approximately 750F. In the first 30 seconds, temperatures in the hallway leading
from the bedroom to the living room dropped from 1,500F to 200F. In the living room, all levels instantly decreased
from approximately 1,600F to less than 1,112F and to less than 500F in the first 30 seconds. All levels in the center
hallway outside the apartment dropped to less than 500F in the first 30 seconds of applying the solid stream to the
ceiling of the bedroom. (4, 291)
Not only should engine company members advancing a hoseline consider these results in making their flow rate
selection, but firefighters conducting search operations opposite the nozzle and fire (such as vent-enter-search
operations) or approaching the fire room in a hallway (such as approaching truck company members in a center
hallway) should truly appreciate the significance of an engine companys members applying the correct flow rate in
the correct form for their own safety.
Simply stated, at conditions indicative of an impending or active flashover, the 1516-inch solid stream at 160 gpm
was able to drop temperatures and heat-flux levels to conditions that structural PPE can handle within approximately
30 seconds. (4, 291)
whereas smooth-bore nozzles with tip diameters between 78-inch and 118-inch produce droplets as large as 2.0 mm
in diameter. This concurs with the average droplet size of 0.25 to 0.35 mm for a fog nozzle as determined by testing
conducted by the Fairfax County (VA) and Montgomery County (VA) Fire Departments and NIST in 1985. (8, 98)
In 1992, the NIST report published by Pietrzak and Dale provided a graph of what happens to water droplets of a
given diameter at a ceiling temperature of 1,112F and a ceiling height of 10 feet. A droplet that does not evaporate at
the ceiling will fall to the floor if it is too heavy for the thermal updrafts to lift. If it is too light, it will get trapped and
circulate in the thermal updrafts. For droplets of the size reported by NIST in 1985 (0.35 mm from a fog nozzle), 75
percent of the droplets will evaporate at the ceiling, 12.5 percent will fall to the floor, and 12.5 percent will be caught in
the thermal column.12
For the larger droplets produced from a smooth-bore nozzle (at least 1.0 mm), approximately 40 percent of the
stream evaporates at the ceiling, 55 percent of the stream falls to the floor, and 5 percent is trapped in the thermal
column. (12)
Water droplets that fall to the floor absorb heat radiated from the ceiling and can then assist with preventing ignition of
the combustible materials that may lead to flashover. The more water that falls from the ceiling to the floor, the more
that stream can prevent floor materials from igniting. According to Pietrzak and Dale, A significant fraction of the
drops with sizes less than 0.35 mm are blown away by hot gases and are not effective in achieving fire control the
larger drops become more effective, since they penetrate better, lose less of their volume by evaporation, and carry
more water to the burning surfaces. (12)
Grimwood reports on research that assessed the ability of streams with different sizes of droplets to cool wall
surfaces during the first two minutes of application: For a droplet 0.33 mm in diameter, the approximate diameter of a
fog-stream droplet, reduced the wall temperature by 135F; however, when droplets with a diameter of 0.78 mm were
evaluated, the wall temperature was reduced by 383F.13 In other words, as the size of the droplets reaching heated
surfaces such as ceilings and walls increases, the magnitude of the temperature reduction also increases. Therefore,
to cool surfaces in a fire faster, the larger the droplets at the ceiling, the greater the temperature reduction throughout
the entire compartment.At a droplet diameter of 0.8 mm (approaching the diameter of a solid stream droplet), 48
percent of the stream falls to the floor, 48 percent evaporates, and about 4 percent is lost in convection current,
where it continues to recirculate in air currents produced by the fire. This 4 percent fraction of the stream does not
evaporate, and it does not fall to the floor. It is essentially wasted, recirculating as hot steam in the center of the room.
At a droplet diameter of 1.0 mm, approximately 42 percent is evaporated at the ceiling level, 55 percent falls to the
floor, and 3 percent is wasted in the convection column.
Figure 1. Median Droplet Diameter
At 2.0 mm and larger diameters, 20 percent is evaporated at the ceiling level, 80 percent falls to the floor, and little to
no water remains in the convection column. Given that the heat-absorbing efficiency of a solid stream when applied
to ceiling gases at near-flashover temperatures has been reported as 50 percent, in this article, an average diameter
of 1.0 mm will be used as the diameter for droplets from solid streams. This diameter size correlates well to the
reported solid stream efficiency of 50 percent.14
As droplet diameter increases, the amount of water that can fall back to the floor and burning materials increases.
Whatever isnt used to cool high-temperature fuel gases and hot surfaces at the ceiling level will fall to the ground,
directly suppress the seat of the fire, and also prevent unignited fuels from reaching their flashover temperature.
Larger droplets place more water where it is neededthe ceiling, walls, and floorand trap less water in the
convection column between the ceiling and the floor.
The fire sprinkler industry has studied water droplet behavior in fires extensively. Sprinklers must produce droplets
that possess a mass and volume heavy enough to produce a terminal velocity that can fall from the ceiling down
through the thermal column and land on the floor and smother burning fuels. Although the smaller and lighter droplets
produced by fog streams have a higher surface area to volume ratio and are highly effective at reducing temperatures
in the convection column, these droplets get trapped between the floor and the ceiling. In this location, these droplets
do not cool burning ground fuels, burning walls, or ceiling surfaces and do not have an immediate effect on the
1,112F flashover fuel gases in upper levels. Be aware that as more droplets and steam get trapped in the convection
column in the center of the room, the more likely you are to experience steam burns to your upper body, neck, and
ears.
Note: Referring to the stream-efficiency values reported by Barnett and Grimwood in 2005 (14, 26), the fog stream is
75 percent efficient in cooling a fire, and the smooth bore is 50 percent efficient. We reiterate that the wide fluctuation
of temperatures when the fog stream was used vs. the instant reduction in ceiling temperatures when the solid
stream was used in the 2009 NIST Firefighting Tactics report (4) supports Grimwoods earlier statement that a fog
stream, when operated from the floor toward a ceiling with gases and smoke at a temperature of 1,112F, is not as
effective at reaching and cooling upper-level ceiling gases as a solid stream. (2, 4)
Water that falls to the floor of a fire compartment and covers unignited combustible materials, such as carpeting and
furniture, can absorb 0.38 MJ/kg, or 0.024 MW/gpm, of radiant heat from the ceiling. (11, 53) HRRs produced by
ceiling gases at a temperature of 1,112F have been reported to be between 1.2 and 2.0 MW just prior to flashover.
When selecting a single-line initial attack flow rate, choose a flow rate that can simultaneously cool the overhead and
prevent floor-level combustibles from flashing over. A floor droplet rate of 84 gpm is needed to effectively absorb an
overall HRR of 2 MW. Considering that solid streams produce droplets equal to or greater than 1.0 mm in diameter,
with at least 55 percent of the stream flow falling back to the floor, we recommend a single-line minimum fireground
flow rate of 152 gpm from a solid stream to penetrate the ceiling gases to ensure that 84 gpm will reach the floor in
droplet form. Using a fog nozzle, which may have approximately 12.5 percent of its droplets fall back to the floor, you
would have to apply a flow rate of 672 gpm to the ceiling to obtain a droplet fallout rate (DFR) of 84 gpm.
In the 2008 NIST study, the 1516-inch smooth-bore nozzle produced a flow rate of 160 gpm. (4, 294) In tests
conducted by the authors, the 1516-inch smooth-bore nozzle produced a fireground flow rate (FFR) of 162 gpm.
Using the 160-gpm flow rate, a field approximation of the maximumin other words, worst-casepeak HRR that a
160-gpm solid stream can effectively absorb at a ceiling temperature of 1,112F is 343 ft2 (30.9 m2) or a room 18.5
feet 18.5 feet, which is estimated to produce a peak HRR of 24 MW.
When 160 gpm is applied at the ceiling, a DFR of 55 percent and approximately 88 gpm is predicted to fall to the floor
onto burning materials and unburned fuels. Once on the floor, this water that is collecting on unburned fuels can
absorb 0.38 MJ/kg, or 0.024 MW/gpm, of radiant heat. At 0.024 MW/gpm, a DFR of 88 gpm can absorb 2.1 MW at
floor level. Dividing 2.1 MW by the maximum square footage associated with the peak HRR that the 1516-inch solid
stream can handle (fireground flow rate of 162 gpm) predicts that 89 gpm at floor level can effectively absorb a heat
flux value of 69.1 kW/m2. This potential heat flux capability value for a 160-gpm solid stream is similar to, and slightly
exceeds, the preflashover heat-flux values reported by the 2009 NIST study. By rapidly sweeping the stream across
the ceiling when preflashover conditions are observed, a nozzle team should be able to distribute droplets throughout
an 18-foot 18-foot room successfully.
If a solid stream with a heat flux capability of exactly 20 kW/m2 for an 18-foot 18-foot room is desired, an initial
fireground flow rate of 46 gpm would be needed, and a DFR of 25 gpm would be predicted to fall from the ceiling.
Although this droplet rate could, in theory, absorb the minimum floor heat flux value of 20 kW/m2 that can initiate a
flashover, the flow rate of 46 gpm from a smooth-bore nozzle at the ceiling could address only a HRR of 6.9 MW at
the ceiling level. Solving for area, at a HRR/ft2 of 0.07 MW/ft2, the maximum square footage this 46 gpm stream
could handle would be 100 ft2, or approximately a room 10 feet 10 feet. A flow rate of 25 gpm at the floor does not
leave much room for error, and the flow rate at the ceiling does not provide enough flexibility to address many rooms
in a residential structure that are often larger than 10 feet 10 feet and that are encountered in a progressive
multiroom interior attack.
Although it is not possible to flow 672 gpm from a fog nozzle in an interior attack with a single nozzle team, you can
easily flow 152 gpm from a single smooth-bore handline. As noted above, the 1516-inch smooth-bore nozzle delivers
180 gpm without kinks and an FFR of 162 gpm when flows with kinks are averaged. With kinks averaged, the flow of
162 gpm from the 1516-inch smooth-bore nozzle has the reach, penetration, and heat-absorbing capability to absorb
the heat produced in a typical residential room near flashover up to 347 ft2, or a room that is 18 feet 18 feet
and, with no kinks, a room that measures 19 feet 19 feet. These values indicate that the 1516-inch solid stream,
with or without kinks, can rapidly knock down a fire in a room of dimensions in the range of up to 18 to 19 feet on
each side. The average flow rate of 162 gpm with kinks produces a DFR of 89 gpm with a heat-absorbing capability
at floor level of 2.14 MW. When no kinks are imposed on the 1516-inch handline, a floor droplet rate of 101 gpm with
a predicted maximum heat-absorbing capability on floor surfaces of 2.38 MW is possible. This suggests that the solid
stream produced by the 1516-inch smooth-bore nozzle also can absorb a considerable amount of radiant heat at
floor level where unignited combustibles are located, thereby providing a secondary protective factor to minimize the
chances of a flashover.
The effectiveness of the 1516-inch stream and its associated characteristics were demonstrated in the NIST winddriven study. The 1516-inch smooth-bore nozzle produced a flow of 160 gpm at 35 psi and exhibited dramatic and
instant results in reducing heat release rates, ceiling temperatures, and radiant heat at floor level in approximately 30
seconds in several of the fire apartment rooms, hallways, and the center corridor outside of the apartment. This
suggests that the heat-absorbing capabilities of a 160-gpm solid stream can handle the post-flashover conditions
associated with a fully involved room at a HRR of 0.07 MW/ft2 in an effective amount of time, even when nozzle
pressure is less than 50 psi because of various fireground situations that can reduce nozzle pressure commonly
encountered on the fireground. The rapid knockdown observed with a solid stream at a flow rate of 160 gpm
suppressed a fire at the HRR measured demonstrated under closely monitored conditions that this flow rate and
stream type rapidly improve conditions for firefighters who may be approaching or operating in such a hostile and
rapidly changing environment.
We have presented a quantitative methodology for selecting an initial attack flow rate and stream type for use in an
interior attack using a single handline. The initial line must be of a flow rate and type that can penetrate the elevated
temperatures and smoke at the ceiling level, instantly and effectively absorbing the anticipated heat release rates
from interior compartment fires approaching flashover.
In addition, todays understaffed engine companies must be able to safely and efficiently handle the nozzle with one
nozzle operator. The flow rate must enable the interior attack nozzle team to protect itself and trapped occupants by
rapidly cooling all levels in a compartment, should the signs of an impending flashover develop. Last, the initial flow
rate and stream type must produce, on average, a flow rate that, even when reduced by kinks and elevation changes,
will reliably be able to instantly and singlehandedly defeat preflashover conditions with a single stream. This approach
to identifying a target flow rate and selecting a stream type provides a nozzle team with the firepower to rapidly reach,
protect, and rescue trapped occupants; minimizes the nozzle teams likelihood of being subjected to a flashover; and
provides for a reliable, aggressive, and rapid knockdown to freeze the fires progression to a possible flashover.
The authors would like to thank the following for their assistance: Sacramento (CA) Metro Fire Department: Assistant
Chief Brian Rice, Battalion Chiefs Andoni Kastros and Ed Crawford; Captains Chris Greene, Randy Gross, and
Darren Taylor; Engineers Mike Welch, Dale Darnell, Ronni Sorgi, and Bryan Barthel; and Firefighters Bob Santee,
Mark Schreck, and Rich Turner. Special thanks also to Oakland (CA) Fire Department Lieutenants Jay Comella and
Darryl Liggins and Denver (CO) Fire Department District Chief David McGrail. The authors also acknowledge the
great contributions of the late Andrew Fredericks.
Endnotes
1. Report on Residential Fireground Field Experiments National Institute of Standards and Technology (NIST)
Technical Note 1661, Gaithersburg, MD: U.S. Dept of Commerce, April 2010, 49.
2. Grimwood, Paul, A Comparison of 3D Water-Fog versus Straight Streams, Using Burst and Pause Cycles to Cool
and Inert Dangerous Fire Gases in the Overhead of a Compartment Fire,www.firetactics.com/.
3. Dunn, Vincent, Flashover, Newsletter. July 2000; http://vincentdunn.com/dunn/newsletters/july/flashover.pdf/, 3.
4. Fire Fighting Tactics Under Wind-Driven Conditions: Laboratory Experiments, NIST Technical Note, Gaithersburg,
MD: U.S. Dept of Commerce, 2009, 335.
5. Dunn, Vincent. Strategy of Firefighting. (Tulsa, OK: Pennwell Corporation, 2007), 358.
6. Dunn, Vincent, e-mail, Nov. 12, 2008.
7. Clark, William E. Firefighting Principles and Practices, 2nd Edition (Saddle Brook, NJ: Fire Engineering Books and
Videos, 1991), 33.
8. Fornell, David P. Fire Stream Management Handbook. (Saddle Brook, NJ: Fire Engineering Books and Videos,
1991), 82.
9. Flatley, Christopher, J Knapp, and T Pillsworth, Nozzle Tests Prove Fireground Realities, Part III, Fire
Engineering, Feb 2004, 67-72.
10. Davis, Simon K. Fire Fighting Water: A Review of Fire Fighting Water Requirements: A New Zealand
Perspective. Project Report: Fire Engineering Report 2000/3 (Feb 2000), University of Canterbury, New Zealand.
11. Sardqvist, Stefan, An Engineering Approach to Fire-Fighting Tactics, Lund Institute of Technology, Sweden,
2006, 55.
12. Users Guide for the Fire Demand Model; A Physically Based Computer Simulation of the Suppression of PostFlashover Compartment Fires, NIST-GCR-92-612. Gaithersburg, MD: U.S. Dept of Commerce, 1992.
13. Grimwood, Paul. Flashover and Nozzle Techniques. Crisis and Emergency Management Centre, London Fire
Brigade, 2002.
14. Grimwood, Paul and C Barnett, Fire-Fighting Flow Rate, www.firetactics.com, Jan 2005, 26.
JASON N. VESTAL has 14 years as a career firefighter. He is a captain with the Sacramento Metropolitan (CA) Fire
Department, where he has worked since 2000. He has an A.S. in fire science from Allan Hancock and a B.S. degree
in environmental and resource sciences with an emphasis in hydrobiology from the University of California at Davis.
ERIC A. BRIDGE has been a career firefighter for 17 years and is a battalion chief with the Sacramento Metropolitan
(CA) Fire Department, where he has worked since 1994. He has an A.S. in fire science and a B.S. in occupational
studies from California State University-Long Beach.