Fundamentals of Power System Protection
Fundamentals of Power System Protection
Electromechanical Relays
Solid State Relays
Numerical Relays
For simplicity in explaining the key ideas, we consider three phase bolted faults.
2.1 Overcurrent Protection
This scheme is based on the intuition that,
faults typically short circuits, lead to currents
much above the load current. We can call
them as overcurrents. Over current relaying
and fuse protection uses the principle that
when the current exceeds a predetermined
value, it indicates presence of a fault (short
circuit). This protection scheme finds usage
in radial distribution systems with a single
source. It is quite simple to implement.
Fig 2.1 shows a radial distribution system with a single source. The fault current is fed from only one end of
the feeder. For this system it can be observed that:
To relay R1, both downstream faults F1 and F2 are visible i.e. IF1 as well as IF2 pass through CT of R1.
To relay R2, fault F1, an upstream fault is not seen, only F2 is seen. This is because no component of
IF1 passes through CT of R2. Thus, selectivity is achieved naturally. Relaying decision is based solely
on the magnitude of fault current. Such a protection scheme is said to be non-directional.
In contrast, there can be situations where for the purpose of selectivity, phase angle information (always
relative to a reference phasor) may be required. Fig 2.2 shows such a case for a radial system with source at
both ends. Consequently, fault is fed from both the ends of the feeder. To interrupt the fault current, relays at
both ends of the feeder are required.
In this case, from the magnitude of the current seen by the relay R2, it is not possible to distinguish whether
the fault is in the section AB or BC. Since faults in section AB are not in its jurisdiction, it should not trip. To
obtain selectivity, a directional overcurrent relay is required. It uses both magnitude of current and phase
angle information for decision making. It is commonly used in subtransmission networks where ring mains
are used.
2.3 Distance Protection
Consider a simple radial system, which is fed from a
single source. Let us measure the apparent impedance
(V/I) at the sending end. For the unloaded system, I = 0,
and the apparent impedance seen by the relay is
infinite. As the system is loaded, the apparent
impedance reduces to some finite value (ZL+Zline) where
ZL is the load impedance and Zline is the line impedance.
In presence of a fault at a per-unit distance m', the
impedance seen by the relay drops to a mZline as shown
in fig 2.3.
The basic principle of distance relay is that the apparent impedance seen by the relay, which is defined as
the ratio of phase voltage to line current of a transmission line (Zapp), reduces drastically in the presence of a
line fault. A distance relay compares this ratio with the positive sequence impedance (Z1) of the transmission
line. If the fraction Zapp/Z1 is less than unity, it indicates a fault. This ratio also indicates the distance of the
fault from the relay. Because, impedance is a complex number, the distance protection is inherently
directional. The first quadrant is the forward direction i.e. impedance of the transmission line to be protected
lies in this quadrant. However, if only magnitude information is used, non-directional impedance relay results.
Fig 2.4 and 2.5 shows a characteristic of an impedance relay and mho relay' both belonging to this class.
The impedance relay trips if the magnitude of the impedance is within the circular region. Since, the circle
spans all the quadrants, it leads to non-directional protection scheme. In contrast, the mho relay which
covers primarily the first quadrant is directional in nature.
,
then trip; else restrain.
While impedance relay has only one design parameter, Zset; 'mho relay' has two design parameters Zn, .
The trip law for mho relay is given by if
,
then trip; else restrain.
As shown in the fig 2.5, is the angle of transmission line. Based upon legacy of electromechanical relays
is also called 'torque angle'.
2.3.1 Example
1. (a) Find out the value of Zn for a mho relay with torque angle 75 which has to give 100% protection to a
50 km long 110kV transmission line with impedance 0.8 per km and angle 80.
Ans: The two design parameters of a mho relay are Zn and . Here the torque angle, of the relay has been
selected as 75.
The transmission line impedance ZLine as on primary = 0.8 x 50 = 40
Since this value will not fall within the operating circle, the mho relay will not trip for this load.
Thus, we can say that differential current under no fault condition is zero.
However in case of fault in the line segment AB, we get
Faulted condition:
Figure 3.1 shows the various time scales involved in modelling system dynamics. The dynamics involved in
switching, lightening, load rejection etc have a high frequency component which die down quickly. In analysis
of such dynamics, differential equations associated with inductances and capacitances of transmission lines
have to be modelled. Such analysis is restricted to a few cycles. It is done by Electromagnetic Transient
Program (EMTP).
At a larger time scale (order of seconds), response of the electromechanical elements is perceived. These
transients are typically excited by faults which disturb the system equilibrium by upsetting the generator-load
balance in the system. As a consequence of fault, electrical power output reduces instantaneously while the
mechanical input does not change instantaneously. The resulting imbalance in power (and torque) excites
the electromechanical transients which are essentially slow because of the inertia of the mechanical
elements (rotor etc).
Detection and removal of fault is the task of the protection system (apparatus protection). Post-fault, the
system may or may not return to an equilibrium position. Transient stability studies are required to determine
the post fault system stability. In practice, out-of-step relaying, under frequency load shedding, islanding etc
are the measures used to enhance system stability and prevent blackouts. The distinction between system
protection and control (e.g. damping of power swings) is a finer one. In the today's world of Integrated
Control and Protection Systems (ICPS), this distinction does not make much sense.
3.2 System Protection Relays
Consider a medium voltage distribution system having
local generation (e.g., captive power generation) as
shown in fig 3.2 which is also synchronized with the
grid. During grid disturbance, if plant generators are not
successfully isolated from the grid, they also sink with
the grid, resulting in significant loss in production and
damage to process equipments. The following relays
are used to detect such disturbances, its severity and
isolate the inplant system from the grid.
Distribution systems are radial in nature. This holds true for both utility and plant distribution systems. If there
is a fault on the utility's distribution system, it may trip a breaker thereby isolating plant from the grid. This
plant may still remain connected with downstream loads as shown in fig 3.4 and 3.5. Consequently, power
will flow from the plant generator to these loads.
If in the prefault state, power was being fed to the plant, then this reversal of power flow can be used to
island the plant generation and load from the remaining system. This approach is useful to detect loss of grid
10
Example
In fig 3.4, consider that the plant imports at all times a minimum power of 5 MW. Studies indicate that for
various faults in utility side, minimum power export from the plant generator is 0.5 MW. Deduce the setting of
reverse power relay. If the plant generator is of 50 MW capacity, what is likelihood of underfrequency or rate
of change of frequency relay picking up on such faults?
Ans: Reverse power flow relay can be set to 0.4 MW. Since minimum reverse power flow is 1% of plant
capacity, it is quite likely, that utility disconnection may not be noticed by underfrequency or the rate of
change of frequency relays.
ZnO varistor is commonly used as lightning arrestor because of its peculiar resistance characteristic. Its
resistance varies with applied voltage, i.e, its resistance is a nonlinear inverse function of applied voltage. At
normal voltage its resistance is high. But when high voltage surges like lightning strokes appear across the
varistor, its resistance decreases drastically to a very low value and the energy is dissipated in it, giving
protection against lightning.
11
Dependability
Security
4.1 Dependability
A relay is said to be dependable if it trips only when it is expected to trip. This happens either when the fault
is in it's primary jurisdiction or when it is called upon to provide the back-up protection. However, false
tripping of relays or tripping for faults that is either not within it's jurisdiction, or within it's purview,
compromises system operation. Power system may get unnecessarily stressed or else there can be loss of
service. Dependability is the degree of certainty that the relay will operate correctly:
False trips do not just create nuisance. They can even compromise system security. For example, tripping of
a tie-line in a two area system can result in load-generation imbalance in each area which can be dangerous.
Even when multiple paths for power flow are available, under peak load conditions, overloads or congestion
in the system may result. Dependability and security are contrasting requirements. Typically, a relay
engineer biases his setting towards dependability. This may cause some nuisance tripping, which can in the
worst case, trigger partial or complete blackout! Security of the relaying system can be improved by
improving selectivity of the relaying system.
4.2.1 Selectivity
Like sensitivity, selectivity also
implies an ability to discriminate. A
relay should not confuse some
peculiarities of an apparatus with a
fault. For example, transformer when
energized can draw up to 20 times
rated current (inrush current) which
can confuse, both overcurrent and
transformer differential protection.
Typically, inrush currents are
characterized by large second
harmonic content.
This discriminant is used to inhibit
relay operation during inrush, there by, improving selectivity in transformer protection. Also, a relay should be
12
Example
The performance of an overcurrent relay was monitored over a period of one year. It was found that the relay
operated 14 times, out of which 12 were correct trips. If the relay failed to issue trip decision on 3 occasions,
compute dependability, security and reliability of the relay.
Number of correct trips = 12
Number of desired trips = 12 + 3 = 15
Note that even though dependability and security are individually above 80%, overall reliability much poor
(only 70.55%).
13
--- (1)
Fig 4.5 shows the pre and post fault
characteristics for the single machine
infinite bus system shown in fig 4.4. Initial
operating point A is on the pre fault
characteristic. Occurrence of fault
reduces Pe to 0. The power generation
imbalance accelerates generator and
hence its (power angle) increases. At
point C the fault is cleared by tripping the
faulted line and the system moves to post
fault characteristics. The power output
jumps to point D. Now Pe > Pm and the
machine decelerates.
14
Nuisance Tripping
Nuisance tripping is the tripping when there is no fault, e.g. an overcurrent relay tripping on load. It
compromises faith in the relaying system due to unnecessary loss of service. On the other hand, tripping on
faults that are outside the relay's jurisdiction also cause an unwarranted loss of service in the healthy parts of
the system.
It has to be mentioned that speed and accuracy bear an inverse relationship. The high-speed systems tend
to be less accurate for the simple reason that a high speed system has lesser amount of information
available at it's disposal for making decision.
Thus, the protection engineer has to
strike a balance between these two
incompatible requirements. Innovations in
protection are essentially driven by such
requirements.
15