SIMATIC PCS 7 Cabinet Design: 6/2 6/2 6/3 Basic Cabinet 6/4 ET 200M I/O Unit 6/5 System Unit
SIMATIC PCS 7 Cabinet Design: 6/2 6/2 6/3 Basic Cabinet 6/4 ET 200M I/O Unit 6/5 System Unit
6/2
6/2
Introduction
Overview
6/3
6/4
6/5
Basic cabinet
ET 200M I/O unit
System unit
6/1
Modular design
System-specific modules
AS 488/TM system unit
ET 200M I/O unit (ET 200U/ET 200B on request)
System-neutral modules
Basic cabinet, consisting of framework, door, outer walls, internal mechanical parts and power supply assembly with:
- Compartment for documents
- Trim
- AC 230 V socket
- AC 230 V or DC 24 V cabinet illumination
- I & C monitoring via automation system or cabinet lamp
Options
Circuit-breaker for protection of max. 6 cabinet tiers
I/O modules for ET 200M I/O unit
High flexibility
Future compatibility as result of universal, system-neutral modules
Modular packaging system permits flexible adaptation to the
respective application
Basic and expansion cabinets based on the same set of modules
Up to 4 system units or 6 I/O units can be fitted in a cabinet
System units and I/O units can be combined within the cabinet
Side walls or partitions can be selected specific to the application
Cabinets can be screwed together into double units or rows
Overview
The cabinet design for components close to the process (automation systems and I/Os) fulfills the technical and economical
demands placed on the AS 488/TM automation systems.
The cabinets consisting of system-specific modules (system
and I/O units) and system-neutral modules (basic cabinets and
options) comply with CE requirements and conform to the guidelines for electromagnetic compatibility. They are designed according to the VGB 4 guidelines, and provide exceptional
protection against unauthorized interventions, mechanical effects, contamination and corrosion.
As a result of their variable modular design, the cabinets can be
readily adapted to different types of system (for batch processes
or continuous processes) and system sizes.
The Siemens standard cabinet 8MC with degree of protection
IP 40 is the preferred basic cabinet. Cabinets with degree of
protection IP 20 and IP 55 are alternatively available.
6/2
Overview
The Siemens standard cabinet 8MC is the preferred basic cabinet. The Siemens standard cabinet 8MC is a sheet-steel cabinet
with rear panel and front door which can be assembled individually or also in rows with further cabinets of this type.
Side walls and partitions are optional, thus permitting variable
adaptation of the cabinet to different installation possibilities.
Up to four system units or six I/O units can be fitted in a cabinet
in conjunction with a DC 24 V or AC 230 V power supply assembly. System and I/O units can also be combined together within
a cabinet. The cables are introduced into the cabinet from below.
Mechanical design
Each delivered cabinet contains:
Cabinet illumination
Preparation of quotation, consulting and ordering
Siemens AG
D-76187 Karlsruhe
Tel.: +49 721 595-3776
Fax: +49 721 595-4711
E-mail: [email protected]
Technical Specifications
Siemens standard cabinet
Dimensions (H x W x D) in mm
Sheet-steel, 2 mm,
frame profile with 10 edges,
cross-member profile with 5
edges
Rear panel
Roof
Partition (option)
Color
Ergo gray to
SN 30 920-C611-B13
When ordering the basic cabinet, the following options are available for the mechanical design of the cabinet:
Plinth: a cabinet plinth should be used if cables cannot be connected through the floor. The plinths are preassembled, and
available with a height of 100 or 200 mm
Pocket for documents
Trim
Max. 40 C
Side walls/partitions: the basic cabinets are suitable for individual assembly or in rows. Therefore side walls and/or partitions
can be selected when ordering.
Max. 55 C
6/3
Overview
Complete ET 200M I/O stations are available for the cabinet
packaging system. The station includes the power supply, components for connection to the PROFIBUS-DP fieldbus (electrical
or optical design), selection of modules for hot swapping, and
wiring of load current connections.
The modular ET 200M I/O station with degree of protection IP 20
can be equipped with signal and function modules from the SIMATIC S7-300 automation system. These modules must be additionally ordered as required.
Power supply
The ET 200M I/O station can be operated with DC 24 V or
AC 120/230 V. With a DC 24 V supply, the I/O station is powered
directly from the cabinets power supply assembly, with an
AC 120/230 V supply, a PS 307 power supply module is additionally required upstream of the IM 153 interface module in the
I/O station in order to convert the AC 120/230 V into DC 24 V. The
DC 24 V input voltage provided by the power supply assembly
or the PS 307 power supply module is used to power the IM 153
and is the load power supply for the I/O modules.
The PS 307 power supply module is available in 5 A and 10 A
versions. The PS 307-1E version with a rated output current of
5 A is standard. If the configuration of the I/O station with
I/O modules results in a higher load, it is recommendable to use
the PS 307-1K with a rated output current of 10 A. Note, however, that the PS 307-1K width of 200 mm (compared to 80 mm
with the PS 307-1E) means that a maximum of six I/O modules
can be plugged onto the rail.
One fuse is fitted in the power supply assembly for each I/O station. With a DC 24 V supply, the IM 153 module and the L+/Mpower supply for I/O modules are fused together.
With an AC 120/230 V supply, the PS 307 power supply module
is fused. The L+/M voltage for the I/O modules is also obtained
from the PS 307.
6/4
Special bus modules are required for the hot swapping function.
In addition to the PS/IM bus module for the IM 153-1, IM 153-2
and IM 153-3 modules, these are the bus module 2 x 40 for accommodation of two I/O modules with a width of 40 mm each
and the bus module 1 x 80 for accommodation of one module
with a width of 80 mm. Up to four bus modules for I/O modules
can be plugged onto each rail in addition to the PS/IM bus module. Bus module covers can be ordered separately for unused
I/O slots.
Ex(i) design
The cable duct with the Ex(i) version is designed as standard in
blue. Ex process cables are routed separately from other cables
in the cable duct. Furthermore, a mechanical separation is required between the IM 153 module and the first Ex I/O module.
An Ex partition is fitted for the hot swapping function to guarantee the specified insulation distance between intrinsically-safe
and non-intrinsically-safe areas of the ET 200M distributed I/Os.
The DM 370 spacer module is used for this purpose if the hot
swapping function is not required.
Load power supply for I/O modules
The load power supply for the I/O modules is connected via
plugs located above the I/O modules. One plug is provided for
each I/O module. The load power supplies are available in versions for four or eight I/O modules. With fewer than four or eight
I/O modules, the unused plug connectors are supplied separately should subsequent installation of I/O modules become
necessary.
Preparation of quotation, consulting and ordering
Siemens AG
D-76187 Karlsruhe
Tel.: +49 721 595-3776
Fax: +49 721 595-4711
E-mail: [email protected]
Overview
The scope of delivery of the AS 488/TM is variable, and is defined specific to the order.
Fundamental components of the AS 488/TM are:
Mounting board for the UR2 rack and the rail for the OLM optical link module
E-mail: [email protected]
PROFIBUS-DP connection for distributed I/Os via EXM 478 extension module, as electrical or optical design. The components for a second PROFIBUS-DP line must be ordered
separately.
Components for connection to the CS 275 or PROFIBUS-TM
system bus, components for PROFIBUS-TM as electrical or optical design.
6/5
6/6