M Family Digital Ground Protection Relay
M Family Digital Ground Protection Relay
User Interfaces
Applications
GE Multilin
Protection
The MIN, a member of the M
Family of protection relays, is a
digital relay that provides ground
directional protection for feeders
of any voltage level and backup/
auxiliary ground directional
protection for transformers,
generators and motors. The MIN
offers advanced protection that
includes:
Ground Time Overcurrent
Ground TOC protection can be
set from 0.1 to 2.4 times In. Four
separate ANSI or IEC TOC curves
can be selected in addition to a
user configurable curve. ANSI
and IEC curves include: definite
time, normal inverse, very
inverse, and extremely inverse.
For each curve, different time
multipliers may be set. This
allows the selection of the optimum curve for co-ordination with
specific equipment.
ANSI
IEC/BS142
normal inverse
very inverse
extremely inv.
definite time
IEC A
IEC B
IEC C
definite time
VN
Vh
OPERATION
ZONE
IN
VI
II
Ih
740752A1.ai
67N1
67N2
METERING
BREAKER HEALTH
OSCILLOGRAPHY
EVENT RECORDING
COLD LOAD PICKUP
CONFIGURABLE I/O AND LEDS
CONFIGURABLE LOGIC
50BF
MIN Option E
740751a1.ai
www.GEindustrial.com/Multilin
Monitoring and
Metering
Typical Wiring
SOURCE
BREAKER
<<
CT CONNECTION WITH
DEDICATED TRANSFORMER
FOR THE GROUND UNIT
DIRECTION OF TRIP
DIRECTION OF TRIP
>>
<<
>>
<<
>>
ALTERNATIVE CT WIRING
IN RESIDUAL CONNECTION
FOR THE GROUND UNIT
AC
or
DC
POLARIZATION CURRENT
C5
C6
IP
C1
C2
C3
C4
A1
A2
C1
C2
C3
IG
IG N
5A
+/L
-/N
IG
IG N
5A
1A
1A
C4
POWER
SUPPLY
CURRENT INPUT
CURRENT INPUT
C B A
User Interfaces
B6
A8
CC1
A9
CC2
A10
COM
RS232
GND
GROUND
BUS
SAFETY
GROUND
B2
SDA
B12(*)
SDB
A12(*)
GND
B11(*)
GROUND
OUT1
B5
B1
B7
OUT1/2
RS485
B8
OUT3
A6
VOLTAGE
INPUTS
B9
OUT4
A5
B10
COM
>>
TRIP COIL
CONTROL POWER
TRIP
TRIP
COIL
<<
52a
DIGITAL OUTPUTS(**)
MIN Model E
52a
DIGITAL
INTPUTS(**)
MIN Guideform
Specifications
GE Multilin
SYSTEM
READY
The user can use the M+PC software for setting and monitoring
functions. Communication is
provided through the RS232 port
on the faceplate or the RS485 rear
port using ModBus RTU protocol
at 19,200 bps. Local interface is
provided through a keypad and
display, with LED indicators.
A7
INPUT
PROGRAMMABLE
CONTROLLER
JX
INPUT
740750a4.ai
Ordering
MIN * * 0 * E000 * 00 *
MIN
Faster orders
via the web
N
L
A
I
E
S
F
H
www.GEindustrial.com/Multilin
C
S
If relays are to be mounted in an M+ system, then either an M050 half 19" rack or M100 full 19" rack case must be
ordered. The M050 and M100 racks are provided at no additional cost based on the number of relays ordered.
enerVista enabled
www.enerVista.com
www.GEindustrial.com/Multilin
Accessories
B1315P1