The First Polyphase System
The First Polyphase System
Thomas J. Blalock
The Origins of
Two-Phase Power
Today, the large-scale generation, transmission, and distribution of electric
power is by means of the three-phase
ac system; that is, three individual single-phase voltages and currents having
a 120 phase relationship to each other
and intermingled on three wires
(excluding a neutral). The three-phase
system has been adopted because it
provides for a constant rather than pulsating power flow to motors, and
because it is an efficient system as far
as the amount of copper required per
kilowatt transmitted. The theoretical
complexity of the three-phase system,
however, delayed its complete acceptance in the early days of electric power
system development.
During the early 1890s, understanding the behavior of simple single-phase
ac was enough of a challenge. It was
not until Charles P. Steinmetz, the legendary General Electric scientist,
developed the concept of the use of the
j operator (unity magnitude at a 90
phase angle) and complex numbers for
ac circuit calculations that the behavior
of voltages and currents in ac circuits
march/april 2004
and machines was truly understandable. Likewise, it was not until the
introduction of what eventually came
to be known as symmetrical components, during the early 20th century,
that the calculation of three-phase voltages and currents became relatively
straightforward. This technique utilized
an a operator that was of unity magnitude at a 120 phase angle (0.5 +
j0.866). This operator was of significant value since, in a balanced threephase system, the voltages and currents
are at 120 phase relationships to each
other.
Symmetrical components actually
facilitated calculations in unbalanced
three-phase circuits. They were originally known as Fortescue components since the method was introduced
in 1918 by Charles L. Fortescue of the
Westinghouse Electric Corporation.
Significant additional work in this area
was later contributed by Edith L.
Clarke of the General Electric Company. During the late 19th century, however, this calculation tool did not exist,
and the fact that changes in voltage or
current magnitudes in one phase of a
three-phase system affected the voltages and currents in the other two phases contributed to the difficulty in
understanding three-phase circuits.
Thus, the first ventures into the
realm of polyphase electric power used
only two alternating current phases
rather than three. The two phases were
generated with a 90 phase difference
between them, and the system that
resulted was called two-phase power.
ISSN 1540-7977/04/$17.002004 IEEE
Two-Phase Power
at Niagara Falls
The experience gained with the use
of two-phase power at the Colombian
Exposition may have had some
IEEE power & energy magazine
63
William Stanley
Adopts Two-Phase
William Stanley, the man credited
with the first practical application of
the ac system using transformers (in
Great Barrington, Massachusetts, in
1886), subsequently formed the Stanley Electric Manufacturing Company
in Pittsfield, Massachusetts, in 1891.
Stanley adhered to the design and construction of two-phase generators and
motors throughout the 1890s. This
was only partly a result of his belief in
the superiority of the two-phase system for voltage regulation purposes.
Another factor had to do with the
march/april 2004
Other Two-Phase
Installations
In the village of Middle Falls, New
York, (northeast of Albany) the Niagara
Mohawk Power Corporation operated a
1900 vintage, 350-kW Stanley twophase generator in a small hydroelectric power station there until 1987.
Another identical unit had been retired
in 1976. The output of the station was
coupled to Niagara Mohawks threephase grid by means of phase-changing
transformers.
The generation of two-phase power
was not exclusively an East Coast phenomenon, however. In 1898, the Pacific
Light and Power Company installed
four 300-kW Westinghouse two-phase
generators in a hydroelectric station
located in San Gabriel Canyon, near
Los Angeles, California. This station
served the nearby town of Azusa.
As the use of ac motors expanded
during the early 20th century, the problem of providing both l15 V for lighting and 230 V for motor use from
two-phase distribution systems became
significant. One solution was the adoption of a two-phase, five-wire system in
which center taps on both phases were
connected together to create a neutral.
This, then, resulted in a star configuration (analogous to the three-phase
wye connection) and, technically,
was a four-phase system. As such, 115
V (single-phase) for lighting was available from any of the four phase wires
to the neutral, while 230 V (two-phase)
was available for motors from the four
phase wires themselves.
In New York City, the Bronx District of the New York Edison Company adopted this form of secondary
65
The Demise of
Two-Phase Systems
Eventually, a hybrid type of three-phase
distribution system, which was known
as a three-phase, four-wire, delta system, came into use in certain regions of
the United States. This system included
a center tap on one phase of a bank of
delta-connected transformers supplying
230 V. The center tap formed a neutral
and, in conjunction with the two phase
wires of that particular phase, was used
to supply 115/230 V services on a single-phase, three-wire basis. Motors
operating at 230 V were supplied from
the three phase wires of this type of
service connection.
Buildings requiring both motor and
lighting service were sometimes provided with two separate services, a single-phase, three-wire service for
lighting and a three-phase, three-wire
service for motors. Otherwise, a single
four-wire service was brought into a
building, but care had to be exercised
by electricians so as not to use the odd
phase wire along with the neutral to
supply lighting loads. This odd phase
was referred to as the high phase or
wild phase because considerably
66
march/april 2004