Transformer Protection
Transformer Protection
Transformer Protection
Introduction
A wide range of transformers with sizes ranging
from a few kVA to several hundred MVA can be
found in modern power systems .
The considerations for a transformer protection
package vary with the application and importance
of the transformer.
Small distribution transformers can be protected
satisfactorily, from both technical and economic
considerations, by the use of fuses or overcurrent
relays.
9Dec13
Introduction
Transformers with capacity less than 2500 kVA are
usually protected by fuses (in North America)
With ratings between 2500-5000 kVA, the
transformer may be protected with fuses, but
instantaneous and time delay over-current relays
may be more desirable.
Between 5000-10000 kVA, differential relays are
used for protection.
Above 10 MVA, a harmonic restraint, percentage
differential relay is recommended.
Pressure and temperature relays are used with all
sizes of transformers but recommended for high
ratings.
9Dec13
Introduction
9Dec13
Introduction
Typical connections of Transformers
Introduction
9Dec13
9Dec13
Source impedance
Neutral earthing impedance
Transformer leakage reactance
Fault voltage
Winding connection
9Dec13
R
f
5 103 1 10 3 25 kW
I1 0.11 A
The current that circulate within the short circuit is 5000 A whereas at the
400 kV terminals the current is only 0.11 A.
Inter-turn faults are difficult to detect by electrical means. This has led to
the development of Buchholz relay which makes use of heat generated and
the consequent decomposition of oil to sense the fault.
Buchholz Relay
When a winding-to core fault of an inter-turn fault occurs on
the transformer winding, there is severe heating of the oil. This
causes gases to be liberated from the oil at around 350.
There is a build-up of oil pressure causing oil to rush into the
conservator and push a vane to close the contacts of the
Buchholz relay. The output of the Buchholz relay may be used
to trip the transformer.
Buchholz Relay
The Buchholz relay also has
another set of contacts operated by
a float.
These contacts stay open when the
transformer tank is filled with oil.
In case of leakage of oil or
decomposition of oil, the float
sinks causing the contacts to close.
Loss of oil will no doubt cause the
transformer temperature to rise but
does not warrant immediate
tripping. Normally these contacts
are wired to an alarm.
9Dec13
13
(e-1) Overload
9Dec13
14
9Dec13
15
(e-3) Over-voltages
9Dec13
16
9Dec13
17
Overcurrent Protection
9Dec13
25
9Dec13
HV
26
9Dec13
27
i1s i2 s
where id i1s i2 s ; ir
2
20,000
Ip
289.8
69
Is
20,000
181.8
110
5
I p 289.8
4.83
300
9Dec13
I s 181.8
5
4.54
200
33
34
35
Withthreewindingsconnectedtoexternal
circuits,threerestrainttransformerdifferential
relaysarerequired.
ThereshouldbeasetofCTsineachcircuit,
connectedtoaseparaterestraintwinding.
Theprotectedzoneistheareabetweenthe
CTs.
Multiwindingtransformerbanksusuallyhave
differentMVAratingfortheseveralwindings,
andtheseareusedtodeterminetheCTratios.
Suppose that the bank ratings are 60, 40, and 25 MVA for the 230, 69
and 13.8 kV windings, respectively. Then the current for the windings
would be:
Toselecttherelaytaps,itisessentialtoselectanyvalueof
MVAandpassitthroughthepairswithzeroMVAintheother
winding.
Assume40MVAfirstflowsfromthe230to69kVsystems
withzerointhe13.8kVsystem.
Thispowergivesacurrentof7.25Ainthe69kVrestraintcoil.
Inthe230kVrestraintcoil,thecurrenttobalanceis
Usingtaps5forthe230kVand6forthe69kV,themismatch
is
Thisiswithintransformerdifferentialrelaycharacteristics
Now,passequalMVAinanotherpair,arbitrary
select25MVAfromthe230kVsystem,which
gives4.36Ainthe13.8kVrestraint.
Inthe230kVrestraint
Choosetap6forthe13.8kV,thenthe
mismatchis
External Fault
Internal
Fault
Example
Zero-sequence
current flow for an
internal ground
fault, with no
current from line
(currents in
amperes)
Example
Zero-sequence
current flow for an
internal ground
fault, with current
from line (currents
in amperes)