Asy - Iom - (MCS)
Asy - Iom - (MCS)
AND
OPERATION MANUAL
INDEX
A. GENERAL
Introduction............
Scope of this Manual.
Safety Consideration & Symbols.
Warranty..
B. PRODUCT INFORMATION
PAGE
3
3
3-4
5
6
7
8
9-10
11-14
15-16
17
Inspection. 18
Rigging Instructions ... 18-19
Storage instructions.... 20
D.
INSTALLATION PROCEDURES
Pre-installation guidelines.
Space Requirements ( installation clearance )
Vibration Isolation and Schematic Mounting Layouts....
Recommendations for Spring Type Isolator Selection
Load distribution (with aluminium fin condenser coils)
Load distribution (with copper fin condenser coils)
Unit installation
Mounting Points
Cooler Piping connections
Cooler Connection Types
Water Requirements .......................................................................................................................
Electrical connections, power & control wiring
Electrical data..
Typical schematic wiring diagram..
Installation Inspection..
21
21-29
30-32
33
34
35
36
37
38-39
39-40
40
41-42
43-45
46-48
49
50
General.. 51
Request for start-up representative.. 51
Pre-start up requisites. 51-52
Start up of the system ( system check out ).......
52-53
53
Lubrication....
System water flow rate and Pressure drop..
53-55
Normal operation and cycling.... 56
Compressor Staging & sequence of operation... 56
Capacity control steps. 57
Unit shutdown 57
Introduction
Master compressor board & slave compressor board
Use interface board description
User sequence of operation
58
58
58
58-89
INDEX
G. APPENDIX
PAGE
GENERAL
INTRODUCTION
ZAMIL ASY-Series liquid chillers are manufactured to provide engineering excellence in comfort air conditioning and
industrial cooling with a superior combination of energy saving, performance, application flexibility, ease of service &
maintenance, environmental friendliness and ability to withstand extreme ambient temperatures.
This manual contains all the information required for correct installation, start-up and commissioning of the units,
together with operating instructions. The manual should be read thoroughly before attempting to perform any of the
aforesaid tasks and all procedures and instructions detailed in this manual must only be carried out by suitably trained
and qualified personnel. The manufacturer will not be liable for any personnel injury or equipment damage caused by
incorrect installation, commissioning or operation resulting from a failure to follow and implement the procedures,
instructions and recommendations detailed in this manual.
Foundation, Support & Isolation: Suitable structural support and vibration isolation must be provided as indicated in
these instructions. Failure to do so may result in injury to the operator or damage to the equipment and/or building.
Discard Intrusions: The units are not designed to bear additional loads or stresses from adjacent equipment,
pipework or structures. Additional components must not be mounted on these units. Any such external loads may
overload the units and cause structural failure resulting in injury to the operator or damage to equipment.
Restricted Access to Equipment: This equipment is a complex engineering product and there are a number of
areas and features which may be a hazard and potentially cause injury when working on the unit unless suitable
safety precautions are taken. It is necessary to ensure that access to the unit is restricted to suitably qualified
personnel who are familiar with the potential hazards and precautions required for safe operation and maintenance of
this equipment.
High Pressure & Temperature System: The units contain refrigerant vapor and liquid under high pressure and
temperature and release of which can be dangerous and cause injury. The user should ensure that care is taken
during installation, operation and maintenance to avoid damage to the pressure system. Access to component parts
of the pressure system shall be restricted to suitably trained and qualified personnel only.
Electrical: The units must be grounded. No installation or maintenance work should be attempted on the units without
first switching OFF, isolating and locking off the power supply. Work on live equipment must only be carried out by
suitably trained and qualified personnel. No attempt should be made to gain access to the control panel or electrical
enclosures during normal operation of the units.
Rotating Parts: Fan guards must remain fixed in their position at all times and if any need arises to remove them for
inspection or maintenance, then remove the guards only after the power supply has been isolated.
Sharp Edges: The fins on the air-cooled condenser coils have sharp metal edges. Sufficient care should be taken
when working in contact with the coils to avoid the risk of abrasions and lacerations. The use of gloves is
recommended.
Refrigerant and Compressor Oil: Refrigerants and oils used in the units are non-flammable and non-corrosive and
do not pose a serious hazard. However, use of safety shoes, gloves and safety goggles is strongly recommended
when working on these units. Avoid direct skin or eye contact with the refrigerant as it results in frostbite injury.
Further, attention should be given to good ventilation when working in confined or enclosed spaces, as the build-up of
refrigerant vapor, from a leak for example, does pose a risk of asphyxiation.
For more detailed information on safety precautions for use of refrigerant, please refer Material Safety Data Sheet
given in the Appendix of this manual.
High Temperature and Pressure Cleaning: High temperature and pressure cleaning methods like hot water or
steam cleaning should not be used on any part of the pressure system as this will cause excessive pressure in the
system and trigger operation of the pressure relief device(s). Detergents and solvents which may cause corrosion
should also be avoided.
The following symbols are used in this manual to alert the reader:
!
WARNING
CAUTION denotes a hazard which could lead to damage to the unit and damage
to other equipment.
CAUTION
WARRANTY
ZAMIL warrants all operating parts in this equipment against factory defects for a period formally agreed upon in the
relevant sales contract. All warranty claims must be supported by proper documentary evidence like copies of
invoices, start-up check out reports, maintenance records etc. to justify the validity of warranty.
In order to avail the warranty, the following requirements must be satisfied:
The initial Start-up and Commissioning of the units must be carried out by suitably trained and qualified personnel
only preferably by Zamil in accordance with the instructions given in this manual.
Upon completion of Start-up and Commissioning, duly filled up and certified check out forms for each unit
(sample check out form given in this manual) should be submitted to Zamil Head Office, Dammam.
This warranty is conditional and nullifies if any of the following violations are committed:
Units are not properly stored, protected or inspected by the client during the period from date of shipment till date
of initial start-up.
Incorrect installation, start-up & commissioning and operation resulting from a failure to follow and implement the
procedures, instructions and recommendations given in this manual.
Equipment is operated without or improperly installed field devices such as water flow switch and chilled water
pump interlocking with chillers.
Any modification to the units which includes changing, adding or removing certain components, altering the
electrical wiring or whatsoever without prior written approval from ZAMIL.
Insufficient maintenance or non-compliance to the maintenance requirements specified in this manual. Also,
maintenance, service or repair carried out by unqualified personnel.
Any misuse of this equipment such as, utilizing it for purposes other than those its designed for and operating
outside the design parameters specified in our application catalogue.
Equipment is operated with refrigerant, oil, water or antifreeze agents which are not approved by ZAMIL.
Equipment has been damaged due to malfunctioning of interface controllers such as DDC, periphery components
etc.
Equipment has been damaged by freezing due to improper protection during cold weather or damaged by
accident, fire or any other conditions not ordinarily encountered (force majeure).
050
060
070
080
090
100
120
130
140
150
160
170
180
190
200
215
230
240
250
270
295
310
330
350
375
400
420
450
475
500
540
560
590
B : R-134a
4, 5 & 6
7
UNIT SIZE REFRIGERANT
F : 460-3-60
M: 380-3-60
(4 WIRE)
(SEE NOTE # 1
BELOW)
E : COPPER FIN
WITH ResisTec
COATING
D : ALUMINUM FIN
WITH ResisTec
COATING
C : COPPER FIN
B : PRE-COATED
ALUMINUM FIN
CIRCUIT
BREAKER
12
COMPRESSOR
OPTIONS
13
HGBP
OPTIONS
14 & 15
OPTIONS
&
B : STANDARD
UNIT WITH UL
LISTED
A : STANDARD
UNIT
WITHOUT UL
16 & 17
UL
OPTIONS
ResisTec
- MULTI-ResisTec PIPING
- SPRING ISOLATOR
- COMPRESSOR ENCLOSURE
A : STANDARD UNIT
SEE NOTE # 2
A : STANDARD WITH A : STANDARD UNIT
VICTAULIC CONN.
WITHOUT SUCTION
WITHOUT HGBP & BELOW
WITHOUT SUCTION
SERVICE VALVE
SERVICE VALVE
B : FLANGE CONN.
(OPTIONAL)
B : UNIT WITH
SUCTION SERVICE B : WITH HGBP &
VALVE
WITHOUT SUCTION
C : ASME STAMPED
WITH VICTAULIC
(OPTIONAL)
SERVICE VALVE
CONN.
(OPTIONAL)
(OPTIONAL)
C : WITHOUT HGBP &
WITH SUCTION
D : ASME STAMPED
SERVICE VALVE
(OPTIONAL)
WITH FLANGE
CONN.
(OPTIONAL)
D : WITH HGBP &
WITH SUCTION
SERVICE VALVE
(OPTIONAL)
11
COOLER
OPTIONS
2. COMPUTER SELECTED DIGITS (FROM 'AA' TO 'ZZ') DESCRIBING OTHER OPTIONS & ACCESSORIES OR COMBINATIONS THEREOF, SUCH AS:
B:
A : STANDARD
10
9
CONDENSER COIL CIRCUIT BREAKER
OPTIONS
8
ELECTRICAL
SUPPLY
( V-Ph-Hz )
NOTES:
AIR COOLED
SCREW WATER
CHILLERS
ASY
1, 2 & 3
BASIC
(SERIES)
MODEL DECODING
MAJOR FEATURES
These chillers incorporate a wide range of features; some of them are as follows:
Compact unit design and excellent serviceability.
Single skid designed for models ASY050B thru ASY500B.
Single point power connection for models ASY050B thru ASY500B. Dual point connection for models ASY540B
thru ASY590B.
Steel sheet panels are zinc coated and galvanized conforming to ASTM A-653 commercial weight G-90 followed by
electrostatic polyester dry powder coat.
High energy efficiency ratio (EER) semi-hermetic compact twin screw compressors.
Compact design shell & tube liquid cooler with enhanced inner grooved copper tubes bundled into U-shape and
expanded into a steel tubular sheet.
Control panel design is equivalent to NEMA 4.
Internal power & control wiring cable identification & markers as per NEC.
Electrical controls used in the control panel are UL approved or equivalent.
Complete wired control panel with advanced microprocessor based controller.
Compressors are provided with Part Winding Start.
Low noise condenser fans, direct drive with rolled venturi design to eliminate short circuiting of airflow.
All fans are die cast aluminum propeller type with aerodynamic design, top discharge & provided with protective
grille.
All fan motors are Totally Enclosed Air Over (TEAO) type with class "F" winding insulation, ball bearings & inherent
thermal protection of automatic reset type.
STANDARD ACCESSORIES
UNIT ON-OFF SWITCH: ON-OFF switch is provided for manually switching the unit control circuit.
INDICATOR LIGHTS: LED lights indicates power ON to the units, MENU adjustment and FAULT indications due to trip on
safety devices.
ELECTRONIC EXPANSION VALVE: Electronic expansion valve is used to regulate the refrigerant flow to the water cooler
and maintain a constant superheat and load optimization.
FILTER DRIER (REPLACEABLE CORE TYPE): Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil
contaminating particles by the filter drier.
SIGHT GLASS: A moisture indicating sight glass is installed in the liquid line. An easy-to-read color indicator shows
moisture contents and provides a mean for checking the system refrigerant charge.
LIQUID LINE SOLENOID VALVE: Closes when the compressor is off to prevent any liquid refrigerant from accumulating in
the water cooler during the off cycle.
CONTROL CIRCUIT TRANSFORMER: On 460V-3Ph-60Hz power supply factory mounted and wired control circuit transformer is furnished eliminating the need for running a separate 220 volt control circuit power supply.
OPTIONS
(All options are at extra cost. Please check with your nearest dealer/sales office)
HOT GAS BYPASS SYSTEM: Hot gas bypass is provided on the lead circuit to permit operation of the system down to 50% of
its unloaded capacity. Under low ambient condition, it controls temperature by eliminating the need to cycle the compressor on
and off, ensuring narrow temperature swing and lengthen the life span of the compressor.
WATER FLOW SWITCH: Paddle type field adjustable flow switch for water cooler circuits. Interlock into unit safety circuits
so that the unit will remain off until water flow is determined.
UNIT MOUNT SPRING ISOLATORS: This housed spring assemblies have a neoprene friction pad on the bottom to
prevent vibration transmission.
LIQUID COOLERS: ASME code stamped liquid cooler.
PRESSURE GAUGES: Suction & discharge pressures gauges.
SUCTION SERVICE VALVE: Compressor suction port service valves.
NON-FUSED MAIN DISCONNECT SWITCHES: De-energize power supply during servicing/repair works as well as with
door interlock.
CONDENSER COIL GUARD: Protects the condenser coils from physical damage.
COMPRESSOR/COOLER GUARD: Protects the compressor from vandalism.
COMPRESSOR OIL LEVEL SWITCH: This monitors the oil level inside the compressor.
COMPRESSOR ENCLOSURE BOX: Reduces compressor operating noise and keeps the compressor clean.
FLANGED COOLER CONNECTION: Easy on-site piping connections.
COOLER HEATER WRAPPED: Prevents freezing up of water on low ambient temperature.
COPPER FINS/TUBES CONDENSER COILS: For seashore salty corrosive environments. Provided with 12 FPI as standard.
COATED COPPER FINS/TUBES CONDENSER COILS: For seashore or acid corrosive environments.
BMS: BACNET-IP, MODBUS-RS485, GSM and stand alone remote display panel.
POWER LINE ANALYZER: Performs motor current limitation. Protects against high motor current & over/under voltage.
: A two component coating system that withstands the extreme climate conditions. The coating can be
applied to all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pre- treatment
and layer build up. Please check ResisTec product information sheets, the heat exchangers can not be coated using this
type. The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenance or rejuvenation
purposes.
UL LISTED CHILLERS: ASY chillers in the range of ASY050B thru ASY500B can be optionally offered as UL listed. These
chillers are UL listed under UL file number SA13167.
HAND HELD CONTROLLER: Enables the chiller technician to monitor and serve the chiller by plugging this portable wired
controller into the chiller controller. With built-in magnets, it provides convenient access for chiller status diagnoses and
trouble shooting.
EXTERNAL COMPRESSOR MOTOR OVERLOAD RELAY: Added protection for compressor motor thermal overloading
and prolonged stalling of the motor.
DUAL MAIN POWER ENTRY: Provide flexibility of connecting the chiller to the field power supply. Applicable for chiller
models ASY090B - ASY500B.
EXTENDED MAIN BUSBAR: Provide extended termination for multi cable that may require for chiller with Single power
Entry point. This is applicable only for ASY180B - ASY590B.
MAIN POWER TERMINAL LUGS: A ready to install power main terminal lugs for easy connection of main cable in the
field. The lug has wide range to accept cable sizes and designed to fix a maximum of 4 cables per lug.
ATTENTION
All control & safety devices, accessories and optional items are factory
installed except for unit mounting spring isolators and water flow switch, which
must be installed on job-site.
10
PHYSICAL DATA
UNIT SIZE
ASY050B ASY060B ASY070B ASY080B ASY090B ASY100B ASY120B ASY130B ASY140B ASY150B
COMPRESSOR
PART NUMBER
208/230V-3Ph-60Hz
800-683-13
800-683-16
800-683-19
800-683-22
800-683-13 (2) 800-683-13 (2) 800-683-16 (2) 800-683-19 (2) 800-683-19 (2) 800-683-19 (2)
380V-3Ph-60Hz
800-683-14
800-683-17
800-683-20
800-683-23
800-683-14 (2) 800-683-14 (2) 800-683-17 (2) 800-683-20 (2) 800-683-20 (2) 800-683-20 (2)
460V-3Ph-60Hz
800-683-15
800-683-18
800-683-21
800-683-24
800-683-15 (2) 800-683-15 (2) 800-683-18 (2) 800-683-21 (2) 800-683-21 (2) 800-683-21 (2)
NUMBER OF COMPRESSORS
15
22
22
22
15
15
22
22
22
22
600
600
600
100 - 50
100 - 25
ELECTRONIC
OIL LUBRICATION
TOTAL CRANKCASE HEATER WATTS
INJECTION
200
300
300
300
400
400
REFRIGERANT
600
R-134a
EXPANSION DEVICE
CONTROL VOLTAGE
220V-1Ph-60Hz
AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8214 3/8314 3/8414 3/8414 3/8414 3/8414 3/8314 3/8414 3/8414 3/8314
COIL
Total face area, Sq. ft.
87.5
87.5
87.5
87.5
100.1
100.1
140
140
140
175
AIRFLOW, CFM
45264
43920
47644
47644
63798
63798
93256
87032
87032
116570
4/762
4/762
4/800
4/800
6/800
6/800
8/800
8/800
8/800
10/800
COOLER
COOLER PART NUMBER
800-894-00 800-894-01 800-894-01 800-894-01 800-894-02 800-894-02 800-894-42 800-894-04 800-894-04 800-894-05
SHELL DIAMETER, mm
219
273
273
273
324
324
106
324
324
406
TOTAL LENGTH, mm
2314
2152
2152
2152
2496
2496
1273
2677
2677
2739
49
76.5
76.5
76.5
120
120
128
117
117
206
75
100
100
100
125
150
125
125
125
150
PART NUMBER
N.A.
N.A.
N.A.
N.A.
N.A.
800-516-68(2)
N.A.
N.A.
EXPANSION DEVICE
N.A.
N.A.
N.A.
N.A.
N.A.
T.E.V.
N.A.
N.A.
T.E.V.
T.E.V.
33
39
45
50
33
33
39
45
47
48
ECONOMIZER
800-516-69(2) 800-516-69(2)
GENERAL
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 72.2/68.7/63.4 72.6/69.1/63.8 75.4/71.9/66.6 75.6/72.1/66.8 74.4/71/65.7
1865/1914 2336/2412 2455/2531 2472/2548 3220/3340 3233/3353 4319/4447 4468/4585 4494/4611 4998/5204
1990/2039 2529/2605 2735/2811 2751/2827 3540/3660 3553/3673 4627/4755 4914/5031 4941/5058 5383/5589
NOTES:
PHYSICAL DATA
UNIT SIZE
ASY160B ASY170B ASY180B ASY190B ASY200B ASY215B ASY230B ASY240B ASY250B ASY270B
COMPRESSOR
PART NUMBER
800-683-22 (2)
208/230V-3Ph-60Hz
800-683-22 (2) 800-683-22 (2) 800-683-16 (3) 800-683-16 (3) 800-683-16 (3) 800-683-19 (1) 800-683-22 (3) 800-683-22 (3) 800-683-16 (4) 800-683-19 (4)
380V-3Ph-60Hz
800-683-23 (2) 800-683-23 (2) 800-683-17 (3) 800-683-17 (3) 800-683-17 (3) 800-683-20 (1) 800-683-23 (3) 800-683-23 (3) 800-683-17 (4) 800-683-20 (4)
460V-3Ph-60Hz
800-683-24 (2) 800-683-24 (2) 800-683-18 (3) 800-683-18 (3) 800-683-18 (3) 800-683-21 (1) 800-683-24 (3) 800-683-24 (3) 800-683-18 (4) 800-683-21 (4)
800-683-23 (2)
800-683-24 (2)
NUMBER OF COMPRESSORS
22
22
22
22
22
22
22
22
22
22
100 - 25
100 - 16
ELECTRONIC
OIL LUBRICATION
TOTAL CRANKCASE HEATER WATTS
100 - 12
INJECTION
600
600
900
900
900
900
REFRIGERANT
900
900
1200
1200
R-134a
EXPANSION DEVICE
CONTROL VOLTAGE
220V-1Ph-60Hz
AIRCOOLED CONDENSER
3/8414
3/8414
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8314 3/8414 3/8314 3/8314 3/8414 3/8314 3/8414 3/8414 3/8314 3/8314
COIL
Total face area, Sq. ft.
175
175
210
210
210
240
240
240
304
304
AIRFLOW, CFM
116570
108790
139884
133524
130548
140892
138276
138276
192048
192048
10/800
10/800
12/800
12/800
12/800
12/800
12/800
12/800
16/800
16/800
COOLER
COOLER PART NUMBER
800-893-05 800-893-05 800-893-06 800-893-06 800-893-06 800-893-07 800-893-08 800-893-08 800-893-04(2) 800-893-05(2)
SHELL DIAMETER, mm
406
406
406
406
406
406
406
406
324
406
TOTAL LENGTH, mm
2739
2739
2749
2749
2749
3241
3741
3741
2677
2739
206
206
190
190
190
225
260
260
234
412
150
150
150
150
150
150
150
150
125
150
PART NUMBER
N.A.
800-516-69(2)
N.A.
N.A.
800-516-69
800-516-69(3)
N.A.
N.A.
EXPANSION DEVICE
N.A.
T.E.V.
N.A.
T.E.V.
T.E.V.
N.A.
T.E.V.
T.E.V.
N.A.
N.A.
50
54
39
42/39
42
50/45
54/50
54
39
45
ECONOMIZER
800-516-69(2) 800-516-69(3)
GENERAL
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 78.9/75.4/70.1 78.9/75.4/70.1 77.1/73.6/68.3 77.1/73.6/68.3 77.1/73.6/68.3 80.3/76.8/71.5 80.4/76.9/71.6 80.4/76.9/71.6 81.4/77.9/72.6 81.4/77.9/72.6
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg
5003/5209 5149/5355 6542/6732 6663/6853 6724/6914 6885/7110 7040/7300 7070/7330 8745/8979 9208/9620
5388/5594 5708/5914 7004/7194 7264/7454 7393/7583 7572/7797 7805/8065 7836/8096 9414/9648 9876/10288
NOTES:
PHYSICAL DATA
UNIT SIZE
ASY295B ASY310B ASY330B ASY350B ASY375B ASY400B ASY420B ASY450B ASY475B ASY500B
COMPRESSOR
PART NUMBER
208/230V-3Ph-60Hz
800-683-22 (2)
800-683-16 (4)
800-683-22 (3) 800-683-22 (4)
800-683-19 (2) 800-683-22 (4) 800-683-13 (2) 800-683-16 (6) 800-683-19 (6) 800-683-19 (6) 800-683-19 (3) 800-683-19 (2) 800-683-22 (6) 800-683-22 (6)
380V-3Ph-60Hz
800-683-23 (2)
800-683-17 (4)
800-683-23 (3) 800-683-23 (4)
800-683-20 (2) 800-683-23 (4) 800-683-14 (2) 800-683-17 (6) 800-683-20 (6) 800-683-20 (6) 800-683-20 (3) 800-683-20 (2) 800-683-23 (6) 800-683-23 (6)
460V-3Ph-60Hz
800-683-24 (2)
800-683-18 (4)
800-683-24 (3) 800-683-24 (4)
800-683-21 (2) 800-683-24 (4) 800-683-15 (2) 800-683-18 (6) 800-683-21 (6) 800-683-21 (6) 800-683-21 (3) 800-683-21 (2) 800-683-24 (6) 800-683-24 (6)
NUMBER OF COMPRESSORS
22
22
22/15
22
22
22
22
22
22
22
1800
1800
1800
100 - 12
100 - 8
ELECTRONIC
OIL LUBRICATION
TOTAL CRANKCASE HEATER WATTS
INJECTION
1200
1200
1600
1800
1800
1800
REFRIGERANT
1800
R-134a
EXPANSION DEVICE
CONTROL VOLTAGE
220V-1Ph-60Hz
AIRCOOLED CONDENSER
3/8414
3/8414
CONDENSER Tube Dia.-Rows-Fins per inch* 3/8414 3/8414 3/8314 3/8414 3/8414 3/8314 3/8314 3/8414 3/8414 3/8414
COIL
Total face area, Sq. ft.
304
304
430.7
430.7
430.7
521.3
521.3
521.3
521.3
521.3
AIRFLOW, CFM
180560
180560
224046
220770
220770
281490
275110
269038
269038
269038
16/800
16/800
18/800
18/800
18/800
22/800
22/800
22/800
22/800
22/800
1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100
COOLER
COOLER PART NUMBER
800-893-05(2) 800-893-05(2) 800-893-09(2) 800-893-09(2) 800-893-06(2) 800-893-06(2) 800-893-06(2) 800-893-10(2) 800-893-10(2) 800-893-10(2)
SHELL DIAMETER, mm
406
406
406
406
406
406
406
457
457
457
TOTAL LENGTH, mm
2739
2739
2741
2741
2749
2749
2749
2754
2754
2754
412
412
412
412
380
380
380
488
488
488
150
150
150
150
150
150
150
200
200
200
PART NUMBER
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
EXPANSION DEVICE
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
T.E.V.
T.E.V.
50/45
50
39/33
39
45
47
50/45
50/45
54/50
54
ECONOMIZER
800-516-69(3) 800-516-69(6)
GENERAL
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 81.5/78/72.7 81.6/78.1/72.8 79.4/75.8/70.6 79.4/75.9/70.6 82.9/79.3/74.1 83.1/79.5/74.3 83.2/79.7/74.4 83.2/79.7/74.4 83.3/79.8/74.5 83.3/79.8/74.5
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg
SHIPPING /OPERATING WEIGHTS (Copper coils), kg
NOTES:
9441/9853
9474/9886
10441/10823 10444/10856 13021/13433 14042/14454 14182/14562 14186/14566 14654/15034 15439/15927 15518/16006 15564/16052
PHYSICAL DATA
UNIT SIZE
ASY540B
ASY560B
ASY590B
COMPRESSOR
PART NUMBER
208/230V-3Ph-60Hz
380V-3Ph-60Hz
460V-3Ph-60Hz
800-683-19 (4)
800-683-16 (4)
800-683-20 (4)
800-683-17 (4)
800-683-21 (4)
800-683-18 (4)
800-683-19 (8)
800-683-20 (8)
800-683-21 (8)
800-683-22
800-683-19
800-683-23
800-683-20
800-683-24
800-683-21
NUMBER OF COMPRESSORS
22
22
22
(4)
(4)
(4)
(4)
(4)
(4)
100 - 6
ELECTRONIC
OIL LUBRICATION
INJECTION
1800
REFRIGERANT
1800
1800
R-134a
EXPANSION DEVICE
CONTROL VOLTAGE
220V-1Ph-60Hz
AIRCOOLED CONDENSER
CONDENSER Tube Dia.-Rows-Fins per inch*
COIL
Total face area, Sq. ft.
3/8414
3/8414
3/8414
608
608
608
AIRFLOW, CFM
361120
361120
361120
32/800
32/800
32/800
1080/1080/1100
1080/1080/1100
1080/1080/1100
800-893-41(2)
800-893-41(2)
800-893-41(2)
SHELL DIAMETER, mm
508
508
508
TOTAL LENGTH, mm
3326
3326
3326
802
802
802
200
200
200
PART NUMBER
N.A.
N.A.
N.A.
EXPANSION DEVICE
N.A.
N.A.
N.A.
45/39
45
50/45
83.6/80.1/74.8
84.4/80.9/75.6
84.6/81/75.8
2 x 9355/2 x 9756
2 x 9390/2 x 9791
2 x 9423/2 x 9824
2 x 10325/2 x 10726
2 x 10360/2 x 10761
2 x 10393/2 x 10794
COOLER
COOLER PART NUMBER
ECONOMIZER
GENERAL
NUMBER OF REFRIGERANT CIRCUITS
REFRIGERANT CHARGE PER COMP., kg
SOUND PRESSURE LEVEL, dBA (3m./5m./10m.)
SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg
SHIPPING /OPERATING WEIGHTS (Copper coils), kg
NOTES:
OVERVIEW
---
- - - - -
- - -
- -- - - -
- -
-- - -
-
- -- --
- - --
- -
-- -
-- - --
- - - - -
- - -
- -
-
-
-
-
-- - - --
-
- --
-- - -
--
-- and Low Superheat
- --
-
--
--
15
-- - -
- - - - ---
-- - - - --
- - - - - - - --
-
- - - - - - -
-- - - - -
- - - --
- -
- - - - - --
-
-- - - -- - - -
- - --
- -- --
-- -
-- - - - - -
- -- -
- - -
- -
- - - - -- -- -
- - - -
- - --- --
-
- - - -
- - -
- - - - -- - - -
- - -- - -
- n - - - The
- - -
- - - -- -- - Ethernet
Ethernet ---- - 1 km --- -
- - - - - - - - - - -- - - - - - - -
Ethernet port and RS232 is available as standard for this MCS-Connect. Contact Zamil AC for complete details.
-- -
- - -
- - and analog (AI) (refer to actual wiring diagram)
/ - (see page 81 )
-- -
-- -
- -
-- - - - - panel -- -
- - - -
-- - - - - -
Notes:
.
This P & I diagram illustrate a single refrigeration circuit. Total number of these circuits in a particular chiller shall be as
many as the number of compressors provided in that chiller.
This P & I applicable for a chiller with standard features. For chillers provided with optional features like pressure gauges,
hot gas bypass system, cooler heater, etc. suitable changes in this diagram should be envisaged.
If Economizer is provided in a refrigerant circuit, it optimizes the system capacity by further sub cooling the high pressure
liquid refrigerant which increases its thermodynamic efficiency. This is accomplished by a refrigerant to refrigerant brazed
plate heat exchanger in which a portion of the high pressure liquid refrigerant is vaporized thereby sub cooling the remaining
liquid refrigerant. Although this has little effect on the suction capacity of the compressor but the effective refrigerating
capacity of the compressor is boosted by the increased heat absorption capacity of the liquid entering the evaporator/cooler.
4.
The Liquid Injection Circuit is provided to allow refrigerant injection for oil cooling. The solenoid valve and liquid injection
valve provided in this circuit open in response to demand sensed by the discharge line temperature sensor (i.e. open when the
refrigerant discharge temperature rises above the set point).
17
RIGGING INSTRUCTIONS
Each unit has been crafted and carefully tested at the factory where every precaution is taken to ensure that it reaches
you in perfect condition. It is very important that the riggers and movers should use the same care and precaution in
moving the equipment into place. Make sure that chains, slings, cables or other rigging equipment are employed so as
to avoid damage to the units.
Before moving the units, ensure that the site is ready and suitable for installing the equipment and is capable of
supporting the weight of units and all associated equipment.
These units are designed for lifting and overhead rigging. Based on weight and dimensions of the units, either rigging
holes are provided in the base rail or lifting eyes extending from the sides of the base rail. These rigging holes or lifting
eyes are centered around the unit center of gravity. For rigging the units, follow these instructions:
For units with rigging holes in the base rail, insert pipes thru these holes to support the whole unit and lift using
rigging slings and hooks or shackles as shown in Figure A below.
For units with lifting eyes on the base rail, attach the hooks or shackles directly into them and lift using rigging
slings as shown in Figures B & C below.
Center of gravity is not unit centerline; ensure center of gravity aligns with main lifting point before lifting.
Use spreader bars when rigging, to prevent slings from damaging the unit (as shown in Fig. A to C).
!
CAUTION
Units must only be lifted from the base and at the points provided.
All unit panels should be in place when rigging.
Extra care must be taken to avoid damage to the condenser coil.
Insert packing material between coils and slings as necessary.
Do not apply pressure to the units body.
Refrigerant piping should never be used as a foothold or handhold.
Never move the unit on roller or using a fork lift truck.
Lifting equipment must be capable of handling the unit weight with adequate
safety factor. For details of unit weights and weight distribution refer to the
Physical data and Load distribution Sections in this manual.
WARNING
18
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS
Hook rigging sling thru holes in base rail, as shown below.
Holes in base rail are centered around the unit center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging, to prevent the slings from damaging the unit.
CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings as necessary.
MODELS: ASY050B - ASY240B
* Please refer to page-31 for the total unit dimensions of ASY540B, ASY560B & ASY590B
MODELS: ASY330B - ASY500B
STORAGE INSTRUCTIONS
If the unit is to be put into storage prior to installation, observe the following precautions:
Store in a dry and clean place preferably sheltered or shaded area.
Place the units on a flat solid surface so that the chiller base does not bend or sag.
Protect equipment from physical damages, store in a location where there is minimal activity, in order to limit the
risk of accidental physical damage.
Condenser coils should be securely covered to protect the fins from damage and corrosion, particularly where the
building work is in progress.
Check that all openings, such as water connections, are securely capped.
It is recommended that the items/accessories supplied loose and the control panel keys are deposited with a
responsible person.
It is recommended that the units are periodically inspected as a proactive measure.
20
INSTALLATION PROCEDURES
PRE-INSTALLATION GUIDELINES
These chillers are designed for outdoor installation and can be installed at ground level or on a suitable rooftop
location. In order to achieve good operation, performance and trouble-free service, it is essential that the proposed
installation location meets the following requirements:
The most important consideration while deciding upon the location of air cooled chillers is the provision for supply of
adequate ambient air to the condenser and removal of heated discharge air from the condenser. This is
accomplished by maintaining sufficient clearances which have been specified in this manual around the units
and avoiding obstructions in the condenser air discharge area to prevent the possibility of warm air circulation.
Further, the condenser fans are propeller type and are not recommended for use with ductwork or other hindrances
in the condenser air stream. Where these requirements are not complied, the supply or discharge airflow
restrictions or warm air recirculation will cause higher condensing temperatures resulting in poor unit operation,
higher power consumption and possible eventual failure of equipment.
The units longitudinal axis should be parallel to the prevailing wind direction in order to ensure a balanced air flow
through the condenser coils. Consideration should also be given to the possibility of down-drafts caused by
adjacent buildings, which may cause recirculation or uneven unit airflow. For locations where significant cross winds
are expected, an enclosure of solid or louver type is recommended to prevent wind turbulence interfering with the
unit airflow. When units are installed in an enclosure, the enclosure height should not exceed the height of the unit.
The location should be selected for minimum sun exposure and away from hot air sources, steam, exhaust vents
and sources of airborne chemicals that could attack the condenser coils and steel parts of the unit. Avoid locations
where the sound output and air discharge from the units may be objectionable.
If the location is an area which is accessible to unauthorized persons, steps must be taken to prevent access to the
unit by means of a protective fence. This will help to prevent the possibility of vandalism, accidental damage or
possible harm caused by unauthorized removal of panels or protective guards exposing rotating or high voltage
components.
The clearance requirements prescribed in this manual are necessary to maintain good airflow and provide access
for unit operation and maintenance. However, it is also necessary to consider access requirements based on
practical considerations for servicing, cleaning and replacing large components.
The unit must be installed on a ONE-PIECE, FLAT and LEVELLED {within (13 mm) over its length and width}
CONCRETE BASE that extends fully to support the unit. The carrying or supporting structure should be capable of
handling complete operating weight of the unit as given in the Physical Data tables in this manual.
For ground level installations, it must be ensured that the concrete base is stable and does not settle or dislocate
upon installation of the unit which can strain the refrigerant lines resulting in leaks and may also cause compressor
oil return problems. It is recommended that the concrete slab is provided with appropriate footings. The slab should
not be connected to the main building foundation to avoid noise and vibration transmission.
For rooftop installations, choose a place with adequate structural strength to safely support the entire operating
weight of the unit. The unit shall be mounted on a concrete slab similar to ground installations. The roof must be
reinforced for supporting the individual point loads at the mounting isolator locations. It must be checked and
ensured that the concrete base is perfectly horizontal and levelled, especially if the roof has been pitched to aid in
water removal. It should be determined prior to installation if any special treatment is required to assure a levelled
installation else it could lead to the above mentioned problems.
SPACE REQUIREMENTS
Dimensional drawings for all chiller models are given in the following pages. In order to ascertain space requirement
for an installation, refer to the respective chiller drawing:
21
DIMENSIONS
ASY050B
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
22
ASY060B
100
ASY070B - ASY080B
275
DIMENSIONS
ASY090B & ASY100B
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
23
DIMENSIONS
ASY150B, ASY160B & ASY170B
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
24
MODEL
ASY180B
2075
2200
500
ASY190B - ASY200B
2075
2200
1650
ASY215B
2185
2700
1115
ASY230B - ASY240B
2185
3200
800
25
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
A
417
457
MODEL
ASY250B
ASY270B - ASY310B
DIMENSIONS
B
1940
1890
2200
2250
445
375
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
2130
ASY450B - ASY500B
A
2200
ASY400B - ASY420B
MODEL
DIMENSIONS
B
3474
3420
487
457
700
500
NOTE:1. Cooler dimensions are subject to change without notice. Final dimensions will be provided upon order placement.
2. All dimensions are in mm, unless otherwise specified.
DIMENSIONS
INSTALLATION CLEARANCE
WALL
MODEL NUMBER
ASY050B - ASY080B
2500
2000
ASY090B - ASY310B
3000
2000
ASY330B - ASY500B
3500
2500
ASY540B - ASY590B
4500
3500
FIGURE - 1
STRAIGHT WALL
FIGURE - 2
CORNER WALL
NOTE: 1. All dimensions are in mm.
2. Pit installations are not recommended. Re-circulation of hot condenser air in combination with surface air
turbulence can not be predicted, hot air re-circulation will severely affect unit efficiency (EER) and can
cause high pressure or fan motor temperature trips.
30
31
32
Seismic Applications:
The SLRS series vertically restrained seismic spring isolation
mounts are recommended as a noise and vibration isolator
for chillers to reduce the transmission of noise and vibration
into supporting structures in seismic zone applications where
static G ratings in three planes are required.
Operating static deflections are available up to 5 to
compensate for long span flexible floor structures and
maintain a high degree of noise and vibration isolation.
33
R1
R2
R3
R4
R5
R6
R7
R8
R9
R10
R11
R12
R13
R14
R15
R16
R17
R18
R19
R20
ASY050
518
491
462
444
ASY060
671
632
571
541
ASY070
702
663
600
569
ASY080
705
669
604
573
ASY090
625
594
578
540
509
493
ASY100
628
597
581
542
510
495
ASY120
848
817
801
687
655
640
ASY130
872
841
825
708
677
661
ASY140
878
847
831
711
680
664
ASY150
729
701
692
683
627
600
590
581
ASY160
730
702
693
684
628
600
591
582
ASY170
749
722
713
703
645
617
608
599
ASY180
964
930
918
907
788
753
742
730
ASY190
981
946
935
923
801
767
756
744
ASY200
989
954
943
931
808
774
763
751
ASY215
1011
977
966
954
835
801
789
778
ASY230
1032
998
986
975
862
827
816
804
ASY240
1037 1003
991
980
864
830
818
807
ASY250
1035 1001
984
978
972
843
809
791
786
780
ASY270
924
889
872
866
861
ASY295
946
912
894
889
883
ASY310
948
914
897
891
885
ASY330
991
941
936
821
803
794
785
776
771
766
ASY350
865
847
838
829
820
815
810
ASY375
872
854
844
835
826
822
817
ASY400
891
871
861
851
841
836
831
ASY420
905
885
875
865
855
850
845
ASY450
961
941
931
921
911
906
901
ASY475
965
945
935
925
915
910
905
ASY500
967
947
937
927
917
912
907
ASY540
943
902
881
874
867
867
874
881
902
943
ASY560
945
904
884
877
870
870
877
884
904
945
ASY590
948
906
886
879
872
872
879
886
906
948
R1
R2
R3
R4
973
964
955
945
R1
R6
R1
R2
R3
R4
R5
R6
R7
R8
R9
R10
R11
R12
R13
R14
R15
R16
R17
R18
R19
R20
ASY050
549
523
492
475
ASY060
719
680
619
587
ASY070
772
733
669
637
ASY080
775
738
672
641
ASY090
679
647
632
594
562
546
ASY100
682
650
634
595
564
548
ASY120
899
868
852
738
707
691
ASY130
947
915
900
783
751
736
ASY140
953
921
906
786
754
738
ASY150
777
750
740
731
675
648
639
629
ASY160
778
750
741
732
676
648
639
630
ASY170
819
792
782
773
714
687
678
669
ASY180
1022
988
976
965
845
811
799
788
ASY190
998
877
842
831
819
ASY200
892
858
846
835
ASY215
921
886
875
863
ASY230
957
923
911
900
ASY240
960
926
914
903
ASY250
910
876
858
853
847
ASY270
991
956
939
933
928
ASY295
991
986
980
ASY310
994
988
982
ASY330
908
890
881
871
862
858
853
ASY350
963
945
936
927
918
913
908
ASY375
970
952
943
933
924
920
915
ASY400
973
953
943
933
923
918
913
ASY420
986
976
966
956
951
946
ASY450
1268 1248 1238 1228 1218 1213 1208 1080 1060 1050 1040 1030 1025 1020
ASY475
1276 1256 1246 1236 1226 1221 1216 1083 1063 1053 1043 1033 1028 1023
ASY500
1280 1260 1250 1240 1230 1225 1220 1086 1066 1056 1046 1036 1031 1026
ASY540
999
978
971
964
964
971
978
999 1040
ASY560
981
974
967
967
974
981
1001 1042
ASY590
983
976
969
969
976
983
1003 1045
R1
R2
R3
R4
R1
R6
UNIT INSTALLATION
Based on the specific project requirements, choose the type of vibration isolators best suited for the application.
Carefully select the vibration isolators models / configuration based on the respective point loads and place each
mount in its correct position following the foregoing Load Distribution Data and Mounting Points Drawing provided
herewith.
Upon completing the mounting of all vibration isolators in their correct positions, move the unit to its installation
location and then lower it carefully in an upright position onto the vibration mounts ensuring that each mount sits in its
correct position with respect to the base rail.
For applications with neoprene pad isolators, equipment and isolators do not require bolting to the concrete base or
substructure. For applications with spring isolators, follow these guidelines:
Ensure that all vibration isolators get engaged in the mounting holes provided in the unit base rail.
Follow the specific instructions for levelling, adjustment etc. based on the type of spring isolator employed.
Isolators should be bolted to the concrete base or substructure and the equipment to isolators.
36
MOUNTING LOCATION
MODELS: ASY050B - ASY080B
MODEL
1249
ASY100B
1249
ASY120B
1858
ASY130B
1858
ASY140B
1858
MODEL
MODULE - A
MODULE - B
ASY090B
ASY150B
1586
ASY160B
1586
ASY170B
1586
ASY180B
2094
ASY190B
2094
ASY200B
ASY215B
ASY230B
ASY240B
2094
2094
2094
2094
!
CAUTION
A flow switch is required to prevent damage to the cooler caused by the unit
operating without adequate liquid flow. The flow switch should be connected in
the external interlock as shown in the wiring diagram in the control panel. The
flow switch MUST NOT be used to start and stop the unit.
The chilled water pump(s) installed in the piping system should discharge directly into the unit cooler. The pump(s)
may be controlled external to the unit - but an interlock must be wired to the unit control panel (as shown in the
wiring diagram) so that the unit can start only upon proof of pump operation.
Flexible connections suitably selected for the fluid and pressure involved should be provided as mandatory in order
to minimize transmission of vibrations to the piping / building as some movement of the unit can be expected during
normal operation. The piping and fittings must be separately supported to prevent any loading on the cooler.
!
CAUTION
Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of each
cooler. Pressure gauges are recommended to check the water pressure before and after the cooler and to
determine if any variations occur in the cooler and system. When installing pressure taps to measure the amount of
pressure drop across the water side of the cooler, the taps should be located in the water piping a minimum of 24
inches downstream from any connection (flange etc.) but as near to the cooler as possible.
Drain and air vent connections should be provided at all low and high points in the piping system to permit complete
drainage of the cooler and piping as well as to vent any air in the pipes. Hand shut-off valves are recommended for
use in all lines to facilitate servicing.
The system water piping must be flushed thoroughly before connecting to the unit cooler. The cooler must not be
exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass
and valve arrangement is installed to allow flushing of the piping system. The bypass can be used during
maintenance to isolate the cooler without disrupting flow to other units.
!
CAUTION
Any debris left in the water piping between the strainer and cooler could cause
serious damage to the tubes in the cooler and must be avoided. The
contractor/owner must also ensure that the quality of the water in circulation is
satisfactory, without any dissolved gases which can cause oxidation of steel
parts within the cooler.
38
The following is a suggested piping arrangement at the chiller for single unit installations. For multiple chiller
installations, each unit should be piped as shown:
OUT
IN
Pressure tapping
Flow Switch
Balancing Valve
Flow meter
Pipe work
Strainer
Flexible connection
Note: For chillers with two coolers, the connecting pipes for entering and leaving water on one cooler must be joined
to the corresponding pipes on the other cooler before connecting to the main headers in the system piping.
39
Flanged Cooler Connections as shown below are available as an option and should be specified with the equipment
order:
WATER REQUIREMENTS
Coolers used in these units are made of carbon steel, copper and brass and are suitable for operation with well
maintained water systems. Using unclean and untreated water may result in scale and deposit formation causing
reduced cooler efficiency or heat transfer and corrosion or pitting leading to possible equipment damage. The more
scale forming material and suspended solids in the system water, the greater the chances of scale and deposit
formation and fouling. These include calcium, magnesium, biological growth (algae, fungi and bacteria), dirt, silt, clays,
organic contaminants (oils), silica, etc. which should be kept to the minimum to retard scale and deposit formation. In
order to prevent corrosion and pitting, the pH value of the water flowing through the cooler must be kept between 7
and 8.5.
ZAMIL recommends that a water treatment specialist is consulted to provide and maintain water treatment, this is
particularly critical with glycol systems.
!
CAUTION
Using unclean and untreated water may result in reduced unit performance and
equipment damage.
40
Main power must be supplied from a single field supplied and mounted Disconnect
switch, using dual element time delay fuse or circuit breaker.
CAUTION
If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
CAUTION
!
WARNING
!
WARNING
ATTENTION
No additional controls (relays, etc.) should be mounted in the unit control panel unless
recommended by Zamil. Power and control wiring not connected to the unit should not
be run through the unit control panel. If these precautions are not observed it could
lead to a risk of electrocution or nuisance faults.
After connection of wiring, do not switch ON main power to the unit out rightly. Some
internal components get live when the main disconnect is switched ON and this must
be done by authorized personnel only.
If the unit is mounted on spring vibration isolators, electrical service to the unit must
also be flexibly connected (by means of a suitable flexible conduit), as some
movement of the unit can be expected during normal operation.
41
In regards to the controls and their wiring, please ensure compliance to the following points to avoid Electro Magnetic
Interference and to optimise the efficiency of EMI filters:
Make sure that the conducting area around board support holes on main, auxiliary and user boards are very well
grounded to the mounting plates through conducting studs, screws and metal spacers.
Cables for transducers, sensors, user boards and serial lines must be wired far from high voltage lines like main
power and controls power.
For shielded cables, connect the shield wire to the ground; exposed wire length must be 15 mm maximum.
Control wiring/cables connected to the control panel should never be run in the
same conduit with power wiring.
CAUTION
Some very important recommendations with regard to the main power switching On & Off to these chillers is as
follows. Failure to follow these recommendations could result in serious damage to the equipment:
!
CAUTION
Removing high voltage power (switching OFF the main disconnect) will
disable the 230VAC supply voltage to controls and the compressor crankcase
heaters. At initial start-up or after a prolonged power disconnection, the
crankcase heaters must be energized for a minimum of 12 hours (main
disconnect should be switched ON) before starting/operating the unit.
CAUTION
WARNING
42
40
46
47
48
RECOMMENDED INSTALLATION
LEAVING/RETURN WATER TEMPERATURE SENSOR & WATER FLOW SWITCH
NOTE: 1. For chiller with 2 coolers, leaving water temperature sensor and return water temperature sensor should be installed in the water piping
main header of every chiller.
2. Water flow switch should be installed vertically on the horizontal pipe line closed to the leaving water port of every cooler.
LEAVING
WATER
CHILLER # 1
CONTROL PANEL
OUT
IN
COOLER 2
FLS1
(FIELD INSTALLATION]
OUT
FS
COOLER 1
FS
IN
FLS2
(FIELD INSTALLATION]
RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]
LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]
CHILLER # 2
CONTROL PANEL
OUT
IN
COOLER 2
FLS1
(FIELD INSTALLATION]
OUT
FS
COOLER 1
FS
IN
FLS2
(FIELD INSTALLATION]
RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]
LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]
CHILLER # n
CONTROL PANEL
OUT
IN
COOLER 2
FLS1
(FIELD INSTALLATION]
OUT
FS
COOLER 1
FS
IN
FLS2
(FIELD INSTALLATION]
RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]
LEGEND :
LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]
RWT
> or <
FS
WATER DIRECTION
NOTE :
1. CHECK WITH THE ENGINEERING DEPARTMENT FOR THE FULL DETAILS
AND ACCURATE DRAWING.
49
RETURN
WATER
INSTALLATION INSPECTION
It is the responsibility of contractor or owner to verify and ensure that the following essential requirements are
complied:
Unit installed on flat concrete base and meets the specified clearances.
Vibration isolators are installed properly.
Ensure that all valves including balancing valves, globe valves, stop valves, motorized valves, drain
& air vent connections and flow meters are installed as per the requirement.
Temperature and pressure gauges provided at inlet and outlet piping of the cooler.
Ensure that all temperature and pressures gauges provided on the system are duly calibrated.
Strainer is installed on chilled water inlet to the unit.
Water flow switch is provided and at its correct location.
Field wiring is complete and all sensors and switches interlocked with the controller.
All optional sensors, gauges, valves etc. if any are installed and connected to the controller.
Ensure that chilled water pump is interlocked with the controller.
Chilled water pumps are suitable to handle the required flow rate, head etc.
All wiring connections are tight.
Unit control panels have the proper schematic diagrams.
Ensure compressor-mounting retainer brackets are removed and adjust the bolts.
Ensure that all condenser fans motor propellers are tightened.
Flexible connections provided at interconnection with chilled water piping and power cable entry.
Chilled water lines to the cooler are insulated.
Check for proper grounding of the chiller.
50
Do not start the unit before completing start-up and commissioning service.
CAUTION
!
CAUTION
PRE-STARTUP REQUISITES
The unit is ready for start-up when the following procedures have been completed:
Installation is complete and has been thoroughly inspected / verified as instructed earlier in this manual.
Ensure that all piping has been completed and tested. Water piping and cooler are filled with clean treated water. If
ambient temperatures are expected to fall below liquid freezing point (0oC for pure water) add pre-determined
amount of non-corrosive anti-freeze (Ethylene glycol) to prevent freeze-up.
Unit has been leak tested, leaks corrected and charging completed.
Electrical connections are made and properly fused.
Compressor crankcase heaters have been energized for a minimum of 12 hours.
Check all refrigerant valves to be sure they are open.
51
52
-
--- - - -
- -- - - - - -
-- - - -- - - - -
-- -- - - --
- - - --
- - -
- - -- - --
-- - ---
- -- - - -
- - - - - --
- - - -- - - -
- - - - -
- - --
- - - - - -
-- - --
- - - --
- - - --
- -- -
- - - - -- - --
- - - -- - -
--
- --
-- -
- --
- o - -
- - - --
- - - -
53
54
The above water flow rate limits must not be exceeded at any time. Operation
outside this range might result in cooler failure. Special care should be taken
when multiple chillers are fed by a single pump.
CAUTION
When using glycol solution, flow rate and pressure drop are higher than with
water. Special care must be taken not to exceed the limits. Consult Zamil for
further information and guidance in this regard.
ATTENTION
55
STAGE ON SEQUENCE:
Staging ON & OFF sequence shall be accomplished by the Leaving water temperature control selection.
Stage # 1:
If the Leaving water temperature is greater than the Stage 1-ON water temperature set point value, the compressor #1
liquid line solenoid & slider control valves shall be switched ON. Now the compressor is in the minimum or unloaded
capacity. The compressor capacity is varied to achieve the full/part load capacity as per the load demand.
As the discharge pressure of Compressor # 1 rises, the corresponding fans are energize accordingly to the fan stageON set point. If the discharge pressure falls below the fan stage- OFF set point value, the corresponding fans will turn
off.
Stage # 2:
If the Leaving Water Temperature is greater than the Stage 2- ON water temperature set point value, the Compressor
# 2 liquid line solenoid & slider control valves shall be switched ON. Now the compressor is in the minimum or
unloaded capacity. The compressor capacity is varied to achieve the full/ part load capacity as per the load demand.
As the discharge pressure of Compressor # 2 rises, the corresponding fans are energize accordingly to the fan stageON set point. If the discharge pressure falls below the fan stage-OFF set point value, the corresponding fans will turn
off.
56
57
- - - - -- --
-
-
- -
--
-- - --
- -
-
-- - - -
- -
- + Extension board for additional digital/analog I/O
--
- --
-
-- - - - o
p
- -
-
- - -
-
-
-
- -
-- - - -
p
-
-
- -
- - - - -
-
-- - - - -
- - - - - -
- -
- - -- -
- -- - -
- - - -
58
-
- - - -- -
-
-- - - - - -- - -
- -- -
- -
- - - - -- - -
-- - - - - -
- - - - - - -
-
- - - - - -
- -
- -- -
- - - -- - -
- - - - - - - -
- - - --
- - - - -
- - - --
- - - - -
-
-- -
- - - -
- - - --- --
-
- - - -- -
- - - --- --
- - - -- - -
COMP PROOF# or EXT# SFTY - - - - - - - - -
Lockouts can - - --
will again -
- - - - - -
- -- - - - - -
- - -
- - - - -
- - - - -
- - - - - - -
- - - -
- - - --
- - -
-
- - - pt.
- - -- -- -
- - -- -
21. FAST UNLOADING : this state is entered when the compressor is starting and during normal OFF.
22. COMP IS LOADING : this state is when the load solenoid is being pulsed to increase the cooling capacity.
23. COMP IS HOLDING : In this state, no movement of the slide valve is required.
24. COMP IS UNLDING : this state is when the unload solenoid is being pulsed to reduce the cooling capacity.
25. COMP UNLOADED : this state is when the slide is fully unloaded and the compressor is in min. capacity.
26. HI DISC UNLOAD : In this state the controller is unloading the compressor to avoid tripping.
27. HI DISC HLD : In this state the controller hold the compressor at existing slide position to avoid trip.
28. LO SUCT UNLOAD : In this state the controller is unloading the compressor to avoid tripping.
29. LO SUCT HOLD : In this state the controller hold the compressor at existing slide position to avoid trip.
30. HI AMP UNLOAD : In this state the controller is unloading the compressor to avoid tripping.
31. HI AMP HOLD : In this state the controller hold the compressor at existing slide position to avoid trip.
59
-- - - - --
-- --
-- - - -
- - --
-- -- --
-- - -
-
- - -
- - - - - -
-- - - - -- -- - -
- - - - --
- -- - --
- - - ---
- -- - - - - -
- - - - --
- - - -- -- --
-
- - - - - ---
-- -- - - - -- -
- - -
- - - - -
- - - - -
- - - -
-
-
-
-
- -- -- --
- - -
60
61
- -
- - -
General Concept
Not all compressors will run exactly at the full load amperage rating that the
manufacturer provides. Likely it will be very close, but some fine tuning of the
configuration will enable the operator to maximize efficiency and control of the unit.
This manual is designed to walk you through the steps of adjusting your slide amp
calculation through MCS-Connect for optimum performance of your system.
c. Wait until the compressor is fully loaded. Then check the value in the FLA% in the circuit grid
for that compressor.
b. Wait until the compressor is fully unloaded and then check the FLA% value in the
circuit grid.
c. Take this number, go to Menu then choose Set points. Look for set point #31 MIN
FLA % and set this number as the new value (Note: if you have multiple compressors you
should use an average of their fully unloaded values).
For the below example the FLA% value in the circuit grid is 51% using MCS connect.
This change of setting is also possible at Display board.
- - -- - -- --
- ---
- - --- - - --
- selected - - - - -
-
- -- -
- -
----
- display(Menu) - - -
--
---
-- -
-- EXT# SFTY or COMP PROOF # or SSPS #
- display(Menu) - -
-
- -
-- -
--
-
-
--
-- -
- -
- - - - -
--
-
--
- -- --
--
- through the display(Menu); only when trip was corrected -
--
--
--
- through the display(Menu); only when trip was corrected -
- - - -
- -
-
- -- --
-
-
-
86
-
- - -
-
- - -
-
-
-
- -
- --
- -
- -
- -
-
- - -
- -
- -
- - -
- -
- -
- -
-
- - - -
- -
- -
-
- -
89
APPENDIX
APPENDIX
Page 1 of 2
Yes
No
Yes
No
Yes
No
91
APPENDIX
Page 2 of 2
Yes
No
Attach all the required testing meters/ inspection gauges to monitor operational
parameters during the commissioning process.
Start and operate each compressor separately and record the amps, pressure,
temperatures in the refrigerant and water lines.
11. Check the compressor oil level in each compressor after one hour of operation.
12. Visual check and acid test of compressor oil after one hour of operation.
13. Repeat the process for every compressor in the chiller.
14. On satisfactory completion of the above, start the system for full operation.
15. Check the superheat.
16. Check the sub-cooling.
17. Check whether the 'leaving-water' temperature is as per design.
18. Check the water pressure drop across the chiller barrel ( P).
19. Check the temperature difference (water-in/ water-out) in chiller barrel ( T).
20. Simulate safety cut-outs functions and ensure its proper operation.
21. Ensure full load is available; if so, leave the system on for 24 hours.
22. Monitor and log performance, etc.
Note :
Check out report (4 pages) provided in this manual to be completed for each unit separately. A certified copy of
the check out report must be forwarded to Zamil Head Office, Dammam in order to avail the warranty.
92
APPENDIX
Page 1 of 4
Serial numbers
Codenser details
Condenser fan motor model
.__________________________________ .__________________________________
.__________________________________ .__________________________________
APPENDIX
Page 2 of 4
INSTALLATION DATA
Refrigerant type________________________________________________________________
Application:
Air Conditioning
Refrigeration
Process cooling
Yes
Other_______________________
No
Yes
No
Yes
No
Yes
No
Water
Counter flow
Brine______% by wt.
REFRIGERANT LEAKS: Thoroughly inspect unit for refrigerant leaks. If any are found, check this block and explain in
detail on a separate sheet. Contact your nearest Zamil office for assistance.
SYSTEM LOAD
Yes
No
Is a full load available during start up?
If full load is not available note under customer discrepancies on page 4 of this Check out report and advise customer
that a return trip at his expense will be required.
No
APPENDIX
Page 3 of 4
UNIT SPECIFICATIONS
This information can be obtained from concerned sales engineer or the service manager.
Refrigerant suction temperature_______________________________Condensing temperature________________________Tons______________________
Chiller :_______________________________GPM_______________Inlet temperature__________________Outlet temperature_______________________
Description
HP switch
LP switch
OP switch
HP transducer
LP transducer
OP transducer
PUMP DOWN
FAN # 1
FAN # 2
FAN # 3
FAN # 4
FAN # 5
FAN # 6
FAN # 7
FAN # 8
HGBP
Description
Discharge temperature
Freeze protection
Suction superheat
CR1
CUT-IN
CUT-OUT
CR1
CUT-IN
CUT-OUT
CUT-OUT
CR2
CUT-IN
CUT-OUT
CR4
CUT-IN
CUT-OUT
CR5
CUT-IN
CR3
CUT-IN
CUT-OUT
CR4
CUT-IN
CUT-OUT
CUT-OUT
CR5
CUT-IN
CUT-OUT
CR6
CUT-IN
CUT-OUT
CR6
CUT-IN
CUT-OUT
CR7
CUT-IN
CUT-OUT
CR7
CUT-IN
CUT-OUT
CUT-IN
CUT-IN
OPERATING INFORMATION
ELECTRICAL DATA
L1-L2
#1
#2
#3
#4
#5
#6
#7
#8
#9
# 10
# 11
# 12
# 13
# 14
# 15
# 16
# 17
# 18
# 19
# 20
# 21
# 22
# 23
# 24
CR3
CUT-IN
TEMPERATURE SETTINGS
CUT-OUT
COMPRESSORS
1A / 1B
2A / 2B
3A / 3B
4A / 4B
5A / 5B
6A / 6B
7A / 7B
8A / 8B
PRESSURE SETTINGS
CR2
CUT-IN
L1-L2
VOLTAGE
L2-L3
VOLTAGE
L2-L3
L3-L1
L1
L3-L1
L1
Notes:
* If two starters are used (part wind, windings A & B), give amperage on all legs.
CR - Compressor refrigeration circuit.
All temperature and pressure units in F and PSIG respectively unless otherwise noted.
95
AMPERAGE*
L2
AMPERAGE*
L2
L3
L3
CR8
CUT-OUT
CR8
CUT-OUT
APPENDIX
Page 4 of 4
TEMPERATURE READINGS
LOCATION
CR1
CR2
CR3
CR4
CR5
CR6
CR7
CR8
CR6
CR7
CR8
PRESSURE READINGS
LOCATION
CR1
CR2
CR3
CR4
CR5
Discharge pressure
Suction pressure
Net oil pressure
Liquid line pressure at pump down solenoid valve
Liguid line entering sub-cooler (economizer)
Oil level
#1
#2
#3
#4
#5
#6
#7
#8
This check out report is to be completely filled out and sent to Chiller Engineering Manager, Zamil Airconditioners, P.O. Box 14440,
Dammam 31424, Saudi Arabia.
Field service engineer____________________________________________________________________________________________
Contractor Name________________________________________________________________________________________________
Address_______________________________________________________________________________________________________
This report filled out by _______________________________________________ Date________________________________________
Signature :____________________________
96
COMPRESSORS:
1. Check system operating pressures and temperatures.
2. Check oil level.
3. Check condition of oil.
4. Check liquid injection operation.
5. Check operation of capacity control device (slider & solenoid valves)
6. Check crankcase heater operation.
7. Sample compressor oil.
8. Check integral check valve
9. Check pressure relief valve and roller bearings
REFRIGERANT FLOW CIRCUIT:
1. Check for pipework damage.
2. Check filter drier
3. Check for leaks (complete leak check)
4. Check liquid line sight glass / moisture indicator
5. Check suction superheat at compressor
6. Check condenser liquid subcooling
7. Check expansion valves, solenoid valves and check valves.
8. Check economizer operation.
AIR COOLED CONDENSERS:
1. Check condenser coils for dirt / debris and clean as required.
2. Check fans and fan guards.
3. Check fan motor bearings.
COOLER:
1. Check water flow.
2. Check water pressure drop & cooler efficiency.
3. Check cooler heater operation (if provided).
4. Check water pH / glycol strenth.
ELECTRICAL & CONTROL SYSTEM:
1. Check condition of control panel and all components
2. Check power and control wiring.
3. Check sensor locations.
4. Check mechanical HP cut-outs and water flow switch operation.
5. Check under voltage monitor and main disconnect.
6. Check tightness of all wiring connections
7. Check compressor contactors/ overloads/ breakers.
8. Check fan contactors / breakers.
9. Check sensor / transducer calibration
10. Check compressor motor protectors.
11. Check contactor contacts.
MICROPROCESSOR CONTROLLER:
1. Check fault history
2. Check operating set points.
3. Check HP and OP safety cut-out funtion.
4. Check pump-down function.
5. Check capacity load / unload function.
6. Check fan control function.
7. Check ambient cut-out function.
UNIT GENERAL:
1. Check thermal insulation on cooler and piping.
2. Check vibration isolators, repair/replace as necessary
3. Check unit structure for loose bolts/ screws and tight as necessary
4. Check for rusted/dented/ damaged body parts and repair/ repaint as
necessary.
WEEKLY
x
x
x
QUARTERLY
APPENDIX
SEMI-ANNUALLY
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
YEARLY
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
NOTES:
1. The above proceedures should be carried out by suitably qualified personnel only. A record of these procedures being successfully carried out must be maintained by the
equipment owner as a proof of adequate maintenance which may be required later for warranty validation purposes.
2. For guidelines and detailed information pertaining to the above maintenance procedures, refer relevant sections in the maintenance manual.
97
- - -
- -
--
- -
- - - -
- -
-
- -
-
-
- -
-
-
-
-
- --
--
-- -
-
---
- -
-
- - -
- - --
- - - -
- -
- - - - -
--
-
- -
- - -
-
-
-
--
-- --
--
-- -- -
- - -
-
-
--
-
- - ---
--
-
--
- -
-- -
-
- -
-
--
--
-- - -
- -
-
---
- -- - -
-
-
- -
- --
--
- ---
-- - -
- - -
-
-
-
--
--
- -
-
- - -
-- --
--
-
-
-
-
--
-
-
-
-
---
-
- -
- - - - -
-
- ---
- -
-- --
-
- -
-
- - - - - -
- - ---
- --
--
-- --
-- --
--
-- -
-
-- -
-
-
- - -
- -
- -
--
-
-
-
- --
- --
--
--
--
- ---
- -
99
--
-
--
-- - -
--
--
- - -
- -
-
- --
--
-
- -
- ---
--
-- --
-- - -
-
-- -
--
-
-
-
--- - -
- - -
-
-
--
--
- - -
-
-
-- -
- -
- -- --
-- --
-- - --
-
- -
- - -
-
- -
-
--
- -
-
--
- -
-
- - - -
-
-
-
-
-
- -
-
-
-
- -
-
- -
-- --
--
-
--- -- -
-- -
-
-- --
-- --
- -
--
-
- -
-- -
- - - -
- -
- --
--
- ---
--
-
--
--
- -
- -
-
-
-
-
NOTES:
* ONLY AUTHORIZED AND QUALIFIED PERSONNEL SHOULD
START
END
YES
NO
NO
NOW
OK?
CHECK
VOLTAGE
SELECTO
R
SETTING
IF
CORRECT
REPLACE
THE
BOARD
O
RELOAD
THE
SOFTWARE
YES
MEASURE VOLTAGE
FROM THE POWER
INPUT TERMINAL
YES
NO
NO
END
YES
NO
CORRECT
THE
POWER
SUPPLY
YES
NOW
OK?
WITH
IN +/10%
DISPL
AY
BACKL
IGHT
ON?
NO
TURN POWER
OFF, WAIT 1
MINUTE THEN
TURN
U
POWER
O
BACK ON .
RESET
LED
LIGHT
CONTI
NOUS
LY?
YES
16VD
C
LED
ON?
FUSE
BLO
WN?
NO
YES
NO
YES
END
YES
NOW
OK?
PRESS RESET
BUTTON ON
BOARD
REPLACE THE
BOARD
REPLACE
FUSE IF FUSE
BLOWN AGAIN
REPLACE THE
BOARD
YES
RESET ALL
LOCKOUTS.
CHECK IF
ERROR
STILL
OCCUR ON
OTHER
SENSOR
INPUT
NO
END
YES
START
RECONNECT ONE
TERMMINAL AND
MEASURE DC VOLTAGE
FROM+5 PIN TO GROUND
CHECK
DC
VOLTAGE
WITHIN
4.75 TO
5.25V
NO
CHECK THE
SENSOR AND ITS
WIRING
YES
CHECK
DC
VOLTAGE
WITHIN
4.75 TO
5.25V
REMOVE ALL
TERMINALS, WAIT 1
MINUTE, THEN MEASURE
DC VOLATGE FROM +5
PIN TO GROUND AT ONE
TERMINAL INPUT
END
CHECK ADDRESS
JUMPER SETTING AND
COM LED IF BLINKING.
REPLACE THE
BOARD
NO
NO
YES
CHECK
DC
VOLTAGE
WITHIN
4.75 TO
5 25V
5.25V
MEASURE DC VOLTAGE
FROM +5 PIN TO
GROUND PIN AT ONE
TERMINAL.
YES
ARE ALL
SENSOR
ON THE
BOARD
NOT OK?
NO
CHECK THE
SENSOR AND ITS
WIRING
YES
CHECK
NOW THE
SENSOR
READING
IF OK
REMOVE THE
CONNECTOR BLOCK
ON THE AFFECTED
SENSOR
END
REPLACE THE
BOARD
NO
REPLACE THE
BOARD
NO
START
END
YES
CHECK
ALL
RELAY
NOW IF
O
OK
END
REPLACE FUSE
CHECK ADDRESS
JUMPER SETTING AND
COM LED IF BLINKING.
YES
YES
NO
CHECK
CONNECTOR
RESISTANCE
BETWEEN
COM AND NC
PIN. IS IT
LESS THAN 1OHM?
REPLACE THE
BOARD
NO
CHECK
RELAY
FUSE IF
BLOWN
YES
ARE ALL
RELAY
ON THE
BOARD
NOT OK?
NO
NO
REPLACE THE
BOARD
STE RELAY
STATUS TO
MANON
YES
CHECK
CONNECTOR
RESISTANCE
BETWEEN
COM AND NC
PIN. IS IT
LESS THAN 1OHM?
REMOVE THE
CONNECTOR BLOCK
ON THE AFFECTED
RELAY AND SET
STATUS TO MANOFF
END
START
CHECK POWER
SUPPLY OF THE
AFFECTED
BOARD
CHECK ADDRESS
JUMPERS ON ALL
BOARD IF CORRECT
YES
NO
NO
CHECK
FUSE IF
BLOWN
O
DOES
THE
AFFECTE
D BOARD
HAS
POWER?
REPLACE THE
BOARD
YES
NO
CHECK IF
ONE OF
THE
BOARD
COM LED
IS
BLINKING
NO
CHECK
BOARDS
COM LED
IF
BLINKIN
G
NO
CHECK
BOARDS
COM LED
IF
BLINKIN
G
YES
END
2.
DISPLAY WILL ASK THE PASSWORD. USING THE 8 BUTTONS IN THE BOARD
ENTER THE CORRECT PASSWORD
PASSWORD. THEN PRESS ENTER BUTTON.
BUTTON
1. FROM THE DISPLAY BOARD PRESS MENU BUTTON. THEN PRESS THE ARROW
BUTTON TO HIGHLIGHT THE PASSWORDS AS SHOWN, THEN PRESS ENTER.
* SECTION # 1:
4.
* SECTION # 1:
* SECTION # 1:
GOOD
READING
57.0 AMP
143.0 AMP
287.0 AMP
77.0 F
100.0 PSI
250.0 PSI
SENSOR
TYPE
CT 100
CT 250
CT 500
T100
TI 200
TI 500
* SECTION # 2:
VOLTAGE SELECTOR
RESET LED
POWER LED(green)
LED(
)
ANALOG/DIGITAL
INPUTS JUMPER
TERMINATION
FOR RS485
BATTERY
JUMPER
COMMUNICATION
TERMINAL
TERMINATION
FOR EXPANSION I / Os
MAIN BOARD
( MAGNUM BOARD )
9 SOFT
BUTTON
DISPLAY SCREEN
6 WIRES
TERMINAL
TO MAIN
BOARD
COM LED
RESET BUTTON
16 INPUT TERMINALS
COM LED
COMMUNICATION
TERMINAL
POWER FUSE
DIGITAL /
ANALOG
JUMPER
TERMINATION
FOR EXPANSION I/O
JUMPERS
ADDRESS
RESET
BUTTON
8 OUTPUT WITH
INDIVIDUAL FUSE
COM
LED
TERMINAL
COMMUNICATION
POWER FUSE
ADDRESS
JUMPERS
TERMINATION
FOR EXPANSION I/O
CN4
CN2
TERMINALS
CN3
FUSE
121
APPENDIX
I UNIT
10 UNITS
I UNIT
10 UNITS
EACH
EACH
EACH
EACH
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
1
2
2
1
1
2
-
1
1
1
4
1
1
4
-
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2
2
1
2
1
Controls
Microprocessor main board
Microprocessor user interface board
Electronic expansion valve board
Electrical
Compressor contactor
Compressor OLR
Compressor circuit breaker
Fan motor contactor
Fan motor circuit breaker
Transformer
Refrigerant circuits
Electronic expansion valve.
Thermal expansion valve
Solenoid valve
Filter core
Sight glass
Others
Flow switch
Oil pressurestat
Pressure transducer
PTC temperature sensor
High pressurestat
Low pressurestat
Sensors
Timer
Crankcase heater
Note : 1) When ordering spare parts, please specify the complete model number on the unit nameplate.
2) If quantity is written, it means, in each model, we must have that much quantity.
3) If percentage is written, number of components per unit multiplied by number of units and then percentage.
122
ASYB
050BM
050BF
060BH
060BM
060BF
070BH
070BM
070BF
080BH
080BM
080BF
80009766(2)
80009767
80009767
80009767(2)
80009767
80009767
80009767(2)
80009768
80009767
80009767(2)
80009768
80009767
80009757(2) 80009751(2)
COMPRESSOR CONTACTOR
R134a/60Hz
050BH
80009748(2)
80009760(2)
80009754(2)
80060687(2) 80060685(2)
80060854(2)
80060688(2)
80060854(2)
80009851(4) 80009851(4)
80009851(4)
80009851(4)
80009851(4)
80055506(4) 80055506(4)
80055506(4)
80023707(4)
80023707(4)
80022433(4) 80022433(4)
80022433(4)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80018155
80018155
80018155
80018155
80018155
80018155
80018155
80018155
80018155
80018164
80018164
80018164
SIGHT GLASS
80020100
80020100
80020100
80020100
80020100
80020100
80020100
80020100
80020100
80020100
80020100
80020100
80070665
80070665
80070665
80070665
80070665
80070665
80070665
80070665
80070665
80070665
80070665
80070665
80064655(3) 80064655(3)
MB TRANSFORMER (24V)
80001200
80001200
80064655(3)
80001200
80001200
80001200
80064655(3)
80001200
80001200
80001200
80001200
80064655(3)
80001200
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80009719(2) 80009722(2)
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80060965
80060963
80004709(4) 80004709(4)
80009713(2)
80060963
80004709(4)
80060966
80060964
80060963
80009720(2)
80060967
80004710(4)
80060965
80060964
80060967
ASYB
COMPRESSOR CONTACTOR
090BH
090BM
80060965
80009722(2)
80060964
80004710(4)
R134a/60Hz
090BF
100BH
100BM
100BF
120BH
120BM
120BF
130BH
130BM
130BF
80009766(4) 80009767(2)
80009766(2)
80009767(4)
80009767(2)
80009757(4) 80009751(4)
80009748(4)
80009757(4)
80009751(4)
80060688(3) 80060685(3)
80060854(3)
80060688(4)
80060854(4)
80009851(6) 80009851(6)
80009851(6)
80009851(8)
80009851(8)
80023707(6) 80023707(6)
80023707(6)
80023707(8)
80023707(8)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80018155(2) 80018155(2)
80064666
80018155(2)
80064666
80018155(2)
80064666
80018155(2)
SIGHT GLASS
80020100(2) 80020100(2)
80020100(2)
80020100(2)
80020100(2)
80070665(2) 80070665(2)
80070665(2)
80070665(2)
80070665(2)
80064655(4) 80064655(4)
80064655(4)
80064655(4)
80064655(4)
MB TRANSFORMER (24V)
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80009719(4) 80009722(4)
80060967
80060965
80004711(6) 80004711(6)
80009713(4)
80060964
80004711(6)
80060967
80060965
80060964
80009719(4)
80060968
80004711(6)
80060966
80060965
80060968
80060966
80009722(4)
80060965
80004712(6)
ASYB
COMPRESSOR CONTACTOR
140BH
140BM
R134a/60Hz
140BF
150BH
150BM
150BF
160BH
160BM
160BF
170BH
170BM
170BF
80009767(4) 80009768(2)
80009767(2)
80009768(4)
80009768(2)
80009760(4) 80009754(4)
80009751(4)
80009760(8)
80009754(4)
80060688(5)
80060854(5)
80060688(4) 80060685(4)
80060854(4)
80009851(8) 80009851(8)
80009851(8)
80023707(8) 80023707(8)
80023707(8)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064645
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80064666
80018155(2) 80018155(2)
80064666
80018155(2)
80064666
80018164(2)
80064666
80018164(2)
SIGHT GLASS
80020100(2) 80020100(2)
80020100(2)
80020100(2)
80020100(2)
80070665(2) 80070665(2)
80070665(2)
80070665(2)
80070665(2)
80064655(4) 80064655(4)
80064655(4)
80064655(4)
80064655(4)
MB TRANSFORMER (24V)
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80009720(4) 80009723(4)
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80060968
80060967
80004712(6) 80004712(6)
80009722(4)
80060966
80004712(6)
80060968
80060967
80060966
80009720(8)
80060968
80004710(8)
80060967
80060966
80060968
ASYB
COMPRESSOR CONTACTOR
FAN MOTOR CIRCUIT BRKR
FAN MOTOR CONTACTOR
CONDENSER FAN MOTOR with FAN & GRILL
MICROPROCESSOR USER INTERFACE BOARD
180BH
180BM
80060967
80009722(4)
80060967
80004711(8)
R134a/60Hz
180BF
80009767(6) 80009767(3)
80009767(3)
80009757(6) 80009751(6)
80009748(6)
80060688(6) 80060685(6)
80060854(6)
190BH
190BM
190BF
80009767
200BH
200BM
200BF
215BF
80009757(6)
80009751(2)
80060688(6)
80060854(6)
80009767(2)
215BM
80009767(6)
80009767
215BH
80009768
80009767(2)
80009767
80009754(4)
80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12)
80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645(2) 80064645(2)
80064645(2)
80064645(2)
80064645(2)
80064666(2) 80064666(2)
80064666(2)
80064666(2)
80064666(2)
80018155(3) 80018155(3)
80018155(3)
80018155(3)
80018164(2)
80018155(1) 80018155(1)
80018155(1)
80020100(3) 80020100(3)
80020100(3)
80020100(3)
80020100(3)
80070665(3) 80070665(3)
80070665(3)
80070665(3)
80070665(3)
80064655(5) 80064655(5)
80064655(5)
80064655(5)
80064655(5)
MB TRANSFORMER (24V)
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
80055741
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80009719(6) 80009722(6)
80009715(6)
80009719(6)
80009722(4)
80009720(2) 80009722(2)
80009722(2)
80060967
80004712(8) 80004712(8)
80060966
80004712(8)
80060969
80060968
80060967
80060969
80004712(8)
80060968
80060967
80060969
80060968
80060967
80004712(8)
ASYB
R134a/60Hz
230BH
230BM
230BF
80009768(2)
80009768
80009768
240BH
240BM
240BF
250BH
250BM
250BF
270BH
270BM
270BF
80009767(8)
80009767(4)
80009757(8)
80009751(8)
80060688(8)
80060854(8)
80009767(4) 80009767(2)
80009767(2)
80009763(2) 80009754(2)
80009754(2)
80009760(4) 80009754(4)
80009754(4)
80060688(6) 80060685(6)
80060854(6)
80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(12) 80009851(16) 80009851(16) 80009851(16) 80009851(16) 80009851(16) 80009851(16)
COMPRESSOR CONTACTOR
80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(12) 80023707(16) 80023707(16) 80023707(16) 80023707(16) 80023707(16) 80023707(16)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645(2) 80064645(2)
80064645(2)
80064645(2)
80064645(2)
80064666(2) 80064666(2)
80064666(2)
80064666(2)
80064666(2)
80018164(3) 80018164(3)
80018164(3)
80018155(4)
80018155(4)
80020100(3) 80020100(3)
80020100(3)
80020100(4)
80020100(4)
80070665(3) 80070665(3)
80070665(3)
80070665(4)
80070665(4)
80064655(5) 80064655(5)
80064655(5)
80064655(6)
80064655(6)
MB TRANSFORMER (24V)
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80001200
80053341
80053341
80053341
80053341
80001200
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80055741
80055741
80055741
80055741
80055741
80055741
80055741(2)
80055741(2)
80009719(8)
80009722(8)
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80009723(2) 80009723(2)
80009722(2)
80009720(4) 80009723(4)
80009722(4)
80060969
80060968
80004712(8) 80004712(8)
80060968
80004712(8)
80060969
80060968
80060968
80060969
80060968
80060967
80060969
ASYB
295BH
295BM
80060968
80060968
80053341
R134a/60Hz
295BF
310BH
310BM
310BF
330BM
330BF
350BH
350BM
80009767(2)
80009767(4) 80009768(2)
80009767(2)
80009760(4) 80009754(4)
80009754(4)
80009760(4) 80009754(4)
80009751(4)
80060688(8) 80060685(8)
80060854(8)
80009851(16) 80009851(16) 80009851(16) 80009851(16) 80009851(16) 80009851(16) 80009851(18) 80009851(18) 80009851(18) 80009851(18) 80009851(18) 80009851(18)
COMPRESSOR CONTACTOR
80009767(8)
80009766(4)
80009767(2) 80009766(2)
350BF
80009767(4) 80009768(2)
330BH
80009767(6)
80009757(8)
80009757(4)
80009751(4) 80009868(4)
80060688(9)
80060854(9)
80023707(16) 80023707(16) 80023707(16) 80023707(16) 80023707(16) 80023707(16) 80023707(18) 80023707(18) 80023707(18) 80023707(18) 80023707(18) 80023707(18)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645(2) 80064645(2)
80064645(2)
80064645(3)
80064645(3)
80064666(2) 80064666(2)
80064666(2)
80064666(3)
80064666(3)
80018164(2) 80018164(2)
80018164(2)
80018155(6)
80018155(6)
80018155(2) 80018155(2)
80018155(2)
SIGHT GLASS
80020100(4) 80020100(4)
80020100(4)
80020100(6)
80020100(6)
80070665(4) 80070665(4)
80070665(4)
80070665(6)
80070665(6)
80064655(6) 80064655(6)
80064655(6)
MB TRANSFORMER (24V)
80001200
80001200
80053341
80053341
80001200
80001200
80001200
80001200
80053341
80053341
80053341
80001215
80001215
80001215
80001215
80001215
80053341
80053341
80053341
80053341
80001215
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
WATER FLOW SWTICH
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80053341
80055741(2) 80055741(2)
80055741(2)
80009720(4) 80009722(4)
80009722(4)
80009720(4) 80009722(4)
80009722(4)
80060869
80060968
80060968
80060969
80060968
80060968
80053341
80055741(2)
80053341
80055741(2)
80009719(8)
80009719(4)
80009722(4) 80009894(4)
80060969
80060968
80060968
80060970
80060968
80060968
80004712(10) 80004712(10) 80004712(10) 80004712(10) 80004712(10) 80004712(10) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14)
ASYB
375BH
375BM
80009767(12) 80009768(6)
R134a/60Hz
375BF
80009767(6)
400BH
400BM
400BF
COMPRESSOR CONTACTOR
FAN MOTOR CIRCUIT BRKR
80060688(9) 80060685(9)
80060854(9)
420BH
420BM
420BF
450BH
450BM
450BF
80009767(6)
80009767(4)
80009767(6)
80009767(2)
80009760(6)
80009754(8)
80009760(6)
80009751(4)
80009851(18) 80009851(18) 80009851(18) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22)
80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645(3) 80064645(3)
80064645(3)
80064645(3)
80064645(3)
80064666(3) 80064666(3)
80064666(3)
80064666(3)
80064666(3)
80018164(3) 80018164(3)
80018164(3)
80018164(3)
80018164(4)
80018155(3)
80018155(2)
SIGHT GLASS
80020100(6) 80020100(6)
80020100(6)
80020100(6)
80020100(6)
80070665(6) 80070665(6)
80070665(6)
80070665(6)
80070665(6)
80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10) 80064655(10)
MB TRANSFORMER (24V)
80001215
80001215
80053341
80053341
80001215
80001215
80001215
80001215
80053341
80053341
80053341
80001215
80001215
80001215
80001215
80001215
80053341
80053341
80053341
80053341
80001215
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
WATER FLOW SWTICH
80055741(2) 80055741(2)
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
80053341
80053341
80055741(2)
80055741(2)
80009720(6)
80009722(8)
80009720(6)
80009722(4)
80060968
80060968
80060970
80060969
80060968
80060970
80060969
80060968
80060970
80060969
80060968
80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14)
SPRING ISOLATORS
80053341
80060970
80055741(2)
ASYB
COMPRESSOR CONTACTOR
FAN MOTOR CIRCUIT BRKR
FAN MOTOR CONTACTOR
CONDENSER FAN MOTOR with FAN & GRILL
MICROPROCESSOR USER INTERFACE BOARD
475BH
475BM
R134a/60Hz
475BF
80009768(6) 80009768(3)
80009768(3)
80009767(6) 80009768(3)
80009767(3)
500BH
500BM
500BF
540BH
540BM
540BF
560BH
560BM
560BF
80009767(8)
80009767(8)
80009767(8)
80009767(4) 80009767(4)
80009760(8)
80009757(8)
80009751(8) 80009748(8)
80060688(11) 80060685(11) 80060885(11) 80060688(11) 80060685(11) 80060885(11) 80060688(16) 80060685(16) 80060885(16) 80060688(16) 80060685(16) 80060885(16)
80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(22) 80009851(32) 80009851(32) 80009851(32) 80009851(32) 80009851(32) 80009851(32)
80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(22) 80023707(32) 80023707(32) 80023707(32) 80023707(32) 80023707(32) 80023707(32)
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064650
80064645(3) 80064645(3)
80064645(3)
80064645(4)
80064645(4)
80064666(3) 80064666(3)
80064666(3)
80064666(4)
80064666(4)
80018164(3) 80018164(3)
80018164(3)
80018155(8)
80018155(8)
SIGHT GLASS
80020100(6) 80020100(6)
80020100(6)
80020100(8)
80020100(8)
80070665(6) 80070665(6)
80070665(6)
80070665(8)
80070665(8)
80064655(16) 80064655(16) 80064655(16) 80064655(16) 80064655(16) 80064655(16) 80064655(20) 80064655(20) 80064655(20) 80064655(20) 80064655(20) 80064655(20)
MB TRANSFORMER (24V)
80001215(1) 80001215(2)
80001215(2)
80001215(2)
80001215(2)
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
WATER FLOW SWTICH
COMPRESSOR OLR
MAIN Non-Fused DISCONNECT SWITCH
SPRING ISOLATORS
80053341
80053341
80055741(2) 80055741(2)
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80053341
80055741(2)
80009720(8)
80009719(8)
80009722(8) 80009715(8)
80060969(2)
80060970
80060969
80055741(2)
80060968
80060970
80060969
80060968
80055741(2)
80060968(2)
80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(14) 80004712(20) 80004712(20) 80004712(20) 80004712(20) 80004712(20) 80004712(20)
ASYB
COMPRESSOR CONTACTOR
FAN MOTOR CIRCUIT BRKR
FAN MOTOR CONTACTOR
CONDENSER FAN MOTOR with FAN & GRILL
MICROPROCESSOR USER INTERFACE BOARD
590BH
590BM
R134a/60Hz
590BF
80009767(8) 80009768(4)
80009767(4)
80009767(8) 80009768(4)
80009767(4)
80009760(8) 80009754(8)
80009754(8)
80009760(8) 80009754(8)
80009751(8)
80064650
80064650
80064650
80064645(4) 80064645(4)
80064645(4)
80064666(4) 80064666(4)
80064666(4)
80018164(4) 80018164(4)
80018164(4)
80018155(4) 80018155(4)
80018155(4)
80020100(8) 80020100(8)
80020100(8)
80070665(8) 80070665(8)
80070665(8)
MB TRANSFORMER (24V)
80001215(2) 80001215(2)
SIGHT GLASS
80001215(2)
OPIONAL ITEMS
HGBP WITH SOLENOID VALVE
WATER FLOW SWTICH
80053341
80053341
80053341
80055741(2) 80055741(2)
80055741(2)
80009720(8) 80009723(8)
80009722(8)
80009720(8) 80009722(8)
80009722(8)
80060969(2) 80060968(2)
80060968(2)
SPRING ISOLATORS
COMPRESSOR OLR
APPENDIX
SAFETY DATA
Toxicity
Inhalation
Stability
Conditions to Avoid
Materials to Avoid
Hazardous
Decomposition
Products
General Precautions
Respiratory Protection
REFRIGERANT R134a
Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous by skin absorption.
Thaw affected areas with water. Remove contaminated clothing carefully - may adhere to skin in
case of freeze burns. Wash affected areas with plenty of warm water. If symptoms occur (irritation
or blistering), obtain medical attention.
Contact with liquid or cold vapor can cause freezing of tissue. Immediately flush with plenty of
clean water for at least 15 minutes. Obtain immediate medical attention.
High concentration of HFC 134a vapor is harmful. It can act as an asphyxiant by limiting available
oxygen. Human health effects of overexposure to HFC- 134a vapors by inhalation may include
temporary nervous system depression with anaesthetic effects such as dizziness, headache,
confusion, incoordination and loss of consciousness. At very high doses, cardiac sensitization to
circulating epinephrine-like compounds can result in fatal cardiac arrhythmias.
If large concentrations are inhaled, immediately remove to fresh air. Keep person calm. If not
breathing, give artificial respiration, perferably mouth to mouth. If breathing is labored, give oxygen.
In the event of cardiac arrest, apply external cardiac massage. Do not admininster adreneline or
similar sympathominectic drugs as cardiac arrhythmias may result. Get immediate medical
attention.
Stable under normal conditions.
Any source of ignition, such as lighted cigarettes, flames, hot spots, welding.
Finely divided metals, magnesium and alloys conatining more than 2% magnesium. Can react
violently if in contact with alkali earth metals such as sodium, potassium, calcium, barium,
powdered aluminium, magnesium and Zinc.
Halogens, halogen acids and possibly carbonyl halides such as phosgene. These are toxic and
corrosive.
Avoid inhalation of high concentrations of vapors. Atmospheric concentrations should be minimized
and kept as low as possible. The vapor is heavier than air and collects at low level and in confined
areas. Ventilate by extraction at lowest levels.
Where doubt exists on atmospheric concentration, suitable breathing apparatus should be worn.
This should be self-contained or of the long breather type.
Storage
Store in a cool, well-ventilated area of low fire risk. Keep cylinders dry. Cylinders should be stored
upright with valve protection cap in place and firmly secured to prevent falling or being knocked
over. Protect cylinders from physical damage; do not drag, roll, slide or drop. Do not allow storage
area temperature to exceed 113F (45C). Keep away from direct sunlight, heat and sources of
ignition. Full and empty cylinders should be segregated. Use a first-in, first-out inventory system to
prevent full containers from being stored for long periods of time.
Protective Clothing
Ensure suitable personal protective clothing and respiratory protection is worn. Evacuate all
personnel from the affected area. Shut off source of leak, if possible without risk. Ventilate spill
area, especially low places where heavy vapors might collect. If possible dike and contain spillage.
Prevent liquid from entering sewers, sumps or pit areas, since vapor can create suffocating
atmosphere. Allow spilled liquid to evaporate.
Disposal
Best to recover and recycle. If this is not possible, destruction is to be in an approved facility which
is equipped to absorb and neutralize acids and other toxic processing products.
Non-flammable.
Containers
Fire exposed containers should be kept cool with water sprays. Containers may burst if overheated.
Self-contained breathing apparatus and protective clothing must be worn in fire conditions.
128
APPENDIX
Pressure
PSIA
PSIG
21.2
22.2
23.3
24.3
25.5
26.6
27.8
29.1
30.4
31.7
33.1
34.5
36.0
37.5
39.1
40.7
42.4
44.2
45.9
47.8
49.7
51.6
53.7
55.7
57.9
60.0
62.3
64.6
67.0
69.5
72.0
74.6
77.2
80.0
82.8
85.7
88.6
91.6
94.8
97.9
101.2
104.6
108.0
111.5
6.5
7.5
8.6
9.6
10.8
11.9
13.2
14.4
15.7
17.0
18.4
19.8
21.3
22.9
24.4
26.1
27.7
29.5
31.3
33.1
35.0
36.9
39.0
41.0
43.2
45.4
47.6
49.9
52.3
54.8
57.3
59.9
62.6
65.3
68.1
71.0
73.9
77.0
80.1
83.2
86.5
89.9
93.3
96.8
Temperature C
-17.78
-16.67
-15.56
-14.44
-13.33
-12.22
-11.11
-10.00
-8.89
-7.78
-6.67
-5.56
-4.44
-3.33
-2.22
-1.11
0.00
1.11
2.22
3.33
4.44
5.56
6.67
7.78
8.89
10.00
11.11
12.22
13.33
14.44
15.56
16.67
17.78
18.89
20.00
21.11
22.22
23.33
24.44
25.56
26.67
27.78
28.89
29.95
129
Pressure
Kpa (Absolute)
Kpa (Gauge)
146.2
153.2
160.4
167.9
175.7
183.7
192.0
200.7
209.6
218.8
228.4
238.2
248.4
258.9
269.8
281.0
292.6
304.6
316.9
329.6
342.6
356.1
370.0
384.3
399.0
414.1
429.7
445.7
462.2
479.1
496.5
514.4
532.7
551.6
570.9
590.8
611.1
632.0
653.5
675.4
698.0
721.1
744.7
769.0
44.9
51.8
59.1
66.6
74.3
82.4
90.7
99.3
108.3
117.5
127.0
136.9
147.1
157.6
168.5
179.7
191.3
203.2
215.5
228.2
241.3
254.8
268.7
283.0
297.7
312.8
328.4
344.4
360.9
377.8
395.2
413.0
431.4
450.2
469.6
489.4
509.8
530.7
552.1
574.1
596.6
619.7
643.4
667.6
APPENDIX
Pressure
PSIA
PSIG
115.1
118.8
122.6
126.4
130.4
134.4
138.6
142.8
147.1
151.6
156.1
160.7
165.5
170.3
175.2
180.3
185.5
190.7
196.1
201.6
207.2
212.9
218.8
224.7
230.8
237.0
243.3
249.8
256.4
263.1
269.9
276.9
284.0
291.3
298.7
306.2
313.9
321.7
329.7
337.9
346.1
354.6
100.4
104.1
107.9
111.7
115.7
119.7
123.9
128.1
132.4
136.9
141.4
146.0
150.8
155.6
160.6
165.6
170.8
176.0
181.4
186.9
192.5
198.2
204.1
210.0
216.1
222.3
228.6
235.1
241.7
248.4
255.2
262.2
269.3
276.6
284.0
291.5
299.2
307.1
315.0
323.2
331.5
339.9
Temperature C
31.11
32.22
33.33
34.44
35.56
36.67
37.78
38.89
40.00
41.11
42.22
43.33
44.44
45.56
46.67
47.78
48.89
50.00
51.11
52.22
53.33
54.44
55.56
56.67
57.78
58.89
60.00
61.11
62.22
63.33
64.44
65.56
66.67
67.78
68.89
70.00
71.11
72.22
73.33
74.44
75.56
76.67
130
Pressure
Kpa (Absolute)
Kpa (Gauge)
793.8
819.2
845.3
871.9
899.2
927.1
955.7
984.9
1014.8
1045.3
1076.6
1108.5
1141.2
1174.5
1208.6
1243.4
1279.0
1315.3
1352.4
1390.3
1428.9
1468.4
1508.7
1549.8
1591.7
1634.5
1678.2
1722.7
1768.1
1814.4
1861.6
1909.8
1958.9
2008.9
2059.9
2111.9
2164.9
2218.9
2274.0
2330.1
2387.2
2445.4
692.5
717.9
743.9
770.6
797.9
825.8
854.3
883.6
913.4
944.0
975.2
1007.2
1039.8
1073.2
1107.3
1142.1
1177.7
1214.0
1251.1
1288.9
1327.6
1367.1
1407.4
1448.5
1490.4
1533.2
1576.8
1621.4
1666.8
1713.1
1760.3
1808.5
1857.6
1907.6
1958.6
2010.6
2063.6
2117.6
2172.7
2228.7
2285.9
2344.1
APPENDIX
= 500 x GPM x
H
GPM
T
500
For systems with glycol solution, this equation can be used with a modified equation factor
(depending on the glycol concentration as tabulated below:
Ethylene Glycol
% GLYCOL
SOLUTION
TEMPERATURE F.
SPECIFIC
HEAT
SPECIFIC
GRAVITY
( )
EQUATION
FACTOR
FREEZE
POINT
BOILING POINT
+32
212
1.00
1.000
500
10
+26
214
0.97
1.012
491
20
+16
216
0.94
1.027
483
30
+4
220
0.89
1.04
463
40
-12
222
0.83
1.055
438
50
34
225
0.78
1.067
416
60
-60
232
0.73
1.079
394
70
<-60
244
0.69
1.091
376
80
-49
258
0.64
1.101
352
90
20
287
0.60
1.109
333
100
+10
287+
0.55
1.116
307
Notes:
1. Specific gravity with respect to water at 60F.
131
APPENDIX
Valves:
Fittings:
132
APPENDIX
Piping Specialities:
Electrical:
133
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
UNIT DATA
Supply Voltage (3Phase)
Nominal
(VPh-Hz)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
EXTENDED B/B
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
TB2 - 600
NA
NA
TB2 - 600
NA
NA
TB2 - 600
NA
NA
TB2 - 750
NA
NA
TB3 - 750
NA
NA
TB3 - 750
NA
NA
TB3 - 750
NA
NA
LUG SIZE
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
QTY per
phase
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Note:
All this lugs can be requested separately from the unit.
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Terminal Number 1 - First Main Power Field Terminal Point of the unit
Terminal Number 2 - Second Main Power Field Terminal Point of the unit ( This is avaible only for chiller with Dual Power Entry Point)
Terminal Number 3 - Control Power Supply, Factory wired, this can be done also in the field when required. This should be connected from bus separate from Terminal Number 1 and 2.
NA - Not Applicable.
TB2 - 600 - Lug capable for two cable of 2 to 600 MCM size.
TB3 - 600 - Lug capable for three cable of 2 to 600 MCM size.
TB2 - 750 - Lug capable for two cable of 1/0 to 750 MCM size.
TB3 - 750 - Lug capable for three cable of 1/0 to 750 MCM size.
TB4 - 750 - Lug capable for four cable of 1/0 to 750 MCM size.
EXTENDED B/B - Terminal B/B extansion for field installation.
LEGENDS:
160
150
140
130
120
100
90
80
70
60
50
MODEL
NO
ASYB
NOT AVAILABLE
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
Ph-Hz)
UNIT DATA
Supply Voltage (3Phase)
Nominal
(V-
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
EXTENDED B/B
TB3 - 750
NA
NA
TB3 - 750
TB2 - 750
TB2 - 600
TB3 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB3 - 600
TB2 - 600
TB4 - 750
TB3 - 600
TB2 - 750
TB4 - 750
TB3 - 600
TB2 - 600
TB4 - 750
TB3 - 600
TB3 - 600
TB3 - 600
TB3 - 750
TB3 - 600
TB3 - 600
TB3 - 750
TB3 - 600
LUG SIZE
1
NA
NA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2
1
1
QTY per
phase
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
TB2 - 600
NA
NA
TB2 - 600
NA
NA
TB2 - 750
NA
NA
TB2 - 750
NA
NA
TB3 - 600
NA
NA
TB3 - 600
NA
NA
TB2 - 600
NA
NA
TB2 - 600
NA
NA
TB3 - 600
NA
NA
TB3 - 600
NA
NA
NA
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
TB2 - 600
NA
NA
TB2 - 600
NA
NA
TB3 - 600
NA
NA
TB3 - 600
NA
NA
Note:
All this lugs can be requested separately from the unit.
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
1
NA
NA
Terminal Number 1 - First Main Power Field Terminal Point of the unit
Terminal Number 2 - Second Main Power Field Terminal Point of the unit ( This is avaible only for chiller with Dual Power Entry Point)
Terminal Number 3 - Control Power Supply, Factory wired, this can be done also in the field when required. This should be connected from bus separate from Terminal Number 1 and 2.
NA - Not Applicable.
TB2 - 600 - Lug capable for two cable of 2 to 600 MCM size.
TB3 - 600 - Lug capable for three cable of 2 to 600 MCM size.
TB2 - 750 - Lug capable for two cable of 1/0 to 750 MCM size.
TB3 - 750 - Lug capable for three cable of 1/0 to 750 MCM size.
TB4 - 750 - Lug capable for four cable of 1/0 to 750 MCM size.
EXTENDED B/B - Terminal B/B extansion for field installation.
LEGENDS:
310
295
270
250
240
230
215
200
190
180
170
MODEL
NO
ASYB
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
230-3-60
380-3-60
460-3-60
(V-Ph-Hz)
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
EXTENDED
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
B/B
EXTENDED B/B
TB3 - 750
TB4 - 750
TB4 - 750
TB3 - 750
TB4 - 750
TB4 - 750
TB3 - 750
TB4 - 750
TB4 - 750
TB3 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB4 - 750
TB3 - 600
TB4 - 750
TB4 - 750
TB3 - 600
TB4 - 750
LUG SIZE
2
1
1
2
1
1
2
1
1
2
1
1
2
1
1
2
1
1
2
2
1
2
2
1
QTY per
phase
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
TB3 - 750
TB2 - 600
TB2 - 600
TB3 - 750
TB2 - 600
TB2 - 600
TB3 - 750
TB2 - 750
TB2 - 600
TB3 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB3 - 600
TB2 - 600
TB4 - 750
TB3 - 600
TB2 - 600
TB4 - 750
TB3 - 600
TB3 - 600
TB4 - 750
TB3 - 600
TB3 - 600
TB4 - 750
TB3 - 750
TB3 - 600
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
TB3 - 750
TB2 - 600
TB2 - 600
TB3 - 750
TB2 - 600
TB2 - 600
TB3 - 750
TB2 - 750
TB2 - 600
TB3 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB2 - 750
TB2 - 600
TB4 - 750
TB3 - 600
TB2 - 600
TB4 - 750
TB3 - 600
TB2 - 600
TB4 - 750
TB3 - 600
TB3 - 600
TB4 - 750
TB3 - 600
TB3 - 600
TB4 - 750
TB3 - 750
TB3 - 600
Note:
All this lugs can be requested separately from the unit.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Terminal Number 1 - First Main Power Field Terminal Point of the unit
Terminal Number 2 - Second Main Power Field Terminal Point of the unit ( This is avaible only for chiller with Dual Power Entry Point)
Terminal Number 3 - Control Power Supply, Factory wired, this can be done also in the field when required. This should be connected from bus separate from Terminal Number 1 and 2.
NA - Not Applicable.
TB2 - 600 - Lug capable for two cable of 2 to 600 MCM size.
TB3 - 600 - Lug capable for three cable of 2 to 600 MCM size.
TB2 - 750 - Lug capable for two cable of 1/0 to 750 MCM size.
TB3 - 750 - Lug capable for three cable of 1/0 to 750 MCM size.
TB4 - 750 - Lug capable for four cable of 1/0 to 750 MCM size.
EXTENDED B/B - Terminal B/B extansion for field installation.
LEGENDS:
590
560
540
500
475
450
420
400
375
350
330
Nominal
NOT AVAILABLE
UNIT DATA
Supply Voltage (3Phase)
NOT AVAILABLE
MODEL
NO
ASYB
NOT AVAILABLE
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
TABUK: Tabuk, Saudi Arabia Phone: (04) 423 2840 Fax: (04) 423 2912
GIZAN: Gizan 81888, Saudi Arabia Pone: (07) 321 3915 Fax: (07) 321 3919