Digital Motor Protection Relay
Digital Motor Protection Relay
Meta-MEC Series
Digital
Motor Protection Relay
General digital type motor protection relays using MCU(Micro Controller Unit)
-Real time processing and high precision
Multiple protection
Protection
Wiring
Over current
Under current
Stsll
Lock
Phase failure
Revers phase
Asymmetry
Grount fault
-S
DMP
-SZ
DMP
Screw type
-SI
DMP
Short circuit
-T
DMP
-TZ
DMP
-T
DMP
Tunnel type
M e t a - M E C
S E R I E S
Elegant design
High class product image
by the elegant design
Specifications of D-EMPR
Digital E M P R
DMP-S
Model No.
Wiring
Panel mount
Operation time
Protection
Over current
Phase failure
Reverse phase
Asymmetry
Stall
Lock
Under current
Ground fault
Short circuit (Note2)
Alarm
Current setting range (A)
Motor capacity
220~240V
(kW)
380~440V
Time setting Definate Delay in starting
range (sec) time
Delay in operating
Inverse time
Reset
Tolerance
Current
Time
Operating power (Note3)
Voltage
Frequency
Aux. contact OL
2-SPST
AL
SPST
Insulation resistance
Surge impulse voltage(IEC1000-4-5)
Fast transient burst(IEC1000-4-4)
Environment Temperature Operation
Storage
Humidity
Display
7-Segment
Bar-Graph
Mounting type
DMP-T
DMP06-S
DMP60-S
Screw type
DMP06-T
DMP60-T
Tunnel type
Unit or Extension(Note1)
Select either reverse time characteristics or definate time characteristics
According to the setting time
3 sec.
Within 0.1 sec.
5 sec.
5 sec.
Within 0.5 sec.
3 sec.
Within 0.05~1 sec. Selectable (0.05~1.0sec)
Within 50ms
Variable (60~110% of the setting current)
0.5~6
5~60
0.5~6
0.09~0.75
1.1~11
0.09~0.75
0.12~1.5
2.2~22
0.09~1.5
0~60sec
0~30sec
0~60sec
Manual reset
5%
5% (or0.5sec)
AC 190~250V
60Hz (50Hz)
3A/250Vac Resistive load
3A/250Vac Resistive load
Over DC 500V 100
1.250 6kV (Apply standard wave form)
2.5kV/5min
-25~70
-30~80
30~90% RH (No freezing)
3 phase current, cause of a fault
60~110% of real load current
35mm Din-rail/Panel
5~60
1.1~11
2.2~22
Note1) In extension type, the digital EMPR is calibrated with combining the display past and mainbody so, please cautious not to
combine the display part and main body with different part No.
Note2) Instantaneous short circuit protection is optional
Note3) Operational voltage of AC 110V and 50Hz is optional
Setting
M e t a - M E C
S E R I E S
Digital E M P R
1. C h e c k t h e o p e r a t i o n o f t h e T e s t / R e s e t b u t t o n
Check the operation when it is tripped
1) Check the wiring method (Refer to P13~14)
2) Press the Test/Reset button and then test is
displayed on the LED and the DMPR is tripped
3) Press the Test/Reset button again and then
it is reset
Note) In order to avoid the trip fault, the push
operation of Test/Reset is not avaiable
when a motor is rotating
R phase
Digital display
Bar graph
S phase
T phase
Display button
Test/Reset button
FUNC button
Sel button
Current knob
Time knob
2. Shift the mode by pressing the FUNC key and then select the values by press the Sel key
You can finish the setting by pressing the Sel key in the Sto mode
To protect the operation under the motor rotating, setting is allowed only in the test mode
FUNC
Sel
Functions
Note
Default is Off
Default is OffNote1)
Alarm function
(With pre-alarm function)
Default is Off
Default is Off
(Z type)
Stall function
Default is Off
Lock function
Default is Off
CT ratio
Default is 1:1
Phase failure
Default is On
to store
Store
Note2)
1) First shift to the test mode by press the Test/Resetbutton and then set the functions
by press the FUNCbutton
2) Each time you press the FUNCbutton, the function mode switches from 1.CHA mode to Sto mode.
When the mode that you want to change is displayed, push the Selbutton to select the value you want.
After you select the value, press the FUNCbutton to finish the settings and it displays the next mode
3) If no button is pressed in the selection mode, it remains in that mode
4) If you select the inverse time characteristics it skips the mode 2 (Definite O-time) and go to the
mode 3 (Reverse phase)
Setting
Digital E M P R
5.A Lt
On
1
0
Off
Normal
Alarm
Alert setting
value
Trip
Trip setting
value
M e t a - M E C
S E R I E S
R phase current
S phase current
Normal condition
T phase current
5A setting
6. Check the causes of the fault by look at the display unit (7-segment)
The causes of the fault is switched on and off for 0.5sec interval. If you press theDisplaybutton at this time,
display you can see the values and the causes of the fault
Overload
Turn on
ex)
Turn
on& off
Under current
Phase fail
Stall
Lock
Reverse phase
Ground fault
Short circuit
Dimensions
Digital E M P R
Type
Mounting dimensions
Dimensions
0.7kg
Aux. contact wire size
:below 8mm2
Torque : 0.5N
DMP-S
DMP-SZ
0.64kg
DMP-S
DMP-SZ
&
Extension
cable
Panel mounting
M e t a - M E C
Type
S E R I E S
Mounting dimensions
Dimensions
0.56kg
Wire size to penetrate a CT
:below 22mm2
DMP-T
DMP-TZ
0.5kg
DMP-T
DMP-TZ
&
Extension
cable
Panel mounting
DMP-S/T
Digital E M P R
DMP- S/ T
Over-current/Under current/Phase failure/Asymmetry
Stall/Lock/Instantaneous short circuit protection
Unit type or extension type is available
- Extension type:Remotely mounts the display unit
on the panel surface
3 phase ampere meter function:Check the 3 phase
current and setting value by press the display button
Select the inverse time or definite time
Easy to operate:Set the most function by the operation
button and knod
Display the causes of the fault and the values
Alarm setting:Load ratio is displayed up to setting current
Protect function
Over current
Depend on setting time
Selectable the inverse/definite
Phase loss
Within 3seconds
Over 70% of the rate of unbalance
Phase unbalance
Within 5seconds
Over 50% of the rate of unbalance
Phase reverse
Within 0.1seconds
Function enable
Stall
Within 5seconds
Over 180% of the setting current
Lock
Within 0.5seconds
Setting 200~900% of rated current
Under current
Within 3seconds
Setting 30~70% of rated current
Lock protection is operated after setting D-time in case of definite time type
Function selection
FUNC
1. CHA
2. dEF
3. r.P
4. Und
5 . A lt
6. S t l
7. Loc
8. Ct
9. P.F
Sto
Sel
Inv/dEF
0~30(S)
oFF/on
oFF/30~70(%)
oFF/60~110(%)
oFF/on
oFF/200~900(%)
1~120
on/oFF
Sto
Description
Operating characteristics setting(Inverse/definite time type)
Setting the operating time(In definite type)
Phase reverse enable
Under current enable and setting
Alerting enable and setting
Stall enable
Lock enable and setting
CT ratio setting
Phase fault enable
Store
Ratings
Model
Type
10
Wiring method
Panel mount
Operating characteristics
Alerting function
Current range(A)
DMP06-
DMP60-
Setting time
Definite Delay(D-T)
Operating(O-T)
Inverse
Reset type
Operating voltage
Voltage
Frequency
Aux. contacts
OL
2-SPST(95~98)
AL
SPST(07-08)
Indicate
7-segment
Bar-LED arrys
Mounting
D M P -S
Screw
D M P -T
Tunnel
Unit or Extension
Inverse/definite type
Variable between 60 and 110%
0.5~6
5~60
0~60seconds
0~30seconds
0~60seconds
Manual reset
AC 190~250V
60Hz (50Hz)
3A/250Vac resistive load
3A/250Vac resistive load
3-phase current value, fault cause
Load ratio (60~110%)
35mm Din-rail/Panel
M e t a - M E C
Wiring method
S E R I E S
1 Phase motor
Note1)
Operational
power
External CT combination
Note1) Please turn off the reverse phase function when it is used for 1 phase motor
11
DMP-SZ/TZ
Digital E M P R
DMP-SZ/ TZ
Over-current/Under current/Phase failure/Asymmetry
Stall/Lock/Ground-fault
Unit type or extension type is available
- Extension type:Remotely mounts the display unit
on the panel surface
3 phase ampere meter function:Check the 3 phase
current and setting value by press the display button
Select the inverse time or definite time
Easy to operate:Set the most function by the operation
button and knod
Display the causes of the fault and the values
Ground fault protect function is added
Protect function
Over current
Phase loss
Phase unbalance
Phase reverse
Stall
Lock
Under current
G r o u n d f a u l t (Note1)
Function selection
FUNC
1. CHA
2. dEF
3. r.P
4. Und
5. g-F
6. S t l
7. Loc
8. Ct
9. P.F
Sto
Sel
Inv/dEF
0~30(S)
oFF/on
oFF/30~70(%)
oFF/0.05~1.0(S)
oFF/on
oFF/200~900(%)
1~120
on/oFF
Sto
Description
Operating characteristics setting(Inverse/definite time type)
Setting the operating time(In definite type)
Phase reverse enable
Under current enable and setting
Ground fault enable and setting
Stall enable
Lock enable and setting
CT ratio setting
Phase fault enable
Store
Ratings
Model
Type
Operating characteristics
Alerting function
Current range(A)
Setting time
Operating voltage
Mounting
Wiring method
Panel mount
DMP06-
DMP60-
Definite Delay(D-T)
Operating(O-T)
Inverse
Reset type
voltage
Frequency
ZCT input (07-08)
OL, GR
2-SPST(95~98)
7-segment
Bar-LED arrays
DMP -SZ
Screw
DMP -TZ
Tunnel
Unit or Extension
Inverse/definite type
Variable between 60 and 110%
0.5~6
5~60
0~60seconds
0~30seconds
0~60seconds
Manual reset
AC 190~250V
60Hz (50Hz)
200mA/110mV(ZCT)30, 50, 65, 80
3A/250Vac resistive load
3-phase current value, fault cause
Load ratio (60~110%)
35mm Din-rail/Panel
M e t a - M E C
S E R I E S
Wiring method
External CT combination
13
Characteristics curve
Digital E M P R
Characteristics curve
14
Ordering
M e t a - M E C
S E R I E S
Digital E M P R
DMP06 - SZ 220
Option
Wiring method
Operational power
06
0.5~6A
Screw
- Standard
220
AC220V
60
5~60A
Tunnel
Z Ground fault
110
AC110V
Dip s/w
Sensitive current
(mA)
100
200
500
1000
1500
2000
2500
Type
D30, DMP-Z
D50, DMP-Z
D65, DMP-Z
D80, DMP-Z
Diameter(A)
30
50
65
80
Ratio
200mA/100mV
Weight(kg)
0.5
0.7
0.9
1.5
Model
LZT-030
LZT-050
LZT-065
LZT-080
Dimension
Unit (m/m)
Model
LZT-030
30
25
LZT-050
50
25
LZT-065
65
LZT-080
80
32
32
32
36
26
39
37
34
40
40
15
2003-09
Safety Instructions
For your safety, please read users manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair,
or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Any maintenance and inspection shall be performed by the personnel having
expertise concerned.