AT 0 Lab Report PDF
AT 0 Lab Report PDF
LAB SHEET
APPLIED THERMODYNAMICS
EME2146
TRIMESTER 2 (2014/2015)
Experiment 1:
Experiment 2:
Refrigeration
Cooling Tower
Note: Students are advised to read through this lab sheet before the experiment.
PROGRAMME OUTCOMES
PO
PO statement
PO1
PO2
PO3
PO4
PO5
PO6
PO7
PO8
PO9
PO10
PO11
PO12
PO13
LEARNING OUTCOMES
LO
LO statement
LO1
LO2
LO3
LO4
LO5
Experiment 1
Experiment 2
PO1
PO2
PO3
Experiment 1
Experiment 2
PO4
PO5
PO6
PO7
PO8
LO1
LO2
LO3
LO4
LO5
Introduction
Domestic refrigerators are commonly used in keeping food fresh, making ice, and etc. The
objective of this experiment is to familiarize us with the operation of a domestic refrigerator.
The basic operation of the unit is as follows. Pumped from a compressor, refrigerant flows
from the compressor through condensers, by which heat has dissipated due to the lower
temperature at the ambient. The refrigerant is cooled, and encounters changing of phase. The
refrigerant then flows through an expansion valve, by which the high pressure has relieved.
Due to the expansion, the temperature of the refrigerant is reduced. The cooled refrigerant
then flows through an evaporator due to the suction from the compressor, by which heat has
absorbed due to the higher temperature inside the freezer compartment. The refrigerant then
flows into the compressor.
A reversed Carnot cycle is used as a refrigeration cycle and its coefficient of performance
(COP) is used as a reference for actual refrigeration system. A reversed Carnot cycle has
isentropic compression and expansion processes and isothermal heat rejection and heat
extraction processes. The impracticalities associated with the reversed Carnot cycle can be
eliminated by vaporizing the refrigerant completely before it is compressed. It is also
practical to replace the turbine with throttling device since there will be very little work
output from the expansion process. The resulting cycle becomes the ideal model for vaporcompression refrigeration system. Refrigerant as saturated vapor at low pressure enters the
compressor and undergoes a reversible adiabatic compression process. Heat is rejected at
constant pressure process at the condenser. The refrigerant exits the condenser as saturated
liquid. An adiabatic expansion process follows, and the refrigerant is then evaporated at
constant pressure to complete the cycle.
The actual refrigeration cycle deviates from the ideal cycle primarily because of pressure
drops associated with fluid flow and heat transfer to or from the surrounding. There is some
drop in pressure as the refrigerant flows through the condenser and the evaporator. During the
compression process, there are irreversibilities due to heat transfer to or from surrounding.
The refrigerant entering the compressor will probably be superheated and the temperature of
the refrigerant leaving the condenser is lower than the saturated temperature. Refrigerating
efficiency is defined as the ratio of the COP of actual refrigeration cycle to the coefficient of
performance of the reversed Carnot cycle.
Data Recording
In this experiment, you are to collect data, in conjunction with the following combination
settings:
- freezer-compartment temperature setting at 0C
- freezer-compartment temperature setting at 5C
Apart from these, you may also require other data, in order to carry out the analyses in the
next section. You may assume the ambient temperature is constant during the experiment.
For each combination setting, record the Amp and Volt readings of the compressor, the
compressor suction and discharge pressure, and the following temperatures:
T1 , the refrigerant temperature at the compressor inlet
T2 , the refrigerant temperature at the compressor outlet
T3 , the refrigerant temperature at the condenser outlet
Introduction
Cooling towers are commonly encountered in power plants, large air-conditioning systems,
etc. The objective of this experiment is to familiarize us with the operation of a cooling
tower. For this purpose, a Prodit water cooling tower unit consisting of a multi-packed
column will be made use of. The basic operation of the unit is as follows. Pumped from a
tank, water flows through a heater, which simulates a heat exchanger in applications, and
reaches the top of the column, by which point its temperature has increased substantially due
to the heat transfer from the heater. The water is atomized, and the resulting droplets fall to
the bottom of the column, at which point the water temperature has dropped as a result of
heat transfer from the droplets to the air inside the column. From the bottom of the column,
the water then returns to the reservoir tank.
The heat transfer between the droplets and air inside the column is both conductive and
convective in nature. Additional cooling of the droplets is contributed by their evaporation.
As the cooling tower is a forced-draft type, there is fan installed at the top of the column a
suction fan, which provides an upward air flow inside the column and, therefore, further
cooling of the droplets. Finally, the column contains a vertical formation of inclined plates.
By slowing down the droplets, this formation increases their retention time inside the column
and, thus, effectively enhances their cooling.
Due to the evaporation of water inside the column, the water level in the tank will drop as the
operation of the cooling tower continues. To prevent this from happening, the water in the
tank will be replenished automatically once it reaches a preset level.
Data Recording
In this experiment, you are to collect data, in conjunction with the following combination
settings:
- heater setting H1, water-flow-rate setting W1
- heater setting H2, water-flow-rate setting W1
- heater setting H3, water-flow-rate setting W1
- heater setting H1, water-flow-rate setting W2
Apart from these, you also require other combination of settings, in order to carry out the
analyses in the next section.
For each combination setting, record the Amp and Volt readings of the heater, the water flow
rate, the average air velocity at the fan outlet and the following temperatures:
T1 , the water temperature at the tower outlet
T3 , the water temperature at the heater outlet
T5 , the water temperature at the tower inlet
T7 , the water temperature at the tank