0% found this document useful (0 votes)
76 views

Short Circuit Current

Short circuit currents occur when there is an abnormally low-impedance path for current to flow, bypassing the normal load impedance and allowing extremely high currents. There are symmetrical and asymmetrical fault currents. Symmetrical currents follow a sine wave, while asymmetrical currents have a decaying DC component added to the sine wave, causing a higher initial peak current. The ratio of reactance X to resistance R (X/R ratio) determines the magnitude of the asymmetrical current component, with higher X/R ratios producing larger asymmetrical faults. Short circuit currents can cause overheating, equipment damage, and magnetic forces on electrical components.

Uploaded by

uplbseles
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views

Short Circuit Current

Short circuit currents occur when there is an abnormally low-impedance path for current to flow, bypassing the normal load impedance and allowing extremely high currents. There are symmetrical and asymmetrical fault currents. Symmetrical currents follow a sine wave, while asymmetrical currents have a decaying DC component added to the sine wave, causing a higher initial peak current. The ratio of reactance X to resistance R (X/R ratio) determines the magnitude of the asymmetrical current component, with higher X/R ratios producing larger asymmetrical faults. Short circuit currents can cause overheating, equipment damage, and magnetic forces on electrical components.

Uploaded by

uplbseles
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

electrical-engineering-portal.

com

http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-1

An Overview Of Short Circuit Current (part 1)


Asif Eqbal

An Overview Of Short Circuit Current (part 1)

Basic concept
There are essentially four types of faults: three-phase, single line-to-ground, double line-to-ground, and line-to-line.
Each of these types of faults can result in different magnitudes of fault current.
In all types, however, there is a common element: an abnormally low-impedance path or shorted path for current to
flow, hence the name short circuit current. Such a condition can lead to extremely high currents.
By Ohms Law, voltage equals current times impedance (resistance) . Therefore, when the impedance becomes
very low and the voltage does not change, the current becomes very high. Large electrical currents produce a lot of
heat transfer, which increases the temperature of cables, transformers, etc.
The increase in temperature can cause insulation damage. These currents also produce high magnetic forces,
which can actually bend buses in switchgear.
High fault currents cause magnetic forces that are proportional to the square of the fault current.

Mathematical background, X/R ratio and type of fault current


The treatment of electrical faults should be carried out as a function of time, from the start of the event at time t = 0+
until stable conditions are reached, and therefore it is necessary to use differential equations when calculating these
currents.
In order to illustrate the transient nature of the current, consider an RL circuit as a simplified equivalent of the
circuits in electricity distribution networks.
This simplification is important because all the system equipment must be modeled in some way in order to quantify
the transient values which can occur during the fault condition.
For the circuit shown in Figure, the mathematical expression which defines the behavior of the current is:
e(t) = L di + Ri(t)
This is a differential equation with constant coefficients, of which
the solution is in two parts:
ia (t): ih (t) + ip(t)
Where:
ih(t) is the solution of the homogeneous equation corresponding to the
transient period.
ip(t) is the solution to the particular equation corresponding to the steadystate period.
By the use of differential equation theory, the complete solution can be
determined and expressed in the following form:

RL circuit as a simplified equivalent of the circuits in


electricity-distribution networks

Where:
the closing angle which defines the point on
the source sinusoidal voltage when the fault
occurs
= tan-1(L/R) or = tan-1(X/R)
The second term in the equation for fault current is
recognized as the DC component of the current, and has an initial maximum value when:
- = / 2, and zero value when = .

Notes:
Here we introduce the concept of X/R ratio. We can very well see that since L = XL or simply X hence DC
component of fault current to large extent depends upon = tan-1(X/R) or simply X/R ratio.
The X/R ratio is important because it determines the peak asymmetrical fault current .

In X/R ratio when X equals zero, there is only symmetrical current with no DC component. With R equals
zero, the DC component would never decay. One can say there will always be both resistance and reactive
components in the system.
The resistance and reactance of a circuit establishes a power factor.
The power factor (p.f.) is given by the following equation: p.f. = cos(tan -1(X/R)) this equation means that the
power factor and X/R ratio are related.
Therefore, system power factor and system X/R ratio are different ways of saying the same thing.
Please note that as power factor decreases, the X/R ratio increases.
It is impossible to predict a that is at what point the fault will be applied or take place on the sinusoidal cycle and
therefore it is not possible to determine exactly what magnitude the DC component will reach.

Symmetrical fault current


If in a circuit mainly containing reactance a short circuit occurs at the peak of the voltage wave, the short-circuit
current would start at zero and trace a sine wave which would be symmetrical about the zero axis.
This is known as a symmetrical short circuit current.

Asymmetrical fault current


Right after a fault occurs, the current waveform is no longer a sine wave.
Instead, it can be represented by the sum of a sine wave and a decaying exponential . Figure below illustrates this
phenomenon. Please note that the decaying exponential added to the sine wave causes the current to reach a much
larger value than that of the sine wave alone.
The waveform that equals the sum of the sine wave and the decaying exponential is called the asymmetrical current
because the waveform does not have symmetry above and below the time axis.
The sine wave alone is called the symmetrical current because it does have symmetry above and below the time axis.

Sine wave, decaying exponential and their sum

Hence we can define asymmetrical fault current in the following way: If, in a circuit containing only reactance, the
short circuit occurs at any point at the peak of the voltage wave, there will be some offset of the current.
The amount of offset depends upon the point on the voltage wave at which the short circuit occurs.
This is known as asymmetrical short circuit current. Maximum asymmetry occurs when short circuit takes place
when voltage is zero.
Asymmetrical fault remains only for few cycles after which it becomes symmetrical fault . Decay of asymmetrical
component depends on the value of X/R. More the value of R, faster is the decay of asymmetrical fault current.
Magnitude of asymmetrical fault current is more than that of symmetrical fault current.
If the short circuit current does not include DC component it is called symmetrical short circuit current. If the short
circuit current contains DC component it is called as asymmetrical component.
Figure above represents the short circuit current with and without DC component.
Will be continued soon

About Author //
Asif Eqbal
Asif Eqbal - Bachelor of Engineering in Electrical & Electronics engineering, from Manipal
University, (Karnataka), India in 2006. Presently involved in the design of EHV outdoor
substation and coal fired thermal power plants for more than seven years. Motto of joining
EEP as a contributor is to share my little engineering experience and help the budding
engineers in bridging the conspicuous gap between academics and Industrial practice. If
you have knowledge, let others light their candles with it, so that people who are genuinely
interested in helping one another develop new capacities for action; it is about creating
timeless learning processes".

RSS Feed for Comments

8 Comments
1.
An example of calculating transformer size and voltage drop due to starting of large motor | EEP
May 12, 2014
[] Short circuit current at TC secondary = 1203 / 5.75 = 20919 Amp []
(reply)
2.
exequiel c. comiling
Jan 20, 2014
Thanks good explaination about faults
(reply)
3.
Electrical Thumb Rules You MUST Follow (Part 4) | EEP
Nov 15, 2013
[...] (1 to 3 Sec)220 VUp to 6 KVA6 KA (1 to 3 Sec)Go back to Rules 2. Substation Capacity and Short Circuit
Current CapacityAs per Central Electricity AuthorityVoltage Sub Station CapacityShort Circuit Current 765
KV4500 [...]
(reply)
4.
sallu25
Mar 30, 2013
Asif,
Good article on this subject.
The DC component is a decaying exponential, it must be a function of time. I just wanted to point out that DC
component in the differential equation for i(t) is missing the variable t in the exponential.
(reply)
5.
Sources and Contributors To Short Circuit Current | EEP
Mar 15, 2013
[...] of the electrical appliance loads limit the current flow to relatively small values, but a short circuit path
bypasses the normal current-limiting load impedance.The result is excessively high current [...]
(reply)

6.
Edvard
Feb 27, 2013
Thanks Asif, very good explanation. Looking forward to following parts.
(reply)
7.
Md Ebrahim Shah
Feb 27, 2013
sometimes short circuits causes for high temperature or heat then insulation loses and short path
made.
(reply)
8.
An Overview Of Short Circuit Current (part 2) | EEP
Feb 27, 2013
[...] (on photo Main Switchboard by jayreynoldsisreal @Flickr) Continued from previous technical article: An
Overview Of Short Circuit Current (part 1) ReactanceSub transient reactance Xd is the apparent reactance of
the stator winding at the [...]
(reply)
RSS Feed for Comments

Leave a Comment
Tell us what you're thinking... we care about your opinion!
and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!

six + 1 =

You might also like