Types of Neutral Earthing in Power Distribution
Types of Neutral Earthing in Power Distribution
2.
3.
4.
5.
6.
7.
1.
2.
3.
2.
4.
5.
In ungrounded system there is no internal connection between the conductors and earth. However, as system, a
capacitive coupling exists between the system conductors and the adjacent grounded surfaces. Consequently,
the ungrounded system is, in reality, a capacitive grounded system by virtue of the distributed capacitance.
Under normal operating conditions, this distributed capacitance causes no problems. In fact, it is beneficial
because it establishes, in effect, a neutral point for the system; As a result, the phase conductors are stressed at
only line-to-neutral voltage above ground.
But problems can rise in ground fault conditions. A ground fault on one line results in full line-to-line voltage
appearing throughout the system. Thus, a voltage 1.73 times the normal voltage is present on all insulation in the
system. This situation can often cause failures in older motors and transformers, due to insulation breakdown.
Advantage:
1.
After the first ground fault, assuming it remains as a single fault, the circuit may continue in operation, permitting
continued production until a convenient shut down for maintenance can be scheduled.
Disadvantages:
1.
The interaction between the faulted system and its distributed capacitance may cause transient over-voltages
(several times normal) to appear from line to ground during normal switching of a circuit having a line-to ground
fault (short). These over voltages may cause insulation failures at points other than the original fault.
2.
A second fault on another phase may occur before the first fault can be cleared. This can result in very high lineto-line fault currents, equipment damage and disruption of both circuits.
3.
4.
Complicate for locating fault(s), involving a tedious process of trial and error: first isolating the correct feeder, then
the branch, and finally, the equipment at fault. The result is unnecessarily lengthy and expensive down downtime.
Solidly grounded systems are usually used in low voltage applications at 600 volts or less.
Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded
system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase
fault current. However, if the reactance of the generator or transformer is too great, the problem of transient over
voltages will not be solved.
While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of
faults, they lack the current limiting ability of resistance grounding and the extra protection this provides.
To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend
from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain
very low impedance to ground faults so that a relatively high fault current will flow thus insuring that circuit
breakers or fuses will clear the fault quickly and therefore minimize damage. It also greatly reduces the shock
hazard to personnel
If the system is not solidly grounded, the neutral point of the system would float with respect to ground as a
function of load subjecting the line-to-neutral loads to voltage unbalances and instability.
The single-phase earth fault current in a solidly earthed system may exceed the three phase fault current. The
magnitude of the current depends on the fault location and the fault resistance. One way to reduce the earth fault
current is to leave some of the transformer neutrals unearthed.
Advantage:
1.
The main advantage of solidly earthed systems is low over voltages, which makes the earthing design common at
high voltage levels (HV).
Disadvantage:
1.
This system involves all the drawbacks and hazards of high earth fault current: maximum damage and
disturbances.
2.
3.
The danger for personnel is high during the fault since the touch voltages created are high.
Applications:
1.
2.
3.
Use of the neutral conductor as a protective conductor with systematic earthing at each transmission pole.
4.
Resistance grounding has been used in three-phase industrial applications for many years and it resolves many
of the problems associated with solidly grounded and ungrounded systems.
Resistance Grounding Systems limits the phase-to-ground fault currents. The reasons for limiting the Phase to
ground Fault current by resistance grounding are:
1.
To reduce burning and melting effects in faulted electrical equipment like switchgear, transformers, cables, and
rotating machines.
2.
3.
4.
5.
6.
7.
Grounding Resistors are generally connected between ground and neutral of transformers, generators and
grounding transformers to limit maximum fault current as per Ohms Law to a value which will not damage
the equipment in the power system and allow sufficient flow of fault current to detect and operate Earth
protective relays to clear the fault. Although it is possible to limit fault currents with high resistance Neutral
grounding Resistors, earth short circuit currents can be extremely reduced. As a result of this fact, protection
devices may not sense the fault.
Therefore, it is the most common application to limit single phase fault currents with low resistance Neutral
Grounding Resistors to approximately rated current of transformer and / or generator.
In addition, limiting fault currents to predetermined maximum values permits the designer to selectively coordinate
the operation of protective devices, which minimizes system disruption and allows for quick location of the fault.
Ground fault current flowing through either type of resistor when a single phase faults to ground will increase the
phase-to-ground voltage of the remaining two phases. As a result, conductor insulation and surge arrestor
ratings must be based on line-to-line voltage. This temporary increase in phase-to-ground voltage should also
be considered when selecting two and three pole breakers installed on resistance grounded low voltage systems.
The increase in phase-to-ground voltage associated with ground fault currents also precludes the connection of
line-to-neutral loads directly to the system. If line-to neutral loads (such as 277V lighting) are present, they must
be served by a solidly grounded system. This can be achieved with an isolation transformer that has a three-
Neither of these grounding systems (low or high resistance) reduces arc-flash hazards associated with phase-tophase faults, but both systems significantly reduce or essentially eliminate the arc-flash hazards associated with
phase-to-ground faults. Both types of grounding systems limit mechanical stresses and reduce thermal damage
to electrical equipment, circuits, and apparatus carrying faulted current.
The difference between Low Resistance Grounding and High Resistance Grounding is a matter of perception
and, therefore, is not well defined. Generally speaking high-resistance grounding refers to a system in
which the NGR let-through current is less than 50 to 100 A. Low resistance grounding indicates that NGR
current would be above 100 A.
A better distinction between the two levels might be alarm only and tripping. An alarm-only system continues to
operate with a single ground fault on the system for an unspecified amount of time. In a tripping system a ground
fault is automatically removed by protective relaying and circuit interrupting devices. Alarm-only systems usually
limit NGR current to 10 A or less.
1.
1.
2.
2.
Initial Current: The initial current which will flow through the resistor with rated voltage applied.
3.
3.
Time: The on time for which the resistor can operate without exceeding the allowable temperature rise.
Low Resistance Grounding is used for large electrical systems where there is a high investment in capital
equipment or prolonged loss of service of equipment has a significant economic impact and it is not commonly
used in low voltage systems because the limited ground fault current is too low to reliably operate breaker trip
units or fuses. This makes system selectivity hard to achieve. Moreover, low resistance grounded systems are not
suitable for 4-wire loads and hence have not been used in commercial market applications
A resistor is connected from the system neutral point to ground and generally sized to permit only 200A to 1200
amps of ground fault current to flow. Enough current must flow such that protective devices can detect the faulted
circuit and trip it off-line but not so much current as to create major damage at the fault point.
Since the grounding impedance is in the form of resistance, any transient over voltages are quickly damped out
and the whole transient overvoltage phenomena is no longer applicable. Although theoretically possible to be
applied in low voltage systems (e.g. 480V),significant amount of the system voltage dropped across the
grounding resistor, there is not enough voltage across the arc forcing current to flow, for the fault to be reliably
detected. For this reason, low resistance grounding is not used for low voltage systems (under 1000 volts
line to-line).
Advantages:
1.
2.
Reduces arcing current and, to some extent, limits arc-flash hazards associated with phase-to-ground arcing
current conditions only.
3.
May limit the mechanical damage and thermal damage to shorted transformer and rotating machinery windings.
Disadvantages:
1.
2.
3.
4.
Conductor insulation and surge arrestors must be rated based on the line to-line voltage. Phase-to-neutral loads
must be served through an isolation transformer.
Used: Up to 400 amps for 10 sec are commonly found on medium voltage systems.
High resistance grounding is almost identical to low resistance grounding except that the ground fault current
magnitude is typically limited to 10 amperes or less. High resistance grounding accomplishes two things.
The first is that the ground fault current magnitude is sufficiently low enough such that no appreciable
damage is done at the fault point. This means that the faulted circuit need not be tripped off-line when the fault
first occurs. Means that once a fault does occur, we do not know where the fault is located. In this respect, it
performs just like an ungrounded system.
The second point is it can control the transient overvoltage phenomenon present on ungrounded systems if
engineered properly.
Under earth fault conditions, the resistance must dominate over the system charging capacitance but not to the
point of permitting excessive current to flow and thereby excluding continuous operation
High Resistance Grounding (HRG) systems limit the fault current when one phase of the system shorts or arcs to
ground, but at lower levels than low resistance systems.
In the event that a ground fault condition exists, the HRG typically limits the current to 5-10A.
HRGs are continuous current rated, so the description of a particular unit does not include a time rating. Unlike
NGRs, ground fault current flowing through a HRG is usually not of significant magnitude to result in the
operation of an over current device. Since the ground fault current is not interrupted, a ground fault detection
system must be installed.
These systems include a bypass contactor tapped across a portion of the resistor that pulses (periodically opens
and closes). When the contactor is open, ground fault current flows through the entire resistor. When the
contactor is closed a portion of the resistor is bypassed resulting in slightly lower resistance and slightly higher
ground fault current.
To avoid transient over-voltages, an HRG resistor must be sized so that the amount of ground fault
currentthe unit will allow to flow exceeds the electrical systems charging current. As a rule of thumb, charging
current is estimated at 1A per 2000KVA of system capacity for low voltage systems and 2A per 2000KVA of
system capacity at 4.16kV.
These estimated charging currents increase if surge suppressors are present. Each set of suppressors installed
on a low voltage system results in approximately 0.5A of additional charging current and each set of suppressors
installed on a 4.16kV system adds 1.5A of additional charging current.
A system with 3000KVA of capacity at 480 volts would have an estimated charging current of 1.5A.Add one set
of surge suppressors and the total charging current increases by 0.5A to 2.0A. A standard 5A resistor could be
used on this system. Most resistor manufacturers publish detailed estimation tables that can be used to more
closely estimate an electrical systems charging current.
Advantages:
1.
Enables high impedance fault detection in systems with weak capacitive connection to earth
2.
3.
The neutral point resistance can be chosen to limit the possible over voltage transients to 2.5 times the
fundamental frequency maximum voltage.
4.
5.
Reduces arcing current and essentially eliminates arc-flash hazards associated with phase-to-ground arcing
current conditions only.
6.
Will eliminate the mechanical damage and may limit thermal damage to shorted transformer and rotating
machinery windings.
7.
Prevents operation of over current devices until the fault can be located (when only one phase faults to ground).
8.
May be utilized on low voltage systems or medium voltage systems up to 5kV. IEEE Standard 141-1993 states
that high resistance grounding should be restricted to 5kV class or lower systems with charging currents of about
5.5A or less and should not be attempted on 15kV systems, unless proper grounding relaying is employed.
9.
Conductor insulation and surge arrestors must be rated based on the line to-line voltage. Phase-to-neutral loads
must be served through an isolation transformer.
Disadvantages:
1.
Generates extensive earth fault currents when combined with strong or moderate capacitive connection to earth
Cost involved.
2.
Requires a ground fault detection system to notify the facility engineer that a ground fault condition has occurred.
Adding inductive reactance from the system neutral point to ground is an easy method of limiting the available
ground fault from something near the maximum 3 phase short circuit capacity (thousands of amperes) to a
relatively low value (200 to 800 amperes).
To limit the reactive part of the earth fault current in a power system a neutral point reactor can be connected
between the transformer neutral and the station earthing system.
1.
Inductive reactance.
2.
The current generated by the reactance during an earth fault approximately compensates the capacitive
component of the single phase earth fault current, is called a resonant earthed system.
The system is hardly ever exactly tuned, i.e. the reactive current does not exactly equal the capacitive earth fault
current of the system.
A system in which the inductive current is slightly larger than the capacitive earth fault current is over
compensated. A system in which the induced earth fault current is slightly smaller than the capacitive earth fault
However, experience indicated that this inductive reactance to ground resonates with the system shunt
capacitance to ground under arcing ground fault conditions and creates very high transient over voltages on the
system.
To control the transient over voltages, the design must permit at least 60% of the 3 phase short circuit current to
flow underground fault conditions.
Example. A 6000 amp grounding reactor for a system having 10,000 amps 3 phase short circuit capacity
available. Due to the high magnitude of ground fault current required to control transient over voltages,
inductance grounding is rarely used within industry.
Petersen Coils:
A Petersen Coil is connected between the neutral point of the system and earth, and is rated so that the
capacitive current in the earth fault is compensated by an inductive current passed by the Petersen Coil. A
small residual current will remain, but this is so small that any arc between the faulted phase and earth will not be
maintained and the fault will extinguish. Minor earth faults such as a broken pin insulator, could be held on the
system without the supply being interrupted. Transient faults would not result in supply interruptions.
Although the standard Peterson coil does not compensate the entire earth fault current in a network due to the
presence of resistive losses in the lines and coil, it is now possible to apply residual current compensation by
injecting an additional 180 out of phase current into the neutral via the Peterson coil. The fault current is thereby
reduced to practically zero. Such systems are known as Resonant earthing with residual compensation, and can
be considered as a special case of reactive earthing.
Resonant earthing can reduce EPR to a safe level. This is because the Petersen coil can often effectively act as a
high impedance NER, which will substantially reduce any earth fault currents, and hence also any corresponding
EPR hazards (e.g. touch voltages, step voltages and transferred voltages, including any EPR hazards impressed
onto nearby telecommunication networks).
Advantages:
1.
Small reactive earth fault current independent of the phase to earth capacitance of the system.
2.
Disadvantages:
1.
2.
For cases where there is no neutral point available for Neutral Earthing (e.g. for a delta winding), an earthing
transformer may be used to provide a return path for single phase fault currents
In such cases the impedance of the earthing transformer may be sufficient to act as effective earthing impedance.
Additional impedance can be added in series if required. A special zig-zag transformer is sometimes used for
earthing delta windings to provide a low zero-sequence impedance and high positive and negative sequence
impedance to fault currents.
Conclusion:
Resistance Grounding Systems have many advantages over solidly grounded systems including arc-flash hazard
reduction, limiting mechanical and thermal damage associated with faults, and controlling transient over voltages.
High resistance grounding systems may also be employed to maintain service continuity and assist with locating
the source of a fault.
When designing a system with resistors, the design/consulting engineer must consider the specific requirements
for conductor insulation ratings, surge arrestor ratings, breaker single-pole duty ratings, and method of serving
phase-to-neutral loads.
Un grounded
Solid
Grounded
Low Resistance
Grounded
High Resistance
Grounded
Immunity to
Transient Over
voltages
Worse
Good
Good
Best
73% Increase in
Voltage Stress
Under Line-toGround Fault
Condition
Poor
Best
Good
Poor
Equipment Protected
Worse
Poor
Better
Best
Safety to Personnel
Worse
Better
Good
Best
Service Reliability
Worse
Good
Better
Best
Maintenance Cost
Worse
Good
Better
Best
Ease of Locating
First Ground Fault
Worse
Good
Better
Best
Permits Designer to
CoordinateProtective
Devices
Not Possible
Good
Better
Best
Reduction in
Frequency of Faults
Worse
Better
Good
Best
Lighting Arrestor
Ungroundedneutral
type
Groundedneutraltype
Ungroundedneutral
type
Ungroundedneutral
type
Less than 1%
Varies,
may be
100% or
greater
5 to 20%
Less than 1%
IEEE Standard 141-1993, Recommended Practice for Electrical Power Distribution for Industrial Plants