Transformer Protection and Control RET615
Transformer Protection and Control RET615
Transformer Protection
RET615 ANSI
Product Version 4.0
1MAC204375-PG Rev. B
Issued: 04.15.2011
Contents
1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
17 Access control . . . . . . . . . . . . . . . . . . . . . . . . 16
2 Standard configurations . . . . . . . . . . . . . . . . 4 - 5
3 Protection functions . . . . . . . . . . . . . . . . . . . 6 - 7
19 Communications . . . . . . . . . . . . . . . . . . 17 - 19
4 Application . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 11
20 Technical data . . . . . . . . . . . . . . . . . . . . 20 - 43
21 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6 Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
22 Mounting methods . . . . . . . . . . . . . . . . . . . . . 45
7 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . 14
9 Events recorder . . . . . . . . . . . . . . . . . . . . . . . . 14
10 Recorded data . . . . . . . . . . . . . . . . . . . . . . . . 14
26 Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 - 49
27 Terminal diagrams . . . . . . . . . . . . . . . . . 49 - 54
28 Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
29 References . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
14 Trip-circuit monitoring . . . . . . . . . . . . . . . . . . 15
15 Self-diagnostics . . . . . . . . . . . . . . . . . . . . . . . 15
32 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Inc.
ABB Inc. assumes no responsibility for any errors that may appear in this document.
Copyright 2011 ABB
All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
1. Description
The RET615 is a dedicated transformer protection and
control relay for power transformers, unit and step-up
transformers including power generator-transformer
blocks in utility and industry power distribution systems.
RET615 is a member of ABBs Relion product family
and a part of its 615 protection and control product
series. The 615 series relays are characterized by their
compactness and withdrawable design. Engineered
from the ground up, the 615 series has been designed to
unleash the full potential of the IEC 61850 standard for
communication and interoperability between substation
automation devices.
Unique RET615 ANSI features
Six setting groups
Drawout design
Sensitive differential protection for turn-to-turn faults
Restricted earth fault (REF) protection
Overexcitation (V/Hz) protection
High-speed (< 1 ms) outputs
Arc flash detection (AFD)
Thermal overload protection of transformer
Ring-lug terminals for all inputs and outputs
Large LCD screen with clearly visible font
Environmentally friendly design with RoHS
compliance
Application
The RET615 is the ultimate protection and control
relay for two-winding power transformers and power
generator-transformer blocks. It can be applied for
protection and control of the most commonly used
power transformer combinations of delta and wye
(grounded or ungrounded) windings. Flexible order
coding allows for choosing current-only or currentand-voltage configurations to best fit your transformer
application needs.
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
2. Standard
configurations
The RET615 relay main application is protection,
control, metering and monitoring of two-winding power
transformers and offers two standard configurations
whose relay functions and features are based on the
analog inputs ordered for each configuration. See Tables
1 and 2 for details.
One configuration comprises only current analog inputs
useful in cost-effective two-winding power transformer
protection, control and monitoring in industrial
Current-based protection and control for a two-winding transformer and two breakers.
Current-based and voltage-based (LV- or HV-side) protection and control for a two-winding transformer and two
breakers.
Current-based and voltage-based (LV- or HV-side) protection and control with RTDs for a two-winding
transformer and two breakers.
Current-based and voltage-based (LV- and HV-side) protection and control for a two-winding transformer and
two breakers.
Functional
application
A B C D
87T, 87H
67P
Ground overcurrents
51G, 50G
67N
49T (1)
Undercurrent (Winding 1)
37 (1)
REF (2)
46 (1)
46 (2)
81LSH
81
Overexcitation
24
38
Phase undervoltage
27
Included = , Optional =
Protection
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Phase overvoltage
59
47
Ground overvoltage
59G
Neutral overvoltage
59N
50BF, 50NBF
86/94-1, 86/94-2
52 (1), 52(2)
TCM
Fuse failure
60
84T
CTSRCTF
Ground current
IG
Control
Circuit breaker control1)
Monitoring and supervision
Trip circuit monitoring
1)
Measurement
Three-phase voltages
VA, VB, VC
Sequence voltages
V1, V2, V0
Ground voltage
VG
P, E, and PF
100Base-FX Ethernet(LC)
100Base-TX and -FX Ethernet (1 LC, 2 RJ-45) + serial glass fiber (ST)
SER
Fault recorder
FLR
DFR
1)
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
3. Protection functions
51P
50P-1
50P-2
49T
37
(1)
51P
50
BF
51N
52
(1)
50P-2
50N-1
50N-2
51N
46
52
(1)
50N
BF
49T
37
50
BF
46
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
24-1
51G
50G-1
50G-2
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
Y
51G
52
(2)
(2)
50G-1
50G-2
AFD11
AFD11
AFD11
51N
50N-1
50N-2
REF
87T
(Low Z)
52
(2)
50N
BF
(2)
REF
(Low Z)
50N-2
24-2
51P
50P-1
50P-2
46
87T
50N
BF
50
BF
3
50
BF
67/
51P
51P
50P-1
50P-2
27
59
47
60
46
(2)
1
50P-1
(1)
or
59G
59N
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
or
(1)
27
59
47
24-1
24-2
67/
51P
51P
50P-1
50P-2
49T
38
-1
60
38
-2
(1)
67/
51N
52
(1)
3
59N
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
51P
50P-1
50P-2
37
51N
52
(1)
59G
49T
37
50
BF
46
81LSH
-2
24-1
(1)
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
51G
50G-1
50G-2
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
Y
52
(2)
AFD11
AFD11
AFD11
51N
50N-1
50N-2
(2)
3
REF
87T
(Low Z)
52
(2)
50N
BF
(2)
REF
(Low Z)
50N-2
24-2
50N
BF
50
BF
3
51P
50P-1
50P-2
50
BF
46
or
(2)
1
or
67/
51P
51P
50P-1
50P-2
27
59
47
60
46
(1)
87T
24-1
24-2
67/
51P
51P
50P-1
50P-2
49T
or
(1)
59
59N
27
59G
60
27
59
47
24-1
24-2
67/
51P
51P
50P-1
50P-2
49T
60
(1)
67/
51N
52
(1)
3
59N
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
(1)
59N
67/
51N
37
52
(1)
59G
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
37
Y
52
(2)
AFD11
AFD11
AFD11
51N
50N-1
50N-2
(2)
3
REF
87T
(Low Z)
52
(2)
50N
BF
(2)
REF
87T
(Low Z)
50N-2
50N
BF
50
BF
3
51P
50P-1
50P-2
46
50
BF
3
38
-1
38
-2
3
(2)
1
67/
51P
51P
50P-1
50P-2
27
59
47
60
46
or
59N
1
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
4. Application
The RET615 provides main protection for two-winding
power transformers and power generator-transformer
blocks. There are two standard configurations offering
comprehensive protection functions for detection
of faults within the transformer and within its zone
of protection. Configuration A offers a current-only
solution for cost-effective protection, control, measuring
and recording of two-winding transformers with
Ethernet communications. Configuration B includes
voltage inputs for more comprehensive transformer
protection and control with voltage protection against
Table 3. Programmable power transformer winding configurations available per a) winding 1 and b) winding 2
a) Winding 1 configuration type
Y: WYE
YN: WYE-GROUNDED
yn:
wye-grounded
D:
DELTA
d:
delta
Z:
ZIG ZAG
z:
zig zag
zn:
zig zag-grounded
30
60
120
150
180
210
240
10
300
11
330
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
or
(1)
(1)
27
59
47
24-1
24-2
67/
51P
51P
50P-1
50P-2
49T
52
(1)
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
Y
52
(2)
(2)
60
3
59N
67/
51N
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
(1)
52
(1)
Y
87T
52
(2)
50N
BF
(2)
50
BF
51P
50P-1
27
24-2
67/
51P
51P
50P-1
50P-2
49T
60
59N
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
37
REF
87T
(Low Z)
50N-2
50N
BF
50
BF
46
50P-2
59
47
60
3
59N
(2)
1
67/
51P
51P
50P-1
50P-2
27
59
47
60
46
(1)
27
59
47
24-1
24-2
67/
51P
51P
50P-1
50P-2
49T
52
(1)
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
or
60
3
59N
67/
51N
(1)
59N
or
or
(1)
24-1
(2)
47
or
59
REF
3
67/
51P
27
67/
51N
37
(Low Z)
50N-2
or
(1)
(1)
27
59
47
24-1
24-2
67/
51P
51P
50P-1
50P-2
49T
59N
67/
51N
37
52
(1)
60
50
BF
46
51N
50N-1
50N-2
50N
BF
81-1
81-2
81LSH
-1
81LSH
-2
51G
50G-1
50G-2
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
37
52
(2)
(2)
AFD11
AFD11
AFD11
67/
51N
51N
50N-1
REF
87T
(Low Z)
50N-2
52
(2)
50N
BF
(2)
50
BF
3
67/
51P
51P
50P-1
50P-2
50N
BF
50
BF
46
27
59
47
60
3
59N
(2)
1
50N-2
67/
51P
51P
50P-1
50P-2
27
59
47
60
46
(2)
87T
or
REF
(Low Z)
or
59N
1
Figure 10. RET615 protection and control of a delta, zig zaggrounded power transformer.
9
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
REF
615
REF
615
52
52
RET
615
REF
615
a)
RET
615
REF
615
b)
52
52
REF
615
REF
615
52
REM
615
52
F1
REM
615
52
52
R
T
D
M1
Fn
IEC 61850
R
T
D
Mn
IEC 61850
Figure 11. High-speed bus protection with the RET615 using IEC61850 in a) utility applications and b) industrial applications.
REF
615
REF
615
52
52
RET
615
RET
615
REF
615
REF
615
52
52
T
REF
615
REF
615
52
52
DG
REF
615
52
DG
F1
Fn
IEC 61850
REF
615
52
DG
F1
DG
Fn
IEC 61850
Figure 12. Open (cold) high-speed bus transfer with the RET615 and IEC 61850 GOOSE messaging.
10
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
REF
615
REF
615
52
52
RET
615
RET
615
REF
615
REF
615
52
52
T
REF
615
REF
615
52
52
DG
F1
52
DG
Fn
IEC 61850
REF
615
REF
615
52
DG
F1
DG
Fn
IEC 61850
Figure 13. Closed (hot) high-speed bus transfer with the RET615 and IEC 61850 GOOSE messaging.
ABB
11
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
5. Supported ABB
solutions
ABBs 615 series protection and control relays together
with the COM600 Station Automation device constitute
a genuine IEC 61850 solution for reliable power
distribution in utility and industrial power systems.
To facilitate and streamline the system engineering
ABBs relays are supplied with Connectivity Packages
containing a compilation of software and relay-specific
information including single-line diagram templates,
a full relay data model including event and parameter
lists. By utilizing the Connectivity Packages the relays
can be readily configured via the PCM600 Protection
and Control Relay Manager and integrated with
the COM600 Station Automation device or the
MicroSCADA Pro network control and management
system.
The 615 series relays offer native support for the IEC
61850 standard also including horizontal GOOSE
messaging. Compared with traditional hard-wired interdevice signaling, peer-to-peer communication over a
switched Ethernet LAN offers an advanced and versatile
platform for power system protection. Fast software-
Version
3.4 or later
MicroSCADA Pro
9.3 or later
12
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
ABB
MicroSCADA
IEC 60870-5-104
COM600
Web HMI
COM600
Web HMI
COM600
COM600
Ethernet switch
Peer-to-peer
GOOSE communication
Ethernet switch
PCM600
Peer-to-peer
GOOSE communication
IEC 61850-8-1
PCM600
IEC 61850-8-1
Binary signal
transfer
REF615
RET615
RED615
Fibre optic LD
communication
RED615
RET615
REF615
Figure 14. Utility distribution network example using 615 series relays, Station Automation COM600 and MicroSCADA Pro
ABB
System 800xA
OPC
COM600
Web HMI
COM600
Web HMI
COM600
COM600
Ethernet switch
Peer-to-peer
GOOSE communication
PCM600
Ethernet switch
IEC 61850-8-1
Peer-to-peer
GOOSE communication
PCM600
IEC 61850-8-1
Binary signal
transfer
REF615
RET615
REM615
RED615
Fibre optic LD
communication
RED615
REM615
RET615
REF615
Figure 15. Industrial distribution network example using 615 series relays, Station Automation COM600 and System 800xA
ABB
13
Transformer Protection
RET615 ANSI
Product Version 4.0
6. Control
The relay offers status and control of two breakers with
a set of push-buttons on the front panel local human
machine interface (LHMI) for opening and closing a
breaker. Interlocking schemes required by the application
are configured with the signal matrix in PCM600.
7. Measurements
The RET615 continuously measures the winding-1
high-voltage (HV) side and winding-2 low-voltage (LV)
sides phase currents and calculated neutral currents of
the protected transformer. Where an applicable ground
neutral CT input is connected, measured ground current
is available. With VT inputs options, voltage, power and
energy (single-phase and three-phase quantities), power
factor and frequency measurements and minimum and
maximum demand watts and vars are available.
In addition, the relay calculates the demand and
minimum and maximum demand currents over a userselectable pre-set time frame plus additional voltage,
power, energy and power factor measurements with the
VT inputs option. Calculated values are also obtained
from the protection and condition monitoring functions
of the RET615.
The values measured can be accessed locally via the user
interface on the LHMI front panel display or remotely
via its user tool interface PCM600. The values can also be
accessed locally or remotely using the web-browser based
user interface.
14
1MAC204375-PG Rev. B
Issued: 04.15.2011
9. Events recorder
The relay includes a sequence of events recorder (SER)
that logs important event activity. The relay has the
capacity to store in non-volatile memory the most recent
1024 events in a first-in-first-out (FIFO) buffer with
each event date and time stamped to 1 ms resolution. The
event log facilitates detailed pre- and post-fault analyses
of feeder faults and disturbances.
The SER information can be accessed locally via the user
interface on the relay front panel or remotely via the
communication interface of the relay. The information
can further be accessed, either locally or remotely, using
the web-browser based user interface.
ABB
Transformer Protection
RET615 ANSI
Product Version 4.0
11. Circuit-breaker
condition monitoring
For continuous knowledge of the operational availability
of the RET615 features, a comprehensive set of
monitoring functions to supervise the relay health, the
trip circuit and the circuit breaker health is included. The
breaker monitoring can include checking the wear and
tear of the circuit breaker, the spring charging time of the
breaker operating mechanism and the gas pressure of the
breaker chambers. The relay also monitors the breaker
travel time and the number of circuit breaker (CB)
operations to provide basic information for scheduling
CB maintenance. For all standard configurations, there
is a condition monitoring feature for each of the two
breakers supported.
1MAC204375-PG Rev. B
Issued: 04.15.2011
15. Self-diagnostics
The relays built-in self-diagnostics system continuously
monitors the state of the relay hardware and the
operation of the relay software. Any fault or malfunction
detected will be used for alerting the operator. A
permanent relay fault will block the protection functions
of the relay to prevent incorrect relay operation.
ABB
15
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
1)
Analog inputs
Standard configuration
Analog inputs
CT
VT
RTD
mA
AA
BA
BB
CA
CB
DA
1)
16
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Binary I/O
BO(PO)
BO(HSO)
BO(TO)
BO(SO)
A1
AA
A2
14
AB
14
B1
12
BA
12
C1
CA
D1
11
DA
11
1)
19. Communications
The self-healing Ethernet ring solution enables a costeffective communication ring solution controlled by
a managed switch with rapid spanning tree protocol
(RSTP) support to be created. The managed switch
controls the consistency of the loop, routes the data
and corrects the data flow in case of a communication
disturbance. The relays in the ring topology act as
unmanaged switches forwarding unrelated data traffic.
The Ethernet ring solution supports the connection of
up to 30 ABB 615 series relays. If more than 30 relays are
to be connected, it is recommended that the network is
split into several rings with no more than 30 relays per
ring. The self-healing Ethernet ring solution avoids single
point of failure concerns and improves the reliability of
the communication. The solution can be applied for the
Ethernet-based IEC 61850, Modbus and DNP3.0 Level
2 protocols.
17
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Ethernet
Serial
100BASE-TX (RJ-45)
100BASE-FX (LC)
RS-232/RS-485
Fiber-optic (ST)
IEC 61850-8-1
SNTP
FTP
Modbus RTU/ASCII
= supported
18
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Client A
Client B
Network
Network
RED615
REF615
RET615
REU615
REM615
ABB
19
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Width
frame
case
Height
frame
case
Depth
case
Weight
relay
7.72 lbs. (3.5 kg)
draw-out unit 3.97 lbs. (1.8 kg)
Type 1
Type 2
V nominal (Vn)
Vn variation
50120% of Vn
(1272 V DC)
Start-up threshold
Burden of auxiliary voltage supply
under quiescent (Pq)/operating
condition
Ripple in the DC auxiliary voltage
Maximum interruption time in the
auxiliary DC voltage without
resetting the relay
Fuse type
20
19.2 V DC
(24 V DC 80%)
DC < 12.0 W (nominal) / < 18.0 W (max),
AC < 16.0 W (nominal) / < 21.0W (max)
50 ms at nominal voltage
T4A/250 V
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Rated frequency
60/50 Hz 5 Hz
Current inputs
Rated current, In
Thermal withstand capability:
Continuously
For 1 s
Dynamic current withstand:
Half-wave value
Input impedance
Voltage inputs
5/1 A1)
0.2 A2)
20 A
500 A
4A
100 A
1250 A
<20 m
250 A
<100 m
Rated voltage Vn
60210 V AC (Parametrization)
Voltage withstand:
Continuous
For 10 s
Burden at rated voltage
2 Vn (240 V AC)
3 Vn (360 V AC)
<0.05 VA
1)
2)
Value
050 In
050 In
Value
Operating range
Rated voltage
24250 V DC
Current drain
1.61.9 mA
Power consumption
31.0570 mW
Threshold voltage
18176 V DC
Reaction time
3 ms
Table 14. Signal outputs (SO) on X120 and X130 [Typical operation time: 58 ms]
Value
Description
ABB
Rated voltage
250 V AC/DC
Continuous carry
5A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
21
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Rated voltage
250 V AC/DC
5A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Table 16. Double-pole power output (PO) relays with TCM [Typical operation time: 811 ms]
Value
Description
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20250 V AC/DC
~1.5 mA
20 V AC/DC (1520 V)
Table 17. Single-pole power output (PO) relays [Typical operation time: 811 ms]
Description
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
Table 18. Double-pole signal output (SO1) on X100 [Typical operation time: 811 ms]
Description
Value
Rated voltage
250 V AC/DC
5A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
22
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Table 19. High-speed output (HSO) devices [Typical operation time: 1 ms]
Description
Value
Rated voltage
250 V AC/DC
6A
15 A
30 A
5 A/3 A/1 A
Front RJ-45
TCP/IP
10 MBits/s
Rear RJ-45 or LC
TCP/IP
100 MBits/s
X5
Serial
115200 bits/s
X16
Serial
115200 bits/s
X12
Serial
Optical ST-connector
115200bits/s
Fiber type1
Wavelength
Max. distance
LC
1300 nm
2 km
<8 dB
ST
820-900 nm
1 km
<11 dB
1
2
Value
B004, B0051
Isolation
500V 1 min.
Modulation
Unmodulated
Logic level
TTL level
Currnt consumption
24 mA
Power consumption
1020 mW
ABB
23
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
-40+212 F (-40100 C)
+284 F (+140 C)
Value
Front side
IP 54
IP 20
Value
-25+55 C
-40+85 C (<16 h) 1, 2
Relative humidity
<93%, non-condensing
Atmospheric pressure
Altitude
-40+85 C
1
2
Degradation in MTBF and HMI performance outside the continuous operating temperature range.
For relays with an LC communications interface, the maximum operating temperature is +70 C .
Reference
96 h at +55 C
16 h at +85 C 1
IEC 60068-2-2
12 h at +85 C 1
IEEE C37.90-2005
96 h at -25 C
16 h at -40 C
IEC 60068-2-1
12 h at -40 C
IEEE C37.90-2005
IEC 60068-2-30
IEEE C37.90-2005
96 h at -40 C
96 h at +85 C
IEC 60068-2-48
IEEE C37.90-2005
For relays with an LC communication interface the maximum operating temperature is +70 C.
24
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Reference
2.5 kV
2.5 kV
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
8 kV
15 kV
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
10 V (emf )
f = 150 kHz80 MHz
IEC 61000-4-6
IEC 60255-22-6, class III
10 V/m (rms)
f=802700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f=900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f=801000 MHz
IEEE C37.90.2-2004
4 kV
1 kV, line-to-earth
Other ports
Power frequency (50 Hz) magnetic field:
Continuous
1-3 s
IEC 61000-4-5
IEC 60255-22-5
4 kV, line-to-earth
2 kV, line-to-line
IEC 61000-4-8
300 A/m
1000 A/m
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-22-7, class A
Emission tests:
Conducted
0.150.50 MHz
0.530 MHz
Radiated
30230 MHz
2301000 MHz
ABB
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
EN 55011, class A
IEC60255-25
< 79 dB(V) quasi peak
< 66 dB(V) average
< 73 dB(V) quasi peak
< 60 dB(V) average
< 40 dB(V/m) quasi peak,
measured at 10 m distance
< 47 dB(V/m) quasi peak,
measured at 10 m distance
25
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
>100 M, 500 V DC
Reference
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
IEC 60255-27
<0.1 , 4 A, 60 s
Requirement
Class 2
Mechanical durability
IEEE C37.90-2005
IEC 602556-6
Class 2
Class 2
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
26
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Protection functions
Table 34. Three-phase non-directional overcurrent protection (51P, 50P)
Characteristic
Value
Pickup accuracy
51P
50P-1, 50P-2
Pickup time 1) 2)
51P, 50P-1, and 50P-2:
IFault = 2 set Pickup value
Minimum
Typical
Maximum
23 ms
25 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Set Trip delay time = 0.02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current
before fault = 0.0 In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Pickup range = 2.5 In, Pickup range multiples in range of 1.5 to 20
Table 35. Three-phase non-directional overcurrent protection (51P, 50P) main settings
Parameter
Function
Value (Range)
Step
Pickup range
51P
0.055.00 In
0.01
50P-1. 50P-2
0.1040.00 In
0.01
51P
0.0515.00
0.05
50P-1. 50P-2
0.0515.00
0.05
51P
40200000 ms
10
50P-1. 50P-2
40200000 ms
10
51P
50P-1. 50P-2
Time multiplier
Definite time delay
Operating curve type
1)
ABB
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter.
27
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Pickup accuracy
Pickup time 1) 2)
IFault = 2.0 set Pickup value
Minimum
Typical
Maximum
38 ms
43 ms
46 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Measurement mode and Pol quantity = default, current before fault = 0.0 In, voltage before fault 1.0 Vn, fn = 50 Hz, fault
current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2)
Includes the delay of the signal output contact
3)
Maximum Pickup range = 2.5 In, Pickup range multiples in range of 1.5 to 20
Function
Value (Range)
Step
Pickup range
67/51P
0.055.00 In
0.01
Time multiplier
67/51P
0.0515.00
0.05
67/51P
40200000 ms
10
Directional mode
67/51P
1 = Non-directional
2 = Forward
3 = Reverse
67/51P
-179180 degrees
67/51P
Characteristic angle
Operating curve type
1)
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
28
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Pickup accuracy
50N, 50G
Pickup time 1) 2)
51N, 51G, and 50N-1, 50N-2, 50G-1,
50G-2: IFault = 2 set Pickup value
Minimum
Typical
Maximum
23 ms
25 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1) Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, earth-fault current with nominal
frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Pickup range = 2.5 In, Pickup range multiples in range of 1.5 to 20
Table 39. Non-directional neutral, ground fault protection (51N, 51G, 50N, 50G) main settings
Parameter
Pickup range
Time multiplier
Definite time delay
Operating curve type 1)
1)
ABB
Function
51N, 51G
Value (Range)
0.055.00 In
Step
0.01
0.1040.00 In
0.01
51N, 51G
0.0515.00
0.05
0.0515.00
0.05
51N, 51G
40200000 ms
10
40200000 ms
10
51N, 51G
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
29
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Depending on the frequency of the current measured:
fn 2Hz
Current:
1.5% of the set value or 0.002 In
Voltage:
1.5% of the set value or 0.002 Vn
Phase angle:
2
Minimum
Typical
Maximum
Pickup time 1) 2)
67/51N: IFault = 2 set Pickup
value
62 ms
65 ms
69 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
Set Definite time delay = 0,06 s, Inverse-time (IDMT) and definite-time (DT) curves = IEC definite time, Measurement mode
= default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, earth-fault current with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Pickup range = 2.5 In, Pickup range multiples in range of 1.5 to 20
Function
67/51N
Value (Range)
0.055.00 In
Step
0.01
Directional mode
67/51N
Time multiplier
67/51N
1=Non-directional
2=Forward
3=Reverse
0.0515.00
0.05
67/51N
60200000 ms
10
67/51N
Operation mode
67/51N
30
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Depending on the frequency of the voltage
measured: fn 2Hz
1.5% of the set value or 0.002 Vn
Pickup time 1) 2)
Minimum
Typical
Maximum
23 ms
27 ms
30 ms
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1)
Pickup range = 1.0 Vn, Voltage before fault 0.9 Vn, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequence
injected from random phase angle, results based on statistical distribution of 1000 measurements.
2)
Includes the delay of the signal output contact
3)
Maximum Pickup range = 1.20 Vn, Pickup range multiples in range of 1.10 to 2.00
Function
59
Value (Range)
0.051.60 Vn
Step
0.01
Time multiplier
59
0.0515.00
0.05
59
40300000 ms
10
59
ABB
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
31
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Depending on the frequency of the voltage measured: fn 2Hz
1.5% of the set value or 0.002 Vn
Pickup time 1) 2)
Minimum
Typical
Maximum
62 ms
66 ms
69 ms
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1)
Pickup range = 1.0 Vn, Voltage before fault 1.1 Vn, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequence
injected from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Minimum Pickup range = 0.50, Pickup range multiples in range of 0.90 to 0.20
Function
Value (Range)
Step
Pickup range
27
0.051.20 Vn
0.01
Time multiplier
27
0.0515.00
0.05
27
60300000 ms
10
27
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
32
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Pickup accuracy
Pickup time 1) 2)
Minimum
Typical
Maximum
33 ms
35 ms
38 ms
25 ms
27 ms
30 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Negative sequence voltage before fault 0.0 Vn, fn = 50 Hz, negative sequence overvoltage with nominal frequence injected
from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
ABB
Parameter
Function
Value (Range)
Step
Pickup range
47
0.0101.000 Vn
0.001
47
40120000 ms
33
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Depending on the frequency of the voltage measured: fn 2Hz
1.5% of the set value or 0.002 Vn
Pickup time 1) 2)
Minimum
Typical
Maximum
55 ms
57 ms
60 ms
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Residual voltage before fault 0.0 Vn, fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle,
results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Function
59G
Value (Range)
0.0101.000 Vn
Step
0.001
59G
40300000 ms
Value
Depending on the frequency of the
current measured: fn = 2Hz
1.5% of the set value or 0.002 In
Pickup time 1) 2)
Minimum
Typical
Maximum
22 ms
25 ms
27 ms
14 ms
17 ms
19 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
3)
Maximum Pickup range = 2.5 In, Pickup range multiples in range of 1.5 to 20
2)
34
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Function
46
Value (Range)
0.015.00 In
Step
0.01
Time multiplier
46
0.0515.00
0.05
46
40200000 ms
10
46
1)
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
Value
Depending on the frequency of the voltage measured: fn 2Hz
Current measurement: 1.5% of the set value
or 0.002 In (at currents in the range of
0.014.00 In)
2.0% of the theoretical value or 0.50 s
Table 53. Thermal overload for protection, two time constants (49T) main settings
Parameter
Temperature rise
Function
49T
Value (Range)
0.0200.0 C
Step
0.1
Max temperature
49T
0.0200.0 C
0.1
Operate temperature
49T
80.0120.0 %
0.1
Weighting factor p
49T
0.001.00
0.01
49T
660000 s
Current reference
49T
0.054.00 In
0.01
Operation
49T
Off
On
Value
Depending on the frequency of the voltage measured: fn 2Hz
3.0% of the set value or 0.002 In
Trip time 1) 2)
Minimum
Typical
Maximum
Low stage
34 ms
40 ms
44 ms
High stage
21 ms
22 ms
24 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Suppression of harmonics
1)
2)
ABB
Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
Includes the delay of the output contact. When differential current = 2 set operate value and fn = 50 Hz.
35
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Table 55. Stabilized differential protection of two winding transformers (87T) main settings
Parameter
Restraint mode
Function
87T
Value (Range)
2.h & 5.h & wav
Step
-
87T
5003000 %
10
87T
550 %
Slope section 2
87T
1050 %
End section 2
87T
100500 %
87T
720 %
87T
1050 %
Operation
87T
Winding 1 type
87T
Winding 2 type
87T
Zro A elimination
87T
Off
On
Y
YN
D
Z
ZN
Y
YN
D
Z
ZN
Not eliminated
Winding 1
Winding 2
Winding 1 and 2
Value
At the frequency f=fn
Reset time
Current measurement:
1.5% of the set value or 0.002 In
Ratio I2f/I1f measurement: 5.0% of set value
+35 ms / -0 ms
Reset ratio
Typical 0.96
+20 ms / -10 ms
36
Function
INR
Value (Range)
5100%
Step
1
INR
2060000 ms
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Depending on the frequency of the current
measured: fn 2Hz
1.5% of the set value or 0.002 In
Table 59. Circuit breaker failure protection (50BF, 50NBF) main settings
Parameter
Current value
(Operating phase current)
Current value Res
(Operating residual current)
CB failure mode
(Operating mode of function)
Function
50BF, 50NBF
Value (Range)
0.051.00 In
Step
0.05
50BF, 50NBF
0.051.00 In
0.05
50BF, 50NBF
50BF, 50NBF
Retrip time
50BF, 50NBF
1=Current
2=Breaker status
3=Both
1=Off
2=Without check
3=Current check
060000 ms
10
CB failure delay
50BF, 50NBF
060000 ms
10
CB fault delay
50BF, 50NBF
060000 ms
10
Value
Pickup accuracy
Trip time
Minimum
Typical
Maximum
Operation mode =
Light+current 1) 2)
9 ms
12 ms
15 ms
9 ms
10 ms
12 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
1)
Phase Pickup range = 1.0 In, current before fault = 2.0 set Phase Pickup range, fn = 50Hz, fault with nominal frequency,
results based on statistical distribution 200 measurements
2)
Includes the delay of the heavy-duty output contact
ABB
Parameter
Function
Value (Range)
Step
AFD
0.5040.00 In
0.01
AFD
0.058.00 In
0.01
Operation mode
AFD
1=Light+current
2=Light only
3=BI controlled
37
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Values (Range)
Value
Pickup accuracy
Pickup time 1) 2)
IFault = 2.0 set Trip value
Minimum
Typical
Maximum
37 ms
40ms
45 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1)
Pickup range = 1.0 Vn, Voltage before fault 0.9 Vn, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequence
injected from random phase angle, results based on statistical distribution of 1000 measurements.
2)
Includes the delay of the signal output contact
38
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Function
Value (Range)
Step
Trip value
REF
550 %
Restraint mode
REF
None
2nd harmonic
REF
1050 %
REF
40300000 ms
Operation
REF
Off
On
Value
Pickup accuracy
Pickup time
Typical < 55 ms
Reset time
< 40 ms
Reset ratio
Typical 1.04
Retardation time
< 35 ms
Function
Value (Range)
Step
Pickup value
37
0.011.00 In
0.01
37
0.010.50 In
0.01
37
400600000 ms
10
Operation
37
Off
On
Value
Pickup accuracy
Pickup time1), 2)
Frequency change:
Typical 200 ms
Voltage change:
Typical < 40 ms
Reset time
< 50 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
1)
2)
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Function
Value (Range)
Step
Pickup value
24
100200%
Curve type
24
Time multiplier
24
0.1100.0
0.1
24
200200000 ms
10
Value
81O/81U 10 mHz
df/dt
Pickup time
81O/81U < 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
Function
Values (range)
Step
Operation mode
81
1=81U
2=81O
3=df/dt
4=81U + df/dt
5=81O + df/dt
6=81U or df/dt
7=81O or df/dt
81
0.9001.200 Fn
0.001
81
0.8001.100 Fn
0.001
81
-0.2000.200 Fn/s
0.005
81
80200000 ms
10
81
120200000 ms
10
Pickup time
Value
81U
10 mHz
df/dt
81U
< 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
40
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Function
Values (range)
Step
81LSH
81U
81U and df/dt
81U or df/dt
Restore mode
81LSH
Disabled
Auto
Manual
81LSH
0.8001.200 Fn
0.001
81LSH
-0.200-0.005 Fn/ds
0.005
81LSH
80200000 ms
10
81LSH
120200000 ms
10
81LSH
0.8001.200 Fn
0.001
81LSH
80200000 ms
10
Value
Pickup accuracy
ABB
Parameter
Function
Value (Range)
Step
Pickup value
MAP
-10000.010000.0
0.1
MAP
0200000 ms
100
Operation mode
MAP
Over
Under
41
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Measurement functions
Table 75. Three-phase current measurements (IA, IB, IC)
Characteristic
Value
Measurement accuracy
Depending on the frequency of the current measured: fn2 Hz at currents in the range
of 0.0140 In)
Current: 0.5% or 0.002 In
Phase angle: 2.5
Suppression of harmonics
Value
Measurement accuracy
Suppression of harmonics
Value
Measurement accuracy
Suppression of harmonics
Value
Measurement accuracy
Suppression of harmonics
Value
Measurement accuracy
Suppression of harmonics
42
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Value
Measurement accuracy
Suppression of harmonics
Value
Measurement accuracy
Table 82. Three-phase and single-phase power and energy (P, SP, E, SE)
Characteristic
Value
Measurement accuracy
Suppression of harmonics
Supervision functions
Table 83. Fuse failure supervision (60)
Characteristic
Trip time
1)
ABB
1)
Value
NPS function:
VFault = 1.1 set Neg Seq voltage Lev
VFault = 5.0 set Neg Seq voltage Lev
< 33 ms
< 18 ms
Delta function:
V = 1.1 set Voltage change rate
V = 2.0 set Voltage change rate
<30 ms
<24 ms
Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase
angle, results based on statistical distribution of 1000 measurements
43
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
21. Display
The relays local HMI includes a large LCD screen
standard. The large LCD display offers full front-panel
user-interface functionality with menu navigation and
menu views.
44
10
20 or more
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
ABB
45
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
D ig it
1) Product Series
2) Standard
3) Main Application
4) Functional Application
1
Ex: HATDDADANBE1BNN1XE
H
D e s c r ip tio n
H: 615 (Tiger including case )
H
A: ANSI
T: Transformer protection and control
2
A
3
T
9-10) Communication
Ports
6 7 8
A D A
A
B
B
C
C
D
A
A
B
A
B
A
9 10 11 12 13 14 15 16 17 18
Notes
N B E 1 B N N 1 X E
5
D
4
D
A : 6 C T + G ro u n d C T
B: 6 CT + Ground CT + 5 VT(Winding 2)
B: 6 CT + Ground CT + 5 VT (Winding 1)
C: 6 CT + Ground CT + 5 VT(Winding 2) + 2 RTD
C: 6 CT + Ground CT + 5 VT(Winding 1) + 2 RTD
D: 6 CT + Ground CT + 6 VT (Windings 1 & 2)
A: 8 BI + 6 BO + 3 HSO
A: 8 BI + 10 BO
A: 14 BI + 9 BO + 3 HSO
A: 14 BI + 13 BO
B: 12 BI + 6 BO + 3 HSO
B: 12 BI + 10 BO
C: 8 BI + 6 BO + 3 HSO
C: 8 BI + 10 BO
D: 11 BI + 6 BO + 3 HSO
D: 11 BI + 10 BO
One port: Ethernet 100FX (LC)
One port: Ethernet 10/100BaseT (RJ45)
A
A
A
A
B
B
C
C
D
D
1
A
2
B
1
A
1
A
1
A
N
N
A
B
1
1
Four ports: [Ethernet 100FX (LC) + 2 * Ethernet 10/100BaseT (RJ45) + serial glass
A
fiber (ST)]
46
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
D ig it
Includes Arc Flash
Detection
9 10 11 12 13 14 15 16 17 18
Notes
N B E 1 B N N 1 X E
N
N
F
G
1
1
Four ports: [Ethernet 100FX (LC) + 2 * Ethernet 10/100BaseT (RJ45) + serial glass
F
fiber (ST) + Arc Flash Detection]
Four ports: [Ethernet 3 * 10/100BaseT (RJ45) + serial glass fiber (ST) + Arc Flash
F
Detection]
Two/three ports: [Ethernet 10/100BaseT (RJ45) + RS-485 (1x4-wire or 2x2wire) + IRIG-B + Arc Flash Detection]
IE C 6 1 8 5 0 + D N P 3 .0 L e v e l 2 + M o d b u s
English
E n g lis h + S p a n is h
E n g lis h + P o r tu g u e s e
L a rg e L C D (s ta n d a rd )
None
None
N o m in a l: 4 8 - 2 5 0 V D C ; 1 0 0 - 2 4 0 V A C 5 0 /6 0 H z
Nominal: 24-48 V DC
Reserved
Version 4.0
11) Protocols
12) Language
E
1
5
8
B
N
N
1
2
X
E
Notes: 1) SNTP is available for time-sync with all Ethernet options. IRIG-B is available for time-sync with all
RS-485 options. Both SNTP and IRIG-B are available for time-sync when both Ethernet and RS-485
options are available.
Example code: H A T B B A B A F F E 1 B N N 1 X E
Your ordering code:
Digit (#)
Code
ABB
10 11 12 13 14 15 16 17 18
47
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Order Number
Tools
PCM600 V2.0 user tool
PCM600-20
Cables
Cable for optical sensors for arc protection 1.5 m
1MRS120534-1.5
1MRS120534-3.0
1MRS120534-5.0
Mounting accessories
Semi-flush mounting kit
1MRS050696
1MRS050697
1MRS050831
604539-K1
604539-K3
604540-K1
604540-K3
604529-K1
604529-K3
604529-K2
604529-K4
Test switches
FT-1, FT-14, and FT-19 Flexitest switches
26. Tools
The relay is delivered as a pre-configured unit. The default
parameter setting values can be changed from the frontpanel user interface, the web-browser based user interface
(WHMI) or the PCM600 tool in combination with the
relay specific connectivity package (CP).
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
Version
PCM600
2.3 or later
IE 7.0 or later
4.0 or later
V3.4 or later
9.3 or later
WebHMI
PCM600
-1)
Signal monitoring
Event viewing
Single-line diagram
(view)
(edit)
= Supported
1)
Analog and digital values pre-mapped to registers for easy individual or grouped register retrieval by Modbus driver
ABB
49
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
(1)
RET615 ANSI
X120
1
52
2
3
4
5
P1
6
7
S1
8
9
S2
P2
10
11
12
13
P1
14
IA(2)
X100
+
1)
Vaux
-
IB(2)
SELF-CHECK ALARM
IC(2)
8
9
10
IG
SO1
11
12
13
SO2
X130
1
2
3
4
5
6
7
8
9
BI 1
PO3
2)
BI 2
TCM1
BI 3
PO4
BI 4
TCM2
BI 5
2)
a
b
c
(2)
BI 1
3
4
BI 2
5
6
BI 3
7
8
9
10
11
12
13
17
15
19
18
20
22
21
23
24
10
SO1
SO2
1
2
14
16
X130
BI 6
X110
52
4
5
PO2
IC(1)
S1
S1
P1
6
7
IB(1)
P2
S2
PO1
IA(1)
S2
P2
2)
SO3
12
11
13
15
14
16
18
17
X110
2)
BI 4
BI 5
14
SO1
SO2
BI 6
SO3
BI 7
16
15
17
19
18
20
22
21
23
SO4
BI 8
24
X110
1
2
3
4
5
6
7
8
9
10
BI 1
2)
BI 2
BI 3
BI 4
X110
BI 5
2)
15
HSO1
BI 6
16
19
HSO2
BI 7
20
23
HSO3
BI 8
24
X13
Light sensor input1
2)
X14
Light sensor input2
X15
Light sensor input3
Figure 21. Terminal diagram for RET615 standard configuration A with options.
50
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
(1)
RET615 ANSI
X120
1
52
IA(2)
2
3
IB(2)
P1
S2
S1
P1
BI 2
5
6
BI 3
da
52
(2)
PO3
TCM1
7
8
SO2
BI 1
3
4
9
10
11
12
13
14
15
16
17
18
a
b
c
11
12
13
X130
1
2
P2
P2
SO1
S1
S2
4
5
8
9
10
IG
14
PO2
IC(1)
12
13
6
7
IB(1)
10
11
PO1
IA(1)
8
9
S2
P2
SELF-CHECK ALARM
IC(2)
6
7
S1
Vaux
-
4
5
P1
X100
+
1)
BI 4
+
+
+
+
+
PO4
not in use
VA (1) or (2)
2)
TCM2
14
16
17
15
19
18
20
22
21
23
24
VB (1) or (2)
VC (1) or (2)
VG (1) or (2)
dn
X110
1
2
BI 1
3
4
BI 2
5
6
BI 3
7
8
9
10
11
12
13
2)
X110
2)
BI 4
BI 5
14
SO1
SO2
BI 6
SO3
BI 7
16
15
17
19
18
20
22
21
23
SO4
BI 8
24
X110
1
2
3
4
5
6
7
8
9
10
BI 1
2)
BI 2
BI 3
BI 4
X110
BI 5
2)
15
HSO1
BI 6
16
19
HSO2
BI 7
20
23
HSO3
BI 8
24
X13
Light sensor input1
2)
X14
Light sensor input2
X15
Light sensor input3
Figure 22. Terminal diagram for RET615 standard configuration B with options.
ABB
51
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
(1)
n
a
RET615 ANSI
N
X120
da
dn
52
IA(2)
2
3
IB(2)
P1
P2
P2
S1
P1
X130
1
+
2 _
3
4
5
6
7
8
S2
9
10
11
12
13
14
15
16
17
18
+
_
mA
11
12
13
SO2
mA 1
RTD1
PO3
G (RTD)
+
_
RTD2
TCM1
G (RTD)
+
+
+
+
+
PO4
not in use
VA (1) or (2)
2)
TCM2
14
16
17
15
19
18
20
22
21
23
24
VB (1) or (2)
VC (1) or (2)
VG (1) or (2)
X110
52
a
b
c
SO1
S1
S2
4
5
8
9
10
IG
14
PO2
IC(1)
12
13
6
7
IB(1)
10
11
PO1
IA(1)
8
9
S2
P2
SELF-CHECK ALARM
IC(2)
6
7
S1
Vaux
-
4
5
P1
X100
+
1)
(2)
1
2
BI 1
3
4
BI 2
5
6
BI 3
7
8
9
10
11
12
13
2)
X110
2)
BI 4
BI 5
14
SO1
SO2
BI 6
SO3
BI 7
16
15
17
19
18
20
22
21
23
SO4
BI 8
24
X110
1
2
3
4
5
6
7
8
9
10
BI 1
2)
BI 2
BI 3
BI 4
X110
BI 5
2)
15
HSO1
BI 6
16
19
HSO2
BI 7
20
23
HSO3
BI 8
24
X13
Light sensor input1
2)
X14
Light sensor input2
X15
Light sensor input3
Figure 23. Terminal diagram for RET615 standard configuration C with options.
52
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
(1)
A
N
n
RET615 ANSI
X120
52
IA(2)
2
3
IB(2)
P1
P2
P2
S2
S1
P1
a
b
c
X130
1
2
BI 2
5
6
BI 3
n
N
(2)
8
9
10
11
12
13
14
15
16
17
18
11
12
13
BI 1
3
4
52
SO1
S1
S2
4
5
8
9
10
IG
14
PO2
IC(1)
12
13
6
7
IB(1)
10
11
PO1
IA(1)
8
9
S2
P2
SELF-CHECK ALARM
IC(2)
6
7
S1
Vaux
-
4
5
P1
X100
+
1)
+
+
+
+
+
+
SO2
PO3
TCM1
VA(1)
PO4
VB(1)
TCM2
VC(1)
14
16
17
15
19
18
20
22
21
23
24
VA(2)
VB(2)
VC(2)
X110
1
2
BI 1
3
4
BI 2
5
6
BI 3
7
8
9
10
11
12
13
2)
X110
2)
BI 4
BI 5
14
SO1
SO2
BI 6
SO3
BI 7
16
15
17
19
18
20
22
21
23
SO4
BI 8
24
X110
1
2
3
4
5
6
7
8
9
10
BI 1
2)
BI 2
BI 3
BI 4
X110
BI 5
2)
15
HSO1
BI 6
16
19
HSO2
BI 7
20
23
HSO3
BI 8
24
X13
Light sensor input1
2)
X14
Light sensor input2
X15
Light sensor input3
Figure 24. Terminal diagram for RET615 standard configuration D with options.
ABB
53
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
X 130
Transducer
a)
Shunt
(44 )
...
...
...
X130
1
2
mA
Resistor sensor
3
b)
RTD1
5 +
6
RTD2
X130
1
2
mA
Resistor sensor
3
c)
+
-
5 +
6
RTD1
RTD2
Figure 25. Typical connections of RET615 standard configuration D for a) mA input, b) 2-wire RTD inputs and c) 3-wire RTD inputs.
54
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
28. Certificates
KEMA has issued an IEC 61850 Certificate Level A1 for RET615. Certificate number: 30710144-Consulting 08-0115
The RET615 is a UL Listed product, UL File/Sec. E103204/2/2.
29. References
The download area on the right hand side of the web page contains the latest product documentation, such as technical reference manual, installation manual, operators manual,etc. The selection tool on the web page helps you find the
documents by the document category and language.
The Features and Application tabs contain product related information in a compact format.
The www.abb.com/substationautomation portal offers you information about the distribution automation product and
service range.
You will find the latest relevant information on the RET615 protection relay on the product page.
ABB
55
Transformer Protection
RET615 ANSI
Product Version 4.0
1MAC204375-PG Rev. B
Issued: 04.15.2011
IEC 61850
RET615
PHLPTOC1
51P (1)
PHLPTOC2
51P (2)
PHHPTOC1
50P-1 (1)
PHHPTOC2
50P-1 (2)
PHHPTOC3
50P-2 (1)
PHHPTOC4
50P-2 (2)
DPHLPDOC1
67/51P (2)
DPHLPDOC2
67/51P (1)
EFLPTOC1
51G
EFLPTOC2
51N (1)
EFLPTOC3
51N (2)
EFHPTOC1
50G-1
EFHPTOC2
50G-2
EFHPTOC3
50N-1 (1)
EFHPTOC4
50N-1 (2)
EFHPTOC5
50N-2 (1)
EFHPTOC6
50N-2 (2)
DEFLPDEF1
67/51N (2)
DEFLPDEF2
67/51N (1)
NSPTOC1
46 (1)
NSPTOC2
46 (2)
ROVPTOV1
59G (2)
ROVPTOV2
59N (2)
ROVPTOV3
59N (1)
ROVPTOV4
59G (1)
PHPTUV1
27 (2)
PHPTUV2
27 (1)
PHPTOV1
59 (2)
PHPTOV2
59 (1)
NSPTOV1
47 (2)
NSPTOV2
47 (1)
Protection
56
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
IEC 61850
RET615
FRPFRQ1
81-1 (2)
FRPFRQ2
81-2 (2)
FRPFRQ3
81-1 (1)
FRPFRQ4
81-2 (1)
OEPVPH1
24-1 (2)
OEPVPH2
24-2 (2)
OEPVPH3
24-1 (1)
OEPVPH4
24-2 (1)
Three-phase thermal overload protection for power transformers, two time constants
T2PTTR1
49T (1)
TR2PTDF1
87T
LREFPNDF1
87LOZREF (2)
CCBRBRF1
50BF (1)
CCBRBRF2
50BF (2)
TRPPTRC1
86/94-1
TRPPTRC2
86/94-2
ARCSARC1
AFD-1 (2)
ARCSARC2
AFD-2 (2)
ARCSARC3
AFD-3 (2)
MAPGAPC1
MAP (1)
MAPGAPC2
MAP (2)
MAPGAPC3
MAP (3)
LSHDPFRQ1
81LSH-1 (2)
LSHDPFRQ2
81LSH-2 (2)
LSHDPFRQ3
81LSH-1 (1)
LSHDPFRQ4
81LSH-2 (1)
PHPTUC1
37 (1)
CBXCBR1
52 (1)
CBXCBR2
52 (2)
TPOSSLTC1
84T
SSCBR1
52CM (1)
SSCBR2
52CM (2)
TCSSCBR1
TCM-1
TCSSCBR2
TCM-2
CTSRCTF1
MCS 3I, I2
Control
Condition monitoring
ABB
57
Transformer Protection
RET615 ANSI
Product Version 4.0
1MAC204375-PG Rev. B
Issued: 04.15.2011
IEC 61850
RET615
SEQRFUF1
60 (1)
SEQRFUF2
60 (2)
CMMXU1
CMMXU2
CSMSQI1
CSMSQI2
RESCMMXU1
IG
VMMXU1
VMMXU2
RESVMMXU1
VG
RESVMMXU2
VG
VSMSQI1
VSMSQI2
SPEMMXU1
SP, SE (1)
SPEMMXU2
SP, SE (2)
PEMMXU1
P, E (1)
PEMMXU2
P, E (2)
2 RTD +1 mA
XARGGIO130
FMMXU1
FMMXU2
Disturbance recorder
RDRE1
DFR
Fault recorder
FLMSTA1
FR
SER
SER
Measurement
Logging functions
58
ABB
Transformer Protection
1MAC204375-PG Rev. B
RET615 ANSI
Issued: 04.15.2011
V2.0
V4.0
32. Notes
ABB
59