High-Impedance Bus Differential Protection Modeling
High-Impedance Bus Differential Protection Modeling
Abstract
This paper presents a modeling of a high-impedance bus differential protection logic using the ATP (Alternative Transients Program) MODELS language. The model is validated using ATP simulations on an electrical system consisting
of a sectionalized bus arrangement with four transmission lines (TLs) and two autotransformers. The obtained results
validate the model and present some of the advantages of using this type of bus protection, such as fast and safe operation, even when under adverse conditions such as current transformers (CTs) magnetic core saturation upon the occurrence of external faults.
Keywords: Bus Protection; High-Impedance Differential Protection; ATP; MODELS
1. Introduction
The increasing demand for energy supplies and lower
fares cause the electricity sector to operate close to its
stability limits, which may compromise the safety of its
operation. In this context, the protection of electric power
system plays a key role in order to extinguish system
faults quickly and appropriately, preserving the integrity
of the system components, avoiding blackouts of major
proportions and preserving load as much as possible.
Among faults in electric apparatus, substation (SE) bus
deserves serious attention. Even though faults in these
components are not very commonabout 5% [1], its
effects are very harmful to the system, and can often lead
it to instability.
With respect to the station-bus protection, two techniques are widely used: low impedance differential protection and high-impedance differential protection. The
second one is typically used in SEs with rated voltage
greater or equal to 500 kV, where buses have arrangements with fixed topology and there are less occurrences
of switching maneuvers in CTs secondary circuits.
Softwares traditionally used for analysis of protection
systems use component models dedicated to the analysis
of the power system at fundamental frequency. As a result, the transient performances of the protection systems
are not evaluated. In this way, EMTP (Eletromagnetic
Transient Programs) softwares have shown to be an appropriate alternative for modeling and simulating protective relays, since they use more thorough models of the
system components and provide suitable environments to
Copyright 2013 SciRes.
M. T. S. ALVARENGA ET
38
Br 1
Br 2
Br 3
Br 4
86
TRIP
AL.
I 'T = I1 + I 2 + I3
(1)
I 'T + I 4 = 0
(2)
VR 0
(3)
RTC
n 1
RL
n 1
R TC
CT B
RL
87Z
86
MOV
IT
Circuit 1
Circuit 2
Circuit 3
Circuit 4
50/51
+
VR
RS
87Z
XM
I4
87B
XM
n 1
MOV
RS
M. T. S. ALVARENGA ET
RL
n 1
n 1
+
V
R
XM
n 1
IT
R TC
RL
RS
M OV
CT A
87Z
AL.
39
H (s) =
(1.65 109 ) ( s 5 + 2.36 103 s 3 + 2.78. 106 s + 1.65 109 )
IT
RL
+
VR
XM
RS
87Z
MOV
R TC
2800
MOV
2600
2400
Voltage [V]
(5)
RS
MODELS
Current
Signals
RELAY 87Z
Signal
Conditioning
Data
Aquisiction
2200
Phasor
Estimation
Phasors
V PICK-UP
2000
Differential
Analysis
1800
TRIP
1600
Br 1
Breaker 1
Trip signal - Br 1
TRIP
Breaker n
1400
i
1200
0
6
Current [A]
10
12
x 10
Br n
Trip signal - Br n
i
M. T. S. ALVARENGA ET
=
FP Z10 ,Res for x0
(9)
(10)
CT
Bus 1
CT
Bus 2
CT
(8)
CT
2Y x b
Z10 = INTouRON
2
Y
CT
(7)
CT
x
Z10 = INTouRON
Res
AL.
CT
CT
40
3.2. Breakers
The breaker model provides the status of the breakers in
the simulated system. The real breakers opening delay
related to the time for energizing the opening coil, openCopyright 2013 SciRes.
TL 1
AT 1
TL 2
TL 3
AT 2
TL 4
ENG
M. T. S. ALVARENGA ET
Z O NE 1
R TC
RL
R TC
RL
TL 1
V p i ck-u p
AT 1
R TC
RL
R TC
RL
Rs
M OV
TL 2
87Z
CT - B us 2
AL.
41
Z1[ / km]
Y0 [S / km]
Y1[S / km]
2.293
3.252
2.164
3.272
From the analysis of Figures 10, the relay did not operate for an external fault on TL 3, as expected. It can be
seen that the voltage phasor magnitude was approximately
zero throughout all the simulation period, guaranteeing
the safety of the protection system. In this case, the protection scheme of transmission line 3, not included in this
paper, should operate to extinguish the defect.
Source
V [pu]
0 []
1 []
TL1
S1
1,01-30
18.401 + j28.691
13.379 + j20.866
TL2
S2
1-30
14.242 + j22.194
10.955 + j17.072
AT1
S3
0,29-30
14.242 + j22.194
10.955 + j17.072
Voltage [V]
1500
600
1000
500
400
500
Voltage [V]
100
Voltage [V]
Magnitude of V [V]
Vpick-up [V]
-1000
16.068 + j25.039
12.050 + j18.779
TL4
S5
0,99-30
18.412 + j28.691
13.389 + j20.866
AT2
S6
2,06-30
16.836 + j26.236
14.177 + j22.093
(11)
(12)
80
60
40
Time [ms]
100
20
(a)
1500
600
1000
500
400
500
0
200
Voltage [V]
Magnitude of V [V]
Vpick-up [V]
20
60
40
Time [ms]
80
100
0
-100
0
20
(c)
Voltage [V]
100
Voltage [V]
Magnitude of [V]
Vpick-up [V]
300
40
60
Time [ms]
80
100
(d)
1500
600
1000
500
400
500
0
-500
Voltage [V]
Magnitude of [V]
Vpick-up [V]
300
200
100
Voltage [V]
Magnitude of V [V]
Vpick-up [V]
-1000
-1500
0
80
100
-1000
-1500
0
60
40
Time [ms]
(b)
-500
20
Voltage [V]
1-30
0
-100
0
Voltage [V]
S4
Voltage [V]
TL3
200
-500
-1500
0
Voltage [V]
Magnitude of [V]
Vpick-up [V]
300
20
40
60
Time [ms]
(e)
80
100
0
-100
0
20
40
60
Time [ms]
80
100
(f)
ENG
M. T. S. ALVARENGA ET
42
700
600
600
500
Voltage [V]
Magnitude of [V]
Vpick-up [V]
Voltage [V]
400
300
200
400
Voltage [V]
500
200
100
100
0
-100
0
Voltage [V]
Magnitude of [V]
Vpick-up [V]
300
20
40
60
Time [ms]
80
-100
0
100
20
(a)
700
500
600
Voltage [V]
Voltage [V]
Magnitude of [V]
Vpick-up [V]
300
200
Voltage [V]
500
400
100
Voltage [V]
Magnitude of [V]
Vpick-up [V]
400
300
200
References
20
40
60
Time [ms]
80
-100
0
100
20
(c)
40
60
Time [ms]
80
100
(d)
700
[1]
[2]
[3]
[4]
[5]
S. G. A. Perez. Modeling Relays for Power System Protection Studies, Ph.D. Dissertation, University of Saskatchewan, Saskatoon, Saskatchewan, Canada, July 2006.
[6]
K. Behrendt, D. Costello and S. E. Zocholl, Considerations for Using High-Impedance or Low-Impedance Relays for Bus Differential Protection, Proceedings of the
35th Annual Western Protective Relay Conference, Spokane, WA, 2008.
[7]
D. G. Hart, D. Novosel and R. A. Smith, Modified Cosine Filters, US Patent 6,154,687, Nov. 2000.
[8]
600
600
500
Voltage [V]
Magnitude of [V]
Vpick-up [V]
400
300
200
400
Voltage [V]
500
Voltage [V]
100
sults validated the model and presented some of the advantages of using this type of bus protection.
This paper also addressed the role of protection in the
event of outbreaks in the electrical system, but the research, still under development, aimed the inclusion of
more thorough analysis of the model and the protection
scheme. Some ideas for future researches include:
Analysis of high-impedance bus differential protection applied to other bus arrangements.
Inclusion of more elements to the considered bus,
such as other transmission lines, transformers, reactors, shunt capacitors, among others.
Implementation of other protection schemes at the
same bus in order to compare their advantages and
disadvantages.
100
Voltage [V]
Magnitude of [V]
Vpick-up [V]
300
200
100
100
0
-100
0
80
(b)
600
-100
0
40
60
Time [ms]
20
40
60
Time [ms]
80
(e)
100
-100
0
20
40
60
Time [ms]
80
100
(f)
6. Conclusions
This paper presented the fundamental concepts of highimpedance bus differential protection and an innovative
approach for its modeling and simulation using the
MODELS language in ATP software. The obtained re-
AL.
ENG