DC Machines Lab Manual
DC Machines Lab Manual
IA marks: 25
Exam marks: 50
I cycle Experiments
1
2
3
4
5
6
7
8
9
10
11
12
13
Performance of synchronous generator connected to infinite bus, under constant power and
variable excitation & vice versa.
Lab Incharge
Teaching Staff: 1. Smt. Ushasurendra
2. Sri. B.S. Srikanthan
3. Mr. Sandeep kumar .K.J
4. Mr. Mohan .N
HOD E&EE
Contents
Sl
No
Page no
3-6
9 - 16
Hopkinson's test.
19 - 23
25 - 27
Swinburne's Test
29 - 32
35 - 36
39 - 41
Slip test.
47 - 50
10
53 - 55
57 - 61
63 - 66
67 - 69
11
12
13
43 - 45
71 - 73
Experiment No.01
Speed control of a DC motor by armature voltage control
and flux control
Aim: To control the speed of a DC motor by
1) armature voltage control method
2) flux control method
CIRCUIT DIAGRAM
Apparatus Required:
Circuit
Ref.
A1
V1
Rfm
Ram
Description
Rating
Quantity
0-2.5A-5A
0-250V
200,1.7A
50,5A
2
1
2
1
THEORY: The working principal of a Dc motor can be stated as when a current carrying
conductor is placed in a magnetic field it experiences a force. In the practical DC motor, the
permanent magnet is obtained by a field winding which produces the required flux is called the
main flux and all the armature conductor mounted on the periphery of the armature drum, get
subjected to the mechanical force. Due to this overall armature experiences a twisting force
called torque and armature of the motor starts rotating. As the armature starts rotating it cuts the
main flux and hence an emf gets induced in the conductors the direction of which is against the
supply voltage and hence an emf gets induced in the conductors, the direction of which is
against the supply voltage and hence it is termed as back emf Eb. (Eb =
Therefore, the supply voltage has to overcome this back emf to keep the conductor rotating.
The speed of the motor automatically adjusts its self to the load so that the electrical power
required to drive the current through the armature is equal to the mechanical power required to
drive the load. The back emf is always less than the supply voltage V.
Therefore Eb = V - IaRa
E Volts
R
RI
E - RI
Rheostatic Control
SERIES
SHUNT
FIELD CONTROL
Procedure
Flux control method:
1.
2.
3.
4.
5.
Inference
Flux control
Armature voltage = __________
Sl
No
If Amps
N rpm
Sl
No
If Amps
N rpm
Voltage control
Field current = __________
Sl
No
V Volts
N rpm
V Volts
N rpm
Typical graph:
N
In rpm
In rpm
V
Volts
If
Amps
Conclusion:
Experiment No.02
Load Characteristics of a DC Shunt generator and
Compound generator
Aim: To draw the load characteristic of a dc shunt generator.
CIRCUIT DIAGRAM
Generator:
Apparatus Required:
Circuit
Ref.
A1, A2
V1, V2
Rfm
Rfg
Ram
Description
Rating
Quantity
0-20A
0-250V
200, 1.7A
500, 1.2A
50, 5A
2
2
1
1
1
Theory:
DC generator works on the principle of dynamically induce emf. The DC generator has the
following characteristics.
Magnetization Characteristics: This characteristic is obtained by plotting a graph of generated
no load voltage E against the field current If, when speed of the generator is maintained
constant. It is also called as no load Characteristic or open circuit Characteristic, since it plotted
without load with output terminals kept open.
Load Characteristics: this is further divided into two Characteristics
1) External Characteristics
2) Internal Characteristics
Compound generator : There are two ways of connecting the shunt field in a compound
generator called short and long shunt. The short shunt is the more usual arrangement as it gives
a somewhat higher voltage due to the fact that the shunt field has the full armature voltage
across it. In the long shunt arrangement, the voltage across the shunt is the armature voltage less
the ohmic drop in the series field.
Load Characteristics of a DC Shunt generator
External Characteristics:
1. Connections are made as shown in the circuit diagram.
2. The motor field resistance Rfm is kept in cut-out position armature resistance Ram is kept
in cut in position and generator field resistance Rfg in cut in position.
3. Keep all the load switches in off position.
4. Close the supply switch and ensure that the motor is rotating in the proper direction.
5. Gradually cut out the Ram completely and slowly cut in the Rfm until the motor reaches
the rated speed.
6. Slowly cut out the generator field rheostat Rfg until the rated voltage is obtained.
7. Now load the generator in steps upto its rated current by closing the load switches one by
one.
8. Corresponding load current Il and terminal voltage V are tabulated at each step by
maintaining the rated speed of the motor by adjusting Rfm.
9. Switch off all the loads and bring back the rheostat Rfg to its original position.
10. The rheostats Rfm, Ram are brought back to their original positions and switch off supply
switch S1 to stop the motor.
11. Find out the values of Rsh and Ra by VA method and tabulate corresponding V and I.
Department of Electrical and Electronics Engineering
Procedure
Starting the DC shunt motor:
1. Connections are made as shown in the circuit diagram.
2. To start the DC shunt motor ensure that the rheostat in series with the motor armature is
completely cut-in and the rheostat in series with the motor field is completely cut-out.
Further ensure that the rheostat in series with the generator field is completely cut-in.
3. Close the supply switch.
4. Cut-out the armature rheostat Ram Slowly and completely.
5. Cut-in the motor field rheostat Rfm slowly until the motor reaches the rated speed.
6. This procedure is followed in all experiments where a DC shunt motor is to be brought to
its rated speed.
Load Test
1. Ensure that the load is disconnected and bring the motor to rated speed as described
above.
2. Now slowly cut-out the generator field rheostat Rfg un-till the voltmeter reads the rated
voltage. This is the no load voltage of the shunt generator.
3. Now close the load switch.
4. Load the generator. For each load measure the generator field current If from ammeter
A1, the load current from ammeter A2 and the terminal voltage V from the voltmeter V1.
5. Continue loading until the rated current of the generator. Ensure the reading are taken at a
constant motor speed.
6. Continue loading and note down the point at which the load current starts decreasing.
This gives the critical load current.
7. Now keeping the load constant at some value, vary the speed and note the effect of speed
on the terminal voltage.
Department of Electrical and Electronics Engineering
10
8. Now remove the load, reduce the generator voltage, cut out the motor field rheostat, cut
in the motor armature rheostat and disconnect the main supply switch.
Load test
N = _____________rpm
Inference
Tabular Column
IL Amps
If Amps
V volts
Ia = If + IL
IaRa
Eg=V+IaRa
V (Volts)
I (Amps)
Ra = V/I
Ohms
11
I (Amps)
Ra = V/I Ohms
12
Generator:
Apparatus Required:
Circuit Ref.
A1
A2
V1
Rfm
Rfg
Ram
Description
Moving coil ammeter
Moving coil ammeter
Moving coil voltmeter
Rheostat
Rheostat
Rheostat
Rating
0-2.5A
0-20A
0-250V
200, 1.7A
500, 1.2A
50, 5A
Quantity
1
1
1
1
1
1
THEORY
The shunt generator gives a terminal voltage which falls of somewhat with increase of load. It is
usual to include an adjustable resistance called shunt regulator in the field circuit, and cutout
some of this resistance when the load increases. The raise in the terminal voltage obtained by
providing shunt generator with additional series excitation, the design being such that, over the
series range, working characteristics does not drop. The characteristics for shunt and series turns
separately are shown in the fig below and that of the compound generator is obtained by adding
ordinates of two curve. If series excitation is such that the terminal voltage on full load is the
same as on no load, the generated is level compounded. If the terminal voltage raises with load
it is over compounded.
Department of Electrical and Electronics Engineering
13
Procedure: Make connections as shown in the circuit diagram. Ensure that the load is NOT
switched on. Cut in resistance Ramin series with the compound motor armature, cut out resistance
Rfm in series with compound motor shunt field and cut in Rfg in series with generator shunt field.
1. Close the supply switch. Cut out Ram completely. Cut in Rfm to bring the compound
motor to rated speed.
2. Now slowly cut out the generator field resistance Rfg un-till the voltmeter reads the rated
voltage. This is the no load voltage of the shunt generator.
3. Now close the load switch.
4. Load the generator. For each load measure the generator field current If from ammeter
A1, the load current from ammeter A2 and the terminal voltage V from the voltmeter V1.
5. Continue loading until the rated current of the generator. Ensure that the readings are
taken at a constant motor speed.
6. Now remove the load, reduce the generator voltage, cut out the motor field resistance, cut
in the motor armature resistance and remove the main supply switch.
7. Repeat the steps for all different connections of the compound generator.
8. Measure the resistances of the armature winding and the series field winding.
Measurement of shunt Field, series Field and armature resistance are found using VI
method as mentioned in the shunt generator experiment.
Load test
N = __________rpm
Tabular Columns
Long shunt cumulative compound generator
IL Amps
If Amps
v volts
Ia = If + IL amps
Ia(Ra+Rse) volts
Eg=V+Ia(Ra+Rse) volts
14
If Amps
v volts
Ia = If + IL amps
Ia(Ra+Rse) volts
Eg=V+Ia(Ra+Rse) volts
IL Amps
If Amps
v volts
Ia = If + IL amps
IL Amps
If Amps
v volts
Ia = If + IL amps
Conclusion:
Department of Electrical and Electronics Engineering
15
16
17
Experiment No.03
Hopkinson's test
AIM: To conduct Hopkinson's test on a pair of identical machines and to calculate their
efficiency
CIRCUIT DIAGRAM
Generator:
Apparatus Required:
Circuit
Ref.
A1,A3,A4
A2,A5
V1,V2
Rfm
Rfg
Ram
S1
Description
Rating
Quantity
0-20A
0-2.5A
250V/500V
200, 1.7A
500, 1.2A
50, 5A
220V , 16A
3
2
2
1
1
1
1
18
THEORY: This is also called as regenerative test, which is carried out preferably on a pair of
identical machine. These are mechanically coupled and are so adjusted electrically that one of
them act as a motor and other acts as a generator. The motor supplies the mechanical power
required to drive the generator, while the electrical power developed in the generator
is utilized in the motor, resulting in no wastage of their outputs.
Thus two machine of any size can be tested under full load condition and power taken from the
supply will be that required to overcome the losses only. The method is therefore invaluable
where tests of long duration under full load condition have to be made on very large machines.
Such test is called heat runs, because the aim of the test is to determine the final temperature
rise. Regenerative tests were first introduced by HOPKINSON and hence the name
HOPKINSONS TEST.
Merits of HOPKINSONS TEST:
a.
The power required for this test is small as compared to full power of the two machine.
b.
Since the machine are tested under full load conditions, results can be more accurate as
regards to temperature rise and commutation quantities
Procedure
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
19
I (Amps)
Ra = V/I
Ohms
20
Inference:
Hopkinsons test
N = __________rpm
Sl.
No.
IL
Amps
Ifm
Amps
Iam
Watts
Ifg Watts
Iag
Watts
V volts
Efficiency of generator
Output (
Watts)
Losses (watts)
Input = output +
losses
Efficiency of Motor
Input (
Watts)
Losses (watts)
Calculations:
Power drawn by supply = V1 X IL =____________Watts
Motor armature copper losses = Iam2X Rarm =____________Watts
Motor field copper losses = V1X Ifm =____________Watts
Total motor loss = Iam2 X Rarm + V1 X Ifm=____________Watts
Generator armature copper losses = Ifg2 X Rarm =____________Watts
Generator field copper losses = V2X Ig =____________Watts
Total generator loss = Ifg2 X Rarm + V2X Ig =____________Watts
Department of Electrical and Electronics Engineering
21
Total stray losses of the two machines (W) = V1 X IL [ (V1X Ifm + Iam2X Rarm) +( V2X Ig + Ifg2
X Rarm)] =____________Watts
Assumeing stray losses to be equally distributed in both the machines, stray losses in each
W
machines =
=____________Watts
2
Efficiency of the motor = (Motor input losses)
Motor input
Generator output
(Generator output + losses)
Conclusion:
22
23
Experiment No.04
Field test on a DC Series motor
Aim: To conduct Field test on DC Series motor.
CIRCUIT DIAGRAM
Generator:
Apparatus Required:
Circuit
Ref.
A1,A2
V1,V2,V3
R1
Description
Rating
Quantity
0-20A
0-250V
18, 12A
2
3
1
Theory: There are three ways of exciting the DC motor; these are series, shunt and compound,
and the characteristics of a motor are determined by the method of excitation. In case of DC
series motor, the flux varies with the motor current and the speed is inversely proportional to flux
and hence the series motor is essentially a variable speed motor. The speed being low on heavy
loads and dangerously high on light loads and for this reason, the DC motor should never be run
with-out load. No-load tests are impossible because of the dangerously high speed attained by
the series motor and hence, tests such as swinburns test, can-not be performed on large size DC
series machines. In view of this field test is quite suitable for DC series machines, because DC
series machines are used for traction purposes and are therefore usually available in pairs.
Department of Electrical and Electronics Engineering
24
In this test two similarly dc series machines are required. These two series machines are
mechanically coupled and their fields are connected in series, in order to make Iron losses of
both the machines equal. This necessitates equal excitation and this is achieved by connecting
the fields in series. One of the machine operates as a motor and drives the other machine
operating as a separately excited generator, the output of the latter being wasted in the adjustable
load R. The connection of the field windings of motor and generator in series, ensures that the
stray losses in each machine will be the same. It should be noted that Fields test is not a
regenerative test, because output of the generator is not fed back to the motor, but is dissipated in
the resistor R.
Procedure
1. Connections are made as shown in the circuit diagram.
2. Keep rheostat R1 cut in and apply at least 50% of load to the generator before
Starting.
3. Switch on the DC supply and start the motor, ensure the direction of rotation.
4. If the motor rotates in the opposite direction stop the motor and interchange the field
connections and repeat the above steps.
5. Cut out resistance R1 completely and bring the motor to the rated speed.
6. Vary the load till the motor current reading reaches its full load value.
7. Simultaneously note down the ammeter and voltmeter readings.
8. With load switches in ON position only the machine is switched off.
9. Cut in the rheostat R1.
10. Switch off the supply.
11. Measure the resistance of the series field winding and armature winding of both the
motor and generator separately.
Observations
Field test:
V1
Volts
V2
Volts
V3
Volts
N rpm
Iam
amps
Iag
amps
% m
% m
25
The stray losses and efficiency of the motor and generator are calculated as follows
Calculations:
Input of motor = VmIam = ________Watts
Output of generator = VgIag =________Watts
Total Losses = W1 = Input Output = VmIm VgIag =________Watts
Motor armature copper loss Wcam = Iam2Ram =________Watts
Motor or Generator field copper loss Wcag or Wcfm = Iam2Rmf =________Watts
Generator armature copper loss Wcag = Iag2Rag =________Watts
Total copper loss WC = Wcam + 2 Wcfg + Wcag =________Watts
Stray Losses Ws = Wt Wc =________Watts
Total losses of the motor Wm= (Wcam + Wcfm) = Ws =________Watts
Output of the Motor = Input Total losses = VmIm - Wm =________Watts
Efficiency of motor = (output of motor) / (Input of motor) =________Watts
Total losses of Generator Wg = Wcag + Wcfg + Ws =________Watts
Input of Generator = Output of Generator + Total losses, Wg
Efficiency of Generator = (Output of Generator)/ (Input of Generator) * 100 =______%
Conclusion:
26
27
Experiment No.05
Swinburne's Test
AIM: To determine the efficiency at any load by conducting Swinburnes test.
CIRCUIT DIAGRAM
Apparatus Required:
Circuit
Ref.
A1
A2
V1
Rfm
Ram
Description
Moving coil ammeter
Moving coil ammeter
Moving coil voltmeter
Rheostat
Rheostat
Rating
0-10A
0-2.5A
0-250V
200, 1.7A
50, 5A
Quantity
1
1
1
1
1
Theory: The methods of testing electrical machines can be divided in to 3 classes, direct,
indirect & regenerative. In the direct method, the motor or generator is put on full load and the
whole of the power developed is wasted & this is especially, so in case of large machines. The
indirect method consist of determining the losses and predetermining the efficiency from this
data. The amount of power required thus is to supply the losses only, so that there is no difficulty
Department of Electrical and Electronics Engineering
28
in applying the method even to very large machines. The only disadvantage is that the machine is
running light during the test so that, all though the efficiency is calculated fairly accurate, it does
not reflect the performance to the machine during temperature raise or to the commutation
qualities of the machine. Swinburns test is simplest one such indirect method in which losses are
measured separately and from this efficiency at any load is predetermined later on. The machine
is made to run under no load. This test applicable to shunt and compound machines, where the
flux remains constant.
The motor is run at its rated speed by applying the rated voltage under no load. The armature
resistance is found decreased slightly by increasing armature current because of the fact that
brush contact resistance is approximately propositional to the armature current.
Following are the advantages and disadvantages of this test.
The advantages of this test are.
1. It is convenient and economical because power required to test large machine is small i.e
only no load input power.
2. The efficiency can be pre-determine at any load because constant losses are known.
The disadvantage of this test are.
1. No account is taken of the change in iron losses from no load to full load. At full load
flux gets distorted due to armature reaction resulting in more iron losses.
2. As test is on no load we cannot know whether commutation is satisfactory at full load and
weather temperature rise is within specified limit.
Procedure
1. Connections are made as shown in the circuit diagram.
2. Keep Ram in cut in position and Rfm in cut out position.
3. Close the supply switch starts the DC motor bring the motor to the rated speed by Cut-out
Ram and cutting in Rfm.
4. Note down all the meter readings and are tabulated.
5. Armature resistance is found out by VA method and calculations are carried out to obtain
efficiency of DC machines when running as a motor and as a generator.
6. A graph of efficiency v/s different loading is plotted for motor and generator.
29
V (Volts)
I (Amps)
Ra = V/I
Ohms
ILO = ______
Ifo = ________
CALCULATION:
Specimen calculation to calculate efficiency of machine when running as MOTOR:
The of the ;machine when running as a motor for different % of loading is given by,
[X is fraction of load]
[ Ir is rated current of the machine]
= __________%
Fraction of load X %
30
[X is fraction of load]
=_______%
Fraction of load X %
Conclusion:
31
32
33
Experiment No.06
Ward Leonard method of speed Control of a DC motor
AIM: To control the speed of DC motor by Ward Leonard speed control method.
CIRCUIT DIAGRAM
DC generator:
DC Motor:
Apparatus Required:
Circuit
Ref.
Description
Rating
Quantity
V1
Rfm
Rfg
R2
S1
0-250V
200,1.7A
500,1.2A
50,5A
16A
1
1
1
1
1
Theory: This method is commonly used where a very delicate speed control over the whole
range from zero to full speed is required, such as in paper mills, elevators, colliery, winders etc.
The method consist simply in working the motor with a constant excitation and applying to its
armature sufficient voltage to get the required speed. i.e. the field of the main motor, whose
speed is to be controlled is connected permanently against the fixed supply terminals and the
supply voltage for this main motor is obtained from a motor generator set.
The variable voltage of the generator can be obtained by varying the resistance in its field
circuit. Thus the applied voltage to the main motor can be changed from zero to maximum value.
The direction of rotation of main motor can also be reversed. Although the system requires a
Department of Electrical and Electronics Engineering
34
large capital for providing a MG set, but it is still preferred as it gives very fine and unlimited
speed control in either direction of rotation.
Procedure
Reverse direction
N rpm
V Volts
N rpm
Conclusion:
Department of Electrical and Electronics Engineering
35
36
37
Experiment No.07
Load test of a DC motor-determination of speed-torque and
HP-efficiency characteristics.
AIM: To draw the load characteristics of DC shunt motor
CIRCUIT DIAGRAM
Apparatus Required:
Circuit
Ref.
A1
A2
V1
Rfm
Ram
Description
Rating
Quantity
0-20A
0-2.5A
0-250V
200, 1.7A
50, 5A
1
1
1
1
1
38
THEROY:
A motor is a device which converts electrical energy into mecha nical energy . in Dc shunt
motor, the field winding is connected in parallel with the armature winding and the combination
is connected across the supply, one of the characteristic of Dc shunt motor is the speed torque
characteristic. Its the mechanical characteristic of the DC motor. The curve of speed torque
characteristic remains constant though torque changes from no-load to full load is small. DC
shunt motor is called constant speed motor because as long as supply voltage is constant, flux
produce is also constat hence the speed. Therefore it has wide applications and is used in
blowers, fans, centrifugal and reciprocating pumps, lathe machines, machine tools, milling
machines, drilling machines.
PROCEDURE:
1. Connction are made as shown in circuit diagram.
2. The rheostat Ram is kept in CUT-IN position and Rfm is CUT-OUT position.
3. Close the supply switch and start the DC motor.
4. CUT-OUT the armature rheostat Ram slowly and completely.
5. CUT-IN the motor field rheostat slowly until the motor reaches the rated speed.
6. Note down the initial readings of all the meters.
7. Now load the motor (machanical loading) in steps nearly to its rated current.
8. For each loading all the meter reading and speed of the motor are tabulated.
9. Release all the loads.
10. Reduce the speed by keeping Rfm in CUT-OUT position and Ram in CUT- IN position
and open the supply switch.
11. Torque, BHP and efficiency of the motor are caculated using formula.
12. The graph - % versas BHP - N versas Torque is plotted
Tabular coulmn
Sl.no V in Load
volts current
in amps
W1
Kg
W2
Kgs
W = (W1W2)
in Kgs
Tsh
= N
Output=
9.81xWxR rpm Tsh 2N
N-m
60
Watts
% =
Output
Input
39
Calculation:
Motor input = VxI=______ Watts
Motor output =
Tsh 2N
Watts
60
Conclusion:
40
41
Experiment No.08
Retardation test electrical braking method.
AIM: To determine the stray losses of the Dc machine.
CIRCUIT DIAGRAM
Description
Moving coil ammeter
Moving coil voltmeter
Rheostat
Rheostat
DPDT Switch
Stop Watch
Rating
2.5A/5A
250V/500V
200,1.7A
50,5A
16A
Quantity
1
1
2
1
1
1
Theory: This is also one of the indirect method of testing DC shunt machines where is the
separation of losses can be conveniently found.
The machine is made to run up to a little way beyond the normal speed and the supply to the
motor is switched off, while keeping the field excited. As a result, the armature slows down and
its kinetic energy is used to supply the various stray losses ( iron, friction and windage losses)
produced by rotation. Hence this test is also called as RUNNING DOWN TEST.
42
Procedure
1. Connections are made as shown in the circuit diagram.
2. Keep shunt field resistance Rfm in cut-out position and resistance in series with the motor
armature Ram, in cut-in position.
3. Keep SPDT switch in position 1
4. By cutting out slowly armature rheostat (Ram ) the speed is built up and cutting in Rfm of the
motor the speed is built up to slightly more than its rated speed.
5. Now open the SPDT switch and hence speed of the motor and the voltage across the armature
false down.
6. The time taken to drop in voltage say about 50 V is noted down.
7. Experiment is repeated for different drop in voltage and corresponding time required (T1) is
tabulated. (Example: 220V-170V, 220V-120V, 220-70V, 220V-0V)
8. Graph is plotted voltages time taken required drop.
9. Now experiment repeated as given as steps2 to 5 by throwing the SPDT switch on position 12side i.e. cut of armature supply and include the load in the circuit.
10. Again time (T2) taken to drop in voltage and corresponding current is noted down
simultaneously
11. Graph of voltage verses current is plotted and average current is obtained.
12. The average drop and average current product will give the electrical losses.
Tabular columns
Without load
Sl V1 Voltage
No drop in volts
With load
Time T1 in
seconds
Sl
No
V2 Voltage
drop in volts
Time T2 in
seconds
I1 in I2 in
amps amps
1.
1.
2.
3.
4.
2.
3.
4.
Where,
T1 is time required to drop in required voltage of V1 (without load)
T2 is time required to drop in required voltage of V2 (with load)
I1 is initial current when SPDT thrown from 1-2 position (towards the load)
I2 is the final current when voltmeter reading comes near the final voltage.(example:220V is the
initial voltage and 170V is the final voltage)
43
Calculations
W1 = V * I (watts)
= average value of drop in voltage value of corresponding current
=____________V
WITH LOAD
WITH OUT LOAD
V1
V1
V2
VOLTAGE
T1>T2
V2
Vt
T2
T1
TIME
I1
I2
I
Conclusion:
44
45
Experiment No.09
Slip test
Aim : Determination of Xd and Xq for an alternator and thereby to determine the regulation of the
alternator.
CIRCUIT DIAGRAM
Apparatus Required:
Circuit
Ref.
A2
V1, V2
Rfm
Ram
AT1
Description
Rating
Quantity
0-5A
0-250-500V
200,1.7A
50,5A
0 - 470V, 10A
1
2
1
1
1
46
Theory:
the effect of armature reaction, fluxes and induced emf are assumed to be constant because of
uniform air gap in a synchronous machine with a cylindrical rotor. However a salient pole
synchronous machine has non uniform air gap because of which its reactance varies with the
rotor position. Thus the salient pole machine possesses two axes of geometric symmetry.
1. Field pole axis called direct axis or d axis.
2. Axis passing through the centers of inter polar space called the quadrature axis or q
axis.
In case of a cylinderical rotor machine there is only one axis of symmetry ( pole axis or direct
axis). Hence in case of salient pole machines, the reluctance of the magnetic path are different
along the direct axis and q axis. The reluctance of the magnetic circuit on the d axis is due to
yoke, teeth of the stator, pole and air gap, and core of the rotor. In quadrature axis the reluctance
is mainly due to large air gap in the inter polar space. Because of the non uniformity of the
reluctance of the magnetic path the mmf of the component is divided into two components
namely a) a direct acting component b) a quadrature acting component. When the armature is in
phase with the excitation voltage, the entire mmf of the armature acts at right angles to the axis
of the salient pole and therefore all the mmf is in quadrature. On the other hand if the armature
current is in quadrature with the excitation voltage, Eo then the entire mmf of the armature acts
directly upon the magnetic paths and thus all the armature mmf is direct acting.
In an alternator excitation is given to the field winding and voltage gets induced in the armature.
But in slip test a three phase supply is applied to the armature having the voltage much lesser
than the rated voltage while the field circuit is kept open. The alternator is run at a speed close to
the synchronous speed. The three phase current drawn by the armature from the three phase
supply produces a rotating magnetic field. This is similar to the rotating magnetic field existing
in a induction motor, since the armature is stationary. When the stator mmf is aligned with the
axis of the pole the effective reactance offered by the alternator is Xd. when the stator mmf is
aligned with the q axis of the poles then the effective reactance offered by the alternator is Xq.
Procedure
1. Connections are made as shown in the circuit diagram. The field of the alternator is open.
The motor armature rheostat is cut in and the field rheostat is cut out.
2. The AC main supply switch is closed. And vary the autotransformer till the voltmeter
across the field winding reads about 80V
3. The DC motor is started observe that volt meter across the field winding decreases so as
to ensure the correct phase sequence
4. Bring the motor to the rated speed.
5. The applied voltage is increased (say around 150V) until the ammeter of the armature of
alternator reads the rated current.
6. By varying the field rheostat of the DC motor, the speed is slightly reduced by 2-3% of
the rated speed.
7. Oscillations are observed in the ammeter and voltmeter. The speed is adjusted until the
oscillations are maximum.
8. The maximum and minimum values of the ammeter and voltmeter are noted down.
Department of Electrical and Electronics Engineering
47
9. The applied voltage is reduced. The motor speed is reduced and the main supply switch
opened.
10. The armature resistance per phase is measured.
Inference
Imax =
Imin =
Vmax =
Vmin =
Measurement of armature resistance
Connect a low voltage power supply with current limiting to the armature winding as shown in
fig. Apply different voltages and measure the current flowing through the armature winding for
each voltage. The ratio of V/I gives the resistance
V (Volts)
I (Amps)
Ra = V/I
Ohms
Calculations
Direct axis synchronous impedance Zd
Zd =
Qudrature axis synchronous impedance
Zq =
Department of Electrical and Electronics Engineering
48
Determination of regulation:
Therefore, % Regulation = (
Xd =
) x 100
Xq =
Zq
Conclusion:
49
50
51
Experiment No.10
V and inverted V curves of synchronous motor
Aim: To obtained V and curves of synchronous motor.
Apparatus:
Circuit
reference
A1
A2
V1
W1,W2
Rfm
Description
Rating
Quantity
0-2.5 A
0 -10 A
0 -500 V
10 A, 600 V
400, 1.7 A
1
1
1
2
1
52
THEORY: Synchronous motor is a machine that operates at synchronous speed and has wide
applications as regards to (i) power factor correction (ii)Voltage regulation (iii) Constant speed
Constant load drives. The main drawback of the synchronous motor is that it is inherently not
self starting and needs a prime mover to starts. This drawback can be addressed by providing a
special winding on the rotor poles called the damper winding or squirrel cage winding. The
damper winding consists of short circuited copper bars embedded in the face of the field poles.
Therefore when Ac supply is fed to the stator in the beginning, the motor starts as a squirrel cage
induction motor because of the presence of damper winding. The exciter moves along the rotor.
As soon as the motor attains 95 % of the rated speed, the rotor is energized with DC. Now the
rotor is magnetically locked with the stator rotating magnetic field and thus motor runs at
synchronous speed. These motors can be constructed with wider air gap than induction motor,
which make them better mechanically.
Application:
1. In substation and power houses in parallel to the bus bars for PF improvement. For this
purpose they are run on without load and are over excited
2. In factories having large numbers of induction motor for power factor improvement.
3. For voltage regulation at end of the transmission line.
4. Because of constant speed independent of the load, it can be used to drive another
alternator to generate a supply at different frequency.
In case of a synchronous motor driving a constant load, variation in the field
current affects not only PF but also current drawn by the motor.
The power drawn by synchronous motor is given by P = 3 VLILcos
Since input power P and supply voltage V are constant, any decrease in the power factor causes
increase in armature current and vice versa. The curves drawn between the armature current and
field current for different constant loads are known as V curves due to the shape of the English
letter V. The V curve of the synchronous motor gives the relation between armature current and
field current for different power inputs. Similarly, the variation of power factor with a variation
in field current (DC excitation) for a constant load gives inverted V curves. From V-curves it is
observed that with low value of field current the armature current is large and lagging. As the
field current increases the pf increases and armature current decreases and reaches its minimum
value. When armature current is minimum, the pf is unity and corresponding field current is
known as normal field current or excitation of the motor for that particular load. The region in
which the field current is less then its normal value is known as region of under excitation or
region of lag. The field current is more then normal value or armature current is known as region
of over excitation or region of lead.
53
Procedure:
1. Connections are made as shown circuit diagram.
2. Now close the AC supply switch and ensure proper direction of rotation of the motor.
3. Close the DC supply switch with the field rheostat completely cut-in, thus exciting the
field of the synchronous motor. Let the motor run on no-load.
4. Synchronous motor runs at synchronous speed.
5. Now vary the excitation of the synchronous motor in steps by varying the field rheostat.
6. Note down the corresponding reading .
7. Further variation of field excitation cause line current to reach to its minimum and
increases from minimum to higher values of load current.
8. Care has to be taken to see that excitation should not be increase further beyond the rated
value.
9. Reduce the excitation to a minimum and repeat the procedure step 5 to 8 for different
loads.
Observations:
Without load
If in
Amps
Ia in
Amps
W1 in
watts
With load
W2 in
watts
If in
Amps
Ia in
Amps
W1 in
watts
W2 in
watts
54
Ideal graph:
WITH LOAD
UPF
WITH OUT
LOAD
Ia
Cos
WITH OUT
LOAD
UNDER EXCITATION
REGION
WITH LOAD
OVER EXCITATION
REGION
If
If
Conclusion:
55
Experiment No.11
Regulation of an alternator by EMF and MMF method
Aim: To determine the voltage regulation (by EMF and MMF method) by conducting open
circuit and short circuit test on a given alternator.
Alternator:
Apparatus Required:
Circuit
Ref.
A1
A2
V1
Rfm
Ram
R1
S1
Description
Rating
Quantity
0-2.5A
0-10A
0-500V
200,1.7A
50,5A
500,1.2A
32A/220V DC
1
1
1
1
1
1
1
56
It should be noted that voltage raise in the terminal voltage when the full load is thrown off is
not the same as the full load terminal voltage when the full load is applied.
The change in the terminal voltage of an alternator with the change in load supplied by it, is due
to the following reasons
I.
Voltage drop on account of armature effective resistance.
II.
Voltage drop on account of armature leakage reactance.
III.
Voltage drop on account of armature reaction.
To determine the regulation of an alternator, open circuit and short circuit tests are to be
performed. Before these tests are conducted it is necessary to know about synchronous reactance,
synchronous impedance, effective resistance etc.
synchronous reactance- The emf setup due to armature reaction MMF is always in quadrature
with the Load current I and is proportional to it. Thus it is equivalent to an EMF induced in an
inductive coil and the effect of armature reaction can therefore considered as equivalent to
reactance drop IXa , where Xa is the fictitious reactance. The armature winding possesses of a
certain leakage reactance XL. The sum of leakage reactance XL fictitious reactance Xa is called
as the
Xs=XL + Xa.
Effective Resistance of the armature winding is somewhat greater than conductor resistance,
called the dc resistance as measured by direct current. This is due to additional losses, over the
purely I2R loss, inside some time outside the conductor, owing to alternating current. The main
source of this additional loss is. 1 ) Eddy currents in the surrounding material, 2 ) magnetic
hysteresis in the surrounding material. 3) Eddy currents OR unequal current distributions in the
conductor itself. Hence it is sufficiently accurate to measure armature resistance by dc and
increase it to a fictitious value say effective resistance, Re which varies widely from 1.25 to 1.75
times more than the DC resistance.
Synchronous impedance - when the Synchronous reactance Xs is combined with armature
effective resistance Re, quantity obtained is called synchronous impedance
Zs = Re + j Xs
Open circuit test: The machine is made to run to its rated speed, by keeping the armature
winding open. With field current raised in suitable steps, until voltage between any pair of
armature terminals little above the rated EMF and corresponding values of V (no-load voltage)
are noted. the Open Circuit voltage per phase, Eo are obtained by dividing the voltmeter readings
by 3 .A curve is drawn between Eo and field current If and is known as open circuit
characteristics. The initial straight part of curve yields the air gap characteristics since at that low
Excitation, reactance offered by core is negligible.
Short circuit test: in this test all the three phases are shorted and since the current in all the three
phases are equal, it is enough to measured current in any one phase. Rheostat of sufficiently high
Ohmic value is inserted in the DC field circuit, to keep the current very low. The machine is run
at synchronous speed and the field excitation is so adjusted to circulate 150 to 200% of full load
current .the short circuit characteristics is drawn by plotting a curve between SC current Isc and
If.
Department of Electrical and Electronics Engineering
57
Synchronous impedance method OR EMF method:The regulation obtained in this method is always higher than actual values, because here Zs is
assumed to be constant, but it is not so. Hence this method is called pessimistic method. This
method is theoretically accurate for non-salient pole machines.
MMF method OR Ampere- turn method:In this method the data obtained from open circuit test are utilized. This method of determining
synchronous impedance is known as optimistic method since it gives values lower than actual
values. The reason being that the excitation to overcome armature reaction is determined on
unsaturated part of the saturation curve.
Procedure for EMF and MMF method:
Open circuit test:
1. Connections are made as shown in the circuit diagram.
2. Armature rheostat Ram is kept in cut-in and Field rheostat of DC motor is kept in cut-out
position. The field rheostat of alternator is kept in cut-in position.
3. Supply is given to the DC motor by closing the switch S1 and the DC motor is started.
4. Bring the motor speed to that of the rated speed of synchronous machine.
5. Close the DPST switch to excite the field of the alternator.
6. Rheostat of the alternator field is cut-out gradually in steps and the corresponding field
current (If) and open circuit voltage of the alternator are tabulated, till the rated voltage of
the synchronous machine is reached.
7. The field rheostat of the alternator is brought back to its original position.(Cut-in
position)
Short circuit test:
1. The TPST switch is closed, so that the stator terminals are short circuited.
2. Field rheostat of alternator is cut-out gradually in steps and at each step armature current
(Ia) and corresponding field current are noted till rated armature current is obtained.
3. Field rheostat of alternator is brought back to cut-in position and DPST switch is open.
4. Armature rheostat & Field rheostat of the motor is brought back to their original position.
5. Supply is switched off.
6. The DC resistance(Rdc) per phase of the stator winding are measured by VA method.
Tabular column:
Open circuit test:
Sl. No.
Vph in volts
Sl. No.
If in amps
Isc in amps
58
TYPICAL GRAPH
Calculation:
EMF method or synchronous impedance method:
Voc
= ______
Isc
Zs =
Ra =_______
Xs =
=________
Eo =
[Note: +
= _______ Volts
for lagging PF
Percentage regulation =
Eo Vph
X 100 = ________%
Vph
Amps
If2 Field current required to circulate the rated armature current during short circuit
If2 =
Amps
3. Ift =
+
_
Department of Electrical and Electronics Engineering
leading pf.
59
4.
% Regulation=
For each voltage E1 , If1 is noted from the graph
For each IfT , E is noted from the graph.
% Reg (lead)
0.2
0.4
0.6
0.8
1.0
Conclusion:
60
61
Experiment No.12
Voltage regulation of an alternator by ZPF method
Aim:- To determine the regulation of an alternator by Z.P.F. method
CIRCUIT DIAGRAM
Alternator:
Apparatus Required:
Circuit
Ref.
Description
Rating
Quantity
A1
A2
V1
Rfm
Ram
R1
S1
L1
0-2.5
0-10A
0-500V
200,1.7A
50,5A
500,1.2A
32A/220V DC
10A
1
1
1
1
1
1
1
1
62
Theory : this method is also called as Potier method of determining the voltage regulation of
an alternator. This method is more accurate than EMF and MMF methods of determination of
voltage regulation. This method is based on the separation of reactances due to leakage flux and
that due to armature reaction flux, therefore it is more accurate, whereas EMF and MMF
methods are based on the total synchronous reactance. In this method XL is called Potier
reactance and hence the name Potier reactance method. The data required for determination of
voltage regulation by ZPF method are
Procedure:
1. Connection is done as per circuit diagram.
2. The open circuit test and short circuit test results conducted as per EMF and MMF
method are used.
3. The machine is run at synchronous speed by the prime mover.
4. Close the DPST switch to excite the field of the alternator, Rated voltage is built up by
varying the excitation.
5. Now close the TPST switch and connect the purely variable inductive load across the
armature terminal.
6. The value of the reactance is then adjusted and the excitation is varied in such a way that
the rated full load current by maintaining rated voltage and rated speed.
7. Note down the corresponding meter readings.
8. Decrease the inductive load as well the excitation by maintaining rated speed. And open
the TPST Switch.
9. Field rheostat of alternator is brought back to cut-in position and DPST switch is open.
10. Armature rheostat & Field rheostat of the motor is brought back to their original
position.
11. Supply is switched off.
12. Plot a graph between the terminal voltage and excitation current as shown in fig. (a) will
give ZPF characteristics.
Observation:
ZPF test
63
Procedure to draw ZPF characteristics: ZPF full load voltage excitation characteristics can be
drawn by knowing two points A and B. point A is obtained from the short circuit test with full
load armature current. Hence OA represents excitation (Field Current) required to overcome the
de-magnetization effect of armature reaction and to balance leakage reactance drop at full load.
Point B is obtained when full load current flows through the armature and wattmeter reads zero.
From B line BC is drawn equal and parallel to AO. Then a line is drawn through C parallel to
initial straight part of OCC (parallel to OG), intersecting the OCC at D. BD is joined and a
perpendicular DF is dropped on BC. The triangle BFD is imposed on various points of the OCC
to obtain corresponding points on the zero factor curve. In triangle BDF, the length BF
represents armature reaction excitation and length DF represents leakage reactance drop IXL.
This is known as Potier Reactance voltage. The Potier reactance is given by
XP =
Fig (a)
Potier regulation diagram: this diagram is drawn as fallows
64
x 100
E0
I2
I1
E
90
IXL
90
V
I
Conclusion:
65
Experiment No.13
Performance of synchronous generator connected to infinite
bus, under constant power and variable excitation
& vice versa.
AIM: To determine the characteristic of Armature current Vs field current and power factor Vs
field current for fixed power and the characteristic of power factor Vs power and armature
current Vs power, for fixed excitation in an alternator.
CIRCUIT DIAGRAM
Alternator:
Apparatus Required:
Circuit
Ref.
A1
A2
V1
W1,W2
Rfm
Ram
R1
SP
Description
Moving coil ammeter
Moving iron ammeter
Moving coil Voltmeter
Watt meters
Rheostat
Rheostat
Rheostat
Synchronizing panel
Rating
0-2.5A
0-10A
0-500V
10A-600V
200,1.7A
50,5A
400,1.7A
Quantity
1
1
1
2
2
1
1
1
66
Theory: In most of power stations (whether DC or AC), it will be found that the power is supplied from
several smaller units (generators) operating in parallel rather than form a single larger unit capable of
taking care of the maximum peak loads. There are a number of good reasons for this practice. The
demand for electrical energy continues to grow at steady space, electrical utilities and other find it
necessary to increase generating capacity at regular intervals. Since it is not economical to discard
serviceable alternator in favour of larger ones, it becomes necessary to operate alternators in parallel. This
provides greater reliability improves efficiency, facilitates repairs and maintenance and makes the supply
of load possible when demands exceeds the capacity of largest single unit available.
Conditions for parallel operation:
1. Terminal voltage of the incoming machine is equal to that of the others (Infinite bus)
2. The frequency of the incoming machine is mach with the bus bar frequency.
3. Phase sequence of the incoming machine voltage must be as same as that of the bus bar voltage.
The behavior of the alternator when running in parallel is quite different from its performance when
operating in the stand alone mode. The underlying principle when operating on infinite bus is that the
excitation controls the reactive power output and power factor where as the power input from the prime
mover controls the active power output and the power angle of the alternator.
At constant power: If the excitation of the alternator is reduced, to make up for the required air gap flux,
the armature current is delivered at a leading power factor as leading power factor armature current is
known to have a magnetizing armature reaction effect. Hence, as the excitation is gradually increased
from a small value, the power factor becomes unity and for further increase if excitation becomes lagging,
i.e. an overexcited alternator delivers lagging armature current. For a fixed power, the product of armature
current and its power factor should be constant. Hence, the change of armature current magnitude is
inverse to the change in the magnitude of power factor, as the excitation is increased. Obviously, the
minimum armature current occurs at the maximum power factor i.e, at unity power facor.
With constant excitation: When the power input is increased there will be commensurate increase of
power output from the alternator i.e. the active component of armature current increases, whereas the
reactive component remains fairly constant since the excitation remains constant. Consequently, the
power factor increases with an increases of power input at constant excitation.
Procedure
1.
2.
3.
4.
5.
67
8. Close the switch on the synchronizing panel. The alternator is now synchronized to the infinite
bus.
9. Vary the excitation of the alternator by varying R1 until alternator reaches its rated current. Note
down the readings of the meters. Do not vary the prime mover field.
10. Decrease the alternator current by varying alternator field excitation by ensuring 0 armature
current open the synchronizing switch, TPST2.
13. Armature rheostat & Field rheostat of the motor is brought back to their original position.
14. Supply is switched off.
Observations:
Input current to DC motor = I (read from A1)
Input voltage to DC motor = Vs (read from V1)
Field current of alternator = If (read from A2)
Armature current of alternator = Ia (read from A3)
Line to line terminal voltage of alternator = V (read from V2)
Three phase power delivered by alternator = W1 + W2
tan=
Three phase reactive power Q = VIaSin
Constant power
If (amps)
Ia (amps)
W1
(watts)
W2
(watts)
P = W1 +
W2
(watts)
Cos
IaCos
Q (vars)
Conclusion:
68
69
How do we conclude that connections between field coils and armature of a generator are
corrected?
The series field winding has low resistance while the shunt field winding has high
resistance why?
How can one differentiate between cumulative compound and differential compound
generator?
Why is field control considered superior to armature resistance control for DC shunt
motor?
70
What is armature reaction? And what are the methods used to reduce armature reaction?
What are inter poles and how do they neutralize cross magnetizing effect?
If the load is removed from a DC series motor in operation, what will happen?
71
Based on the construction, name the two types of constructions employed in synchronous
machines?
Which type of synchronous generators are used in hydro electric plants and why?
Name the various methods for pre-determining the voltage regulation of three phase
alternator.
What are the advantages and disadvantages of estimating the voltage regulation of an
alternator by EMF method?
Name the method with which leakage reactance of an alternator can be separated.
What is the effect on speed if the load is increased on a three phase synchronous motor?
What are direct and quadrature axis in salient pole synchronous machines?
Why is ZPF method better than when compared with EMF and MMF method?
72