Modbus is a common industrial protocol used for communication between automation devices. It was originally developed in 1979 for serial communication but now supports TCP/IP and UDP networks. Modbus follows a request-response master-slave architecture and uses function codes to access and modify data in different memory ranges like coils, holding registers, and input registers. The LabVIEW Modbus API provides low-level control for sequencing requests while Modbus I/O servers provide a higher-level method of automatically communicating with devices.
Modbus is a common industrial protocol used for communication between automation devices. It was originally developed in 1979 for serial communication but now supports TCP/IP and UDP networks. Modbus follows a request-response master-slave architecture and uses function codes to access and modify data in different memory ranges like coils, holding registers, and input registers. The LabVIEW Modbus API provides low-level control for sequencing requests while Modbus I/O servers provide a higher-level method of automatically communicating with devices.
Overview The Modbus industrial protocol was developed in 1979 to make communication possible between automation devices. Originally implemented as an application-level protocol intended to transfer data over a serial layer, the protocol has expanded to include implementations over serial, TCP/IP, and the user datagram protocol (UDP). Today, it is a common protocol used bycountless devices for simple, reliable, and efficient communication across a varietyof modern networks. Table of Contents 1. The Request-Response Cycle 2. The Modbus Data Model 3. Modbus Function Codes 4. LabVIEW Modbus API 5. Modbus I/O Servers 6. NI OPC Servers With OPC I/O Servers or OPC UA Introduction to Modbus Modbus is typicallyused for SupervisoryControl and Data Acquisition (SCADA)-style network communication between devices. For example, a large server maybe used to master a programmable logic controller (PLC) or programmable automation controller (PAC), while that PLC/PAC mayin turn master a sensor, valve, motor, or anyother embedded device. To meet these needs, Modbus was designed as a request-response protocol with a flexible data and function modelfeatures that are part of the reason it is still in use today. 1. The Request-Response Cycle The Modbus protocol follows a master and slave architecture where a master transmits a request to a slave and waits for the response. This architecture gives the master full control over the flow of information, which has benefits on older multidrop serial networks. Even on modern TCP/IP networks, it gives the master a high degree of control over slave behavior, which is helpful in some designs. Figure 1. The Master-Slave, Request-Response Relationship of Modbus Devices In Modbus, this request is a layered set of data. The first layer is the application data unit (ADU), which is what most people consider to be the typeof Modbus used. There are three ADUs: ASCII, remote terminal unit (RTU), and TCP/IP. TCP is a modern format that allows for efficient handling of Modbus requests and responses in software, as well as more efficient networking through the use of dedicated connections and identifiers for each request. RTU and ASCII are older serial ADU formats with the primarydifference between the two being that RTU uses a compact binaryrepresentation while ASCII sends all requests as streams of ASCII characters. For most applications, the preferred ADU depends on the desired physical network (Ethernet, serial, or something else), the number of devices on the network, and the ADUs supported bythe master and slave devices on the network. From the point of view of the application using Modbus, data should simplybe exposed as if the ADU did not exist. Within each ADU, there is a protocol data unit (PDU) that is the core of the Modbus protocol. Each PDU contains a function code and associated data. Each function code has a well-defined response, and you can think of this function code as the command being sent to the slave. In some cases, errors can occur. Modbus defines a specific PDU for exceptions, which lets the master know what happened. Most drivers convert this to a form that makes sense for the language or application in use. 2. The Modbus Data Model Modbus manages the access of data simplyand flexibly. Natively, Modbus supports two data types: a Boolean value and an unsigned, 16-bit integer. In SCADA systems, it is common for embedded devices to have certain values defined as inputs, such as gains or proportional integral derivative (PID) settings, while other values are outputs, like the current temperature or valve position. To meet this need, Modbus data values are divided into four ranges (see Table 1). A slave can define as manyas 65,536 elements in each range. Memory Block Data Type Master Access Slave Access Coils Boolean Read/Write Read/Write Discrete Inputs Boolean Read-only Read/Write Holding Registers Unsigned Word Read/Write Read/Write Input Registers Unsigned Word Read-only Read/Write Table 1. Modbus Data Model Blocks In manycases, sensors and other devices generate data in types other than simplyBooleans and unsigned integers. It is common for slave devices to convert these larger data types into registers. For example, a pressure sensor maysplit a 32-bit floating point value across two 16-bit registers. 10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 1/7 Modbus exposes these values in a completelyconceptual way, meaning theymaynot actuallyexist in memory. For example, a slave device maybe defined such that holding registers and input registers actuallyshare the same memoryif that behavior makes sense for the slave. In most cases, slaves store each type of data that it supports in separate memory, and limits the number of data elements that a master can access. This flexibilityis an option because of the waydata is exposed through the well-defined behavior of Modbus function codes. 3. Modbus Function Codes Modbus function codes determine how data is accessed and modified bythe master. Unlike the data ranges, which are conceptual, function codes have a well-defined behavior. When a slave is asked to perform a function code, it uses the parameters of the function to execute that well-defined behavior. Figure 2 shows this link between a function request and the actual memoryof the device. Figure 2. The Mapping Between a Function Code, Data Ranges, and the Actual Memoryof a Slave Device The most common function codes are named after the conceptual data range theymodifyor access. For example, read holding registerstakes the action of pulling data out of the memorydefined as holding registers and returning it to the master. Table 2 identifies the most common function codes. 10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 2/7 Table 2. Common Function Codes Getting Started With Modbus in LabVIEW NI provides three primarymechanisms for interfacing with Modbus devices: (1) a high-level OPC server, (2) a Modbus I/O server, and (3) a low-level Modbus API introduced in NI LabVIEW 2014 software through the LabVIEW Real-Time or LabVIEW Datalogging and SupervisoryControl (DSC) modules. 4. LabVIEW Modbus API The low-level Modbus API is the preferred option when your application needs a high level of control over the sequencing and timing of Modbus requests. The low-level API is typicallyalso the preferred choice where flexibilityis paramount. In contrast, the flexibilityand power offered bythe LabVIEW Modbus API also means that your application code must be more complexto correctlymanage the API. To help you understand this complexity, LabVIEW provides two examples. Modbus Introductory Example The first example, Modbus Library.lvproj, provides a basic overview of the APIs functionality. It also demonstrates the differences between an implementation on a PC and a real-time target. Figure 3 shows the code involved in the Real-Time Modbus Master example. 10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 3/7 [+] Enlarge Image Figure 3. Master on RT Target.vi This example demonstrates the core requirements of a Modbus application using the LabVIEW API. First, a Modbus instance is created. In this case, a TCP master. However, you can switch this example to a serial master bychanging the polymorphic instance selector. Figure 4. Changing the Type of Modbus Master When the instance is created, you can begin polling the slave device for data. The example shows the use of the function code Read Input Registers. All Modbus function codes supported bythe API are shown on the appropriate palette. Because of implementation of the protocol, the slave API has additional functions that the master cannot implement. For example, a slave can write to the input register range, while a master mayonlyread from that range. Figure 5 shows the function codes. [+] Enlarge Image Figure 5. Modbus Master and Slave Palettes Showing the Function Codes Finally, the Modbus instance is closed, de-allocating the memoryassociated with the instance. This also closes anyreferences, including the TCP connection or NI-VISA serial references used bythe instance. Onlythe master example has been discussed thus far; however, everyexample follows the same basic pattern familiar to most LabVIEW users: open, read/write, and close. Finally, although the API does look the same, it is important to understand the keydifference. If your device is a master, it must send a request across the network to the appropriate slave to acquire data. The slave, on the other hand, has its own local data storage and can access it quickly. Redundant Mast er Example The basic example maysuffice for some applications; however, it maynot be enough for complicated applications where the goal is to talk to a sensor or gateway. To help bridge this gap, a sample application shows how to use two masters to communicate with a given slave. If one of the masters fails and loses connection with either the slave or human machine interface (HMI), the other master takes over. 10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 4/7 Figure 6. Design of the Redundant Master Example If this design meets the needs of your application, or if you are interested in a more complexexample of Modbus communication, view Redundant Modbus Masters.lvproj in the Example Finder. 5. Modbus I/O Servers Modbus I/O servers, which are in the LabVIEW DSC and LabVIEW Real-Time modules, provide a high-level engine for communicating over Modbus. Rather than specifying a function code that you wish to send, you register the set of data you would like to access and the I/O server schedules the requests automaticallyat the specified rate. To use I/O servers, you add a new I/O server to the desired target in your project. As with the low-level API, you can choose between a Modbus master or slave, and these lead to additional parameters. For example, a master has a defined polling ratethe rate at which everyrequest is sent to the slave, while slaves must wait on those requests and have no predefined timing. After the I/O server is created, you mayspecifythe items on the device you wish to read. Unlike the low-level API, where you must generate and process the requests yourself, Modbus I/O servers let you select from a wide varietyof formats and data types. For example, you can read the holding register at address 0 bymapping a variable to the item 400001, read the first bit of this register by selecting 400001.1, and read the single precision float that is stored in registers 0 and 1 byselecting F400001. After selecting variables to access, you can read or write these variables using shared variable nodes on the block diagram. You can even alias the variable names. Figure 7. A Simple I/O Server Application The programming effort involved with an I/O server application is minimal and easier to understand. Remember that this ease of use comes with limitations. Data updates at onlythe predefined rate, and there is no wayto add or remove requested data at run time. If these limitations are acceptable for your application, I/O servers are the recommended cross-platform option. For more information and a step-by-step guide, view Connect LabVIEW to AnyPLC With Modbus. 6. NI OPC Servers With OPC I/O Servers or OPC UA For complicated applications involving manyslave devices that communicate over different protocols, the standard Modbus I/O might not suffice. A common solution is to use an OPC server, which acts as a data aggregator for all of your systems, and then use the OPC I/O servers included in the LabVIEW DSC Module to communicate with that OPC server. Figure 8 shows an example of this architecture, with NI OPC Servers using Modbus to communicate directlywith sensors and OPC UA to communicate with an NI CompactRIO PAC. After data is aggregated in NI OPC Servers, an OPC I/O server can retrieve data and share it with the LabVIEW application. 10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 5/7 Figure 8. A SCADA Application Using Modbus, NI OPC Servers, and OPC I/O Servers You can also develop a similar architecture that uses the OPC UA driver included in the LabVIEW DSC Module in place of OPC I/O servers. However, the OPC UA driver is a low-level driver and does not provide the ease of use afforded byOPC I/O servers. To develop an application like this, you must first generate a valid configuration for NI OPC Servers to communicate with your slave devices. This is done bygenerating channelswhich define a driver configurationand deviceswhich define an individual endpoint for that driver. After you have configured a device, you can then generate tags. [+] Enlarge Image Figure 9. A Sample Configuration in NI OPC Servers for the Above Architecture And after you have configured NI OPC Servers, you can configure an OPC I/O server to communicate with these tags. While Modbus I/O servers are configured to access registers, OPC I/O servers are configured to access tags in the OPC server. 10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 6/7 Figure 10. Configuring OPC I/O Servers This binding process generates variables you can then use in your application. Figure 11. A Simple Application Using OPC I/O Servers Find a full walkthrough of this process at Connect LabVIEW to AnyPLC Using OPC. Meeting the Needs of Your Application Modbus is a simple protocol that you can use in various ways to implement powerful applications. For Modbus communication, NI provides three primaryoptions that provide a wide arrayof functionalityto meet the needs of your application. First, a low-level API provides fine control over the protocol, with high performance, at the expense of ease of use. Everything must be done manuallywhen using the low-level API. For simpler monitoring applications, Modbus I/O servers provide a simpler and easier API for accessing or serving up Modbus data. In exchange for ease of use, I/O servers give up the tight control over the protocol that can be required for some applications. Finally, for large and complexsystems, it maybe beneficial to consider a full-featured OPC server to serve as a data aggregator. Then, simplyuse a tool like the LabVIEW OPC UA driver or OPC I/O servers to provide your application access to this data.
10/14/2014 Introduction to Modbus - National Inst www.ni.com/white-paper/7675/en/ 7/7