Operation Control and Energy Management of Grid Connected DG Final Report
Operation Control and Energy Management of Grid Connected DG Final Report
\
|
+
= |
.
|
\
|
+
=
o
o
o
(11)
Where i
1LPF
is given by
1 1
i
s
i
LPF
|
.
|
\
|
+
=
o
o
(12)
Equation (12) can be expressed in differential equation form as
1 1 1
i i i
dt
d
LPF LPF
o o + =
(13)
A new state vector is defined as x
e
T
= [v
c
i
1
i
1LPF
]. Then combining (8) with (13), an augmented
state space equation is obtained of the form
c e e e e
u B x A x + =
(14)
The discrete-time equivalent (14) is given as
( ) ( ) ( ) k Gu k Fx k x
c e e
+ = +1
(15)
where k is time index and the matrices F and G can be computed as per (Kuo, 1980)
From Figure 18 (c), the feedback control law is given by
( ) ( ) ( ) ( ) ( ) k i k k v k k v k k u
HPF c cref c 1 2 1 1
+ = q
(16)
Substituting (11) in (16), we get
( ) ( ) ( ) ( ) ( ) ( )
| | ( ) ( ) ( ) k v k k x k k k
k i k k i k k v k k v k k u
cref e
LPF c cref c
1 2 2 1
1 2 1 2 1 1
+ + =
+ + =
q
q
(17)
Combining (17) with (15), the closed-loop state equation is given by
( ) | | ( ) ( ) ( ) ( ) k v B k k x k k k B A k x
cref e e e e e 1 2 2 1
1 + + = + q
(18)
Consider the system shown in H-bridge converter with LC filter connected to an RL plus back emf
load Figure 19 in which the converter is connected with an RL plus back emf load. The frequency
of the triangular waveform (v
tri
) is taken as 15 kHz and the sampling frequency is chosen twice of
this frequency, i.e., 30 kHz. The resonance frequency of the filter is around 2.2 kHz.
36
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 19: H-bridge converter with LC filter connected to an RL plus back emf load
The closed-loop frequency response, for various values of HPF coefficiento, is shown in Figure 20.
In this the input is the voltage reference v
cref
and the output is the capacitor voltage v
c
. It can be
seen that a = 500, the circuit behaves like an ideal amplifier with a gain of 0 dB (i.e., v
cref
= v
c
) till
around 3 kHz. The 3 dB cut-off frequency is around 6.5 kHz, indicating that the converter will track
a voltage reference up to this frequency. The tracking error however increases as o increase.
However, it is still less than 2 dB, indicating a maximum tracking error of 20%.
Figure 20: Closed-loop frequency response for various values ofo.
The phase of the closed-loop system, for two values ofo, is shown in Figure 21. It can be seen that
the phase shift between the reference and output voltages is almost zero when the system
frequency is 100 Hz or less. This implies that the converter is able to track a reference waveform of
50 Hz without any appreciable phase shift. However, the phase shift increases as the system
frequency increases. Also note that the phase shift is more for lower values ofo. From Figure 20
and Figure 21, it is evident that o = 500 is sufficient for tracking fundamental frequency (50 Hz)
waveforms. However, for higher frequency tracking, this value has to chosen as a compromise
between phase error and magnitude error.
37
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 21: Closed-loop phase shift for two values of o
To evaluate the converter tracking performance, let us assume that the converter is required to
track a 50 Hz voltage waveform with a peak of 230 V. The HPF coefficient is chosen as o = 500.
The system performance is shown in Figure 22. The reference and converter output voltages are
shown in Figure 22 (a). The error between these two voltages is shown in Figure 22 (b). It can be
seen that the peak of the tracking error is around 10 V.
Figure 22: Voltage tracking performance for a 50 Hz reference voltage
In a similar way, two high-pass filters are required for the current controller using the LCL filter.
The purpose of the control is to track a reference current i
2ref
. Therefore two HPFs, one for
i
1
and the other for v
c
, are used
to eliminate their references from the control loop. The
HPFs are derived in the same fashion as (11) to (13). The closed-loop control scheme is
shown in Figure 23.
38
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 23: The current control structure
Consider the same system as given in Figure 24. The system tracking performance is shown
in Figure 25. The peak of the tracking error is below 1 A. Hence the tracking performance is
adequate and acceptable. In general, a current tracking can work perfectly if the current
flows through a low impedance path. However, when the current has to flow through a
relatively large inductor, the controller has to work harder and may saturate. This problem
is not associated with a voltage controller since it can have a direct control over the
capacitor voltage, especially since the capacitors are connected in shunt.
Figure 24: H-bridge converter with LCL filter connected to an RL plus back emf load
Figure 25: Current tracking with incomplete system knowledge
39
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
4.3. Summary
In this section, control strategies for a DG converter were presented considering different filter
structures. This analysis is imperative since most of the sources in a microgrid are interfaced
through converters. Both voltage and current control converters were considered. The converters
generate harmonics and to suppress these harmonics, the design of passive filter circuits was
presented.
40
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
5. PARALLEL OPERATION OF DGS
When two or more DGs are operating in parallel, the high droop gains can make the system
unstable. Therefore it is imperative that a thorough stability analysis is performed before droop
gains are chosen. In this section, it will be shown through eigenvalue analysis that unwanted droop
gains can lead to instability.
There are two ways of performing eigenvalue analysis. In one approach, it can be assumed that
the converters track the fundamental frequency reference voltages perfectly. Therefore the filter
dynamics is not included in this kind of stability studies. This can only act as a screening tool to set
the droop gains accordingly. The other approach is to use a full model of the converter with their
switching states. This will give information about the interaction amongst the filters. In this section,
both these will be presented.
5.1. Stability Analysis with Voltage Source Model
Let us consider the system shown in Figure 26. This contains two voltage source converters that
are connected through a feeder with resistance of (R
x1
+ R
x2
) and inductances of (L
x1
+ L
x2
). The
converters are represented by the voltage sources v
1
and v
2
and they supply an RL load (R
L
, L
L
).
The current supplied by each converter is also depicted in the figure.
Figure 26: Single-line diagram of two converters supplying a load
From Figure 26, the following Kirchoffs voltage law (KVL) equations can be written for each phase
of the system
( ) ( ) c b a i
dt
di
L
dt
di
L L L i R i R R v
i x
L
i x
L x i x L i x L x i
, , ,
2 1
1 1 2 1 1 1
= + + + + + + =
(19)
( ) ( ) c b a i
dt
di
L L L
dt
di
L i R R i R v
i x
L x
i x
L i x L x i x L i
, , ,
2
2 2
1
2 2 1 2
= + + + + + + =
(20)
These quantities will now be converted into an equivalent d-q-0 plane, which is given by
( )
( )
abc dq
c
b
a
q
d
Pf f
f
f
f
t t t
t t t
f
f
f
=
(
(
(
(
(
(
(
(
(
(
|
.
|
\
|
+ |
.
|
\
|
|
.
|
\
|
+ |
.
|
\
|
=
(
(
(
0
0
2
1
2
1
2
1
3
2
sin
3
2
sin sin
3
2
cos
3
2
cos cos
3
2 t
e
t
e e
t
e
t
e e
41
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Where f can be either voltage or current. Since we shall only consider balanced operation, the
zero-sequence component can be taken as 0. We now define the following vectors
(
(
(
(
(
=
(
(
(
(
(
=
q x
d x
q x
d x
dq
q
d
q
d
dq
i
i
i
i
x
v
v
v
v
v
2
2
1
1
2
2
1
1
,
Then the state space equation of the state space equation of the system in d-q plane can be
written as
dq dq dq dq dq
v B x A x + =
(21)
where A
dq
= u
1
I and B
dq
= u
1
and
( )
( )
( )
( )
(
(
(
(
+ + +
+ + +
+ + +
+ + +
= I
L x L x L L
L x L x L L
L L L x L x
L L L x L x
R R L L L R L
L L L R R L R
R L R R L L L
L R L L L R R
2 2 2
2 2 2
1 1 1
1 1 1
e e
e e
e e
e e
(
(
(
(
+ +
+ +
+ +
+ +
= u
L x L
L x L
L L x
L L x
L L L L
L L L L
L L L L
L L L L
2 2
2 2
1 1
1 1
0 0
0 0
0 0
0 0
Let the voltage of the three phases of converter-1 be given by
( ) ( ) ( ) + = = = 120 sin , 120 sin , sin
1 1 1 1 1 1
t V v t V v t V v
m c m b m a
e e e
In the frame of converter-1 output voltage, these voltages can be expressed as
(
=
(
1 1
1
0
m Q
D
V v
v
(22)
In a similar way, choosing converter-2 voltages as
( ) ( ) ( ) + = = = 120 sin , 120 sin , sin
2 2 2 2 2 2
t V v t V v t V v
m c m b m a
e e e
The d-q axis voltages can be expressed in the frame of converter-2 voltage as
(
=
(
2 2
2
0
m Q
D
V v
v
(23)
These voltages are defined in terms of the reference frame of each converter output voltage. Let
us assume that the state model (21) is derived based on a common reference, from which
converter-1 voltage vector leads by o
1
and converter-2 voltage vector leads by o
2
. The relation
between two frames that are separated by an angle o is shown in Figure 27.From these figure we
can write:
42
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
(
=
(
Q
D
q
d
f
f
f
f
o o
o o
cos sin
sin cos
(24)
Figure 27: Relation between d-q and D-Q frames
Combining (22) with (24), we get
1
1
1
1
1
1 1
1 1
1
1
cos
sin
cos sin
sin cos
m
Q
D
q
d
V
v
v
v
v
(
=
(
=
(
o
o
o o
o o
(25)
In a similar way, combining (23) with (24), we get
2
2
2
2
2
cos
sin
m
q
d
V
v
v
(
=
(
o
o
(26)
Equations (25)and (26) are nonlinear. For eigenvalue analysis, these will have to be linearized
around a nominal operating point. Denoted by the nominal values by the subscript 0 and perturbed
values byA, these two equations are given as
1
10 10
10 10
1
10
10
1
1
sin
cos
cos
sin
o
o
o
o
o
A
(
+ A
(
=
(
A
A
m
m
m
q
d
V
V
V
v
v
(27)
2
20 20
20 20
2
20
20
2
2
sin
cos
cos
sin
o
o
o
o
o
A
(
+ A
(
=
(
A
A
m
m
m
q
d
V
V
V
v
v
(28)
Linearizing (21) and substituting (27) and (28) in the linearized equation, we get
o A + A + A = A
dq m dq dq dq dq
B V B x A x
2 1
(29)
where
(
A
A
= A
(
A
A
= A
2
1
2
1
,
o
o
o
m
m
m
V
V
V
(
(
(
(
(
=
(
(
(
(
(
=
20 20
20 20
10 10
10 10
2
20
20
10
10
1
sin
cos
0
0
sin
cos
,
cos
sin
0
0
cos
sin
o
o
o
o
o
o
o
o
m
m
m
m
dq dq dq dq
V
V
V
V
B B B B
43
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
We shall now combine the angle droop equations (4) with the state model (29). The active power P
and the reactive power Q are average quantities. These quantities are computed based on their
instantaneous quantities using lowpass filter as per
e
c
c
e
c
c
Q
s
Q
P
s
P
e
e
e
e
+
=
+
=
(30)
Where P
e
and Q
e
are instantaneous measured values. Linearizing, these equations can be written
in the following state space form
e c c
e c c
Q Q Q
P P P
A + A = A
A + A = A
e e
e e
(31)
The instantaneous active and reactive powers can be defined in terms of d-q axis voltages and
current as
( )
xq q xd d e
i v i v P + =
2
3
(32)
( )
xq d xd q e
i v i v Q =
2
3
(33)
Substituting (25) in the above equations, we get for converter-1
( )
1 1 1 1 1 1
cos sin
2
3
m q x d x e
V i i P o o =
(34)
( )
1 1 1 1 1 1
sin cos
2
3
m q x d x e
V i i Q o o + =
(35)
Linearizing the above equations we get
1 14 1 13 1 12 1 11 1
o o o o o A + A + A + A = A
m q x d x e
V i i P
(36)
1 14 1 13 1 12 1 11 1
o | | | | A + A + A + A = A
m q x d x e
V i i Q
(37)
where
( )
10 0 1 10 0 1 13 10 10 12 10 10 11
cos sin
2
3
, cos
2
3
, sin
2
3
o o o o o o o
q x d x m m
i i V V = = =
( )
10 0 1 10 10 10 14
cos sin
2
3
o o o
q x xd m
i i V + =
( )
10 0 1 10 0 1 13 10 10 12 10 10 11
sin cos
2
3
, sin
2
3
, cos
2
3
o o | o | o |
q x d x m m
i i V V = = =
( )
10 0 1 10 10 10 14
cos sin
2
3
o o |
q x xd m
i i V =
To linearize the droop equations (4), it is to be noted that the derivative of the rated values are
zero. Therefore, for converter-1 we get
44
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
1 1 1
1 1 1
Q n V
P m
m
A = A
A = Ao
(38)
Therefore eliminating AV
m1
and Ao
1
using (38) and combining (31) with (36) and (37), we get
1 14 1 13 1 12 1 11 1
Q P i i P
q x d x
A + A + A + A = A
(39)
1 14 1 13 1 12 1 11 1
Q P i i Q
q x d x
A + A + A + A = A
(40)
where
( )
13 1 14 14 1 13 12 12 11 11
, 1 , , o e o e o e o e n m
c c c c
= + = = =
( )
13 1 14 14 1 13 12 12 11 11
1 , , , | e | e | e | e n m
c c c c
+ = = = =
In a similar fashion, we can write the following two equations for converter-2
2 24 2 23 2 22 2 21 2
Q P i i P
q x d x
A + A + A + A = A
(41)
2 24 2 23 2 22 2 21 2
Q P i i Q
q x d x
A + A + A + A = A
(42)
Further we eliminate AV
m
and Ao from (29) using (38) to get
Q B P B x A x
dq dq dq
A + A + A = A
2 1
(43)
where
(
A
A
= A
(
A
A
= A
2
1
2
1
,
Q
Q
Q
Q
P
P
(
=
(
=
2
1
1 2
2
1
2 1
0
0
,
0
0
n
n
B B
m
m
B B
dq dq
We now define an extended state vector as
| |
T
T T T
dq
Q P x x =
Then combining (39) to (43), we get a homogeneous state equation of the form
x A x A = A
(44)
where
(
(
(
=
33 32 31
23 22 21
13 12 11
A A A
A A A
A A A
A
2 13 1 12 11
, , B A B A A A
dq
= = =
45
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
(
=
(
=
22 21
12 11
31
22 21
12 11
21
0 0
0 0
,
0 0
0 0
A A
| | | | | | | |
24 14 33 23 13 32 24 14 23 23 13 22
, , , diag A diag A diag A diag A = = = =
Let us now consider the system of Figure 26. The system parameters used for eigenvalue analysis
are listed in Table 3. The droop gain of converter-2 (m
2
) is varied from 0.1 rad/MW to 5 rad/MW,
while the droop gain of converter-2 is chosen as m
1
= 1.5m
2
. This choice is reciprocal of the
output impedances of the two converters. The trajectory of the dominant eigenvalues is shown in
Figure 28. The eigenvalues cross over to the right-half plane at around m
2
= 3.8 rad/MW. This
means that this is the limiting value of the droop gain that can be used.
Table 3: System parameters for converter parallel operation
System Quantities Parameter
values
System frequency 50 Hz
Load resistance (R
L
) 6 O
Load inductance (L
L
) 1 mH
Converter-1 output inductance (L
1
) 17.5 mHF
Converter-2 output inductance (L
2
) 25.5 mH
Line resistance (R
x1
, R
x2
) 0.025 O
Line inductance (L
x1
, L
x2
) 4 mH
Base voltage (L-L) 415 V
Figure 28: Eigenvalue trajectory of the two converter system
5.2. Stability Analysis with Converter Model
In this section, we shall discuss hysteresis control and converter stability analysis. In this, we shall
consider the full systems dynamics. As we have presented in the previous section, the load
sharing or the real and reactive power sharing can be achieved by controlling two independent
quantities angle (or frequency) and the fundamental voltage magnitude. The converter model
must include the droop control equations for stability analysis. A multi-converter system with
instantaneous power sharing control is effectively a high order multi variable system. The VSCs
should be controlled in such a manner that ensures a stable operation of the system.
46
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
In this section, the theory for the analysis of hysteretic VSCs operating in a power system is
developed. Under mild assumptions, the standard line dynamic analysis tools such as eigen-study
become possible. There are two main tools available to analyze converters operating in power
systems. The first uses controlled fundamental frequency voltage sources, which ignores
transients associated with the connecting filters (as shown in the previous section and (Coelho et
al., 2002)). The second approach uses the switch state averaging of pulse width modulated signals
(Pogaku et al., 2007, Ghosh et al., 2011). The quality of the hysteretic converter modeling is
demonstrated in this section on the special case of two VSCs closely connected. The novel
contribution here is that the widely used hysteretic converters can now be modeled as a part of a
power system using linear tools, which has not been done before.
We assumed that all the DGs are ideal DC voltage source supplying a voltage of V
dc
to a VSC. The
structure of the VSC is shown in Figure 19.The equivalent circuit of one phase of the converter is
shown in Figure 29. In this, uV
dc
represents the converter output voltage, where u is the switching
function and is given by u = 1. The main aim of the converter control is to generate u. From the
circuit of Figure 29 the following state vector is chosen
| |
c f T
T
v i i z =
(45)
Then the state space equation of the system can be written as
p
Cv Bu Az z + + =
(46)
where u is the switching function and
(
(
(
=
(
(
(
=
(
(
(
=
0
1
0
,
0
0 ,
0 1 1
1 0 0
1 0
f
T dc
f f
f
T T T
L C
L V
B
C C
L
L L R
A
Figure 29: Single-phase equivalent circuit of VSC
The main aim of the converter control is to generate u
c
from a suitable state feedback control law
such that the output voltage and current are tracked properly according to their references. It is
easy to generate references for the output voltage v
c
and current i
f
from the fundamental power
flow requirements However, the same cannot be said about the reference for the current i
T
(Ghosh
and Ledwich, 2003). On the other hand, once the reference for v
c
is obtained, it is easy to calculate
a reference for the current i
c
through the filter capacitor (see Figure 29).
47
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
To facilitate this, we define a new state vector as (Ghosh and Ledwich, 2003)
| |
c f c
T
v i i x =
(47)
We then have the following state transformation matrix
z C z x
P
=
(
(
(
=
1 0 0
0 1 0
0 1 1
(48)
The transformed state space equation is then given by combining (46) and (48) as
p p p p p
Cv C Bu C x AC C x + + =
1
(49)
If the system of (49) is sampled with a sampling time of AT, then its discrete-time description can
be written in the form
( ) ( ) ( ) ( ) k Hv k Gu k Fx k x
p
+ + = +1
(50)
To control the converter, we shall employ a discrete time linear quadratic regulator (LQR) to obtain
the control of the form
( ) ( ) ( ) | | | | ( ) ( ) | |
( ) ( ) ( )
c cref f fref c cref
ref ref c
v v k i i k i i k
k x k x k k k k x k x K k u
+ + =
= =
3 2 1
3 2 1
(51)
where x
ref
is the reference vector and K is the feedback gain matrix. From u
c
(k), the switching
function is generated as
( )
( ) 1 then elseif
1 then If
= <
+ = >
u h k u
u h k u
c
c
(52)
where h is a small number.
A Linear Quadratic Regulator is shown to produce an infinite gain margin and a phase margin of at
least 60 (Anderson and Moore, 1971). This has been used in (Aredes et al., 1997) robust
hysteretic LQR state feedback switching controller. The following example demonstrates the
effectiveness of this control.
A composite model of the converter in the d-q domain is developed, which also includes the
controller. Traditional sliding mode design consider a function S and control such that
0 s S S
. Then
the system will approach S = 0, which is called the sliding line (Slotine and Li, 1991, Khalil, 2002).
When a finite switch rate constraint is applied, the system will chatter around S = 0, at the
switching frequency. Provided that the switch frequency is sufficiently high, the power system
impact at switch frequency will be negligible. We also assume that the load disturbances are small
enough that the rate of change of current is within the capability of the converter thus the model of
the system being on the sliding line will be valid.
From equivalent circuit shown in Figure 29, the following equations are obtained for each of the
phases of the three-phase system
48
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
( )
T
dc c c
T
T
T T
L
V u v
i
L
R
dt
di . +
+ =
(53)
( )
f
f T
c
C
i i
dt
dv
=
(54)
dt
di
L v v
f
f p c
=
(55)
Equations (53) to (55) are transformed into a d-q reference frame of converter output voltages,
rotating at system frequency in the same manner as discussed in Section 6.
Defining a state vector as
T
cq cd fq fd Tq Td i
v v i i i i z ] [ =
(56)
The state equation in the d-q frame is given by
pdq zi cdq zi i zi i
v C u B z A z + + =
(57)
where u
cdq
and v
tdq
are vectors containing the d and q axis components of u
c
and v
t
and
(
(
(
(
(
(
(
(
=
0 1 0 1 0
0 0 1 0 1
1 0 0 0 0
0 1 0 0 0
1 0 0 0
0 1 0 0
e
e
e
e
e
e
f f
f f
f
f
T T T
T T T
zi
C C
C C
L
L
L L R
L L R
A
(
(
(
(
(
(
(
(
=
(
(
(
(
(
(
(
(
=
0 0
0 0
1 0
0 1
0 0
0 0
and
0 0
0 0
0 0
0 0
0
0
f
f
zi
T dc
T dc
zi
L
L
C
L V
L V
B
Let us now define a new state vector as
T
cq cd fq fd cq cd i
v v i i i i x ] [ =
(58)
Then using dq transformation given in the previous section, we get the following state equation
pdq i dq i i i i
v C u B x A x + + =
(59)
From (51), the d and q components of the sliding plane are given as
( )
(
= =
(
q
d
i refdq i
cq
cd
S
S
x x H
u
u
(60)
49
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
where
(
=
3 2 1
3 2 1
0 0 0
0 0 0
k k k
k k k
H
i
T
cqref cdref fqref fdref cqref cdref refdq
v v i i i i x ] [ =
To analyze the system, we transform the state variables to a new vector w as
T
cq cd fq fd q d i
v v i i S S w ] [ =
(61)
Then, from (60), the states of (58) can be written in terms of (61) as
refdq i i i refdq
i
i
i
i
x F x T x
H
x
I
H
w + =
(
+
(
=
6 4 4 2 4
0 0
(62)
where 0
nm
is an nm null matrix and I
n
is nn identity matrix. From the above, we get the two
following equations
( )
refdq i i i i
x F w T x =
1
(63)
refdq i i i i
x F x T w + =
(64)
From (71) and (76), we get
( )
refdq i pdq i dq i i i i i
x F v C u B x A T w + + + =
(65)
Substituting (75) in (77), we get
refdq i pdq i i dq i i refdq i i i i i i i i i
x F v C T u B T x F T A T w T A T w + + + =
1 1
(66)
Since u
dq
is chosen such that S
d
= S
q
= 0, we can eliminate them from the state vector w
i
.
Let us define a new state operator such that
| |
i i
T
cq cd fq fd i
w N v v i i y = =
(67)
where
| |
4 2 4
0 I N
i
=
.
Now since w
i
= N
i
T
y
i
and N
i
F
i
= N
i
T
i
B
i
= 0, (78) can be re-expressed as
pdq i refdq i i i i
v C x B y A y + + =
(68)
where
i i i i i i i i i i
T
i i i i i i
C T N C F T A T N B N T A T N A = = =
, ,
1 1
To solve the state equation (68), the reference vector x
refdq
is required as input. In this sub-section,
we shall discuss how they can easily be written in terms of the known quantities. We must however
50
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
remember that all the d-q quantities are expressed in the reference frame of the converter output
voltages. Let us define the three-phase instantaneous reference converter output voltages as
( ) ( ) ( ) + = = = 120 sin , 120 sin , sin t V v t V v t V v
cm ccref cm cbref cm caref
e e e
Then the d-q transformation will result in
(
=
(
cm cqref
cdref
V v
v 0
(69)
Consequently, the reference for the capacitor currents that are leading the corresponding voltages
by 90 are given as
(
=
(
0
f cm
cqref
cdref
C V
i
i e
(70)
Now the expression for the power and reactive power are given by (32)and (33). Let the real and
reactive power that are desired to be injected to the PCC by the converter be denoted respectively
by P
ref
and Q
ref
. Then from (69), (32)and (33), we can write
(
=
(
ref
ref
cm
fqref
fdref
P
Q
V
i
i
3
2
(71)
Combining (69) - (71), we form the reference vectors in terms of V
cm
, P
ref
and Q
ref
.
The reference quantities are defined in terms of the reference frame of the converter output
voltage. These need to be converted into a common reference frame. Let us choose the PCC
voltage as the common reference frame D-Q. Let also the angle between the PCC voltage and the
converter voltage beo. Then using the transformation given in (24) and Figure 27, the converter
equation (68) can then be re-written as
pDQ i refDQ i i i i
v C x B y A y + + =
(72)
Note that the states also get transformed into D-Q. However the subscripts are avoided here for
brevity.
We now develop the model when two VSCs are operating in parallel. The single-line diagram of
the system considered is shown in Figure 30. In this, the PCC is connected to an infinite bus with a
voltage of v
s
. A load; with an impedance of R
L
+ jeL
L
is connected to the PCC. The load current is
denoted by i
L
. The system parameters and quantities of the two VSCs are denoted by subscripts 1
and 2.
51
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 30: Single-line diagram of parallel operation of two VSCs
The state equations of the VSCs can be written in the form (72) as
pDQ i DQ ref i i i i
v C x B y A y
1 1 1 1 1 1
+ + =
(73)
pDQ i DQ ref i i i i
v C x B y A y
2 2 2 2 2 2
+ + =
(74)
Furthermore, the load current in D-Q component is given as
(
+
(
=
(
PQ
pD
L
L
LQ
LD
L L
L L
LQ
LD
v
v
L
L
i
i
L R
L R
i
i
dt
d
/ 1 0
0 / 1
e
e
(75)
Therefore defining a composite state vector as
| |
LQ LD
T
i
T
i
T
t
i i y y x
2 1
=
We can combine (73)-(75) to form the overall state space equation of the system.
For this case, we assume that the PCC is a floating source, i.e., the voltage source v
p
in Figure 30
is absent and the two converters operate in parallel to share the load through droop
characteristics. We consider the angle droop based on the active power and a voltage magnitude
droop based on reactive power as given in (4). We shall also assume that these are filtered by the
lowpass filters given in (30).
Since the PCC is not connected to an infinite bus, we have to eliminate the vector v
pDQ
from the
state equation. From (75), we can write
(
=
(
LQ
LD
L L
L L
L
LQ
LD
L
PQ
pD
i
i
L R
L R
L
i
i
dt
d
L
v
v
e
e
(76)
Again, using Kirchoffs current law (KCL) at PCC, we get
Q f Q f LQ D f D f LD
i i i i i i
2 1 2 1
and + = + =
(77)
Let us now define a new set of state vectors that contain only the state equations of the two
converters. This is given by
| |
T
i
T
i
T
c
y y x
2 1
=
52
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
We can then express (88) in terms of the above state vector and its derivative as
c P c P
PQ
pD
x B x A
v
v
+ =
(
(78)
where the matrices A
p
and B
p
both have dimensions (28) and are computed from (76) and (77).
From (73), (74) and (78), the model for the autonomous operation of the two VSCs is derived as
( )
c P c P
i
i
crefDQ
i
i
c
i
i
c
x B x A
C
C
x
B
B
x
A
A
x +
(
+
(
+
(
2
1
2 6 4
6 4 1
2 4 4
4 4 1
0
0
0
0
(79)
The above equation can be regrouped to form the state space equations for the autonomous
operation of the VSCs as
crefDQ c c c c
x B x A x + =
(80)
where
P
i
i
A
C
C
I E
(
=
2
1
8
,
|
|
.
|
\
|
(
+
(
P
i
i
i
i
c
B
C
C
A
A
E A
2
1
2 4 4
4 4 1 1
0
0
,
(
2 6 4
6 4 1 1
0
0
i
i
c
B
B
E B
Since the system response obtained by the mathematical model closely matches that of the
PSCAD simulation, the VSC model developed in the previous sections can be used to find an
autonomous small signal model of the system discussed in the previous section. To facilitate this,
we must eliminate the reference vector from (80).
From (30), (32) and (33), we can write
( )
( )
fq cd fd cq
c
e c e
fq cq fd cd
c
e c e
i v i v Q Q
i v i v P P
+ =
+ + =
2
3
2
3
e
e
e
e
(81)
Linearizing the above equations around an operating point, we obtain
( )
( )
dq fq fq cd cq fd fd cq
c
e c e
cq fq fq cq cd fd fd cd
c
e c e
v i i v v i i v Q Q
v i i v v i i v P P
A A A + A + A = A
A + A + A + A + A = A
0 0 0 0
0 0 0 0
2
3
2
3
e
e
e
e
(82)
where the suffix A defines a perturbed quantity and subscript 0 signifies the nominal values.
Defining a vector of active and reactive powers as
| |
T
e e e e pq
Q P Q P x
2 2 1 1
=
equation (82) can be written as
c pq pq pq pq
x B x A x A + A = A
(83)
Where A
pq
= diag (e
c
e
c
e
c
e
c
) and B
pq
can be derived from (94).
53
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
We now replace the reference quantities by AP
e
and AQ
e
. To do that, we first linearize the droop
equations as given in (38). Also transforming (69) into the common reference frame, we get
(
=
(
cm cQref
cDref
V v
v 0
cos sin
sin cos
o o
o o
Linearizing the above equation and substituting (38), we get
(
A
A
(
=
(
A
A
e
e
cm
cmo
cQref
cDref
Q
P
n mV
n mV
v
v
0 0 0
0 0
cos sin
sin cos
o o
o o
(84)
In a similar way, we find the references for the capacitor current are given as
(
A
A
(
=
(
A
A
e
e
cQref
cDref
Q
P
i
i
0 2 0 1
0 2 0 1
sin cos
cos sin
o o
o o
(85)
here
1
= meC
f
V
cm0
and
2
= neC
f
. Finally replacing P
ref
and Q
ref
by P
e
and Q
e
respectively in (71),
we get the linearized expressions for the injected currents as
(
A
A
(
=
(
A
A
e
e
cm
fQref
fDref
Q
P
V
i
i
22 21
12 11
0
1
| |
| |
(86)
here
( )( )
( )
( )( )
( )
0 0 22
0 0 0 0 0 21
0 0 12
0 0 0 0 0 11
sin 3 2
cos cos sin 3 2
cos 3 2
sin cos sin 3 2
fQ
e e
fD
e e
ni
mQ mP
ni
mP mQ
+ =
+ =
+ =
+ =
o |
o o o |
o |
o o o |
We can then write the reference vector in (80) as
pq c crefDQ
x M x A = A
(87)
where the elements of M
c
are obtained from (84)-(86). Combing (80), (84) and (87), we get a
homogeneous state space description of the complete system as
(
A
A
(
=
(
A
A
pq
c
pq pq
c c c
pq
c
x
x
A B
M B A
x
x
(88)
This homogenous model can now be used for eigenvalue analysis.
54
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Table 4: system parameters
System Quantities Values
Systems frequency 50 Hz
PCC voltage V
p
11 kV (L-L, rms)
PCC voltage phase 0 (Reference)
DC voltage V
dc
3.0 kV
Single-phase
transformers
3//11 kV, with 10%
leakage reactance (L
T
=
31.8 mH)
Transformer losses
R
T
0.1 O
Filter capacitor C
f
50 F
Filter inductance L
f
250 mH
For eigenvalue analysis we vary a parameter m from 0.0110
6
rad/W to 1.810
6
rad/W.
Furthermore we choose the angle droop gains as m
1
= m and m
2
= 1.25m. The plots of the
dominant eigenvalues are shown in Figure 31. The dominant eigenvalues cross imaginary axis at
m = 1.4902210
6
rad/W, which is pointed out in this figure. Also the oscillation frequency of the
dominant eigenvalues is roughly 314 rad/s (50 Hz). From eigenvectors it has been determined that
these eigenvalues are associated with real and reactive power supplied by the VSCs.
Figure 31: Eigenvalues plots from stability analysis
To validate the eigenvalue results, PSCAD simulations studies are carried out for the same
system. With the system operating at steady state with the nominal values of droop gains given in
example, the value of m is changed suddenly at 0.1 s. Figure 32 shows the plots of the real power
output of VSC-2 for three different values of m. Figure 32 (a) shows a damped oscillation for m =
1.310
6
rad/W, for which all the eigenvalues are in the left half s-plane. Figure 32 (b) shows
55
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
sustained oscillation for m = 1.4902210
6
rad/W, for which the dominant eigenvalues are on the
imaginary axis. The unstable case for which the dominant eigenvalues are on the right half s-plane
are shown in Figure 32 (c) for m = 1.810
6
rad/W. Also notice that there are five peaks and five
troughs in each 0.1 s, indicating that the oscillation frequency is 50 Hz. This fundamental
frequency oscillation is also predicted by the eigenvalues.
Figure 32: VSC-2 output power showing stable, undamped and unstable
It is to be noted that the reactive droop gains n
1
and n
2
do not have a significant influence on the
eigenvalues. However, if they are chosen arbitrarily large, the voltage regulation will fail and the
converter output voltage will collapse leading to instability in which no power can be transferred.
5.3. Summary
High droop gains can cause microgrid instability. Therefore, a proper study must be performed for
the selection of droop gains. In this section, two eigenvalue analysis techniques were presented.
One of the techniques assumes that the converters are ideal voltage sources that track the desired
reference voltages accurately. The second technique of eigenvalue analysis presented a method
for linear analysis of hysteretic controlled state feedback converters. These proposed techniques
can be effectively utilised to analyse and design droop gains for multiple DGs in a microgrid.
56
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
6. MICROGRID PROTECTION
6.1. Protection with overcurrent relays
The penetration level of distributed generators (DGs) into distribution network is increasing rapidly.
The higher level of DG penetration can cause considerable impact on operational, control and
protection of the existing network (Chowdhury et al., 2008). Overcurrent (OC) protection has been
usually employed to protect a radial distribution network due to its simplicity and low cost (Gomez
and Morcos, 2005). However, after the DG connections into the network, several protection issues
can be identified and they are well documented (Zamani et al., 2010, Cho et al., 2010, Martinez
and Martin-Arnedo, 2009, Javadian et al., 2009, Cheung et al., 2009).
As according to current practice, all the DGs will be disconnected for a fault in the utility grid
(IEEE.Std.1547, 2003). This automatic disconnection of DGs during loss of main grid supply
drastically reduces the DG benefits (Chowdhury et al., 2008). The DG benefits can be maximized if
as many DG connections as possible are maintained (Tan and Salman, 2009). Also, the islanded
operation with DGs is usually not allowed since restoration by reclosing is difficult and due to
power quality issues (Martinez and Martin-Arnedo, 2009). However, if the protection scheme is
able to isolate the faulted segment allowing intentional power islands to operate with adequate
protection, the reliability can be increased (Perera et al., 2008).
In this section, a control and protection solution is proposed to enhance the benefits of converter
interfaced DGs in a network containing high level of DG penetration. The proposed solution
includes isolating the faulted segment from both upstream and downstream side of a radial feeder
using overcurrent (OC) relays, a converter control strategy for a DG to achieve fault isolation, self
extinction of arc, islanded and grid-connected operation without disconnecting DGs from unfaulted
segments, and a method to perform system restoration in the presence of DGs using auto
reclosers in a network. These proposed strategies in this report are discussed below.
6.1.1. Proposed protection scheme for fault isolation
One of the main aims of the proposed protection scheme is to isolate the faulted segment from a
radial feeder allowing DGs to supply the loads in unfaulted segments either in grid-connected or
islanded mode. The upstream relay to a fault will see both utility current and current coming from
any DG connected further upstream to the relay. However, the downstream relay will only see the
fault current coming from DGs located further downstream from the relay. If the DGs are
intermittent or not connected all the time to a network, the fault current level in the network cannot
be predicted in advance. In this circumstance, the existing settings of OC relays will not work to
isolate the faulted segment. Therefore, it is proposed to change the relay settings according to the
present system configuration. The digital type OC relays, which have the communication
capability, are necessary to accomplish the proposed strategy. The relay acquires the each DG
circuit breaker states to work out the present system configuration. Based on the number of DG
connections, the relay selects the most appropriate setting for fault detection
57
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
6.1.2. Proposed converter control strategy for a DG
A control strategy for a voltage source converter (VSC) is proposed based on the fold back current
control characteristic to help in successful fault isolation and fast system restoration with converter
interfaced DGs. During a fault in the network, the VSC control maintains a sufficient fault current
level for a defined time period. This results in effective fault detection by OC relays which are
located downstream from the fault point. Also, the VSC control helps to self extinction of an arc
fault without disconnecting the DG from a network. Moreover, the system restoration and
coordination between network reclosers and DGs are achieved with the aid of proposed VSC
control strategy. The VSC operates either in current control or voltage control mode. The proposed
VSC control for a converter interfaced DG is explained below.
6.1.3. A. During grid connected and islanded operation
In grid connected mode, the VSC operates in current control mode injecting rated power. The
converter injects current in phase with the point of connection (PC) voltage to supply only real
power to the utility grid. On the other hand, in islanded mode, the VSC operates in voltage control
mode maintaining the standard voltage and frequency in the islanded section while sharing both
real and reactive power requirements of the loads.
6.1.4. B. During a fault
A fault can occur when the DGs are operating either in grid connected or islanded mode. In both
cases, each VSC limits its output current to twice the rated current and operates in current control
mode. The VSC identifies a faulted condition by monitoring the PC voltage. The PC voltage
reduces during a fault and this change of voltage triggers to apply the limit to the output current.
The VSC maintains the current limiting for a defined time period (t
cc
), if the fault exists. The time
period (t
cc
) allows OC relays which are located downstream from the fault to detect and isolate the
fault. This time period (t
cc
) can be adjusted depending on the relay characteristics selected. Also,
the maximum allowable time given in IEEE 1547 (IEEE.Std.1547, 2003) to disconnect a DG during
a low voltage condition can be considered when selecting the t
cc
. The VSC can recover if the fault
is cleared before t
cc
elapses depending on the system configuration exists after the fault isolation.
If the DG is still connected to the faulted segment after the time period t
cc
, the VSC folds back the
output current to a very small value for another defined time period t
sm
. The operating mode of
VSC in current control mode during this time is called as sleep mode. During the sleep mode, the
DG injects a small current without disconnecting from the network. The sleep mode operation of
VSC results in self extinction of any temporary arc fault which is not cleared by relays successfully
during the time t
cc
. Therefore the sleep mode operation enables the arc extinction without DG
disconnection. The sleep mode time duration can be set based on the arc deionization time which
can be calculated using the equation given in (Kaur and Vaziri, 2006).
The behaviour of a VSC during a fault is shown in Figure 33 assuming the fault is not cleared by
protective relays. The VSC injects the current (I
o
) in pre-fault mode. The fault occurs at point A.
The VSC limits the output current to twice the rated current for the time period of t
cc
as shown in
the figure. The VSC then rapidly reduces its output current to a very small value given by nI
r
where
n is a small number and remains in the sleep mode for the time period of t
sm
. The restoration
process starts after this period and it is explained in the next sub-section.
58
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 33: Proposed DG behavior during a fault
6.1.5. C. System restoration
The system restoration is started once sleep mode time period elapses. During this process, each
VSC tries to restore the system either in grid connected or islanded mode depending on the
system configuration exists after the fault. The recovery characteristic of the VSC is shown in
Figure 34 by assuming the DG capacity is sufficient to supply the load demand and the fault has
cleared when restoration begins. The line DEF represents the restoration boundary in current
control mode. In sleep mode, the VSC starts at point D and calculate the PC voltage which is given
by point K on the load line. Then VSC calculates the corresponding current on the line DE. After
that VSC injects the calculated current which will result to move the operating point to M on the
load line. Again, the VSC controller calculates the required current which is the rated current at
point N. The injection of rated current increase the voltage above the rated value and thus
operating point moves to O on the load line by successfully recovering the system.
During the restoration process, the VSC is not allowed to inject beyond the rated current to make
sure the DG capacity is sufficient to restore the system. The restoration process is continued for a
defined time period t
res
. If the DG is not recovered during the t
res
due to the higher load demand or
faulted condition, the DG is then disconnected using its own circuit breaker. For the illustration
purposes, a constant impedance type load is considered. However, the restoration characteristic of
different types of loads may be different. Many constant power type loads such as motors and
electronic devices change their characteristic below some voltage level to constant impedance
type or tripping of load occurs below a specified voltage (IEEE, 1993). The proposed intelligent
control algorithm for the VSC is shown in Figure 35.
Figure 34: Proposed restoration characteristic for a DG
59
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 35: The proposed VSC control algorithm
6.1.6. DG coordination with network reclosers
Reclosing can be considered as a major protection issue when several DGs are connected to a
distribution network. Thus, an effective method is proposed to coordinate network reclosers with
converter interfaced DGs in a distribution feeder. The total time (defined as t
dg
which includes t
cc
+t
sm
+ t
res
) associated with proposed DG control during a fault is used to coordinate the network
reclosers with DGs. Two methods are introduced to coordinate a recloser with a DG. In the first
proposed method, the DG takes the opportunity to restore the system before the operation of any
auto recloser. This method is advantageous, if DG penetration level is significant and DGs have
the ability to supply the load demand in islanded mode. As mentioned in VSC control strategy,
elapsing t
dg
after a fault, the DGs either supply power (i.e., in grid connected or islanded mode) to
the network due to successful restoration or they are disconnected from the network due to
unsuccessful restoration (i.e., uncleared fault or higher load demand). Then, the recloser which
sees the fault as forward takes the first opportunity to perform the reclosing and it can result in a
live to live or live to dead reclosing depending on the result of DG restoration. The recloser which
sees the fault as reverse will always wait until the upstream side is restored.
In the second method, an opportunity is given to the recloser to restore the system before DG
starts to restore the system. This method can be used for a system when DG capacity is not
sufficient to supply the load demand in an islanded section. In this case, the DGs are kept in sleep
mode until reclosing finishes. The recloser may restore the system depending on the fault status. If
the system is successfully restored, then DG can start the restoration process which will be
successful. This results in maximizing the DG benefits to the customer by connecting DGs quickly.
On the other hand, if the reclosing fails to restore the system, DGs will be disconnected
automatically after the defined time period of restoration.
60
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
A synchronism check element is used in each recloser to make sure whether two sides of a
breaker is in exact synchronism when performing the live to live reclosing. The DGs maintained the
original phases since they are not disconnected during a fault. Also, they maintain the standard
voltage and frequency during the operation in islanded mode. However, there may be a slight
phase angle mismatch due to frequency deviations in grid side. In that case, the recloser waits
until phase angle on the both side becomes closer to join the two systems. However, the DG itself
has the protection to withstand for contingency conditions and it is discussed in next section.
6.1.7. DG protection
It is important to consider the consequences of out of phase reclosing when DGs are not
disconnected during the auto recloser open time. The risk of DG damage due to the out of phase
reclosing is lower, if DG is connected through a converter (Kumpulainen and Kauhaniemi, 2004a).
In the proposed reclosing scheme, the recloser is capable of checking the synchronization which
ensures there is no phase mismatch when it performs live to live reclosing.
From the point of DG protection, the DG should be protected itself. To achieve basic DG protection
requirements, in the proposed method, a DG is employed with several protective elements: fold
back current control, reverse power flow, over voltage and synchronism check. The proposed
current limiting and fold back current control protect the DG from excessive current injection and
unsuccessful system restoration. The reverse power flow protection is activated to trip the DG
when current flows towards the DG. The over voltage element responds, when the terminal voltage
of the DG rises above a predefined limit. However, under voltage protection is incorporated with
the proposed fold back current control since DG is allowed to operate under the rated voltage in
current control mode for a defined time interval. The synchronism check element ensures a trouble
free connection to the feeder when it is being reconnected after any disconnection. These
protection schemes will minimise the DG safety risks associated with reclosing.
6.1.8. The need of communication for the protection
To achieve the proposed protection and control strategies, communication between relays and
each DG controller is required. The each DG operates in voltage control mode in grid connected
operation while current control mode is selected in islanded operation. Each relay-breaker status is
available for all the DGs to determine the mode of operations (i.e. either grid connected or
islanded).
Also, each DG circuit breaker status is available for all the relays in the feeder. The proposed
protection scheme is employed to isolate the faulted segment from both the upstream and
downstream side of a fault. In this study, the converter interfaced DGs are only considered and
they are intermittent and limiting output currents during a fault. Therefore the fault current level
changes depending on the DG connections and the fault current seen by downstream relay is low.
Under this circumstance, isolating the faulted segment using the existing OC relays will be difficult.
Thus the OC relay settings are changed with the aid of communication according to the number of
DG connections.
In the case of communication failure, each relay selects its default setting which has been set
during the initial relay settings. Also, the DGs switch into current control mode assuming they are
connected to grid connected mode. However, if they are not connected to grid, they can sense that
the standard voltage and frequency are not within the defined limits which will lead to disconnect
all the DGs from the network.
61
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
6.1.9. Simulation studies
Consider the radial distribution feeder shown in Figure 36 to validate the proposed protection and
control strategies. Three converter interfaced DGs, DG1, DG2 and DG3 are connected at BUS-2,
BUS-3 and BUS-4 respectively. It is assumed that the DGs are controlled in angle droop to share
the load power in islanded mode according to a predefined ratio (Majumder et al., 2009a,
Majumder et al., 2009b). However, different converter structures and controls can be used to
achieve the proposed converter control strategy. The DG circuit breakers CB
DG1
, CB
DG2
and CB
DG3
provide the protection for each DG. The feeder is protected by OC relays R
1
, R
2
and R
3
which are
located at BUS-1, BUS2 and BUS3 respectively. It is assumed that all the circuit breakers
associated with these relays have the reclosing capability since one of the main objectives of this
study is to show the system restoration performing auto reclosing in the presence of DGs. The
system parameters of the study system are given in Table 5.
Table 5: System parameters of the study system
System data Value
System frequency 50 Hz
Source voltage 11 kV rms (L-L)
Source impedance (Z
s
) 0.078 + j 0.7854
O
Feeder impedance (Z
12
=Z
23
=Z
34
)
0.52 + j 2.60 O
Each load impedance 190 + j 142
DG data
DG1 source impedance 0.9375 + j 15.708
O
DG2 source impedance 0.75 + j 12.566 O
DG3 source impedance 1.2503 + j 20.954
O
DG1 output power 0.5 MVA
DG2 output power 0.625 MVA
DG3 output power 0.375 MVA
62
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 36: Simulated radial feeder with DGs
The directional feature is added to the OC relays, since different relay settings are required in
forward and reverse directions. In the forward direction, relays R
1
, R
2
and R
3
are graded with IEC
standard inverse time OC characteristic (Tan et al., 2002) with a 0.3 s discrimination time margin.
Also, instantaneous tripping time element is added for each relay to isolate the faults fast which
have higher fault currents. The calculated maximum and minimum fault current levels for different
fault locations are given in Table 6: Fault currents at different buses in forward direction Table 6.
Based on these values, the relay settings are calculated and they are given in Table 7. The tripping
time of each relay for different fault currents in forward direction is shown in Figure 37. It can be
seen that each upstream relay provides the backup protection for the immediate downstream
relay.
In the reverse direction, relays R
2
and R
3
are graded with definite time OC relay characteristic. The
definite time element is selected due to lower fault current level in the reverse direction since the
current limited DGs supply the fault current during a fault. However, the setting of definite time
element should be changed according to the available number of DG connections. The maximum
load current seen by each relay is taken into consideration when selecting the relay settings in the
reverse direction. For example, with the absence of Load1, Load2 and Load3, the DGs connected
to the network will inject current back into the utility grid. Therefore the relay pickup current is
selected calculating the maximum load current and allowing a safety margin of 1.5 times the
maximum load current. The calculated relay settings in the reverse direction are given in Table 8.
A number of simulation studies are carried out by creating different types of faults at different
locations in PSCAD to evaluate the performance of proposed protection and control strategies.
However, few results are presented here.
63
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Table 6: Fault currents at different buses in forward direction
Table 7: Relay settings in forward direction
Relay CT ratio
Pickup current
(A)
Time multiplier
setting (TMS)
R1 300/5 5 0.25
R2 250/5 4.0 0.15
R3 250/5 4.0 0.05
Figure 37: Relay tripping characteristics in forward direction
Table 8: OC relay settings in reverse direction
DG
Configuration
DG1
I
r
=26.2A
DG2
I
r
=32.8
A
DG3
I
r
=19.7
A
R
2
R
3
Max. load
current
(A)
Pickup
current
(A)
Max. load
current
(A)
Pickup
current
(A)
1 0 0 0 0.0 Blocked 0.0 Blocked
2 0 0 1 19.7 29.9 19.7 29.9
3 0 1 0 32.8 49.2 32.8 49.2
4 0 1 1 52.5 78.7 52.5 78.7
5 1 0 0 26.2 39.3 0.0 Blocked
6 1 0 1 45.9 68.8 19.7 29.9
7 1 1 0 59 88.5 32.8 49.2
8 1 1 1 78.7 118 52.5 78.7
Fault current (A)
BUS-1 BUS-2 BUS-3 BUS-4
Maximum 8054 1843 1040 724
Minimum 6967 1596 901 627
64
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
6.1.10. A. Fault between BUS-1 and BUS-2 in Grid Connected Mode
It is assumed that all the DGs and loads are connected to the feeder shown in Figure 36. A three
phase to ground fault is created between BUS-1 and BUS-2 at 0.2 s. The relays R
1
and R
2
respond to isolate the fault at 0.267 s and 0.312 s respectively. After successful faulted segment
isolation, the DGs restore the system beyond BUS-2 supplying the load power requirement in the
islanded mode. The response of DG1 is shown in Figure 38. It can be seen that the DG limits its
output current once fault occurs helping the downstream relay R
2
to detect the fault. However, once
R
2
isolates the fault from downstream side, the DG terminal voltage rises to rated voltage and it
causes DG to switch over to voltage control mode.
The DGs supply only the real power to the utility before the fault in grid connected operation.
However, after the system is restored in islanded mode, the DGs supply both real and reactive
power requirement of the loads.
The relay R
1
which sees the fault as forward starts the reclosing first at 1.012 s. However, the
downstream relay R
2
waits until the upstream side is restored. In this simulation, it is assumed that
the fault is temporary and it is cleared after the faulted segment is isolated. Therefore the first
reclosing of R
1
(i.e., live to dead) is successful. The relay R
2
then starts the reclosing process by
sensing the voltage of the upstream side. In this study, it is assumed that the grid side frequency
has increased to 50.5 Hz from the nominal 50 Hz when the reclosing process of R
2
begins. Due to
the frequency mismatch, the reclosing cannot be performed soon after starting the process. Thus
R
2
waits until the phase angle get matched in both sides and so it performs the reclosing
successfully at 2.4 s. The voltage of both grid side and islanded side of the reclosing breaker is
shown in Figure 40 (a). The reclosing is performed when phase angles of grid and islanded sides
are equal. The voltage and current of DG1 during the reclosing are shown in Figure 40 (b) and
Figure 40 (c) respectively. The smooth transition from islanded mode to grid connected operation
validates the suitability of the proposal control strategy. It is to be noted that if the fault is
permanent, R
1
reclosing will be unsuccessful and islanded section operates in autonomous mode
until fault is cleared and restore the upstream system. The variation of DG power during the
transition from islanded mode to grid connected is shown in Figure 41.It can be seen that the DGs
start to inject rated power in grid connected mode.
Figure 38: DG1 response before, during and after the fault
65
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 39: The real and reactive power variation of DGs
Figure 40: Behaviour of system during reclosing
66
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 41: Real and reactive power variation during transition
6.1.11. B. Fault between BUS-2 and BUS-3
It is assumed that a permanent fault occurs between BUS-2 and BUS-3 at 0.2 s. The relays R
2
and
R
3
isolate the faulted segment at 0.265 s and 0.507 s respectively. The fault isolation from
downstream side relay leads to restore the islanded system containing DG2 and DG3 with Load2
and Load3 beyond BUS-3. The current limiting of DG1 during the fault is shown in Figure 42(a).
However, the DG1 switches into sleep mode as shown in Figure 42 (b) at 0.56 s since it is still
connected to the faulted segment. After the sleep mode time duration, the DG1 starts the
restoration at 0.755 s. The restoration process of DG1 will be unsuccessful due to the fault.
Therefore it is disconnected from the network at 0.82 s. The DG1 output current during the
restoration process is shown in Figure 42 (c). It can be seen that DG1 output current is very small
and the current will not rise due to the lower terminal voltage appears during the fault.
The relay R
1
starts the reclosing after DG1 has been disconnected. The attempt of reclosing will
also be unsuccessful due to the permanent fault. The variation of output real and reactive power of
DGs during and after the fault is shown in Figure 43. It can be seen that DG2 and DG3 supply the
power requirement in islanded mode while DG1 has been disconnected due to unsuccessful
restoration.
67
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 42: The output current variation of DG1
Figure 43: The variation of DG real and reactive power
6.1.12. C. System restoration with induction motor type loads
The system restoration with induction motor type loads is investigated in study. It is assumed that
two induction motors are connected at buses 3 and 4 respectively. The power rating of each motor
is selected as (0.128+ j 0.075) MVA. A half of the constant impedance load given in Table 5 is
assumed to be connected to buses 3 and 4. Thus, each load at buses 3 and 4 consists of induction
motor and constant impedance type load. A fault is created at 0.2 s between BUS-2 and BUS-3.
Once the downstream relay R
3
responds to isolate the fault at 0.507 s, the islanded system beyond
BUS-3 is recovered with two induction motors. The real and reactive power variation of DG2, DG3
and one of the induction motor is shown in Figure 44. According to the figure, the induction motor
draws higher reactive power initially and the reactive power requirement is supplied by DG2 and
DG3.
68
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
If large induction motors are present in the network during the constant current and sleep mode
time duration, these induction motors located near to a fault will be automatically disconnected due
to its own protection. Therefore when DGs start the restoration, the restoration will be easier and
quicker with the absence of induction generators.
Figure 44: The variation of DG and induction motor power
The current practice of immediate DG disconnection for every fault drastically reduces the benefits
of DGs to both utility and customers. In this section, the identified protection and control issues
which lead to immediate DG disconnections are addressed by proposing a protection scheme and
a control strategy for a converter. These proposals are capable of isolating a faulted segment, self
extinction of arc and automatic system restoration.
6.2. Protection using ITA relays
Overcurrent (OC) relays are sensitive to fault current levels in a network. Thus, protection of a DG
connected network using OC relays is difficult without a proper communication channel. To avoid
this problem, a new inverse time admittance (ITA) relay has been proposed for a DG connected
network to detect and isolate faults under low fault current levels or changing fault current levels
(Dewadasa et al., 2009a, Dewadasa et al., 2010). In this section, the new relay fundamentals are
briefly explained. Moreover, an application of ITA relays for a DG connected meshed network is
discussed.
6.2.1. Relay fundamentals
A radial distribution feeder as shown in Figure 45 is considered to explain the ITA relay
characteristics. It is assumed that the relay is located at node R and node K is an arbitrary point on
the feeder. The total admittance of the protected line segment is denoted by Y
t
while the measured
admittance between the nodes R and K is denoted by Y
m
. Then the normalized admittance (Y
r
) can
be defined in terms of Y
t
and Y
m
as
69
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
t
m
r
Y
Y
Y =
(89)
Figure 45: A radial distribution feeder
The variation of normalized admittance along a radial feeder is shown in Figure 46 by assuming
the feeder has a length of 3000m while the total feeder impedance is (0.195 + j 1.4451) . It can
be seen that normalized admittance decreases when measured point moves away from the relay
location.
Figure 46: The variation of normalized admittance
The change of normalized admittance along the feeder is used to obtain an inverse time tripping
characteristic for the relay. The general form for the inverse time characteristic of the relay can be
expressed as
k
Y
A
t
r
p
+
=
1
(90)
where A, and k are constants, while the tripping time is denoted by t
p
. The values for these
constants can be selected based on the relay location in a feeder and the protection requirements.
The shape of the proposed inverse time tripping characteristic can be changed by varying the
constants to obtain the required fault clearing time. When a network consists of different types of
protective devices, these constants can be selected appropriately for coordination purpose. The
70
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
relay tripping characteristic for A = 0.0047, = 0.08 and k = 0 is shown in Figure 47. The
magnitude of the normalized admittance (i.e. Y
r
) becomes higher as the fault point moves towards
the relay location. As a result, the relay gives a lower tripping time for a fault near to the relay. On
the other hand, higher fault clearing time can be obtained when the fault is further away from the
relay location.
Figure 47: Relay tripping characteristic curve
It is to be noted that the normalized admittance in (89) should be greater than 1.0 for relay tripping.
This implies that the measured admittance is greater than the total admittance as shown in (91).
This constraint is used by the relay algorithm to detect a faulted condition in the network.
Moreover, the relay algorithm checks this constraint continuously during the faulted condition until
relay issues the trip command to avoid any unnecessary tripping due to the effect of transients.
The tripping time is decided depending on the calculated value of measured admittance.
t m
t
m
r
Y Y
Y
Y
Y > > > 1 1
(91)
The ITA relay reach settings can be implemented by choosing a suitable value for the Y
t
. This is
totally dependent on the protection requirements such as primary and backup protections. For a
particular relay, different values of Y
t
can be assigned to generate a number of required zones of
protection. In each zone, the relay has a unique tripping characteristic. It checks whether the
measured admittance is greater than the total admittance of that particular zone before starting the
relay tripping time calculation. A large coverage and minimum tripping time can be achieved by
increasing the number of zones. It also leads to a good coordination amongst the relays in a
feeder. Any upstream relay always provides the backup protection for the immediate downstream
relay in the feeder. More details on relay hardware implementation and limitations can be found in
(Dewadasa et al., 2011).
71
INTELLIGENT GRID RESEARCH CLUSTER
Operation control and Energy Management of grid connected Distributed Generation in based on a microgrid
6.2.2. Simulation Studies using ITA relays
To demonstrate an application of ITA relays to a meshed network protection, a system shown in
Figure 48 is considered. This system has a partly meshed network containing BUS-1, BUS-2 and
BUS-5. There are three DGs and three loads in this system. All the DGs are connected through
voltage source converters (VSCs). These VSCs limit their output current to twice of the rated
current during a fault. Eight ITA relays are employed for secure and reliable operation of the
system. The relay locations are shown in the figure. The one of the main aims of the ITA relays is
to isolate the faulted segment quickly in the event of a fault allowing unfaulted sections to operate
either in grid connected or islanded mode depending on the fault location. In the case of an
islanded mode operation, each DG or DGs in the islanded section can operate in autonomous
mode if there is sufficient generation to supply the load demand. The system parameters are listed
in Table 9. In this study, no communication between relays is considered for a simple and cost
effective solution.
Figure 48: Meshed network under study
Table 9: System parameters
System parameter Value
Voltage 11 kV L-L rms
Frequency 50 HZ
Source impedance (0.078 + j 0.7854)
Each feeder
impedance (0.585 + j 4.335)
The relays R
12
, R
21
, R
15
, R
51
, R
52
and R
25
which are located in the meshed network have the
directional blocking feature in which these relays only respond to forward faults. This results in
proper relay coordination within the meshed network. For example, consider relay R
15
. It protects
the line segment between BUS-1 and BUS-5. Also it provides the backup protection for the line
segment between BUS-5 and BUS-2. However, R
15
is blocked for the reverse faults since R
12
should operate for the faults between BUS-1 and BUS-2. The relays R
12
and R
52
cover the line
segment between BUS-2 and BUS-3 in forward direction. On the other hand, the relay R
32
has the
directional feature and thus it can detect faults in either sides of BUS-3. The relay R
43
is also a
directional blocking relay which only responds for reverse faults since it is located at the end of the
feeder.
72
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
The relay reach settings of Zone-1 and Zone-2 are selected to cover 120% and 200% of the first
line length respectively. The selected constants for tripping characteristics of Zone-1 and Zone-2
are given in Table 10. The reach setting of Zone-3 is selected to cover fault resistance of 50 .
However, the grading of relays for Zone-3 is different to Zone-1 and Zone-2. In this system, R32,
R52, R15 and R12 in the forward direction and R51, R25, R21, R32 and R43 in the reverse
direction should be coordinated separately. When performing the ITA relay grading in Zone-3,
tripping time for forward faults should be increased, while it should be decreased for reverse faults
from downstream to upstream relays in the network. The graded Zone-3 tripping characteristics of
ITA relays are given in Table 11.
Table 10: Zone characteristics of ITA relay
Zone number A p k
Zone-1 0.0037 0.08 0.05
Zone-2 0.0037 0.1 0.1
Table 11: Zone-3 grading of ITA relays
Relay grading for forward faults Relay grading for reverse faults
3 . 0
1
0037 . 0
1 . 0 32
_ 3
+
=
r
R F Zone
Y
t
5 . 0
1
0037 . 0
1 . 0 43
_ 3
+
=
r
R R Zone
Y
t
4 . 0
1
0037 . 0
1 . 0 12
_ 3
+
=
r
R F Zone
Y
t
4 . 0
1
0037 . 0
1 . 0 32
_ 3
+
=
r
R R Zone
Y
t
4 . 0
1
0037 . 0
1 . 0 52
_ 3
+
=
r
R F Zone
Y
t
3 . 0
1
0037 . 0
1 . 0 21
_ 3
+
=
r
R R Zone
Y
t
5 . 0
1
0037 . 0
1 . 0 15
_ 3
+
=
r
R F Zone
Y
t
3 . 0
1
0037 . 0
1 . 0 25
_ 3
+
=
r
R R Zone
Y
t
2 . 0
1
0037 . 0
1 . 0 51
_ 3
+
=
r
R R Zone
Y
t
The system is simulated in PSCAD. A single-line-to-ground (SLG) fault is created at different
locations with different values of fault resistances at 0.2 s. The ITA relay fault clearing times and
subsequent system response are listed in . In each line segment, two fault locations are
considered. As can be seen from the results, the relays respond to isolate the faulted segment
effectively. For example, in the event of a fault between BUS-1 and BUS-2, the relays R
12
and R
21
respond to isolate the faulted segment. In this case, the rest of the system operates in grid
connected mode after the successful isolation of the faulted segment. Higher fault clearing time
can be experienced for resistive faults due to the relay grading and infeed effect of DGs. Within the
meshed configuration, fault current seen by relays are coming from different directions.
73
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Table 12: Fault clearing time of ITA relays
Fault location (between)
Fault clearing time of respective relay (seconds)
R
f
= 0.05 R
f
= 20
BUS-1 and
BUS-2
10% from BUS-1 R
12
=0.071,R
21
=0.137 R
12
=0.438,R
21
=0.774
90% from BUS-1 R
12
=0.137,R
21
=0.072 R
12
=0.443,R
21
=0.359
All the loads are supplied in grid connected mode without line Z
12
BUS-1 and
BUS-5
10% from BUS-1 R
15
=0.071,R
51
=0.137 R
15
=0.540,R
51
=0.774
90% from BUS-1 R
15
=0.136,R
51
=0.073 R
15
=0.544,R
51
=0.251
All loads are supplied in grid connected mode without line Z
15
BUS-2 and
BUS-5
10% from BUS-2 R
25
=0.072,R
52
=0.137 R
25
=0.348,R
52
=0.445
90% from BUS-2 R
25
=0.137,R
52
=0.073 R
25
=0.458,R
52
=0.443
All loads are supplied in grid connected mode without line Z
25
BUS-2 and
BUS-3
10% from BUS-2
R
12
=0.150,R
52
=0.158,
R
32
=0.082
R
12
=0.459,R
52
=0.472
R
32
=0.480
90% from BUS-2
R
12
=0.410,R
52
=0.427,
R
32
=0.075
R
12
=0.481,R
52
=0.494
R
32
=0.509
Load3 is supplied in grid connected mode while Load1 and Load2 supplied in
islanded mode without line Z
23
BUS-3 and
BUS-4
10% from BUS-3 R
32
=0.074,R
43
=0.137 R
32
=0.345,R
43
=0.615
90% from BUS-3 R
32
=0.139,R
43
=0.072 R
32
=0.349,R
43
=0.913
Load1 and Load3 are supplied in grid connected mode while Load2 is
supplied in islanded mode without line Z
34
6.3. Protection using Current Differential Relays
The power flow within a microgrid can be bi-directional due to DG connections at different locations
or its meshed configuration. This will create new challenges for protection. Some of the DGs
connected to a microgrid are intermittent in nature (e.g., solar photovoltaic based DGs). Therefore
different fault current levels can be experienced in the microgrid depending on the active DG
connections (Chowdhury et al., 2008). As a result, implementation of protection schemes based on
fault current level will be made difficult further. The reliability of a microgrid can be increased by
forming a meshed configuration. However, the protection schemes proposed for radial microgrids
cannot be effectively deployed in meshed microgrids (Prasai et al., 2010). The fault current seen
by each relay within the meshed configuration will not have an appreciable difference due to short
line segments in the microgrid. In this circumstance, fault detection and isolation will be difficult
without employing reliable communication channels.
In this section, protection strategies required for a microgrid are presented using current deferential
relays. The protection challenges associated with bi-directional power flow, meshed configuration,
changing fault current level due to intermittent nature of DGs and reduced fault current level in an
islanded mode are avoided in the microgrid using the proposed protection schemes. The relay
settings, communication requirements and the selection of a current transformer (CT) for a relay
are also discussed.
74
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
6.3.1. Protection Strategies
Protection strategies are proposed for a microgrid to achieve a safe and a reliable operation
thereby minimizing the identified issues. The proposed protection scheme (PS) should detect any
abnormal condition in the microgrid and it should isolate the smallest possible portion, thus
allowing rest of the system to continue operation. The PS should also allow the microgrid to
operate either in grid connected or islanded modes of operation providing appropriate safety to
customers and equipment. Consider the microgrid shown in Figure 49. The microgrid is connected
to the utility grid through a step up transformer. It has a partly meshed network containing BUS-1,
BUS-2 and BUS-5. There are four loads connected to the system. The protection should be
designed to incorporate both meshed and radial configurations.
Protection of the microgrid is discussed under different subgroups such as feeder and bus.
Different protection strategies are considered for each of the subgroups to provide appropriate
protection. The PS has a primary and a backup protection. If primary scheme fails then the backup
scheme comes into the operation appropriately. The primary PS for the microgrid is proposed with
the aid of communication while backup PS is designed to operate in the event of a communication
failure. The proposed PSs are discussed in the next subsections.
Figure 49: Schematic diagram of the microgrid
6.3.2. A. Feeder Protection
Each feeder in the microgrid is protected using two relays which are located at the end of the
feeder. In normal operating condition, current entering to a particular feeder should be equal to the
current leaving from that feeder. However, this condition will not be satisfied during a fault on the
feeder. Therefore, current differential protection is proposed to detect and isolate the feeder faults.
The differential protection is capable of providing the protection for a specified feeder effectively
while not responding to faults outside the region. The current differential protection is chosen for
the microgrid since it is not sensitive to bi-directional power flow, changing fault current level and
the number of DG connections. It also provides the required protection for both grid connected and
islanded modes of operation. Moreover, the protection is not affected by a weak infeed where it
can detect internal faults even without having any DG connected.
75
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
In the proposed current differential PS, each relay has five elements to provide the required
protection. Three phase elements for each phase and two other elements for negative and zero
sequence currents. The phase differential elements are responsible for providing high speed
protection for faults which have high currents. The negative and zero sequence differential
elements provide more sensitive earth fault protection for lower current unbalanced faults such as
high impedance ground faults in a feeder. Fast operating times can be obtained using this
differential protection due to the accuracy in fault detection. In addition to the differential protection
elements, overcurrent and under voltage based backup protection elements are incorporated. If
overcurrent based backup protection is only provided, the relays in an islanded microgrid will not
sense sufficient currents to detect faults due to lower fault current levels. However, the system
voltage will drop significantly since converters limit output currents during the fault. Therefore, the
reduction in system voltage can be used to implement the under voltage backup protection
scheme in the event of an overcurrent backup failure. However, the backup protection schemes
remain blocked during the normal operating condition of differential protection and it will activate
immediately, if communication failure is detected by a relay.
Figure 50 shows the single line representation of a current differential feeder protection for the
microgrid. Each relay at the end of the protected feeder is connected to its local current
transformer (CT) while two relays are connected through a communication link. Two relays
exchanges time synchronized phase current samples (i.e., phase currents of I
a
, I
b
and I
c
). Each
relay also calculates the negative sequence and zero sequence currents of local and remote end
relay locations. The current differential elements of each relay then compare phase and calculated
sequence parameters with respective remote end location quantities to identify a fault condition in
the feeder. If a fault is detected (i.e., internal fault), each relay will issue a trip command to its local
circuit breaker. The current differential protection is effective since it is sensitive, selective and fast.
Each relay has its operating and restraint characteristics to avoid any false tripping. A more
sensitive characteristic for a current differential relay can be implemented in modern digital relays
where operating and restrain regions can be separated by user defined slopes.
Figure 50: Differential feeder protection for microgrid
The bias current and the differential current are the two quantities which define the relay
characteristic for the operating and the restraint regions. The differential and bias currents are
defined in (92)and (93) respectively.
2 1
I I I
diff
+ =
(92)
2
2 1
I I
I
bias
+
=
(93)
I
1
and I
2
are secondary CT phase currents in each relay location. The relay may have two stages
(low and high) in tripping characteristic to provide a flexible and a secure operation. Such two
stage differential relay characteristic is shown in Figure 51. The high stage of the relay is defined
above a certain value of the differential current. This is a non-biased stage where the bias current
is not taken into consideration when issuing the tripping command. In this high set stage, the relay
76
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
shows a fast response.
The low stage is the biased stage with different user defined slopes. The relay has definite time
and inverse definite minimum time (IDMT) characteristics in this region. As can be seen from the
Figure 51, the relay tripping characteristic for low set stage has two slopes. These slopes can be
set by defining the percentage bias settings K1 and K2. The I
diff1
is the minimum differential current
threshold (i.e., pickup current for the relay). The pickup differential current increases with the fault
current increases. The current I
bias1
should be also defined and it differentiates the two slopes. This
dual slope characteristic provides a higher sensitivity during lower fault currents and improved
security for higher fault currents in which CT errors are large. The relay issues the trip command
when one of the following conditions given in (94) or (95) is satisfied.
1 1 1 diff bias diff bias bias
I I K I and I I + > <
(94)
1 1 1 2 2 1
) (
diff bias bias diff bias bias
I I K K I K I and I I + > >=
(95)
Figure 51: Differential relay characteristic
In normal operating condition, the differential current should be zero. However, due to the line
charging, CT saturation and inaccuracies in CT mismatch, it may not equal to zero. The problem of
saturation is overcome in modern numerical relays by using saturation detectors (Ganesan, 2006).
A calculation need to be carried out to determine the minimum pickup current for the relay (I
diff1
).
The setting of current differential relays should be performed lower enough to detect all types of
faults on the feeder while ensuring the relays do not respond for external faults due to the CT
errors and other measuring errors. The relay setting sensitivity is very important. However, the
increase in sensitivity may also cause to decrease the security.
6.3.3. B. Bus Protection
Buses in the microgrid may have connected to loads, DGs and feeders. Therefore, a high speed
protection is very important for a bus fault to avoid any extensive damage in the microgrid. The
differential protection arrangement for a bus protection is shown in Figure 52. The protection
principle is similar to the one explained in differential feeder protection. However, in this case, the
relay will issue a trip command to all the circuit breakers connected to the bus during a bus fault.
77
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 52: Differential bus protection
6.3.4. C. DG Protection
All the DGs in the microgrid should be protected from abnormal conditions. Therefore, each DG is
employed with several protection elements; under voltage, reverse power flow, over voltage and
synchronism check. The relay associated with these protection elements issue a trip command to
DG circuit breaker once any abnormal condition is detected. The under voltage tripping is activated
below a set voltage level after a defined time period. The defined time allows microgrid relays to
isolate a fault and restore the system maintaining as many DG connections as possible. The
reverse power flow protection activates to trip the DG when current flows towards the DG. The
over voltage element responds, when the voltage at point of connection rises above a predefined
limit. The synchronism check element ensures a trouble free connection to the microgrid when it is
being reconnected after any disconnection. These protection schemes will ensure the DG safety.
6.3.5. D. The Need for Communication
A communication link between feeder end relays is a key requirement in current differential
protection scheme. Therefore, a reliable communication channel is required. Relay to relay
communication can be performed using wires, power line carrier, microwave, fiber optic or
Ethernet connection. However, with the deployment of smart system technologies, communication
channels will be readily available for the future microgrids.
The current information at the remote end needs to be transferred to the local end. The digital
current differential relays sample the line currents and then send them over a communication
channel to the other relay. This may introduce a time delay which can be seen as a phase shift
between local and remote end current samples and as a result, the relays may calculate a
differential current. To avoid this problem, proper time synchronization of current phasors is
required. The modern digital relays are capable of measuring the time delay and performing the
compensation during the calculation. The channel based synchronization methods such as ping-
pong can be used to estimate the time delay. By knowing the time delay, it is possible to align the
local data with the remote end data. At the same time, the communication link should be
monitored. When a failure in communication link is detected, the relays should automatically switch
into their backup protection schemes.
78
INTELLIGENT GRID RESEARCH CLUSTER
Operation control and Energy Management of grid connected Distributed Generation in based on a microgrid
6.3.6. E. Current Transformer Selection for Protection
IEEE C57.13 (IEEE standard requirements for instrument transformers) and IEEE C37.11 (IEEE
guide for the application of current transformers used for protective relaying purposes) provide
guidelines in selecting CTs for protective relays. CT ratio (rated primary and secondary current),
CT accuracy class, polarity, saturation voltage, knee point voltage, excitation characteristics and
primary side voltage rating and current rating are some of the major factors should be considered
when selecting a CT for a protective relay application.
The turn ratio of a CT defines the rated primary and secondary current of the CT. Usually the
secondary rated current is 5A. The primary current rating of a CT is selected considering the
maximum current in normal operating condition and the maximum symmetrical fault current. The
selected primary current should be greater than the maximum current that the CT is expected to
carry in normal operating condition and it should also be greater than one twentieth (1/20) of the
maximum symmetrical fault current. The latter condition will satisfy that the secondary current of
the CT will be less than 20 times the rated secondary current during the maximum fault current.
When the voltage increases in the secondary of a CT, the exciting current also increases. With the
increase of secondary voltage further beyond a limit causes the magnetic saturation of the CT core
due to higher flux. The CT saturation results in the increase of ratio error and distorted secondary
current waveform. A particular CT behavior can be found by using its excitation curves which show
the relationship between secondary voltage and the excitation current of the CT. The knee-point
voltage and the saturation voltage can be found using the excitation curve in a CT. If the selected
CT ratio is very low such that the secondary current of a CT exceeds 20 times the rated current
during a fault, the CT may end with severe saturation. To avoid the saturation in a CT, the
secondary saturation voltage (V
x
) should satisfy the condition in (96) (IEEE.Std.C37.110, 2008).
) (
B L S S x
Z X R I V + + >
(96)
where I
S
the ratio between the primary current and the CT turns ratio, R
S
is the CT secondary
resistance, X
L
is the leakage reactance and Z
B
is the total secondary burden which includes
secondary leads and devices. Moreover, DC transients present during a fault can cause CT
saturation. Depending on the time a fault occurs (i.e., a point at fault occurs in the wave), the
magnitude of the DC component will change and it decays with a time constant. The saturation
due to both AC and DC components can be avoided by selecting the saturation voltage of a CT
according to (97).
(
+ + + >
R
X
Z X R I V
B L S S x
1 ) (
(97)
where X is the primary system reactance and R is the resistance up to the fault point. It can be
seen that the value of saturation depends on the X/R ratio of the system. The effect of CT
saturation may be avoided by selecting appropriate CT ratios to have the saturation voltage above
the value expected from AC and DC transient fault currents. Also a CT takes a finite time period to
become its saturated state.
A CT used for protective relays has an accuracy rating. A letter and a CT secondary terminal
voltage define the ANSI CT relaying accuracy class (IEEE.Std.C37.110, 2008). Most of the CTs
designed for relays are covered by C and K classes. These two classes indicate that the
secondary winding is uniform around the core thus leakage flux is negligible. The standard
accuracy classes for C class CTs are C100, C200, C400 and C800 with standard burden of 1, 2, 4,
8 respectively. The ratio error of a CT should be less than 10% for any current between 1 to 20
79
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
times secondary rated current at the standard burden or any lower standard burden
(IEEE.Std.C37.110, 2008). For example, if a CT with C100 class is selected, the ratio current error
will not exceed 10% at any current from 1 to 20 times rated secondary current (i.e., 5A) with a
standard 1 burden. However, if the saturation of a CT occurs then the error ratio will exceed
10%.
6.3.7. Microgrid Protection Studies
Consider the microgrid system shown in Figure 49. The parameters of the microgrid are given in
Table 13. The microgrid connection/disconnection is controlled by the microgrid control switch
(MGCS). It is assumed that all the DGs are converter interfaced and the DG control is designed to
enable the microgrid islanded operation during a grid disturbance. Moreover, these DGs limit their
output currents to twice the rated current during a fault in the microgrid to protect their power
switches.
The CT ratio for a particular CT is selected based on the maximum load current and the maximum
fault current seen by the relay. To calculate the maximum load current seen by a relay, different
system configurations are considered. For example, the relay R
12
senses the maximum load
current when all the DGs inject current into utility grid without any load is connected to microgrid
and the feeder section between BUS-1 and BUS-5 is not in service. The maximum possible fault
current seen by each relay also calculated. The CT ratio for a relay is then selected based on the
criteria that the CT can deliver 20 times rated secondary current without exceeding 10% ratio error
and the rated primary current to be above the maximum possible load current. The accuracy class
for CTs is selected as C200. The selected CT ratio for each relay is given in Table 14.
Table 13: System Parameters
System parameter Value
Voltage 11 kV L-L rms
Frequency 50 HZ
Transformer power rating 5MVA
Transformer impedance
(0.05 + j 2.1677)
Each feeder impedance
(0.94 + j 2.5447)
Each load impedance (100 + j 75)
DG1 power rating 0.8 MVA
DG2 power rating 1.2 MVA
DG3 power rating 1.5 MVA
DG4 power rating 1.0 MVA
80
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Table 14: CT ratio selection
Relay I
fmax
(A) I
fmax
/20 (A) I
Lmax
(A)
CT ratio
R
12
2535 126 236 300:5
R
21
1478 74 236 300:5
R
15
2541 127 236 300:5
R
51
956 48 236 300:5
R
25
1111 56 184 200:5
R
52
998 50 184 200:5
R
23
1478 74 142 150:5
R
32
917 46 142 150:5
R
34
917 46 79 100:5
R
43
654 33 79 100:5
I
fmax
-Maximum fault current
I
Lmax
- Maximum possible load current
To show how selected CT ratios perform during a fault, the CT associated with relay R
12
is
considered. The selected CT ratio for this relay is 300:5 and CT class is C200. During the
maximum fault current, the CT secondary current will be 42.25A. Now consider the voltage
saturation equation in (97) to calculate the maximum allowable saturation voltage for this relay.
The burden for a numerical relay is small. The parameters for this calculation are X/R=1.3, R
s
=0.15
, X
L
=0, relay burden= 0.02 , leads resistance=0.25 . Substituting these values in (97) gives,
| | 3 . 1 1 ) 02 . 0 25 . 0 0 15 . 0 ( 25 . 42 + + + + >
x
V
V V
x
81 . 40 <
This shows that the saturation voltage of the CT should be above the 40.81 V to avoid saturation.
The selected CT is satisfied this condition. Also, it can be seen that the leads resistance can be
changed by selecting different wire sizes to allow a better margin for the CT saturation if
necessary.
The effect of capacitive charging current on current differential protection can be negligible since
the microgrid consists of short line segments. The slope settings are selected to ensure the
differential elements do not respond for external faults due to CT ratio and other measurement
errors. The minimum setting for differential current is calculated allowing for errors arising from
CTs. It is assumed that the CT error will not exceed 2% for currents less than the rated secondary
current (i.e., 5A). The maximum error is then calculated assuming one CT to be +2% while the
other CT to be -2%. Therefore, the error of 4% due to both CTs produces current of 0.2 A (50.04).
Thus it is proposed to select the setting of I
diff1
above 0.2 A. The other settings for the differential
relay characteristic shown in Figure 51 are selected based on the fault behavior of the microgrid
and they are given below.
K
1
=30%, K
2
=100%, I
bias1
=5 A, I
diff1
=0.2 A
With the selected settings and CTs, fault response of the microgrid is investigated. Different types
of faults are generated at different locations. The fault resistance is varied from 1 to 20 . The
maximum CT ratio error of 10% is assumed. The fault response of relays R
12
and R
21
for internal
and external feeder faults is shown in Figure 53. It can be seen that the response of relays for
internal feeder faults are within the operating region, while for the external faults, the response lies
within the restraint region.
81
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 53: Relays R
12
and R
21
response for microgrid faults
The response of relays R
23
and R
32
which are located in radial feeder is next investigated. The fault
response of relays for both internal and external faults is shown in Figure 54. It is clear that these
relays detect only internal faults distinguishing from external faults.
Figure 54: Relays R
23
and R
32
response for microgrid faults
The simulation results obtained from PSCAD for a single line to ground fault between BUS-2 and
BUS-5 are shown in
Figure 55 and Figure 56. The fault is created at 0.4 s with a 10 resistance. In this case it is
assumed that 10ms communication channel delay exists for the differential relays.
Figure 55 shows the variation of differential and bias currents during the fault while relay response
for this fault is shown in Figure 56. The simulated fault in PSCAD gives 13.04 A and 6.52 A for
differential and bias current respectively. In MATLAB, differential and bias current for this fault is
calculated as 13.16A and 6.61A respectively. This verifies the calculated results in MATLAB with
the simulation results.
82
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
83
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Figure 55: The variation of differential and bias current
Figure 56: The relay response for a fault between BUS-2 and BUS-5
The investigation of relay response in islanded operation is very important to ensure the relays are
capable of detecting faults in the islanded microgrid. A fault is created at different locations in the
microgrid. The fault resistance is varied from 0.1 to 20 . The response of relays R
12
and R
21
is
shown in Figure 57. The relay response for the faults is accurate. It can be seen that the fault
current level is significantly low due to the current limiting of converters. However, the relays detect
the internal faults effectively avoiding any external faults. Therefore, it can be concluded that these
relays are capable of detecting faults either in grid connected or islanded modes of operation
without changing any relay settings.
Figure 57: Relays R
12
and R
21
response for faults in islanded microgrid
84
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
In this section, a primary protection scheme for a microgrid is presented using current differential
relays with the aid of a communication channel. The protection issues associated with meshed
structure, microgrid islanded operation, fault detection under low fault current levels are avoided
with the use of modern differential relays. Relay settings and CT selection requirements are also
discussed. Results show that the proposed protection strategies can provide selectivity and high
level of sensitivity for internal faults in both grid-connected and islanded modes of operation
thereby allowing a safe and a reliable operation for a microgrid.
6.4. Summary
In this section, protection strategies were proposed to overcome the protection issues associated
with radial and meshed microgrids. Protection schemes were designed to detect and isolate the
smallest portion of a faulted section allowing unfaulted sections to operate either in grid-connected
or islanded mode operation. Firstly, a protection scheme for a DG connected radial network was
proposed using overcurrent and communication channels. Secondly, a new inverse time
admittance relay characteristic was presented. Finally, the protection of a meshed microgrid using
current differential relays was presented. The proposed techniques can be effectively used to
minimise protection issues of microgrids thereby assuring a safe and a reliable operation.
85
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
7. CONCLUSIONS
The concept of microgrid facilitates the integration of distributed energy resources into a
distribution network in a more intelligent way. Renewable based energy sources can be effectively
connected and managed to increase reliability to customers in a microgrid. The microgrid can
operate either in grid connected or islanded (i.e., autonomous) mode. The available power of all
DG units should meet the total load demand for autonomous operation; otherwise load shedding
need to be implemented. The frequency and voltage in an islanded microgrid should be maintained
within the predefined limits to ensure a safe operation.
DGs in a microgrid are different from one another. They have different transient characteristics.
The inertial based DGs show a slower response while non-inertial DGs can respond very quickly
during transient events. This mismatch of response rate in different DGs creates transient
oscillations in an islanded microgrid where no strong source is present to control the system
frequency and voltage. Also, output power of intermittent DGs such as wind and solar is not
dispatchable to control the microgrid frequency and voltage. Moreover, intelligent control strategies
are required for energy storage devices. Therefore, power management strategies are vital when
non-dispatchable DGs and energy storage devices are present in the microgrid.
In this report, improved control and power management strategies for a microgrid are proposed.
The efficacy of angle based droop over conventional frequency based droop in a converter
interfaced autonomous microgrid is presented in this report. The angle droop and the frequency
droop controllers are designed to provide the same stability margin. The results reveal that the
frequency variation with the frequency droop controller is significantly higher than that with the
angle droop controller. Thus, the angle based droop improves the transient stability of the
microgrid minimizing the frequency and power oscillations.
Furthermore, improved droop control strategy called integral to system droop line is proposed for a
microgrid containing both inertial and non-inertial DGs. This proposal alleviates the problem
associated with different response rates of DGs thereby minimizing the oscillations. It also ensures
the proper load power sharing amongst the DGs. Moreover, power management strategies are
presented to incorporate dispatchable, non-dispatchable and energy storage devices. The Non-
dispatchable DGs are controlled in MPPT. An intelligent controller for battery storage (BS) is
proposed to manage the charging and discharging while maintaining the operating reserve in the
BS to achieve the system stability. To enhance a flexible operation in the microgrid maximizing the
benefits of renewable energy, an adaptive droop line is proposed for the BS. During the charging
and discharging, the slope of the droop is selected appropriately by the BS intelligent controller.
Control strategies for a DG converter are imperative since most of the sources in a microgrid are
interfaced through converters. Therefore, control design for converters is presented in this report.
A voltage source converter can either be controlled by PWM or by hysteresis control.
Since the droop gains can cause instability in the microgrid system, proper study must be
performed for the selection of droop gains in a microgrid containing several DGs. Two eigenvalue
analysis techniques that can be applied when more than one converter operate in decentralized
droop control are presented. One of the techniques assumes that the converters are ideal voltage
sources that track the desired reference voltages accurately. The filter dynamics are not
considered for this purpose. This eigenvalue analysis technique can be used as a screening tool
for droop gain selection. This simple technique is independent of converter control strategy and will
provide desired result irrespective of the converter structure and its control.
86
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
The second eigenvalue analysis technique presents a method for linear analysis of hysteretic
controlled state feedback converters. One of the features of the proposed analysis is that state
order is lower than those required for PWM converters. The process of analysis is illustrated using
two VSCs that are connected at a bus. There is risk of oscillations of filter states the converters
when they are connected at close proximity (e.g. in a microgrid). The robustness of the LQR based
hysteretic design is able to be clearly shown using the Eigen-analysis tool developed in this report.
The analysis process can be easily extended to include multiple converters, both hysteric and
PWM controlled, that are connected to multiple buses of a power system.
In this report, protection issues associated with both radial and meshed microgrids are addressed.
Protection schemes are proposed to detect and isolate the smallest portion of a faulted section
allowing unfaulted sections to operate either in grid-connected or islanded mode thereby
maintaining as many DG connections as possible in a microgrid.
Disconnection of DGs for every fault in a network drastically reduces the reliability and DG benefits
to customers when DG penetration level is high. A control strategy for a converter and a protection
scheme using digital OC relays are proposed, for a radial network containing high level of DG
penetration, to achieve fault isolation, self extinction of arc, islanded and grid-connected operation
without disconnecting DGs from unfaulted segments, and a method to perform system restoration
in the presence of DGs using auto reclosers. One way communication is used between DGs and
relays to change the relay reach settings appropriately.
Inverse time admittance (ITA) relay is presented to isolate a faulted section in a meshed microgrid
avoiding the limitations of the existing overcurrent relays. It is shown that ITA relays are capable of
detecting faults under lower fault current levels and changing fault current levels in the microgrid
containing converter interfaced DGs. Moreover, a primary protection scheme for a meshed
microgrid is presented using current differential relays with the aid of a communication channel.
The protection issues associated with meshed structure, microgrid islanded operation, fault
detection under low fault current levels are avoided with the use of modern differential relays.
Results show that the proposed protection strategies can provide selectivity and high level of
sensitivity for internal faults in both grid-connected and islanded modes of operation thereby
allowing a safe and a reliable operation for a microgrid.
The control, power management and protection strategies presented in this report addressed the
issues and challenges associated with a successful microgrid operation. The results of this study
show that the incorporating proposed methods will lead to a stable, reliable and a safe microgrid
operation in both grid connected and islanded modes of operation. The alleviation of potential
barriers for the implementation of future microgrids is the major outcome of this study conducted.
87
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
8. REFERENCE LIST
AHN, S. J., PARK, J. W., CHUNG, I. Y., MOON, S. I., KANG, S. H. & NAM, S. R. 2010. Power-
Sharing Method of Multiple Distributed Generators Considering Control Modes and
Configurations of a Microgrid. IEEE Transactions on Power Delivery, 25, 2007-2016.
AL-NASSERI, H., REDFERN, M. A. & LI, F. 2006. A Voltage Based Protection for Micro-grids
Containing Power Electronic Converters. IEEE Power Engineering Society General
Meeting.
ANDERSON, B. D. O. & MOORE, J. B. 1971. Linear Optimal Control, Prentice-Hall, Englewood
Cliffs, N.J.
AREDES, M., HAFNER, J. & HEUMANN, K. 1997. Three-phase four-wire shunt active filter control
strategies. Power Electronics, IEEE Transactions on, 12, 311-318.
BRABANDERE, K. D., BOLSENS, B., KEYBUS, J. V. D., WOYTE, A., DRIESEN, J. & BELMANS,
R. 2007. A Voltage and Frequency Droop Control Method for Parallel Inverters. IEEE
Transactions on Power Electronics, 22, 1107 - 1115.
BRUCOLI, M., GREEN, T. C. & MCDONALD, J. D. F. 2007. Modelling and Analysis of Fault
Behaviour of Inverter Microgrids to Aid Future Fault Detection. IEEE International
Conference on System of Systems Engineering 1-6.
CHANDORKAR, M. C., DIVAN, D. M. & ADAPA, R. 1993. Control of parallel connected inverters in
standalone AC supply systems. IEEE Transactions on Industry Applications, 29, 136 - 143
CHEUNG, H., HAMLYN, A., WANG, L., YANG, C. & CHEUNG, R. 2009. Investigations of Impacts
of Distributed Generations on Feeder Protections. IEEE Power & Energy Society General
Meeting.
CHO, S.-M., SHIN, H.-S. & KIM, J.-C. 2010. Impact of Distribution System Quality on DG
Interconnection Protection. IEEE Power & Energy Society General Meeting.
CHOWDHURY, S. P., CHOWDHURY, S., TEN, C. F. & CROSSLEY, P. A. 2008. Islanding
Protection of Distribution Systems with Distributed Generators A Comprehensive Survey
Report IEEE Power and Energy Society General Meeting.
COELHO, E. A. A., CORTIZO, P. C. & GARCIA, P. F. D. 2002. Small-signal stability for parallel-
connected inverters in stand-alone AC supply systems. Industry Applications, IEEE
Transactions on, 38, 533-542.
DEWADASA, M., GHOSH, A. & LEDWICH, G. 2009a. An inverse time admittance relay for fault
detection in distribution networks containing DGs. IEEE Region 10 Conference (TENCON).
Singapore.
DEWADASA, M., GHOSH, A. & LEDWICH, G. 2010. Fold back current control and admittance
protection scheme for a distribution network containing distributed generators. IET
Generation Transmission & Distribution, 4, 952-962.
DEWADASA, M., GHOSH, A., LEDWICH, G. & WISHART, M. 2011. Fault isolation in distributed
generation connected distribution networks. IET Generation, Transmission & Distribution.
DEWADASA, M., MAJUMDER, R., GHOSH, A. & LEDWICH, G. Year. Control and protection of a
microgrid with converter interfaced micro sources. In: Power Systems, 2009. ICPS '09.
International Conference on, 27-29 Dec. 2009 2009b. 1-6.
DRIESEN, J., VERMEYEN, P. & BELMANS, R. 2007. Protection Issues in Microgrids with Multiple
Distributed Generation Units. Power Conversion Conference - Nagoya, 646-653.
GANESAN, S. Year. Selection of current transformers and wire sizing in substations. In:
88
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
Protective Relay Engineers, 2006. 59th Annual Conference for, 0-0 0 2006. 10 pp.
GHOSH, A. & JOSHI, A. 2000. A new approach to load balancing and power factor correction in
power distribution system. Power Delivery, IEEE Transactions on, 15, 417-422.
GHOSH, A. & LEDWICH, G. 2003. Load compensating DSTATCOM in weak AC systems. Power
Delivery, IEEE Transactions on, 18, 1302-1309.
GHOSH, A., LEDWICH, G., ZARE, F. & MAJUMDER, R. 2011. Stability analysis of multiple
voltage source converters connected at a bus. Int. Conf. on Smart Grids, Green
Communications and IT Energy-aware Technologies. Venice, Italy.
GOMEZ, J. C. & MORCOS, M. M. 2005. Coordination of Voltage Sag and Overcurrent Protection
in DG Systems. IEEE Transactions on Power Delivery, 20, 214-218.
GREEN, T. C. & PRODANOVI, M. 2007. Control of Inverter-based Micro-grids. Electric Power
Systems Research, ScienceDirect, 77, 1204-1213.
GUERRERO, J. M., BERBEL, N., DE VICUNA, L. G., MATAS, J., MIRET, J. & CASTILLA, M.
Year. Droop control method for the parallel operation of online uninterruptible power
systems using resistive output impedance. In: Applied Power Electronics Conference and
Exposition, 2006. APEC '06. Twenty-First Annual IEEE, 19-23 March 2006 2006. 7 pp.
GUERRERO, J. M., DE VICUNA, L. G., MATAS, J., CASTILLA, M. & MIRET, J. 2004. A wireless
controller to enhance dynamic performance of parallel inverters in distributed generation
systems. Power Electronics, IEEE Transactions on, 19, 1205-1213.
GUERRERO, J. M., VICUNA, L. G. D., MATAS, J. & MIRET, J. 2002. Steady-state invariant-
frequency control of parallel redundant uninterruptible power supplies. IECON 02 [Industrial
Electronics Society, IEEE 2002 28th Annual Conference of the]
IEEE 1993. Load Representation for Dynamic Performance Analysis IEEE Transactions on Power
Systems, 8, 472 - 482
IEEE.STD.1547 2003. IEEE Standard for Interconnecting Distributed Resources with Electric
Power Systems.
IEEE.STD.C37.110 2008. IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes. IEEE Std C37.110-2007 (Revision of Std C37.110-1996).
J. A. P. LOPES, C. L. MOREIRA & A. G. MADUREIRA 2006. Defining Control Strategies for
MicroGrids Islanded Operation. IEEE Transactions on Power Systems, 21, 916-924.
J. DRIESEN, P. VERMEYEN & R. BELMANS 2007. Protection Issues in Microgrids with Multiple
Distributed Generation Units. Power Conversion Conference - Nagoya, 646-653.
JAVADIAN, S. A. M., HAGHIFAM, M. R. & REZAEI, N. 2009. A Fault Location and Protection
Scheme for Distribution Systems in Presence of DG Using MLP Neural Networks IEEE
Power & Energy Society General Meeting.
JIANG, Z. H. & YU, X. W. 2009. Active Power - Voltage Control Scheme for Islanding Operation of
Inverter-Interfaced Microgrids. IEEE Power & Energy Society General Meeting, 1738-1744.
KARIMI, H., NIKKHAJOEI, H. & IRAVANI, R. 2007. A Linear Quadratic Gaussian Controller for a
Stand-alone Distributed Resource Unit-Simulation Case Studies IEEE Power Engineering
Society General Meeting.
KATIRAEI, F. & IRAVANI, M. R. 2006. Power management strategies for a microgrid with multiple
distributed generation units. IEEE Transactions on Power Systems, 21, 1821-1831.
KATIRAEI, F., IRAVANI, R., HATZIARGYRIOU, N. & DIMEAS, A. 2008. Microgrids management.
IEEE Power & Energy Magazine, 6, 54-65.
KAUR, G. & VAZIRI, M. 2006. Effect of Distributed Generation (DG) Interconnection on Protection
of Distribution Feeders. IEEE Power Engineering Society General Meeting
89
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
KHALIL, H. K. 2002. Nonlinear Systems, Prentice-Hall, Upper Saddle River, N.J.
KRISHNAMURTHY, S., JAHNS, T. M. & LASSETER, R. H. 2008. The Operation of Diesel
Gensets in a CERTS Microgrid. IEEE Power & Energy Society General Meeting.
KUMPULAINEN, L. & KAUHANIEMI, K. 2004a. Distributed Generation and Reclosing
Coordination. Nordic Distribution and Asset Management Conference.
KUMPULAINEN, L. K. & KAUHANIEMI, K. T. 2004b. Analysis of the Impact of Distributed
Generation on Automatic Reclosing. Power Systems Conference and Exposition, 1, 603-
608.
KUO, B. C. 1980. Digital Control Systems, Holt-Saunders, Tokyo,.
LAAKSONEN, H. J. 2010. Protection Principles for Future Microgrids. IEEE Transactions on Power
Electronics, 25, 2910-2918.
LOIX, T., WIJNHOVEN, T. & DECONINCK, G. Year. Protection of microgrids with a high
penetration of inverter-coupled energy sources. In: CIGRE/IEEE PES Joint Symposium on
Integration of Wide-Scale Renewable Resources Into the Power Delivery System 29-31
July 2009 2009. 1-6.
LOPES, J. A. P., MOREIRA, C. L. & MADUREIRA, A. G. 2006. Defining control strategies for
microgrids islanded operation. IEEE Transactions on Power Systems, 21, 916-924.
MAJUMDER, R., CHAUDHURI, B., GHOSH, A., LEDWICH, G. & ZARE, F. 2010. Improvement of
Stability and Load Sharing in an Autonomous Microgrid Using Supplementary Droop
Control Loop. IEEE Transactions on Power Systems, 25, 796-808.
MAJUMDER, R., GHOSH, A., LEDWICH, G. & ZARE, F. 2008. Control of parallel converters for
load sharing with seamless transfer between grid connected and islanded modes
IEEE Power and Energy Society General Meeting.
MAJUMDER, R., GHOSH, A., LEDWICH, G. & ZARE, F. 2009a. Angle Droop Versus Frequency
Droop in a Voltage Source Converter Based Autonomous Microgrid IEEE Power & Energy
Society General Meeting.
MAJUMDER, R., GHOSH, A., LEDWICH, G. & ZARE, F. 2009b. Load Sharing and Power Quality
Enhanced Operation of a Distributed Microgrid. IET Renewable Power Generation, 3, 109-
119.
MAJUMDER, R., SHAHNIA, F., GHOSH, A., LEDWICH, G., WISHART, M. & ZARE, F. 2009c.
Operation and Control of a Microgrid Containing Inertial and Non-Inertial Micro Sources.
IEEE Region 10 Conference (Tencon). Singapore: IEEE.
MARTINEZ, J. A. & MARTIN-ARNEDO, J. 2009. Impact of Distributed Generation on Distribution
Protection and Power Quality IEEE Power & Energy Society General Meeting.
MOHAN, N., UNDELAND, T. M. & ROBBINS, W. P. 2003. Power Electronics: Converters,
Applications and Design, John Wiley, New York.
NIKKHAJOEI, H. & LASSETER, R. H. 2007. Microgrid Protection. IEEE Power Engineering
Society General Meeting, 1-6.
PERERA, N., RAJAPAKSE, A. D. & BUCHHOLZER, T. E. 2008. Isolation of Faults in Distribution
Networks with Distributed Generators. IEEE Trans. on Power Delivery, 23, 2347-2355.
POGAKU, N., PRODANOVIC, M. & GREEN, T. C. 2007. Modeling, Analysis and Testing of
Autonomous Operation of an Inverter-Based Microgrid. Power Electronics, IEEE
Transactions on, 22, 613-625.
PRASAI, A., YI, D., PAQUETTE, A., BUCK, E., HARLEY, R. & DIVAN, D. Year. Protection of
meshed microgrids with communication overlay. In: IEEE Energy Conversion Congress
and Exposition, 12-16 Sept. 2010 2010. 64-71.
90
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation
REZA, M., SUDARMADI, D., VIAWAN, F. A., KLING, W. L. & VAN DER SLUIS, L. Year. Dynamic
Stability of Power Systems with Power Electronic Interfaced DG. In: Power Systems
Conference and Exposition, 2006. PSCE '06. 2006 IEEE PES, Oct. 29 2006-Nov. 1 2006
2006. 1423-1428.
SHAHABI, M., HAGHIFAM, M. R., MOHAMADIAN, M. & NABAVI-NIAKI, S. A. 2009. Dynamic
Behavior Improvement in a Microgrid with Multiple DG Units Using a Power Sharing
Approach. In: TOMA, L. & OTOMEGA, B. (eds.) IEEE Bucharest Power Tech Conference.
SLOTINE, J. J. E. & LI, W. 1991. Applied Nonlinear Control, Prentice-hall, Englewood Cliffs, N.J.
SVENSSON, J. 2001. Synchronisation methods for grid-connected voltage source converters. IEE
Generation, Transmission and Distribution 148, 229 - 235.
TAN, J. C., MCLAREN, P. G., JAYASINGHE, R. P. & WILSON, P. L. 2002. Software Model for
Inverse Time Overcurrent Relays Incorporating IEC and IEEE Standard Curves. IEEE
Canadian Conference on Electrical and Computer Engineering
TAN, S. F. & SALMAN, S. K. 2009. Application of Single Pole Auto Reclosing in Distributaion
Networks with High Pentration of DGS Universities Power Engineering Conference (UPEC)
VASQUEZ, J. C., GUERRERO, J. M., MIRET, J., CASTILLA, M. & DE VICUNA, L. G. 2010.
Hierarchical Control of Intelligent Microgrids. Industrial Electronics Magazine, IEEE, 4, 23-
29.
ZAMANI, A., SIDHU, T. & YAZDANI, A. 2010. A Strategy for Protection Coordination in Radial
Distribution Networks with Distributed Generators. IEEE Power & Energy Society General
Meeting.
ZAMANI, M. A., SIDHU, T. S. & YAZDANI, A. 2011. A Protection Strategy and Microprocessor-
Based Relay for Low-Voltage Microgrids. IEEE Transactions on Power Delivery, PP, 1-1.
ZEINELDIN, H. H., EL-SAADANY, E. F. & SALAMA, M. M. A. 2006. Distributed Generation Micro-
Grid Operation: Control and Protection. IEEE Power Systems Conference: Advanced
Metering, Protection, Control, Communication, and Distributed Resources.
ZHANG, L., HARNEFORS, L. & NEE, H.-P. 2010. Power-Synchronization Control of Grid-
Connected Voltage-Source Converters. IEEE Transactions on Power Systems, 25, 809 -
820.
91
INTELLIGENT GRID RESEARCH CLUSTER
Operation Control and Energy Management of grid connected Distributed Generation