Vc33 Kompend Kap06 e
Vc33 Kompend Kap06 e
2001
Parameterizing steps
Parameterizing steps
The chapter entitled "Parameterizing Steps" describes the parameter
assignments to be made for starting up SIMOVERT MASTERDRIVES:
In addition to this chapter, you should also refer to Chapter 3 (First
Start-Up) and Chapter 8 (Parameterization) in the operating
instructions.
The parameterizing steps are divided into different categories:
Parameter reset to factory setting (6.1)
Quick parameterization procedures (6.2)
Detailed parameterization (6.3)
Parameter reset to
factory setting
The factory setting is the defined initial state of all the parameters of a
unit. The units are delivered with this setting.
A detailed description is given in section 6.1.
Quick
parameterization
procedures
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-1
Parameterizing steps
10.2001
Detailed
parameterization
Supply
conditions
Power sections
CUVC
Optional
boards
Motor
Drive setting
(P060 = 5)
Function adjustment
Fig. 6-1
6-2
Procedures for
quick parameterization
As-delivered state
Board configuration
(P060 = 4)
Detailed
parameterization
Motor
encoder
10.2001
6.1
Parameterizing steps
Parameter name
P050
Language
P070
P072
P073
P366
Select FactSet
P947
Fault memory
P949
Fault value
Table 6-1
If the parameters are reset to the factory setting via one of the
parameters (SST1, SST2, SCB, 1.CB/TB, 2.CB/TB), the interface
parameters of that interface are not changed either. Communication via
that interface therefore continues even after a parameter reset to the
factory setting.
Parameter number
Parameter name
P053
Parameterization enable
P700
P701
P702
P703
P704
Table 6-2
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-3
Parameterizing steps
10.2001
Parameter number
Parameter name
P053
Parameterization enable
P696
SCB protocol
P700
P701
P702
P703
P704
Table 6-3
Parameter number
Parameter name
P053
Parameterization enable
P711 to P721
CB parameters 1 to 11
P722
P918
CB bus address
Table 6-4
NOTE
6-4
The factory setting is made via interface SCB2: Parameters that are not
changed by the factory setting either. None of the indices of the
parameters is changed.
10.2001
Parameterizing steps
P053 = 6
P060 = 2
P366 = ?
P970 = 0
Unit carries out parameter
reset and then leaves the
"Fixed settings" menu
Fig. 6-2
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-5
Parameterizing steps
10.2001
Factory settings
dependent on P366
Para- Designation of the Factory setting Factory setting
meters parameter on the
with
with
depenOP1S
PMU
OP1S
dent on
P366
(Src = Source)
P366 = 0
P366 = 1
BICO2
(i002)
KK040
Cabinet unit
with
OP1S or
terminal strip
P366 = 2
BICO1
(i001)
KK040
BICO2
(i002)
KK040
Cabinet unit
with PMU or
terminal strip
Cabinet unit
with NAMUR
terminal strip
(SCI) 1)
P366 = 3
P366 = 4
P443
Src MainSetpoint
KK058
P554
Src ON/OFF1
B2100 1) B0022
B6100 2)
KK058
P555
Src1 OFF2
B0001
P556
Src2 OFF2
P565
P566
P567
P568
B0020 B0001
B0020
B0001
B0001
B0001
B0001
B0001 B0001
B0001
B0001
B0001
B0001
B2107
B0000
B0000 B0000
B0000
B0000
B0000
B0000
B0000
B0018 B0000
B0018
B0000
B0010
B0000
B0000
B2108 1) B0000
B6108 2)
B0000
P571
B0001
B2111 1) B0001
B6111 2)
B0001
P572
B0001
B2112 1) B0001
B6112 2)
B0001
P573
Src MOP UP
B0008
B0000 B0000
B0000
B0000
B0000
B0008
P574
B0009
B0000 B0000
B0000
B0000
B0000
B0009
P575
Src No ExtFault1
B0001
B0001 B0001
B0001
B0018
B0018
B0018
P588
B0001
B0001 B0001
B0001
B0020
B0020
B0020
P590
B0014
B0014 B0014
B0014
B0012
B0012
B0012
P651
Src DigOut1
B0107
B0107 B0107
B0107
B0000
B0000
B0000
P652
Src DigOut2
B0104
B0104 B0104
B0104
B0000
B0000
B0000
P653
Src DigOut3
B0000
B0000 B0000
B0000
B0107
B0107
B0107
K0000
K0000 K0000
K0000
K0000
K0000
K0000
K0000
K0000 K0000
K0000
K0000
K0000
K0000
K0000
K0000 K0000
K0000
K0000
K0000
K0000
B0000
B0000 B0000
B0000
B0000
B0000
B0000
B0000
B0000 B0000
B0000
B0000
B0000
B0000
B0000
B0000 B0000
B0000
B0000
B0000
B0000
B0000
B0000 B0000
B0000
B0000
B0000
B0000
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms 100 ms 100 ms
P796
Compare Value
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
2.0
2.0
P797
Compare Hyst
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
1.0
1.0
r229
r229
P405
P405
P405
P405
r229
r229
r229
r229
P049.4 OP OperDisp
Table 6-5
6-6
10.2001
Parameterizing steps
All other factory setting values are not dependent on P366 and can be
taken from the parameter list or from the block diagrams (in the
Compendium).
The factory settings for Index 1 (i001) of the respective parameter are
displayed in the parameter list.
Significance of the binectors and connectors for factory setting:
Entry
Description
B0000
Fixed binector 0
-15.4-
B0001
Fixed binector 1
-15.4-
B0005 1)
PMU ON/OFF
-50.7-
B0008
PMU MOP UP
-50.7-
B0009
-50.7-
B0010
DigIn1
-90.4-
B0012
DigIn2
-90.4-
B0014
DigIn3
-90.4-
B0016
DigIn4
-90.4-
B0018
DigIn5
-90.4-
B0020
DigIn6
-90.4-
B0022
DigIn7
-90.4-
B0100
Rdy for ON
-200.5-
B0104
Operation
-200.5-
B0107
No fault
-200.6-
B0108
No OFF2
-200.5-
B0120
CompV OK
-200.5-
B2100
-100.8-
B2115
-100.8-
B4100 1)
-Z10.7- / -Z30.4-
...
...
B4115 1)
-Z30.8-
B6100
-101.8-
B6115
-101.8-
r229
n/f(set,smooth)
...
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-7
Parameterizing steps
10.2001
Entry
Description
P405
Fixed setpoint 5
-290.3-
KK0020
Speed (smoothed)
K0022
-285.8- / -286.8-
K0024
Torque (smoothed)
-285.8-
KK0040
Current FixSetp
-290.6-
KK0058
MOP (Output)
-300.8-
Bxxxx =
Binector =
Kxxxx =
Connector =
BICO data
set
B0010
P567
B0012
B0014
P590
P590
P590
P590
P590
P567
P590
P590
P590
B0016
P580
P580
P580
P580
B0018
P567
P567
P575
P575
P575
P575
P575
P575
B0020
P555
P555
P588
P588
P588
P588
P588
P588
B0022
P554
P554
P554
P580
P554
6-8
Description
P554
Src ON/OFF1
-180-
P555
Src1 OFF2(electr)
-180-
P567
-180-
P575
Src No ExtFault1
-180-
P580
-190-
P588
-190-
P590
-190-
10.2001
6.2
Parameterizing steps
6.2.1
NOTE
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-9
Parameterizing steps
Function diagram
modules
10.2001
Function diagram modules (function diagrams) are shown after the flow
chart for parameter modules stored in the unit software. On the first few
pages are the :
setpoint and command sources (sheets s0 to s83), on the following
pages are the
analog outputs and the display parameters (sheet a0) and the
open-loop and closed-loop control types (sheets r0 to r5).
It is therefore possible to put together the function diagrams to exactly
suit the selected combination of setpoint/command source and
open/closed-loop control type. This will give you an overview of the
functionality parameterized in the units and of the necessary
assignment of the terminals.
The function parameters and visualization parameters specified in the
function diagrams are automatically adopted in the user menu
(P060 = 0) and can be visualized or changed there.
The parameter numbers of the user menu are entered in P360.
Reference is made in the function diagrams to the respective function
diagram numbers (Sheet [xxx]) of the detail diagrams (in the
Compendium).
6-10
10.2001
Parameterizing steps
P060 = 3
P071 = ?
P095 = ?
P095=2 P095=10
P095=11
P097 = ?
P100 = ?
P095=2
P097>0
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-11
Parameterizing steps
10.2001
P101 = ?
P102 = ?
P104=?
P105=?
P106=?
P107 = ?
P108 = ?
P109 = ?
SIEMENS
4
50 Hz
7.5 kW
cos 0.82
3
3 ~Mot.
IP 55
132 M/IM B3
1LA7133-4AA10
Nr.E H984 6148 01 002
EN 60034 Th.Cl. F
230 / 400V
/D
26.5 / 15.3 A
1455 / min
60 Hz
8.6 kW
cos 0.83
220-240 / 380-420 V /
26.5-27.0 / 15.3-15.6 A
SF 1.1
&(
460 V
14.7 A
1755 / min
440/480 V
15.0-15.2 A
P114 = ?
P100=1,2
6-12
WARNING!
INCORRECT SETTINGS CAN BE DANGEROUS!
For vector control only:
Process-related boundary conditions for control
0: Standard drives
(default)
1: Torsion, gear play
2: Acceleration drives
3: Load surge
4: Smooth running characteristics
5: Efficiency optimization
6: Heavy-duty starting
7: Dynamic torque response in field-weakening range
See "Drive setting" section for description
10.2001
Parameterizing steps
Thermal motor
protection desired?
no
yes
P095=2
P097>0
P382 = ?
P383 = 0
P383 = ?
P368 = ?
P368 = 0,1,2,3
4,7
P700.01 = ?
P918.01 = ?
P370 = 1
P060 = 0
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-13
Parameterizing steps
P368
setpoint source
10.2001
Faster / slower
Arrow up / down
CCW / CW
" key.
0 = PMU
1 = OP1S
7 = OP1S
7 = OP1S
0 = PMU
8 = OP1S
Setting notes
6-14
10.2001
1LA-/1LL motors
Parameterizing steps
Type
2pole
4pole
6pole
8pole
10pole
12pole
1LA5063
480
780
1LA5070
480
600
720
1LA5073
480
600
720
1LA5080
480
600
720
1LA5083
600
600
720
1LA5090
300
540
720
720
1LA5096
360
660
720
840
1LA5106
480
720
720
960
1LA5107
720
960
1LA5113
840
660
780
720
1LA5130
660
600
780
600
1LA5131
660
600
1LA5133
600
840
600
1LA5134
960
1LA5163
900
1140
1200
720
1LA5164
900
1LA5166
900
1140
1200
840
1LA5183
1500
1800
1LA5186
1800
2400
2700
1LA5206
1800
2700
1LA5207
1800
2100
2700
3000
1LA6220
2400
3300
1LA6223
2100
2400
3000
3300
1LA6253
2400
2700
3000
3600
1LA6280
2400
3000
3300
3900
1LA6283
2400
3000
3300
3900
1LA6310
2700
3300
3600
4500
1LA6313
2700
3300
3600
4500
1LA6316
2880
3480
3780
4680
1LA6317
2880
3480
3780
4680
1LA6318
3780
4680
1LA831.
2100
2400
2700
2700
3000
3000
1LA835.
2400
2700
3000
3000
3300
3300
1LA840.
2700
3000
3300
3300
3600
3600
1LA845.
3300
3300
3600
3600
4200
4200
1LL831.
1500
1500
1800
1800
2100
2100
1LL835.
1800
1800
2100
2100
2400
2400
1LL840.
2100
2100
2100
2100
2400
2400
1LL845.
2400
2100
2400
2400
2700
2700
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-15
Parameterizing steps
1LA7 motors
1PH6 motors
10.2001
Type
2pole
4pole
6pole
8pole
10pole
12pole
1LA135.
1800
2100
2400
1LA140.
2100
2400
2700
2700
1LA145.
2400
2700
3000
3000
3300
3300
1LA150.
3000
3000
3300
3300
3900
3900
1LA156.
3600
3300
3600
3600
4200
4200
1LL135.
1200
1200
1500
1LL140.
1500
1500
1800
1800
1LL145.
1800
1800
1800
1800
2100
2100
1LL150.
2100
1800
2100
2100
2400
2400
1LL156.
2400
2100
2100
2100
2400
2400
The data for 1LA5 motors are also applicable for 1LA7 motors with the
same designation.
Type
T1 in s
1500
1800
2100
2400
2400
2400
Shaft height
100
132
160
180
225
T1 in s
1500
1800
2100
2400
2400
1PL6 motors
Shaft height
180
225
T1 in s
1800
1800
Shaft height
100
132
160
T1 in s
1500
1800
2100
1PH4 motors
NOTE
6-16
10.2001
Parameterizing steps
Dependent
reference values
P350
Reference current
in A
P351
Reference voltage
in V
P352
Reference frequency
in Hz
P353
Reference speed
in rpm
P354
Reference torque
in Nm
60
P109
R W,ref =
P354 P353 2
60
Pmot,rated =
P113 2 P108
60
Automatic motor
identification
WARNING
During motor identification inverter pulses are released and the drive
rotates!
For reasons of safety, identification should first be carried out without
coupling of the load.
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-17
6-18
Sh.[50]
Lower key
OFF key
Toggle key
ON key
1
Setpoint source
PMU and MOP (P368=0)
X300
Sh. [300] :
Explanations:
PMU
Raise key
Reversing key
Note:
If P366 = 3
P590 = B0012
P651 = B0000
P652 = B0000
P653 = B0107
*)
MOP
/5
/4
B0014
P653.1 (0)
B
B0012
P652.1 (104)
B
B0010
P651.1 (107)
B
M24
P24
Lower MOP
Raise MOP
ON/OFF1
*)
*)
*)
B0009
B0008
B0005
P425
Conf.MOP
P422
MOP (min.)
MASTERDRIVES VC
8
- s0 -
M
(for T control)
N
Src.T Setp
P486.B (58) to sheet [320.1]
KK
to sheet [180]
n959.81 = 4
MOP(Outp)
r424
Src ON/OFF1
MOP (max)
P421
P574.1 (9)
P573.1 (8)
operation
no fault
P554.1 (5)
P590 (14)
B
B0104
B0107
1=operation
0=fault
/3
/2
/1
4
5
Not valid for Compact PLUS!
Sheet [300]
-X101
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
Sheet [90]
corresponds to
0-10 ... 10 V
D
AnaIn2 Smoothing
P634.2
1
2
Setpoint source
Analog input and terminal strip (P368=1)
X102/18
X102/17
Analog input 2
<3>
<2>
Analog input 1
-X101
AnaIn1 Smoothing
P634.1
Analog inputs
*)
Terminal strip
B0022
B0020
B0018
B0016
P654.1
B
B0014
AnaIn2 Offset
P631.2
*)
*)
*)
*)
Src1 OFF2
P555.1 (20)
B
Src ON/OFF1
Src3 Acknowledge
P554.1 (22)
B
P567.1 (18)
B
alarm
operation
no fault
P561.1 (16)
B
B0115
B0104
B0107
AnaIn2 Setpoint
K0013
AnaIn2 Setpoint
r637.2
(only T-control)
Src.T setpoint
P486.B (11) to sheet[320.1]
KK
AnaIn1 Setpoint
r637.1
P653.1 (115)
B
B0012
P652.1 (104)
B
B0010
P651.1 (107)
B
M24
P24
AnaIn1 Offset
P631.1
<1>
/8
/7
/6
/5
/4
1=operation
0=fault
/3
/2
/1
-20 ... 20 mA
-20 ... 20 mA
-04 ... 20 mA
-10 ... 10 V
-10 ... 10 V
closed
open
CUVC
S3
switch
4-5
5-6
Terminal X102/15
Terminal X101/9
6-19
MASTERDRIVES VC
8
- s1 -
Compact PLUS
Jumper on EBV
S3 switch
2
3
4
0
1
AnaIn Conf.
P632
to sheet [180]
n959.82 = 4
10.2001
Parameterizing steps
6-20
P408.F
Fixed setpoint8
P407.F
Fixed setpoint7
P406.F
P405.F
Fixed setpoint6
Fixed setpoint5
P404.F
Fixed setpoint4
P403.F
Fixed setpoint3
P402.F
Fixed setpoint2
Fixed setpoint1
P401.F
Sheet [290]
KK0048
KK0047
KK0046
KK0045
KK0044
KK0043
KK0042
KK0041
<1>
/8
/7
/6
/5
1=operation
/4
0=fault
/3
/2
/1
P24
B0022
B0020
B0018
B0016
P654.1
B
B0014
P653.1
B
B0012
P652.1
B
B0010
P651.1
B
M24
*)
*)
*)
*)
Src1 OFF2
FSetp FSetp
Bit 2
Bit 3
P418.B P417.B
Src ON/OFF1
Src3 Acknowledge
P555.1 (20)
B
P554.1 (22)
B
P567.1 (18)
B
Src.FSetp Bit 0
operation
no fault
P581.1 (16)
B
P580.1 (14)
B
B0104
B0107
-X101
1
2
Setpoint source
Fixed setpoints and terminal strip (P368=2)
in Hz
in %
Sheet[90]
Fixed setpoints
*)
Terminal strip
(for T control)
8
- s2 -
Src T setpoint
P486.B (40) to sh. [320.1]
KK
MASTERDRIVES VC
Act.FSetp
KK0040
Active FSetp
r420
to sheet [180]
n959.83 = 4
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
MOP MP
Sheet [300]
Sheet [90]
1
2
Setpoint source
MOP and terminal strip (P368=2)
*)
MOP and
terminal strip
-X101
<1>
/8
/7
/6
/5
/4
B0012
B0022
B0020
B0018
B0016
P654.1
B
B0014
P653.1
B
*)
*)
Src3 Acknowledge
Src1 OFF2
Src ON/OFF1
P567.1 (18)
B
P555.1 (20)
B
P554.1 (22)
B
Lower MOP
Raise MOP
P422
MOP (min.)
P425
Conf MOP
operation
no fault
P574.1 (16 )
B
P573.1 (14)
B
B0104
)
P652.1 (104) *
B
B0010
B0107
)
P651.1 (107) *
B
M24
P24
1=operation
0=fault
/3
/2
/1
MOP (outp)
KK058
MOP (outp)
r424
6-21
MASTERDRIVES VC
(for T control )
Src T Setpoint
P486.B (58) to sheet [320.1]
KK
to sheet [180]
n959.84 = 4
8
- s3 -
10.2001
Parameterizing steps
Baud rate:
9.6 kB
<1> <2>
/11 / 36
RS485N
PKW: 4
PZD: 2
PKW #
P702.1
PcD #
P708.1
ZUW1
1
2
Setpoint source
USS1 (P368=4) with Simatic
PKW
PKW
B (2112)
P572.1
B (2111)
P571.1
B (2108)
P568.1
B (2107)
P565.1
P555.1
B (2101)
MASTERDRIVES VC
External fault
Raise MOP
Negative Spd
Raise MOP
Positive Spd
B2111
B2113
PcD control
B2110
B2112
Jog Bit1
Jog Bit0
B2109
B2108
B2106
Acknowledge
No RGen Stop
Setpoint Release
B2105
B2107
Inv. Release
RGen Release
B2104
OFF3 (QStop)
B2102
8
- s4 -
to sheet [180]
control word 1
r550
Src 1 Acknow
Src OFF2
P554.1
B (2100) Src ON/OFF1
from sheett
[200]
from sheet
[350.7], [351.7]
[352.7], [400.7]
Src T setpoint
P486.B
to sheet [320.1]
K
B2103
OFF2 (electr.)
ON/OFF1
B2101
B2100
B2215
B2200
Receive setpoints
For T control:
K2002
SComWord2
r709.2
K2001
ZUW1
r552
n/f(act)
n959.85 = 4
Main setpoint
to sheet [316.1]
P443.B
K (2002)
K0032
P707.1(32)
K
SCom1Word1
r709.1
KK0148
P707.2
K
Bit14 B2114
Bit15 B2115
Bit7
Bit1
Bit0
Bit0
up to Bit15
Control word
Status word
15
PKW
PKW
Sheet [100]
Receive
Transmit
Sheet [110]
Reserve
pos./neg. speed setp
Ramp-function gen. active
Energize main cont.
Undervoltage fault
Comp. Setp reached
PZD control
Set/actual deviation
Alarm effective
Switch-on ihibit
OFF3 effective
OFF2 effective
Fault effective
Operation
Ready
Ready for ON
6-22
<1> <2>
/10 / 35
RS485P
<1>
<2>
-X101 / -X100
Baud rate
P701.1
Parameterizing steps
10.2001
CB
configuration
Sheet [120]
Receive
Transmit
Sheet [125]
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
ZUW1
1
2
Setpoint source
PROFIBUS 1st CB (P368=6)
PKW
PKW
Src OFF2
P572.1
B (3112)
P571.1
B (3111)
P568.1
B (3108)
8
- s6 -
to sheet [180]
control word 1
r550
P566.1
B (3107) Src 2 Acknow
P555.1
B (3101)
MASTERDRIVES VC
External fault
Raise MOP
Negative Spd
Raise MOP
Positive Spd
B3111
B3113
PcD control
B3110
B3112
Jog Bit1
B3109
Jog Bit0
B3108
B3106
Acknowledge
No RGen Stop
Setpoint Release
B3105
B3107
Inv. Release
RGen Release
B3104
OFF3 (QStop)
B3102
P554.1
B (3100) Src ON/OFF1
from sheett
[200]
from sheet
[350.7], [351.7]
[352.7], [400.7]
Src T setpoint
P486.B
to sheet [320.1]
K
B3103
OFF2 (electr.)
ON/OFF1
B3101
B3100
B3215
B3200
Receive setpoints
For T control:
K3002
1. CB Word2
r733.2
K3001
ZUW1
r552
n/f(act)
Main setpoint
to sheet [316.1]
P443.B
K (3002)
K0032
P734.1(32)
K
1. CB Word1
r733.1
KK0148
P734.2
K
Bit14 B3114
Bit15 B3115
Bit7
Bit1
Bit0
Bit0
up to Bit15
Control word
Status word
15
PKW
PKW
Reserve
pos./neg. speed setp
Ramp-function gen. active
Energize main cont.
Undervoltage fault
Comp. Setp reached
PZD control
Set/actual deviation
Alarm effective
Switch-on ihibit
OFF3 effective
OFF2 effective
Fault effective
Operation
Ready
Ready for ON
CB Bus Address
0 ... 200
P918.01 (3)
CB/TB TlgOFF
0 ... 6500 ms
P722.01 (10)
P722.01 =0 :
No monitoring
CB Parameter 11
0 ... 65535
P721.01 to .05
CB Parameter 10
0 ... 65535
P720.01
CB Parameter 1
0 ... 65535
P711.01
10.2001
Parameterizing steps
6-23
/11
RS485N
Baud rate:
9.6 kB
PKW:127
PcD: 2
Sheet [110]
Sheet [100]
Receive
Transmit
PcD #
P708.1
ZUW1
PKW
Jog
Reset
Control word 1
Status word 1
4
5
Not valid for Compact PLUS!
OP1S keys
1
2
3
Setpoint source
OP1S / SIMOVIS and fixed setpoints at USS1 (P368=7)
PKW
PKW
15
PKW
Reserve
pos./neg. speed setp
Ramp-function gen. active
Energize main cont.
Undervoltage fault
Comp. setpoint reached
PcD control
Set/actual deviation
Alarm effective
Switch-on inhibit
OFF3 effective
OFF2 effective
Fault effective
Operation
Ready
Ready for ON
6-24
/10
RS485P
-X101
Bit15
Bit12
Bit11
Bit8
Bit7
Bit1
PcD control
B2110
Raise MOP
External fault
8
- s7 -
to sheet [180]
control word 1
r550
P572.1
Src negative spd
B (2112)
P571.1
Src positive spd
B (2111)
P568.1
B (2108)
P565.1
B (2107) Src1 Acknow.
MASTERDRIVES VC
B2115
Lower MOP
B2113
B2114
Negative Spd
B2112
Positive Spd
Jog Bit1
B2109
B2111
Jog Bit0
B2108
Acknowledge
No RGen Stop
Setp Release
B2106
B2107
RGen Release
B2105
Inv Release
B2103
B2104
OFF2 (electr.)
OFF3 (QStop)
P554.1
B (2100) Src ON/OFF1
B2102
ON/OFF1
N
Src T setpoint
P486.B
to sh. [320.1]
K
Main setpoint
to sh. [316.1]
from sh.
[200]
from sh.
[350.7], [351.7]
[352.7], [400.5]
P443.B
K (2002)
B2101
Bit0
B2200
bis Bit15
B2215
Bit0
B2100
Receive setpoints
for T control:
K2002
SCom1Word2
r709.2
K2001
ZUW1
r552
n/f(act)
K0032
P707.1
K
SCom1Word1
r709.1
KK0148
P707.2
K
n957.88 = 4
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
If P366 = 2
P590 = B0012
P651 = B0000
P652 = B0000
P653 = B0107
P408.F
Fixed setpoint8
P407.F
Fixed setpoint7
P406.F
Fixed setpoint6
P405.F
Fixed setpoint5
P404.F
Fixed setpoint4
P403.F
Fixed setpoint3
P402.F
Fixed setpoint2
1
2
Setpoint source
OP1S and fixed setpoints (P368=7)
in Hz
See P049.4
in %
P401.F
Fixed setpoint1
Sheet [290]
Fixed
setpoints
*)
Sheet [90]
Terminal strip
KK0048
KK0047
KK0046
KK0045
KK0044
KK0043
KK0042
KK0041
/5
/4
1=operation
0=fault
/3
/2
/1
B0014
P653.1 (0)
B
B0012
P652.1 (104)
B
B0010
P651.1 (107)
B
M24
P24
(for T control)
-X101
*)
*)
*)
P590 (14)
B
B0104
B0107
6-25
(for T control)
- s71 -
Src T setpoint
P486.B (40) to sheet[320.1]
KK
MASTERDRIVES VC
Act.FSetp
KK0040
Active FSetp
r420
to sheet [180]
Operation
No fault
n959.89 = 4
10.2001
Parameterizing steps
/8
RS485N
Baud rate:
9.6 kB
PKW:127
PcD: 2
Sheet [111]
Sheet [101]
Receive
Transmit
PcD #
P708.2
ZUW1
PKW
Control word 1
Status word 1
4
5
Only applicable for Compact PLUS!
Jog
Reset
OP1S keys
1
2
3
Setpoint source
OP1S and fixed setpoints at USS2 (P368=7)
PKW
PKW
15
PKW
Reserve
pos./neg. speed setp
Ramp-function gen. active
Energize main cont.
Undervoltage fault
Comp. setpoint reached
PcD control
Set/actual deviation
Alarm effective
Switch-on inhibit
OFF3 effective
OFF2 effective
Fault effective
Operation
Ready
Ready for ON
6-26
/3
RS485P
-X103
Bit15
Bit12
Bit11
Bit8
Bit7
Bit1
PcD control
B6110
Raise MOP
External fault
- s72 -
to sheet [180]
control word 1
r550
P572.1
Src negative spd
B (6112)
P571.1
Src positive spd
B (6111)
P568.1
B (6108)
P565.1
B (6107) Src1 Acknow.
MASTERDRIVES VC
B6115
Lower MOP
B6113
B6114
Negative Spd
B6112
Positive Spd
Jog Bit1
B6109
B6111
Jog Bit0
B6108
Acknowledge
No RGen Stop
Setp Release
B6106
B6107
RGen Release
B6105
Inv Release
B6103
B6104
OFF2 (electr.)
OFF3 (QStop)
P554.1
B (6100) Src ON/OFF1
B6102
ON/OFF1
N
Src T setpoint
P486.B
to sh. [320.1]
K
Main setpoint
to sh. [316.1]
from sh.
[200]
from sh.
[350.7], [351.7]
[352.7], [400.5]
P443.B
K (6002)
B6101
Bit0
B6200
bis Bit15
B6215
Bit0
B6100
Receive setpoints
for T control:
K6002
SCom2Word2
r709.18
K6001
ZUW1
r552
n/f(act)
K0032
P708.1
K
SCom2Word1
r709.17
KK0148
P708.2
K
n957.88 = 4
Parameterizing steps
10.2001
Baud rate:
9.6 kB
PKW:127
PZD: 2
PKW #
P702.1
Sheet [110]
Sheet [100]
Receive
Transmit
PZD #
P708.1
ZUW1
PKW
PKW
Jog
Reset
Control word 1
Status word 1
4
5
Not valid for Compact PLUS!
OP1S-keys
PKW
1
2
3
Setpoint source
OP1S / SIMOVIS and MOP at USS1 (P368=8)
PKW
15
Reserve
pos./neg. speed setp
Ramp-function gen. active
Energize main cont.
Undervoltage fault
Comp. setpoint reached
PcD control
Set/actual deviation
Alarm effective
Switch-on inhibit
OFF3 effective
OFF2 effective
Fault effective
Operation
Ready
Ready for ON
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
/11
RS485N
/10
RS485P
-X101
Baudrate
P701.1
Bit15
Bit12
Bit11
Bit8
Bit7
Bit1
No RGen Stop
Setp Release
B2105
B2106
6-27
External fault
Lower MOP
Raise MOP
Negative Spd
Positive Spd
to sh. [320.1]
P574.1
B (2114)
P573.1
B (2113)
8
- s8 -
P572.1
Src negative spd
B (2112)
P565.1
B (2107) Src1 Acknow.
to sh. [180]
Control word 1
r550
P554.1
B (2100) Src ON/OFF1
MASTERDRIVES VC
B2115
B2114
B2113
B2112
B2111
Jog Bit1
PcD control
B2110
Jog Bit0
B2109
B2108
Acknowledge
RGen Release
B2104
B2107
Inv Release
B2103
OFF2 (electr.)
OFF3 (QStop)
P486.B
Src T setpoint
B2102
ON/OFF1
from sh.
[200]
from sh.
[350.7], [351.7]
[352.7], [400.5]
to sh. [316.1]
Main setpoint
P443.B
K (2002)
B2101
Bit0
B2200
bis Bit15
B2215
Bit0
B2100
Receive setpoints
for T control:
K2002
SST1Word2
r709.2
K2001
ZUW1
r552
n/f(act)
K0032
P707.1
K
SST1Word1
r709.1
KK0148
P707.2
K
n957.90 = 4
10.2001
Parameterizing steps
6-28
Sheet [300]
Sheet [90]
1
2
Setpoint source
OP1S and MOP (P368=8)
MOP MP
Terminal strip
Lower MOP
Raise MOP
/5
/4
P24
Lower MOP
Raise MOP
Negative Spd
1 Acknowledge
B0014
B2114
B2113
B2112
B2107
B2100
P422
MOP (min.)
to sheet [180]
n959.91 = 4
MASTERDRIVES VC
(for T control )
Src T Setpoint
P486.B (58) to sheet [320.1]
KK
Src1 Acknowledge
Src ON/OFF1
MOP(Outp.)
KK058
MOP(Outp.)
r424
P574.1 (9)
P573.1 (8)
P572
P565
operation
no fault
P554.1 (5)
P590 (14)
B
B0104
B0107
4
5
Not valid for Compact PLUS!
P425
Conf MOP
*)
*)
*)
MOP (max)
P421
P653.1 (0)
B
B0012
P652.1 (104)
B
B0010
P651.1 (107)
B
M24
ON/OFF 1
1=operation
0=fault
/3
/2
/1
-X101
- s81 -
Parameterizing steps
10.2001
Baud rate:
9.6 kB
PKW:127
PZD: 2
PKW #
P702.2
Sheet [111]
Sheet [101]
Receive
Transmit
PZD #
P708.2
ZUW1
1
2
Setpoint source
OP1S and MOP at USS2 (P368=8)
PKW
PKW
Control word 1
Status word 1
4
5
Only applicable for Compact PLUS!
Jog
Reset
OP1S-keys
PKW
PKW
15
Reserve
pos./neg. speed setp
Ramp-function gen. active
Energize main cont.
Undervoltage fault
Comp. setpoint reached
PcD control
Set/actual deviation
Alarm effective
Switch-on inhibit
OFF3 effective
OFF2 effective
Fault effective
Operation
Ready
Ready for ON
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
/8
RS485N
/3
RS485P
-X103
Baudrate
P701.2
Bit15
Bit12
Bit11
Bit8
Bit7
Bit1
No RGen Stop
Setp Release
B6105
B6106
6-29
External fault
Lower MOP
Raise MOP
Negative Spd
Positive Spd
to sh. [320.1]
P574.1
B (6114)
P573.1
B (6113)
- s82 -
P572.1
Src negative spd
B (6112)
P565.1
B (6107) Src1 Acknow.
to sh. [180]
Control word 1
r550
P554.1
B (6100) Src ON/OFF1
MASTERDRIVES VC
B6115
B6114
B6113
B6112
B6111
Jog Bit1
PcD control
B6110
Jog Bit0
B6109
B6108
Acknowledge
RGen Release
B6104
B6107
Inv Release
B6103
OFF2 (electr.)
OFF3 (QStop)
P486.B
Src T setpoint
B6102
ON/OFF1
from sh.
[200]
from sh.
[350.7], [351.7]
[352.7], [400.5]
to sh. [316.1]
Main setpoint
P443.B
K (6002)
B6101
Bit0
B6200
bis Bit15
B6215
Bit0
B6100
Receive setpoints
for T control:
K6002
SST2Word2
r709.18
K6001
ZUW1
r552
n/f(act)
K0032
P708.1
K
SST2Word1
r709.17
KK0148
P708.2
K
n957.90 = 4
10.2001
Parameterizing steps
6-30
Sheet [300]
Sheet [90]
1
2
Setpoint source
OP1S and MOP (P368=8)
MOP MP
Terminal strip
Lower MOP
Raise MOP
/5
/4
P24
Lower MOP
Raise MOP
Negative Spd
1 Acknowledge
B0014
B6114
B6113
B6112
B6107
B6100
P422
MOP (min.)
to sheet [180]
n959.91 = 4
MASTERDRIVES VC
(for T control )
Src T Setpoint
P486.B (58) to sheet [320.1]
KK
Src1 Acknowledge
Src ON/OFF1
MOP(Outp.)
KK058
MOP(Outp.)
r424
P574.1 (9)
P573.1 (8)
P572
P565
operation
no fault
P554.1 (22)
P590 (14)
B
B0104
B0107
4
5
Only applicable for Compact PLUS!
P425
Conf MOP
*)
*)
*)
MOP (max)
P421
P653.1 (0)
B
B0012
P652.1 (104)
B
B0010
P651.1 (107)
B
M24
ON/OFF 1
1=operation
0=fault
/3
/2
/1
-X101
- s83 -
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
1
2
Analog outputs and display variables
from sheet
[285.3]
[286.3]
*)
DC Link Volts
r006
Torque
r007
Output power
Output voltage
Output Amps
r004
n/f (act)
r218
n/f(act)
KK148
Actual speed
KK020
*
Torque
K0024
T(act) *
K0241
UZk(ist)
K0240
DC Link Volts
K0025
Output power
K0023
U(set,v/f)
K0204
Output voltage
K0021
I(Output Amps)
K0242
Output Amps
K0022
Actual Speed
r015
P038.x
K
K
P040.x
K
K
K
P042.x
K
K
K
.01
.02
.01
.02
.03
.01
.02
.03
AA2 Offset
P644.2
AA1 Offset
P644.1
Reference torque *)
P354
rpm
Reference speed
P353
Hz
Reference frequency
P352
Display torque
r039.1 to .2
Display speed
r041.1 to .3
Display frequency
r043.1 to .3
*)
Sheet [30]
Switch S4
0 ... 20 mA
A 5
4 +/- 10 V
6
Switch S4
0 ... 20 mA
A 2
1 +/- 10 V
3
-X102/22
-X102/21
-X102/20
-X102/19
AA2
AA1
0 mA ... 20 mA
-10 V ... 10 V
Smin
Smax
xB
Smax
Smin
Amin
Amax
6-31
AA2
5-6
4-6
- a0-
MASTERDRIVES VC
Explanations:
P644 =
P643 =
2-3
1-3
AA1
n959.80 = 3
AA2 Scaling
P643.2
Display parameters
AA1 Scaling
P643.1
<1>
Sheet [81]
- -
2s
30 ms
2s
2s
Rot Freq
r002
Analog outputs
- -
from sheet
[285.7]
from sheet
[285.7]
[286.7]
from sheet
[285.3]
[286.3]
from sheet
[285.3]
[286.3]
from sheet
[350.7]
[351.7]
[352.7]
[400.5]
2s
Display variables
10.2001
Parameterizing steps
6-32
Normalization
Tacho M
Track A
Track B
Zero track
Control tr.
Tacho P15V
n/f(act,encoder)
KK091
Ana.tach.
Imp.tach.
Motor encoder
P130.M (11) *)
Sheet 250
P453.F (-110.0%) *)
n/f(max,neg.Spd)
1
2
3
V/f characteristic with speed controller (P100=0)
n/f(act)
KK148
n/f(act)
r218
Sheet 352
KK075
Smooth. n/f(act)
P223.M
r014
Setpoint speed
n/f(set,smooth)
r229
P240.M
n/f-Reg.Tn
P235.M
n/f-Reg.Gain1
Sheet 364
Speed controller
n/f(set)
r482
Sheet 318
n/f(max,pos.spd)
P452.F (110.0%) *)
P138.M (3000)
Ana.TachScale
23
24
25
26
27
28
<1>
X103
Sheet 317
Setpoint channel
Pulse #
P151.M (1024) *)
Srce AddSetp1
P433.B (0)
KK
Ref.
Frequency: P352 *)
Speed:
P353 *)
Sheet 316
r129
Imax-Ctrl Gain
P331.M
Output
current
Current
Lim.
Maximum
current
P128.M
f(Slip)
KK0188
Imax-Ctrll.Tn
P332.M
Sheet 401
Sh. [300] :
3
Motor
encoder
Smooth. vd(act)
P287.M
Sheet 286
MASTERDRIVES VC
8
- r0 -
Asyc.
Mot. 3~
Gating unit
f(set,stator)
KK199
Explanations:
P330.M
Src SelCurve *)
Volts
mod
depth
FSetp Boost
P325.M
Mot.voltage
P101.M *)
max.Outp Volts
r346
Boost End
Field Weak
Freq
Mot.Freq.(n)
Freq
P326.M P107.M (50) *) P293.M
Sheet 405
v/f characteristic
n957.85 = 0
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
Sheet 317
P453.F (-110.0%) * )
n/f(max,neg.spd)
1
2
V/f characteristic (P100=1)
KK075
n/f(set)
r482
Sheet 318
n/f(max,pos.spd)
P452.F (110,0%) * )
Setpoint channel
Ref,
frequency: P352 *)
speed:
P353 *)
Sheet 316
r129
f(Slip)
KK188
Imax controller Tn
P332.M
Imax controller Kp
P331.M
Output Amps
Current
lim.
Maximum
current
P128.M
r014
Setpoint speed
n/f(set,smooth)
r229
Slip comp Kp
P336.M (0)
n/f(ist)
r218
Sheet 400
KK148
6-33
Asyc.
Mot. 3~
- r1 -
Smooth vd(act)
P287.M
Sheet 286
Gating unit
f(set,Stator)
KK199
MASTERDRIVES VC
P330.M
Src Select Char.
Volt.
Mod.
Depth
FSetp Boost
P325.M
Mot. Volts
P101.M * )
max.Outp Volts.
r346
Boost end
Field weak.
frequency Mot.Freq.(n) frequency
P326.M P107.M (50) * ) P293.M
Sheet 405
V/f characteristic
n957.86 = 0
10.2001
Parameterizing steps
6-34
Sheet 317
Setpoint channel
P453.F (-110,0%) * )
n/f(max,neg.spd)
n/f(max,pos.spd)
P452.F (110,0%) * )
KK075
n/f(set)
r482
Sheet 318
1
2
V/f characteristic (P100=2)
Textile
Src AddSetp.1
P433.B (0)
KK
Ref.
frequency: P352 *)
speed:
P353 *)
Sheet 316
r129
Imax controller Tn
P332.M
Imax controller Kp
P331.M
Output Amps
Current
lim.
Maximum
currents
P128.M
r014
Setpoint speed
n/f(set,smooth)
r229
n/f(act)
r218
Sheet 402
KK148
Asyc.
Mot. 3~
- r2 -
Smooth Vd(act)
P287.M
Sheet 286
Gating unit
f(set,stator)
KK199
MASTERDRIVES VC
P330.M
Src Select Char.
Volt.
Mod.
Depth
FSetp boost
P325.M *)
Mot.voltage
P101.M *)
max.outp. volts
r346
Boost end
Field weakening
frequency Mot.Freq.(n) frequency
P326.M P107.M (50) * ) P293.M
Sheet 405
V/f characteristic
n957.87 = 0
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
Scal.T(pre)
P471.M (0)
P493.B (170)
Src TorqLimit1
Sheet 319
KK075
Smooth.n/f(act)
P223.M
r014
Setpoint speed
n/f(set,smooth)
r229
P235.M
n/f-Reg.Kp1
Torque/current limit
P127.M (80%)
R(rotor)Ktmp
Current
model
Sheet 396
Slip frequency
KK188
T(droop) P278.M
T(dynam.) P279.M
Sheet 382
x
y
ModDepth Headrm
P344.M
Sheet 381
Msoll,reg
K0153
K0165
T(set,limitr)
r269
TorqLImit2,act
K0173
TorqLimit1,act
K0172
Torque limitation
r129
Sheet 367
Sheet 372
Maximum current Pw,max(gen)
P128.M
P259.M
i-Anteil
K0155
P240.M
n/f-Reg.Tn
Sheet 362
Speed controller
1
2
3
4
Closed-loop speed control without encoder (frequency control) P100=3
Master drive (P587 = 0)
n/f(ist)
r218
P453.F (-110,0%) * )
n/f(max,neg.spd)
n/f(ist)
KK148
Sheet 351
Sheet 318
P499.B (171)
n/f(max,pos.spd)
P452.F (110,0%) * ) n/f(set)
r482
K171
K170
K
Src TorqLimit2 FSetp
Src
TorqLimit2
P498.F (-100%)
Start-up time
P116.M
Sheet 317
Setpoint channel
Note:
P354 is referred to
P113 *)
Ref.
frequency: P352 *)
speed:
P353 *)
torque: P354 *)
Sheet 316
Tn
P284.M
EMF
model
Isd (act)
6-35
Asyc.
Mot. 3~
- r3 -
Smooth Vd(act)
P287.M
Sheet 285
Gating unit
f(set,stator)
KK199
MASTERDRIVES VC
i-comp.
P339.M *)
ModSystem
Release
Volt.
Mod.
Depth
P315.M P316.M
EMF Reg.Kp EMF-Reg.Tn
Kp
Tn
Isq(act) P283.M P284.M
K0184
Kp
P283.M
Isq(set)
K0168
Sheet 390
Current controller
n957.88 = 0
10.2001
Parameterizing steps
6-36
T-add. FSetp
P505.F (0.0)
Start-up time
P116.M (~)
P453.F (-110,0%) * )
n/f(max,neg.spd)
n/f(max,pos spd)
P452.F (110 %) * )
-1
n/f(soll)
r482
r502
Mgrenz2
n/f(act)
KK148
n/f(act)
r218
Sheet 351
KK075
Mgrenz2 FSW
P498.F (-100%)
TorqLimit1 FSetp
P492.F (100%) TorqLimit1
r496
Sheet 320
Smooth.n/f(act)
P223.M
r014
setpoint speed
n/f(setl,smooth)
r229
P235.M
n/f-Reg.Kp1
P127.M (80%)
R(rotor)Ktmp
Current
model
Sheet 396
Slip frequency
KK188
T(droop) P278.M
T(dynam.) P279.M
Sheet 382
ModDepth Headrm
P344.M
max.Ausg.spg. r346
K0165
M(set,limitr)
r269
x
y
TorqLimit2, act
K0173
TorqLimit1,act
K0172
Torque limitation
Sheet 372
Maximum
current Pw,max(gen)
P128.M
P259.M
Torque/current limit
Sheet 381
Tset,reg
K0153
i-comp.
K0155
P240.M
n/f-Reg.Tn
Sheet 363
Speed controller
1
2
3
4
Closed-loop speed control without encoder (frequency control) P100=3
Slave drive (P587 = 1)
P354 is referred to
P113 *)
Ref.
frequency: P352 *)
speed: P353 *)
torque: P354 *)
Setpoint channel
Kp
P283.M
Tn
P284.M
P339.M *)
ModSystem
Release
Volt.
Mod.
Depth
Sheet 285
- r31 -
f(set,Stator)
KK199
Asyc.
Mot. 3~
Gating unit
Smooht. Vd(act)
P287.M
MASTERDRIVES VC
P315.M P316.M
EMF Reg Gain EMF Reg.Tn
EMF
Model
Isd (act)
Kp
Tn
Isq(act) P283.M P284.M
K0184
Isq(set)
K0168
Sheet 390
Current controller
n957.89 = 0
Parameterizing steps
10.2001
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
Normalization
Tacho M
Track A
Track B
Zero track
Control track
Tacho P15V
n/f(act,encoder)
KK091
Ana.tach.
Imp.tach.
Motor encoder
P130.M (11) *)
P493.B (170)
Src TorqLimit1
Sheet 318
P499.B (171)
Smooth.n/f(pre)
P216.M
KK075
n/f(ist)
KK148
n/f(act)
r218
Sheet 350
P453.F (-110,0%)
n/f(max,neg.spd)
*)
n/f(max,pos.spd)
P452.F (110,0%) *) n/f(set)
r482
K171
K170
K
TorqLimit2 FSetp
P498.F (-100%) Src TorqLimit2
TorqLimit1 FSetp
P492.F (100%)
Sheet 319
1
2
Closed-loop speed control (P100=4)
Master drive (P587 = 0)
P138.M (3000)
Ana.TachoComp
23
24
25
26
27
28
<1>
X103
Sheet250
Scal.Torq(pre.)
P471.M
Sheet 317
Setpoint channel
Start-up time
P116.M
Pulse #
P151.M (1024) *)
P354 is referred to
P113 *)
Ref.
frequency: P352 *)
speed: P353 *)
torque: P354 *)
Sheet 316
Smooth n/f(act)
P223.M
r014
Setpoint speed
n/f(set,smooth)
r229
P127.M (80%)
R(rotor)Ktmp
Current
model
Blatt 395
ModDepth Headrm
P344.M
Sheet 380
Msoll,reg
K0153
Slip frequency
KK188
Field weakening
characteristic
max.outp.volt.
r346
x
y
K0165
T(set,limitr)
r269
TorqLimit2,act
K0173
TorqLimit1,act
K0172
Torque limitation
r129
Sheet 370
Torque/current limit
Sheet 365
i-Anteil
K0155
P235.M
P240.M
n/f-Reg.Kp1 n/f-Reg.Tn
Sheet 360
Speed controller
Tn
P284.M
6-37
P316.M
EMF Reg.Tn
P339.M *)
ModSystem
Release
Volt.
Mod.
Depth
Asyc.
Mot. 3~
- r4 -
Motor
encoder
Smooth Vd(act)
P287.M
Sheet 285
Gating unit
f(set,Stator)
KK199
MASTERDRIVES VC
P315.M
EMF Reg Gain
EMF
Model
Isd (act)
Kp
Tn
Isq(act) P283.M P284.M
K0184
Kp
P283.M
Isq(set)
K0168
Sheet 390
Current controller
n957.90 = 0
10.2001
Parameterizing steps
6-38
Normalization
Tacho M
Track A
Track B
Zero track
Control track
Tacho P15V
n/f(act,encoder)
KK091
Ana.tach.
IPulse tach.
Motor encoder
P130.M (11) *)
Sheet 250
n/f(act)
KK148
n/f(act)
r218
Sheet 350
KK075
n/f(set)
r482
r502
P498.F (-100%) TorqLimit2
TorqLimit2 FSetp
Smooth.n/f(FWD)
P216.M
P453.F (-110,0%)
n/f(max,neg.spd) *)
n/f(max,pos spd)
P452.F (110 %) *)
-1
TorqLimit1 FSetp
P492.F (100%) TorqLimit1
r496
Sheet 320
Sheet 361
Smooth n/f(act)
P223.M
r014
Setpoint speed
P127.M (80%)
R(rotor)Ktmp
Current
model
Sheet 395
ModDepth Headrm
P344.M
Sheet 380
Tset,reg
K0153
Slip frequency
KK188
Field weakening
characteristic
max.outp. volts
r346
K0165
M(set,limitr)
r269
TorqLimit2,act
K0173
TorqLimit1,act
K0172
Torque limitation
x
y
Sheet 371
Torque/current limit
Maximum current Pw,max(gen)
P128.M
P259.M
i-comp.
K0155
P235.M
P240.M
n/f-Reg.Kp1 n/f-Reg.Tn
n/f(set, smooth)
r229
1
2
3
Closed-loop speed control / torque control (P100=4/5)
Slave drive (P587 = 1)
P138.M (3000)
Ana.TachoComp
23
24
25
26
27
28
<1>
X103
Pulse
P151.M (1024) *)
Ref.
frequency: P352 *)
speed:
P353 *)
torque:
P354 *)
Setpoint channel
Speed limitation
controller
Tn
P284.M
P316.M
EMF-Reg Tn
P339.M *)
Pulse system
release
Volt.
Mod.
Depth
Sheet285
f(set, stator)
KK199
- r5 -
Motor
encoder
Asyc.
Mot. 3~
Gating unit
Smooth. Vd(act)
P287.M
MASTERDRIVES VC
P315.M
EMF Reg Gain
EMF
model
Isd (act)
Kp
Tn
Isq(act) P283.M P284.M
K0184
Kp
P283.M
Isq(set)
K0168
Sheet 390
Current controller
n957.91 = 0
Parameterizing steps
10.2001
10.2001
Parameterizing steps
Parameter assignments depending on setpoint source (P368) and control type (P100):
P368 = Setpoint source
P368 = 0 P368 = 1 P368 = 2 P368 = 3 P368 = 4 P368 = 6 P368 = 7 P368 = 8
PROFIPMU + Analog FSetp + MOP +
USS
OP1S + OP1S +
BUS
MOP 1)
inp. + terminals terminals
FSetp
MOP
Parameter description
terminals
B0005
B0022
B0022
B0022
B2100
B3100
B2100 1)
B6100 2)
B2100 1)
B6100 2)
B0020
B0020
B0020
B2101
B3101
B0016
1
B2107 1)
B6107 2)
B2107
B2107
B2107
B2107
B2107
B2107
B2107 1)
B6107 2)
B0018
B0018
B0018
0
0
B2108
B3108
B2108 1)
B6108 2)
B2111
B3111
B2111 1)
B6111 2)
B2112
B3112
B2112 1)
B6112 2)
B2112 1)
B6112 2)
B0008
B0014
B2113 1)
B6113 2)
B0009
B0016
B2114 1)
B6114 2)
B0014
B0016
B0014 *
B0014
B0014 *
B0014 **
B0107 *
B0107
B0107
B0107
B0107
B0107
B0107 *
B0107 *
B0104 *
B0104
B0104
B0104
B0104
B0104
B0104 *
B0104 *
0*
B0115
0*
0*
KK0040
KK0058
P590
KK0058
K0011
KK0040
KK0058
K2002
K3002
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-39
Parameterizing steps
10.2001
P100 = 0
V/f + n
P100 = 1
V/f
P100 = 2
Textile
f-Reg.
n-Reg.
(P587 = 0) (P587 = 0)
P100 = 5
T-Reg.
P038.1
DispTorqConn.r39.1
Sw-KP
P038.1
DispTorqConn.r39.2
K0165
P040.1
DispSpdConn.r41.1
Setp CP
Setp CP
Setp CP
Setp CP
Setp CP
KK0150
P040.2
DispSpdConn.r41.2
KK0148
KK0148
KK0148
KK0148
KK0148
KK0148
P040.3
KK0091
KK0091
KK0091
P042.1
Setp CP
Setp CP
Setp CP
Setp CP
Setp CP
KK0150
P042.2
KK0148
KK0148
KK0148
KK0148
KK0148
KK0148
P042.3
KK0199
KK0199
KK0199
KK0091
KK0091
KK0091
6.2.2
NOTE
P060 = 2
P366 = ?
P970 = 0
Unit carries out parameter
reset and then leaves the
"Fixed settings" menu
Fig. 6-3
6-40
10.2001
Parameterizing steps
6.2.3
Download
100.0A 380.0V zz
*-300.000Hz
#-300.000Hz
Run
Operating mode
Type of construction
I
O
USS-Bus
Jog
+/-
Reset
X103
X300
(SCom1)
Bus operation
Compact PLUS
Compact, chassis
X100
X101
Operating mode
OP1S
SIEMENS
Terminal
Fault
Run
US
S
via
RS
48
5
X300
X103
X300
(SCom1)
Laptop
Operating mode
Type of construction
Bus operation
Terminal
ific
ec
-sp
s
bu
Automation unit
(e. g. SIMATIC S7)
Fig. 6-4
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-41
Parameterizing steps
Downloading with
the OP1S
10.2001
Table 6-6
Parameter name
P060
Menu selection
P070
P072
P073
The OP1S operator control panel also stores and transfers parameters
for configuring the USS interface (P700 to P704). Depending on the
parameterization of the unit from which the parameter set was originally
upread, communication between the OP1S and the unit can be
interrupted on account of changed interface parameters after
downloading has been completed. To enable communication to recommence, briefly interrupt the connection between the OP1S and the
unit (disconnect OP1S or the cable). The OP1S is then newly initialized
and adjusts itself after a short time to the changed parameterization via
the stored search algorithm.
Download with
SIMOVIS /
DriveMonitor
6-42
10.2001
NOTICE
Parameterizing steps
Parameter name
P109
P352
P353
Table 6-7
6.2.4
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-43
Parameterizing steps
6.3
10.2001
Detailed parameterization
Detailed parameterization should always be used in cases where the
application conditions of the units are not exactly known beforehand
and detailed parameter adjustments need to be carried out locally. An
example of a typical application is initial start-up.
6.3.1
WARNING
If CUVC boards are changed over between different units without the
power section being re-defined, the unit can be destroyed when it is
connected up to the voltage supply and energized.
The unit has to be switched to the "Power section definition" state for
carrying out the power section definition. This is done by selecting the
"Power section definition" menu. The power section is then defined in
this menu by inputting a code number.
P060 = 8
P070 = ?
P060 = 1
NOTICE
6-44
To check the input data, the values for the converter supply voltage in
P071 and the converter current in P072 should be checked after
returning to the parameter menu. They must tally with the data given on
the unit rating plate.
10.2001
Parameterizing steps
6.3.1.1
6.3.1.2
In [A]
PWE
6SE7011-5EP60
1.5
6SE7013-0EP60
3.0
6SE7015-0EP60
5.0
6SE7018-0EP60
8.0
6SE7021-0EP60
10.0
6SE7021-4EP60
14.0
13
6SE7022-1EP60
20.5
15
6SE7022-7EP60
27.0
17
6SE7023-4EP60
34.0
19
In [A]
PWE
6SE7012-0TP60
2.0
6SE7014-0TP60
4.0
6SE7016-0TP60
6.1
6SE7021-0TP60
10.2
6SE7021-3TP60
13.2
12
6SE7021-8TP60
17.5
14
6SE7022-6TP60
25.5
16
6SE7023-4TP60
34.0
18
6SE7023-8TP60
37.5
20
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-45
Parameterizing steps
6.3.1.3
3 AC 200 V to 230 V
6-46
10.2001
Order number
In [A]
PWE
6SE7021-1CA60
10.6
14
6SE7021-3CA60
13.3
21
6SE7021-8CB60
17.7
27
6SE7022-3CB60
22.9
32
6SE7023-2CB60
32.2
39
6SE7024-4CC60
44.2
48
6SE7025-4CD60
54.0
54
6SE7027-0CD60
69.0
64
6SE7028-1CD60
81.0
70
Order number
In [A]
PWE
6SE7016-1EA61
6.1
6SE7018-0EA61
8.0
6SE7021-0EA61
10.2
11
6SE7021-3EB61
13.2
18
6SE7021-8EB61
17.5
25
6SE7022-6EC61
25.5
35
6SE7023-4EC61
34.0
42
6SE7023-8ED61
37.5
46
6SE7024-7ED61
47.0
52
6SE7026-0ED61
59.0
56
6SE7027-2ED61
72.0
66
Order number
In [A]
PWE
6SE7014-5FB61
4.5
6SE7016-2FB61
6.2
6SE7017-8FB61
7.8
6SE7021-1FB61
11.0
16
6SE7021-5FB61
15.1
23
6SE7022-2FC61
22.0
30
6SE7023-0FD61
29.0
37
6SE7023-4FD61
34.0
44
6SE7024-7FD61
46.5
50
10.2001
6.3.1.4
Parameterizing steps
DC 270 V to 310 V
DC 510 V to 650 V
DC 675 V to 810 V
Order number
In [A]
PWE
6SE7021-1RA60
10.6
15
6SE7021-3RA60
13.3
22
6SE7021-8RB60
17.7
28
6SE7022-3RB60
22.9
33
6SE7023-2RB60
32.2
40
6SE7024-4RC60
44.2
49
6SE7025-4RD60
54.0
55
6SE7027-0RD60
69.0
65
6SE7028-1RD60
81.0
71
Order number
In [A]
PWE
6SE7016-1TA61
6.1
6SE7018-0TA61
8.0
10
6SE7021-0TA61
10.2
12
6SE7021-3TB61
13.2
19
6SE7021-8TB61
17.5
26
6SE7022-6TC61
25.5
36
6SE7023-4TC61
34.0
43
6SE7023-8TD61
37.5
47
6SE7024-7TD61
47.0
53
6SE7026-0TD61
59.0
57
6SE7027-2TD61
72.0
67
Order number
In [A]
PWE
6SE7014-5UB61
4.5
6SE7016-2UB61
6.2
6SE7017-8UB61
7.8
6SE7021-1UB61
11.0
17
6SE7021-5UB61
15.1
24
6SE7022-2UC61
22.0
31
6SE7023-0UD61
29.0
38
6SE7023-4UD61
34.0
45
6SE7024-7UD61
46.5
51
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-47
Parameterizing steps
6.3.1.5
6-48
10.2001
Order number
In [A]
PWE
6SE7031-0CE60
100.0
13
6SE7031-3CE60
131.0
29
6SE7031-6CE60
162.0
41
6SE7032-0CE60
202.0
87
Order number
In [A]
PWE
Air-cooled
PWE
Water-cooled
6SE7031-0EE60
92.0
74
6SE7031-2EF60
124.0
82
6SE7031-5EF60
146.0
90
6SE7031-8EF60
186.0
98
6SE7032-1EG60
210.0
102
6SE7032-6EG60
260.0
108
6SE7033-2EG60
315.0
112
6SE7033-7EG60
370.0
116
6SE7035-1EK60
510.0
147
233
6SE7036-0EK60
590.0
151
237
6SE7037-0EK60
690.0
164
168
Order number
In [A]
PWE
Air-cooled
PWE
Water-cooled
6SE7026-1FE60
61.0
60
6SE7026-6FE60
66.0
62
6SE7028-0FF60
79.0
68
6SE7031-1FF60
108.0
78
6SE7031-3FG60
128.0
84
6SE7031-6FG60
156.0
94
6SE7032-0FG60
192.0
100
6SE7032-3FG60
225.0
104
6SE7033-0FK60
297.0
136
222
6SE7033-5FK60
354.0
141
227
6SE7034-5FK60
452.0
143
229
10.2001
Parameterizing steps
Order number
In [A]
PWE
Air-cooled
PWE
Water-cooled
6SE7026-0HF60
55.0
58
6SE7028-2HF60
82.0
72
6SE7031-0HG60
97.0
76
6SE7031-2HF60
118.0
80
6SE7031-5HG60
145.0
88
6SE7031-7HG60
171.0
96
6SE7032-1HG60
208.0
106
6SE7033-0HK60
297.0
137
223
6SE7033-5HK60
354.0
142
228
6SE7034-5HK60
452.0
146
232
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-49
Parameterizing steps
6.3.1.6
DC 270 V to 310 V
DC 510 V to 650 V
6-50
10.2001
Order number
In [A]
PWE
6SE7031-0RE60
100.0
20
6SE7031-3RE60
131.0
34
6SE7031-6RE60
162.0
86
6SE7032-0RE60
202.0
92
Order number
In [A]
PWE
Air-cooled
PWE
Water-cooled
6SE7031-0TE60
92.0
75
6SE7031-2TF60
124.0
83
6SE7031-5TF60
146.0
91
6SE7031-8TF60
186.0
99
6SE7032-1TG60
210.0
103
6SE7032-6TG60
260.0
109
6SE7033-2TG60
315.0
113
6SE7033-7TG60
370.0
117
6SE7035-1TJ60
510.0
120
206
6SE7036-0TJ60
590.0
123
209
6SE7037-0TK60
690.0
126
212
6SE7038-6TK60
860.0
127
213
6SE7041-1TM60
1100.0
134
6SE7041-1TK60
1100.0
135
221
6SE7041-3TM60
1300.0
140
226
6SE7041-6TM60
1630.0
150
236
6SE7042-1TQ60
2090.0
153
239
6SE7041-3TL60
1300.0
154
199
6SE7037-0TJ60
690.0
163
167
6SE7038-6TS60
6450.0
181
247
6SE7041-1TS60
6270.0
185
250
6SE7042-5TN60
2470.0
194
244
10.2001
DC 675 V to 810 V
Parameterizing steps
Order number
In [A]
PWE
Air-cooled
PWE
Water-cooled
6SE7026-1UE60
61.0
61
6SE7026-6UE60
66.0
63
6SE7028-0UF60
79.0
69
6SE7031-1UF60
108.0
79
6SE7031-3UG60
128.0
85
6SE7031-6UG60
156.0
95
6SE7032-0UG60
192.0
101
6SE7032-3UG60
225.0
105
6SE7033-0UJ60
297.0
110
200
6SE7033-5UJ60
354.0
114
202
6SE7034-5UJ60
452.0
118
204
6SE7035-7UK60
570.0
121
207
6SE7036-5UK60
650.0
124
210
6SE7038-6UK60
860.0
128
214
6SE7041-0UM60
990.0
130
216
6SE7041-1UM60
1080.0
132
218
6SE7041-2UM60
1230.0
138
224
6SE7041-4UM60
6SE7041-4UQ60
1400.0
144
230
6SE7041-6UM60
6SE7041-6UQ60
1580.0
148
234
6SE7041-1UL60
1080.0
155
195
6SE7042-4UR60
2450.0
157
6SE7041-2UL60
1230.0
159
197
6SE7043-3UR60
3270.0
161
6SE7044-1UR60
4090.0
165
6SE7044-8UR60
4900.0
169
6SE7045-7UR60
5720.0
173
6SE7046-5UR60
6540.0
177
6SE7036-5US60
4940.0
179
245
6SE7038-6US60
6540.0
182
248
6SE7041-1US60
6160.0
186
251
6SE7041-2US60
5840.0
188
253
6SE7042-1UN60
2050.0
190
240
6SE7042-3UN60
2340.0
192
242
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-51
Parameterizing steps
DC 890 V to 930 V
6-52
10.2001
Order number
In [A]
PWE
Air-cooled
PWE
Water-cooled
6SE7026-0WF60
60.0
59
6SE7028-2WF60
82.0
73
6SE7031-0WG60
97.0
77
6SE7031-2WG60
118.0
81
6SE7031-5WG60
145.0
89
6SE7031-7WG60
171.0
97
6SE7032-1WG60
208.0
107
6SE7033-0WJ60
297.0
111
201
6SE7033-5WJ60
354.0
115
203
6SE7034-5WJ60
452.0
119
205
6SE7035-7WK60
570.0
122
208
6SE7036-5WK60
650.0
125
211
6SE7038-6WK60
860.0
129
215
6SE7041-0WM60
990.0
131
217
6SE7041-1WM60
1080.0
133
219
6SE7041-2WM60
1230.0
139
225
6SE7041-4WM60
6SE7041-4WQ60
1400.0
145
231
6SE7041-6WM60
6SE7041-6WQ60
1580.0
149
235
6SE7034-5WK60
452.0
152
238
6SE7041-1WL60
1080.0
156
196
6SE7042-4WR60
2450.0
158
6SE7041-2WL60
1230.0
160
198
6SE7043-3WR60
3270.0
162
6SE7044-1WR60
4090.0
166
6SE7044-8WR60
4900.0
170
6SE7045-7WR60
5720.0
174
6SE7046-5WR60
6540.0
178
6SE7036-5WS60
4940.0
180
246
6SE7038-6WS60
6540.0
183
249
6SE7041-1WS60
6160.0
187
252
6SE7041-2WS60
5840.0
189
254
6SE7042-1WN60
2050.0
191
241
6SE7042-3WN60
2340.0
193
243
10.2001
6.3.2
Parameterizing steps
Board configuration
During board configuration, the control electronics is informed in what
way the installed optional boards have to be configured. This step is
always necessary when CBx or SLB optional boards are used.
The unit must be switched to the "Board configuration" status for this
purpose. This is done by selecting the "Board configuration" menu. In
this menu, parameters are set which are required for adapting the
optional boards to the specific application (e.g. bus addresses, baud
rates, etc.). After leaving the menu, the set parameters are transferred
and the optional boards are initialized.
P060 = 4
SCB inserted ?
yes
no
P696 = ?
CBx inserted ?
no
yes
P711.1...2 = ?
to
P721.1...10 = ?
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-53
Parameterizing steps
10.2001
SLB inserted ?
no
P740 = ?
P741 = ?
P745 = ?
P746 = ?
P749.1...8 = ?
CBx inserted ?
yes
no
P918.1...2 = ?
P060 = 1
6-54
10.2001
Board codes
Parameterizing steps
Index
Position
r826
Basic board
r826
Slot A
r826
Slot B
r826
r826
r826
r826
r826
General board
codes
Parameter
Index
Position
r826
Mounting position 2
r826
Mounting position 3
Parameter value
90 to 109
Meaning
Mainboards or Control Unit
110 to 119
120 to 129
130 to 139
Technology Board
140 to 149
150 to 169
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-55
Parameterizing steps
10.2001
Board
Parameter
value
CUVC
92
CUMC
93
CUMC+
94
CUVC+
95
CUA
106
108
TSY
110
SBP
111
SCB1
121
SCB2
122
T100
Technology board
131
T300
Technology board
131
T400
Technology board
134
CBX
Communication Board
14x
CUSA
CBP
143
CBD
145
CBC
146
CBL
147
148
EB1
Expansion Board 1
151
EB2
Expansion Board 2
152
SLB
161
CBP2
6-56
Meaning
10.2001
6.3.3
Parameterizing steps
Drive setting
The drive setting function extends the start-up facilities of quick
parameterization.
During the drive setting, the control electronics is informed about the
incoming voltage supply with which the drive converter is operating,
about the connected motor and about the motor encoder. In addition,
the motor control (V/f open-loop control or vector control) and the pulse
frequency are selected. If required, the parameters necessary for the
motor model can be calculated automatically. Furthermore, the
normalization values for current, voltage, frequency, speed and torque
signals are determined during the drive setting.
For start-up of the induction motor, first enter the manufacturers
parameters completely (see below):
In doing so, you must observe whether the induction motor has a
star or a delta connection.
You must always use the S1 data from the rating plate.
You must enter the r.m.s. base frequency of the rated voltage and
not the total r.m.s. value (including harmonic content) for converter
operation.
You must always enter the correct rated motor current P102 (rating
plate). If there are two different rated currents on the rating plate for
special fan motors, you must use the value for M ~ n for constant
torque (not M ~ n2). A higher torque can be set with the torque and
active-current limits.
The accuracy of the rated motor current has a direct effect on the
torque accuracy, as the rated torque is normalized to the rated
current. If a rated current is increased by 4 %, this will also
approximately result in a 4 % increase in the torque (referred to the
rated motor torque).
For group drives, you have to enter the total rated current
P102 = x*Imot,rated
If the rated magnetizing current is known, you should enter it during
the drive setting in P103 (in % Imot,rated). If this is done, the results
of the "Automatic parameterization" (P115 = 1) will be more precise.
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-57
Parameterizing steps
10.2001
6-58
10.2001
Parameterizing steps
P060 = 5
Output filter
P068 = ?
P071 = ?
P095 = ?
P095=2 P095 =
10,12,13
P095=11
P097 = ?
P100 = ?
P095=2
P097>0
P101 = ?
P102 = ?
P103 = ?
IEC
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-59
Parameterizing steps
P104=?
10.2001
P105=?
P106=?
P107 = ?
P108 = ?
P109 = ?
P100>2
P100=1,2
P114 = ?
P115 = 1
6-60
WARNING!
INCORRECT SETTINGS CAN BE DANGEROUS!
Process-related conditions for closed-loop control
0: Drive for standard applications (e.g. pumps)
1: Drive with strong torsion, gear play, large moments of inertia
(e.g. paper machine)
2: Drive for very dynamic accelerations (without load inertia)
(e.g. shears)
3: Drive for strong schock stressing (e.g. roll drive)
4: Drive with high smooth running characteristics at low speeds.
5: Drives with modest response requirements, which can be
optimized in their efficiency with frequent part-load operation.
6: Drive with high starting torque.
7: Dynamic torque response in field-weakening range
See next section for description
10.2001
Parameterizing steps
P130 = ?
P130 =
10,13,14
P151 = ?
Select TmpSensor
0: KTY84 (evaluation via P380/P381)
3: PT100 (evaluation only possible for SBP)
P131 = ?
P139 = ?
P140 = ?
P141 = ?
P100 =
0,1,2
P330 = ?
P339 = ?
P340 = ?
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-61
Parameterizing steps
10.2001
P350 = ?
P351 = ?
P352 = ?
P353 = ?
P354 = ?
P357 = ?
Thermal motor
protection desired ?
no
yes
P380 = ?
P381 = ?
P095=2
P097>0
P382 = ?
P383 = 0
6-62
P383 = ?
10.2001
Parameterizing steps
P384.02 = 0
P384.02 = ?
P452 = ?
P453 = ?
P060 = 1
P128 = ?
P462 = ?
P463 = ?
P464 = ?
P465 = ?
P115 = 2
yes
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-63
Parameterizing steps
10.2001
Analog tachometer?
no
yes
Adjust
tachometer
Adjust tachometer
Tachometer to ATI: See operating instructions for ATI
Tachometer to terminal strip: See function diagrams for analog
inputs
f, n, T control?
(P100 = 3, 4, 5)
no
yes
P115 = 4
Wait
P536 = ?
P115 = 5
Wait
Finished
6-64
10.2001
6.4
Parameterizing steps
Reference quantities Reference variables are intended as an aid to presenting setpoint and
actual value signals in a uniform manner. This also applies to fixed
settings entered as a "percentage". A value of 100 % corresponds to a
process data value of 4000h, or 4000 0000 h in the case of double
values.
All setpoint and actual value signals (e.g. set speed and actual speed)
refer to the physically applicable reference variables. In this respect, the
following parameters are available:
P350
Speed and
frequency reference
values
Reference current
in A
P351
Reference voltage
in V
P352
Reference frequency
in Hz
P353
Reference speed
in rpm
P354
Reference torque
in Nm
60
P109
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-65
Parameterizing steps
Torque reference
value
10.2001
Since the torque signals and parameters in the control system are
always specified and displayed as a percentage, the ratio of the
reference torque (P354) to the rated motor torque (P113) is always
important for accuracy. If both values are the same, a display value of
100 % corresponds exactly to the rated motor torque, irrespective of the
values actually entered in P354 and P113.
For purposes of clarity, however, it is advisable to enter the true rated
torque of the drive in P113 (e.g. from catalog data).
P113 =
Reference power
value
PW (mot, rated)
2n(mot,rated)
60
The reference power (in W) is calculated from the reference torque and
reference speed:
R W ,ref =
P354 P353 2
60
Power values for the control system are also always specified as a
percentage referred to the specified reference power. The ratio of
PW,ref / Pmot,rated can be used for conversion to the rated motor
power.
Pmot,rated =
P113 2 P108
60
Reference current
value
NOTE
6-66
10.2001
Example
Parameterizing steps
P107 = 52.00 Hz
P109 = 2
Pre-assignment:
P352 = 52.00 Hz
Reference frequency
Reference speed
For a maximum speed of four times the rated motor speed you must set
the reference speed to at least 3000 rpm. The reference frequency is
adjusted automatically (P352 = P353 / 60 x P109).
P352 = 100.00 Hz
P353 = 3000 rpm
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-67
Parameterizing steps
Automatic
parameterization
and motor
identification
10.2001
6-68
10.2001
Parameterizing steps
Temperature
monitoring of the
motor
P380 / P381 / Sensor
C
C
f-control (P100 = 3)
n-control (P100 = 4)
2 x Kp
Kp
P223 = Smooth.n/f(act)
0 ms
4 ms
4.8 ms
0.0 ms
KK0000
KK0000 (KK0091)
Alarm A23 in
ready
Alarm A23 in
operation
Fault F20 in
ready
Fault F20 in
operation
=0
=0
=0
=1
PTC
no
yes 1)
=1
=0
PTC
no
yes 1)
yes 1)
=1
=1
PTC
no
yes 1)
yes 1)
=0
>1
KTY84
yes
yes 3)
>1
=0
KTY84
yes
yes 3)
yes 3)
yes 4)
yes 2)
>1
>1
KTY84
yes
yes 3)
yes 3)
yes 4)
yes 3)
=1
>1
KTY84
no
yes 1)
yes 3) 2)
>1
=1
KTY84
no
yes 3)
yes 3)
yes 4)
yes 2)
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-69
Parameterizing steps
6.4.1
10.2001
6-70
10.2001
Parameterizing steps
P216=Smooth n/f(FWD)
P114 = 0
P114 = 1
0ms (n-ctrl.)
4ms (f-ctrl.)
4.8ms
(n-ctrl.)
0=off
P223=Smooth n/f(act)
4ms (n-ctrl.)
0ms (f-ctrl.)
P114 = 2
P114 = 3
P114 = 4
100ms
12.0 (n-ctrl.)
P236=n/f-Reg Gain2
3.0 or 5.0
12.0 (n-ctrl.)
6*P357 (T0)
P240=n/f-Reg Tn
400ms
P279=Torque (dynamic)
20.0%
P291=FSetp Flux(set)
3*P357
40ms (n-ctrl.)
80% (f-ctrl.)
100%
110%
100%=off
99.9%
50%
P303=Smooth Flux(set)
10-20ms
60ms
100 (n-ctrl.)
500 (f-ctrl.)
P339=ModSystRelease
P295=Efficiency Optim.
P114 = 7
2=on
3.0 or 5.0
P287=Smooth Vd(act)
P114 = 6
2=on (n-ctrl)
P235=n/f-Reg Gain1
P273=Smooth Isq(set)
P114 = 5
Gain(n)
1.5*Gain(n) 1.5*Gain(n)
(f-ctrl.)
(f-ctrl.)
0=All syst
P344=ModDepthHeadrm
0.0%
3.0%
P536=n/f RegDyn(set)
50%
20%
3=only RZM
3.0%
30.0%
25%
The start-up time is the time taken by the drive to accelerate to rated
speed when the rated torque is specified. This is determined during
automatic speed controller optimization.
Notes for the setting of parameters
The following explanations provide additional information to that
contained in the respective parameter descriptions.
With P114 = 0, automatic parameterization is set for reliable operation
of all application examples with average dynamic performance. The
relevant parameter values are indicated in the first column of the table.
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-71
Parameterizing steps
P216
P217
P223
P235, P236
P240
P273
P279
6-72
10.2001
10.2001
P287
P291
P295
P303
P315
Parameterizing steps
= SmoothDCBusVolts(act):
The Vd correction is set more dynamically by reducing the smoothing
time, in order to ensure correct precontrol of the current controller if
there are rapid changes in the DC link bus voltage. As smoothing is
automatically increased in the range of optimized pulse patterns, it is
sensible for the pulse-edge modulation (P339 = 3) to be disabled in this
context.
= FSetp Flux (set):
Flux setpoint in the basic speed range. A load-dependent flux boost to
110 % may be appropriate for efficiency optimization. For this, P295
must be set to values below 100 %.
= Efficiency Optim:
Drives which are continuously operated in the partial load range (below
30 % load) can be improved in their efficiency by a load-dependent flux
reduction (to a minimum of 50 %). The flux build-up and reduction is
smoothed via P303. The dynamic performance of the speed controller
has to be reduced.
If flux tracking is powered up (99.9 %), the differentiation of the flux
setpoint for forming the field-generating current component is switched
off. This enables a calmer controller response to be achieved in the
field weakening range for slow acceleration and deceleration times
without negatively influencing flux build-up und reduction. For fast
acceleration, the field-generating current is reduced, but flux build-up
and reduction are slowed down.
A further reduction of the value does not then make sense. The flux
setpoint smoothing time constant P303 does not have to be increased
as it does for load-dependent flux reduction.
= Smooth Flux (set):
Smoothing of the flux setpoint must be switched on during loaddependent flux reduction in order to rule out the risk of unstable control
performance.
In the field weakening range, the flux setpoint may have to be
smoothed for the sake of a calmer control performance.
= cEMF Reg Gain:
The EMF controller is responsible for generating the speed actual-value
during frequency control. For dynamic closed-loop control, the EMF
controller must therefore also be set more dynamically. In general,
high-response drives without an encoder should only be used if the
operating speeds are higher than approx. 20 %.
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-73
Parameterizing steps
P339
P344
P348
P536
6-74
10.2001
= ModSystemRelease:
During complete pulse-edge modulation system release (P339 = 0) the
modulation depth is raised to a maximum of 96 % (Uoff = Uon). For
this, a switchover of the modulation systems in the gating unit is
necessary (optimized pulse pattern = flange-edge modulation).As the
sampling rate of current control decreases in this range while, on the
other hand, the torque ripple increases slightly, pulse-edge modulation
has to be disabled for highly dynamic and very sensitive systems
(P339 = 3).
If space vector modulation is overmodulated (P339 = 4), the maximum
modulation depth P342 must be restricted to approx. 90 %.
= ModDepth Headrm
The modulation depth headroom increases the interval between the
setpoint voltage and the maximum voltage in the field weakening area
in a steady-state (not dynamic) manner. The modulation depth
headroom prevents a switchover of the current controller dynamic
response when it reaches the voltage limit.
= Dead Time Comp
To reduce the torque ripple (with 6-fold stator frequency) in the speed
range from approx. 10 Hz, it may be appropriate in the case of motors
above approx. 11 kW to switch in the deadtime compensation of the
gating unit. Software with at least version 3.1 and a CUVC controller
module with a version higher than C are necessary in this case.
= n/f RegDyn(set):
Dynamic response of the speed control circuit only affects the setting of
the speed controller during automatic controller optimization (P115 = 5).
A dynamic value of 200 % corresponds to the symmetrical optimum.
This cannot be achieved on geared drives or with load-dependent flux
reduction.
The dynamic response must, however, be increased in case of load
surges and for requirements on the smooth running characteristics (and
maybe in the case of rapid accelerations).
10.2001
6.4.2
Parameterizing steps
In addition to this, the new special function "User parameter" has been
introduced, and the special function "Drive setting" (P052 = 5) has been
subdivided into the functions "Quick parameterization" and "Drive
setting". The new special function "Quick parameterization" involves
parameterization for standard applications, and the new special
function "Drive setting" involves parameterization for expert
applications.
Siemens AG
6SE7087-6QX60 (Version AE)
SIMOVERT MASTERDRIVES
Compendium Vector Control
6-75
Parameterizing steps
10.2001
Menu selection
P052 (former)
Function selection
0=
User parameter
--
1=
0=
Return
2=
Parameter menu
Fixed settings 1)
1=
Param. Reset
3=
Quick parameterization
5=
Drive Setting
4=
Board configuration
4=
HW Config.
5=
Drive setting
5=
Drive Setting
6=
Download
3=
Download
7=
Upread
3=
Download
8=
2=
MLFB input
1) Selection in the factory setting menu (P366 Factory setting type, activation with P970)
P115
P052
(former)
Function
selection
1=
Automatic parameterization
6=
Auto Param.
2=
7=
Mot ID Stop
3=
8=
Mot ID All
4=
No-load measurement
9=
No Load Meas
5=
10=
Reg Optim.
6=
Self-test
11=
Auto Test
7=
Tachometer test
12=
Tach Test
The new special function P060 = 0 (User parameter) enables the user
to put together an important list of parameters especially for his own
application.
When P060 = 0 (User parameter) is selected, apart from parameters
P053, P060 and P358, only those parameters whose numbers have
been entered in indices 4 to 100 of parameter P360 are visible.
6-76