What is and Why use the
Digital Panel Meter
In the manufacturing industry and in the process control Should you need a simple indicator, a controller for every
applications, it is of vital importance the monitoring and kind of variable, or a more complex instrument - able for ex-
the control by means of alarms of several physical ample to manage four alarms, to be connected in a RS485
variables. In addition analogue or serial retransmission of network, to linearise the non-linear input signals and to
the measured value can be required in order to provide a show different conditions with different display colours - we
feedback to the system which controls the process, or to have the panel meter that better suits your demands. The
log the history of the monitored plant. Whatever are range is completed with a universal signal conditioner,
your needs and requirements in the process you have whose flexible and advantageous modular architecture is
to control, Carlo Gavazzi has the right solution. common to the other medium and high-end panel meters.
2
The charactersitics
Wide range of available inputs for all
the applications: voltage, current,
frequency, resistance, temperature.
Modular architecture available in the
medium and high-end meters, making
them flexible and easy to configure.
Different type of outputs available to
retransmit the measured variable:
analogue signal, alarm contacts or serial port
Easy programmability by means of a handy
keypad. The more complex instruments are
configurable by means of dedicated software tool.
3, 3 1/2 or 4-digit LED display with alarm
and over range indication.
3
USC: 5-slot module holder
A new concept of Modularity
• Maximum in-field flexibility
• Quick assembly and configuration
• Easy future expansion
Measurement inputs
0.2-2-20mA AC/DC
0.2-2-20mA AC/DC + excitation output
0.2, 2, 5A AC/DC; 20, 200, 500V AC/DC
TC: J-K-S-T-E, Pt100-250-500-1000, Ni100
Ω: 0.02, 0.2, 2, 20kΩ
4
UDM35: 3 1/2-digit read-out,
or 3-digit + dummy 0 read-out
Display Base
UDM40: 4-digit
read-out, 3-colour display
Power Supply
90 to 260V AC/DC
18 to 60V AC/DC
Communication Port Outputs
RS485 and RS232 ports Analogue outputs:
Max 1 analogue output
0 to 20mA and 0 to 10VDC
Alarm outputs:
1 relay output
2 relay outputs
2 relay + 2 open collector outputs
4 relay outputs. 5
Features and Benefits of the Digital Panel Meters
DI3 DIN, DI3 72, LDI3
• Indicators for DIN-rail and panel mounting
• Multi input capabilities €
• Easy product configuration UDM40
MDM40
• Two-alarm tachometer USC
UDM35
• Dual input and multifunction capability
MDM40
• Management of all available sensors
• Reverse speed control
LDI35/LDM35
LDI35, LDM35H
• Multi range and multi signal indicator and controller
DI3 LDI3
• Powerful scaling capability
• Universal power supply (LDM35H only)
Features/Functions
UDM35
• Powerful performance
• Plug and play modules
• Maximum in-field flexibility UDM40 Color Display
• Possibility to expand the inputs/outputs RED - High priority,
only when really needed by the application abnormal condition
UDM40
AMBER - Low priority,
• State of art performances
abnormal condition
• Maximum in-field flexibility
• Input signal linearization capability
• 3-colour display GREEN - Normal
condition
USC
• Universal signal conditioner
• Maximum in-field flexibility
• Input signal linearization capability LDI35, LDM and UDM
• Programming and network software In the process control
applications, it is a
mandatory condition to
DI3 DIN, DI3 72, LDI3 be able to manage sig-
The instruments are easily configurable by dip-switches. nals such as “mA and
That allow to set the position of the decimal point and volts” which are propor-
the primary of the current transformer or to connect the tional to pressure or other
potential transformer. variables being measured.
The LDI35/LDM/UDM se-
ries answers to this request
with powerful scaling and filter
in order to show the vari-
able in a stable and reli-
able way on the display.
6
The available modules
Type Channels UDM35 UDM40 USC OrderingCode
UDM35 base BD35
UDM40 base BD40
USC base BDXX
AC/DC inputs: 200µA, 2mA, 20mA, 200mV, 2V, 20V 1 BQLSX
AC/DC inputs: 200µA, 2mA, 20mA, 200mV, 2V, 20V + excitation output 1 BQLSE
AC/DC inputs: 200mA, 2A, 5A, 20V, 200V, 500V 1 BQHSX
Inputs: 20Ω, 200Ω, 2kΩ,20kΩ; TC: J-K-S-T-E, Pt100-250-500-1000, Ni100 1 BQTRX
Analogue output: 0 to 20mA, 0 to 10V DC 1 BOAV
Relay output 1 BOR1
Relay output 2 BOR2
Outputs: 2 relays + 2 open collectors 4 BOR4
Relay output 4 BOR5
RS485 communication port 1 BRSX
RS232 communication port 1 BRSY
18 to 60V AC/DC power supply BPL
90 to 260V AC/DC power supply BPH
UDM35 / UDM40 USC
Slot A B C D A B C D E
Inputs/Outputs 1 2 3 4 1 2 3 4 5
Measurement inputs: LSX, LSE, HSX, TRX
RS485 communication port: SX
RS232 communication port: SY
Analogue output (*): AV
Relay and open collector outputs: R1, R2, R4, R5
Power supply: H, L
(*) Note: Max one analogue output module
7
DI3 DIN DI3 72 LDI3 LDI35
Page 10 Page 10 Page 10 Page 11
DIN rail mounting
Panel mounting
Modular
Indicator
Controller
3-colour display
Signal conditioner
Linearization capability
Multi input (A-V)
Temperature measurement
Tachometer
Command inputs
Up to 1 alarm
Up to 2 alarms
Up to 4 alarms
Analogue output
Serial communication
Universal power supply
8
LDM35H MDM40 UDM35 UDM40 USC
Page 12 Page 13 Page 14 Page 15 Page 16
9
DI3 DIN DI3 72 LDI3
With just four basic models this product family is the ideal
solution for the panel builders.
The product philosophy meets the panel builder and dis-
tributor requests in terms of features and flexibility granting
therefore a consistent stock reduction.
DI3 DIN DI3 72 LDI3
Description 3-DGT µP-based indicator
Housing (H x W x D) 89 x 53.5 x 58.8 mm (DIN) The best to suit your needs!
72 x 72 x 75 mm (72)
48 x 96 x 83 mm (LDI3)
Mounting DIN rail, panel mounting (72, LDI3)
Display type 3 DGT, red LED
Variables on display YES
Performances
Measured signals 1A/60mV/100-500VDC
1A/100VAC, 5A/500VAC
1 to 1000Hz 72, LDI3
Type signals DC or AC
Engineering units mA, A, V, Hz DIN
Accuracy ±(0.5%FS, + 1DGT)
Temperature drift ±350ppm/°C
Sampling rate 1 time/s
Command inputs NO Hardware Functions In-Out
Outputs: Alarm NO
Analogue NO
Serial NO
Signal/display scaling YES (CT and PT sel. by dip-switch)
Power supply 24V, 48V, 115V, 230V AC
Approvals CE, DI3 72:c CSA us;
LDI3: c CSA us, UR
Protection degree IP40 (DIN); IP50 (72), IP50
(LDI3), IP65 (LDI3 on request)
10
LDI35
The family is available in two basic versions:
• LDI35, simply as indicator;
• LDI35, up to 1 alarm relay output.
On each basic model it is possible to have a specific version for:
• process applications with 2-20mA and 0.2-20V-200V
input;
• panel builders with 2-5A and 200-500VAC/DC input. The range is completed by a multi probe temperature
controller and ohmmeter.
LDI35
Description 3 1/2-DGT µP-based indicator
and controller The best to suit your needs!
Housing (H x W x D) 48 x 96 x 83 mm
Mounting Panel mounting
Display type 3 1/2-DGT or 3DGT+ dummy 0, red LED
Variables on display YES
Measured signals (2-20mA, 20-200V); (2-5A, 200-
Performances
500V); (TC: J-K-S-T-L, Pt100-1000,
Ni100, 200-2000 Ω)
Type signals DC and AC
Engineering units Label set
Accuracy DC: ±(0.3%FS + 1DGT)
AC: ±(0.5%FS + 1DGT)
Temperature drift ±200ppm/°C
Sampling rate 4 times/s
Command inputs NO Hardware Functions In-Out
Outputs: Alarm Up to 1
Analogue NO
Serial NO
Other available characteristics Signal/display scaling. Digital
filter, Peak and valley. Burn-out
control on temperature input
Power supply 24, 48, 115, 230VAC, 9 to 32VDC,
40 to 150VDC
Approvals CE, c CSA us, UR
Protection degree IP65 (on request)
11
LDM35H
The family is available in two basic versions:
• LDM35H, simply indicator;
• LDM35H, up to 2 alarm relay outputs.
Both of them provided with universal power supply.
On each basic model it is possible to have a specific version for:
• process applications with 0.2-2-20mA and
0.2-2-20V DC/AC input;
• panel builders with 0.2-2-5A and 20-200-500V AC/DC
LDM35H
input.
Furthermore TRMS method improves significantly the
Description 3 1/2-DGT µP-based indicator accuracy of the measurement on both distorted current
and controller and voltage.
Housing (H x W x D) 48 x 96 x 83 mm
Mounting Panel mounting
Display type 3 1/2-DGT or 3-DGT + dummy 0,
red LED
Variables on display YES
Measured signals (0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V)
Type signals DC and AC TRMS The best to suit your needs!
Engineering units Self sticking label set
Accuracy DC: ±(0.3%RDG + 3DGT)
AC: ±(0.5%RDG + 3DGT)
Temperature drift ±150ppm/°C
Sampling rate 5 times/s
Performances
Command inputs NO
Outputs: Alarm Up to 2
Analogue NO
Serial NO
Other available characteristics Signal/display scaling. Digital
filter, Peak and valley.
Power supply 90 to 260V AC/DC,
18 to 60V AC/DC
Approvals CE, c CSA us and UR pending
Hardware Functions In-Out
Protection degree IP65
12
MDM40
MDM40 tachometer is an extract of flexibility and perform-
ances in only one product.
This instrument is suitable to be used in all applications
thanks to:
• the capability to measure a very slow speed/
frequency (0.001 Hz);
• the management of pulse signals from proximity switches,
MDM40
photo switches, NAMUR proximities, encoders and
magnetic pick-up’s;
Description 4-DGT multi-range controller for • the rate-tacho-frequency-period meter functions.
pulse signal
Housing (H x W x D) 48 x 96 x 124 mm The two independent inputs, with proper parameter pro-
Mounting Panel mounting gramming are able to measure rate, speed, frequency and
Display type 4 DGT, red LED period variables using mathematical formulas like: A, B,
Variables on display YES 1/A, A/B, A-B, (A-B)/B, B/(A+B) and revers speed control.
Measured signals Speed, frequency, rate, period
Type signals DC or AC
Engineering units Label set
Accuracy ±(0.001% RDG + 3DGT) The best to suit your needs!
Temperature drift ±100ppm/°C
Sampling rate Programmable
Command inputs 1 (display hold, key pad lock)
Outputs: Alarm 2
Analogue 1 (20 mA, 10 VDC)
Serial
Performances
RS485
Other available characteristics Signal/disp. and analogue out. scaling.
Digital filter.
Peak and valley.
Power supply 24,48,115,120,230,240 VAC
9 to 32, 40 to 150 VDC
Approvals CE, UR
Protection degree IP65
Hardware Functions In-Out
13
UDM35
UDM 35 is a universal high-tech instrument that has been
developed to meet the most advanced application needs.
UDM35 offers to the user many solutions and advantages
that can be summarized in:
• quick assembly and maintenance using
plug and play modules;
• easy and quick parameter programming and
parameter cloning on other UDM’s by means of
UdmSoft or PC Hyperterminal;
• powerful variable control by means of up to 4 alarms;
UDM35
• remote control facilities like analogue output and
RS485, RS232 communication ports.
Description 3 1/2-DGT µP-based controller
with modular housing The different type of alarm controls:
Housing (H x W x D) 48 x 96 x 105 mm • up-down functions with automatic reset;
Mounting Panel mounting • up-down functions with manual reset;
Display type 3 1/2-DGT or 3-DGT + dummmy 0, • down with disable function at power-on.
red LED These alarms can be
Variables on display YES combined so to have
Measured signals (0.2-2-20mA, 0.2-2-20V); (0.2-2-5A, up to 4 abnormal steps
20-200-500V); (TC: J-K-S-T-E, RTD, Ω) notified as pre-alarms
Type signals DC and AC TRMS and alarms.
Engineering units Self sticking label set
Accuracy DC: ±(0.1%RDG + 3DGT)
AC: ±(0.3%RDG + 3DGT) The best to suit your needs!
Temperature drift ±150ppm/°C
Sampling rate 5 times/s
Command inputs 1 (display hold, key pad lock or
latch alarm reset)
Outputs: Alarm Up to 4
Performances
Analogue 1 (20mA,10VDC)
Serial RS485, RS232
Other available characteristics Signal/display scaling. Analogue
output scaling. Digital filter, Peak
and Valley. Burn-out control on
temperature inputs only.
Power supply 90 to 260 AC/DC,
18 to 60V AC/DC
Approvals CE; c CSA us and UR pending Hardware Functions In-Out
Protection degree IP65
14
UDM40
UDM40 has the same basic characteristics of UDM35.
Other benefits can be summarized as follows:
• display colour adaptable to other existing instruments
by means of a 3-colour choice;
• management of non linear signals coming from special
process transmitters using a 16-point linearization capability;
• reliable information to the process, working out a
complex or disturbed signal by a programmable
input integration time and/or a smart digital filter.
Controller UDM40
Description 4-DGT µP-based controller with Alarm status given at a glance using the easy traffic lights
modular housing principle. The instrument may show the alarm status based on
Housing (H x W x D) 48 x 96 x 105 mm a sequence of colours that can be programmed by the user.
Mounting Panel mounting
Display type 4-DGT, coulor LED
Variables on display YES
Measured signals (0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
Type signals DC and AC TRMS
Engineering units Self sticking label set
Accuracy DC: ±(0.1%RDG + 3DGT)
AC: ±(0.3%RDG + 3DGT)
Temperature drift ±150ppm/°C The best to suit your needs!
Sampling rate 5 times/s
Command inputs 1 (display hold, key pad lock or
latch alarm reset)
Outputs: Alarm Up to 4
Analogue 1 (20mA, 10VDC)
Performances
Serial RS485, RS232
Other available characteristics Signal/display scaling. Analogue
output scaling. Digital filter. Integra-
tion time. Peak and valley. Burn-
out control on temp. inputs only.
Linearization. Traffic lights function.
Power supply 90 to 260 AC/DC,
18 to 60V AC/DC
Approvals CE; c CSA us and UR pending Hardware Functions In-Out
Protection degree IP65
15
USC
The winning point of the USC “Universal Signal
Conditioner” is its architecture. It is formed by a module
holder on which it is possible to plug in modules with dif-
ferent purposes: power supply-measurement-alarm con-
trol-signal retransmission. The different combination of the
modules allows to have a simple signal conditioner or a very
sophisticated controller with communication port.
The main advantages given by USC can be summarized The LEDs on modules show
as follows: the power supply and com-
munication status all the
time.
Signals conditioner USC
Description µP-based signal conditioner with • easy and quick parameter programming and parameter
modular housing cloning on other USC’s by means of UscSoft or PC
Housing (H x W x D) 44 x 113 x 107 mm Hyperterminal;
Mounting DIN-rail mounting • powerful variable control by means of up to 4 alarms;
Display type NO • remote control facilities like analogue output and
Variables on display NO RS485, RS232 communication ports;
Measured signals (0.2-2-20mA, 0.2-2-20V); (0.2-2-5A, • management of non linear signals coming from special
20-200-500V); (TC: J-K-S-T-E, RTD, Ω) process transmitters using a 16-point linearization capability;
Type signals DC and AC TRMS • reliable information to the process, working out a
Engineering units NO complex or disturbed signal by a programmable input
Accuracy DC: ±(0.1%RDG + 3DGT) integration time and/or smart digital filter.
AC: ±(0.3%RDG + 3DGT)
Temperature drift ±150ppm/°C
Sampling rate 5 times/s The best to suit your needs!
Command inputs 1 (latch alarm reset)
Outputs: Alarm Up to 4
Analogue 1 (20mA, 10VDC)
Serial RS485, RS232
Other available characteristics Signal/display scaling. Analogue
output scaling. Digital filter.
Performances
Integration time. Peak and valley.
Burn-out control on temp. inputs
only. Linearization up to 16 points.
Power supply 90 to 260 AC/DC,
18 to 60V AC/DC
Approvals CE; c CSA us and UR pending
Protection degree IP20
Hardware Functions In-Out
16
Accessories
Types SIU-PC85 SIU-DIN 8585 SIU-DIN.RLY PSU-DIN (DC/AC) PSU-DIN (AC/DC)
Description Serial communication Serial communication Serial communication Power supply unit Power supply unit
line adapter line amplifier, driver relay outputs DC to AC AC to DC
Housing Front: 65x80mm Front: 89x71.5mm Front: 89x71.5mm Front: 89x71.5mm Front: 89x71.5mm
Signal input RS232 RS485, RS422 RS485, RS422 N.A. N.A.
Working mode 2-wire comm. 2 or 4-wire comm. 2 or 4-wire comm. N.A. N.A.
Line Bias N.A. YES N.A. N.A. N.A.
Line termination N.A. YES YES N.A. N.A.
Connections 9-pole, female Screw terminal block Screw terminal block Screw terminal block Screw terminal block
Output RS422 RS422 4 relays 24VDC (max. 250mA) 5VDC (max. 200mA)
RS485 5A, 250V 48VDC (max. 125mA) 12VDC (max. 100mA)
115VDC (max. 50mA) 24VDC (max. 50mA)
Working mode 4-wire comm. 4-wire comm. SPDT contacts Switching mode By transformer
Line Bias YES YES N.A. N.A. N.A.
Line termination YES YES N.A. N.A. N.A.
Connections Screw terminal block Screw terminal block Screw terminal block Screw terminal block Screw terminal block
Baud rate Max 19200 Baud Max 19200 Baud Max 9600 Baud N.A. N.A.
Protection All inputs/outputs All inputs/outputs N.A. Output: by fuse Output: electronic
Indication Power-on Power-on Power-on Power-on Power-on
(by means of LEDs) Data-stream Comm. status
Output status
Insulation Input/output: 2kV Input/output: N.A. Input/output: 2kV N.A. Input/output: 4kV
input/output and input/output and input/output and
power supply: 4kV power supply: 4kV power supply: 4kV
Operating temperature 0 to +50°C (R.H. 0 to +50°C (R.H. 0 to +50°C (R.H. 0 to +50°C (R.H. 0 to +50°C (R.H.
≤90% non condens- ≤90% non condens- ≤90% non condens- ≤90% non condens- ≤90% non condens-
ing) ing) ing) ing) ing)
Storage temperature -10 to +60°C (R.H. -10 to +60°C (R.H. -10 to +60°C (R.H. -10 to +60°C (R.H. -10 to +60°C (R.H.
≤90% non condensing) ≤90% non condensing) ≤90% non condensing) ≤90% non condensing) ≤90% non condensing)
Included set 1.8m cable with 9 to N.A. N.A. N.A. N.A.
9-pole connectors,
power supply cable
Other characteristics Wrong-line connec- Dual purpose: dis- 4 relay outputs to be Stabilised AC voltage Stabilised DC voltage
tion and full overvolt- tance increase by driven by an RS485 output. output.
age protection. 1200m per unit; net- communication port Stability: ≤4% Stability: ≤0.5%
Reverse conversion work increase Un @ max. current Un @ max. current
capability. Non-stabilised DC
voltage outputs: 2V-
20V-30VDC
Power supply input 24VAC, 48VAC 24VAC, 48VAC 24VAC, 48VAC 80 to 240VDC 24VAC, 48VAC
115VAC, 230VAC 115VAC, 230VAC 115VAC, 230VAC 18 to 60VDC 115VAC, 230VAC
9 to 16VDC
Protection degree IP20 IP40 IP40 IP40 IP40
17
Current Transformer
Types TADK TADK2 TAD 2 TAD 3 TAD 4
Class 0.5 0.5 0.5/ 1/ 3 0.5/ 1 0.5/1
Bus–bar size Wounded primary 25x5 mm fixed bar Ø 22 mm 21x14 or 31x11 mm 32x16, 41x11, Ø 32 mm
Dimensions (H x W x D) 115.5x75x44 mm 115.5x75x44 mm 98.5x58x44 mm 98.5x58x44 mm 75x115.5x44 mm
Standards IEC 60185/EN 60185 IEC 60185/EN 60185 IEC 60185/EN 60185 IEC 60185/EN 60185 IEC 60185/EN 60185
Accuracy class Class 0.5 Class 0.5 Class 0.5 1 3 Class 0.5 1 Class 0.5 1
depending on the Burden Burden Burden Burden Burden
burden output VA VA VA VA VA VA VA VA VA
Primary current at 1 A 10 1 A 10 40 A 3 100 A 3 100 A 3
rated output 5 A 10 5 A 10 50 A 3 150 A 3 4 150 A 3
current of 1A/5A 10 A 10 10 A 10 60 A 3 200 A 3 4 200 A 4
15 A 10 15 A 10 80 A 3 250 A 5 8 250 A 6
25 A 10 25 A 10 100 A 3 4 300 A 5 8 300 A 6
40 A 10 40 A 10 150 A 3 4 6 400 A 6 10 400 A 10
50 A 10 200 A 3 4 6 500 A 6 10 500 A 10
60 A 10 250 A 5 8 10 600 A 6 10 600 A 10
80 A 10 300 A 5 8 10 800 A 10
100 A 10
150 A 10
200 A 10
250 A 10
Types TAD 6 TAD 8 TAD 12 TACO 110 TACO 200
Class 0.5/1 0.5/1/5P10 0.5/1/5P10 0.5/1/5P10 0.5/1/5P10
Bus–bar size 55x22, 65x20, Ø 52 mm 82x32 or 65x34 mm 127x51 or 102x53 mm Max. Ø 110 mm Max. Ø 200 mm
Dimensions (H x W x D) 105x145x44 mm 140x120x55 mm 183x170x65 mm 183x170x 65 mm 295x280x45 mm
Standards IEC 60185/EN 60185 IEC 60185/EN 60185 IEC 60185/EN 60185 IEC 60185/EN 60185 IEC 60185/EN 60185
Accuracy class Class 0.5 1 Class 0.5 1 5P10 Class 0.5 1 5P10 Class 0.5 1 5P10 Class 0.5 1 5P10
depending on the Burden Burden Burden Burden Burden
burden output VA VA VA VA VA VA VA VA VA VA VA VA VA VA
Primary current at 400 A 6 12 400 A 4 8 5 800 A 15 30 10 800 A 15 30 10 1000A 15 30 10
rated output 500 A 6 12 500 A 6 12 5 1000A 20 40 10 1000A 20 40 10 1500A 15 30 10
current of 1A/5A 600 A 10 20 600 A 10 20 5 1200A 30 60 10 1500A 40 80 10 2000A 15 30 10
800 A 10 20 800 A 15 30 5 1500A 40 80 10 2000A 50 100 10 2500A 40 80 10
1000A 20 40 1000A 20 40 5 2000A 50 100 10 2500A 60 120 10 3000A 40 80 10
1200A 20 40 1200A 30 50 5 2500A 60 120 10 3000A 80 160 10 4000A 50 100 10
1500A 30 60 1500A 40 60 5 3000A 80 160 10 4000A 100 200 10 5000A 50 100 10
2000A 30 60 2000A 50 80 5 4000A 100 200 10 6000A 50 100 10
2500A 60 100 5
Cable/Bus–bar type current transformers. Standard output 5A (1A on request). Rated primary currents from 40A to 6000A. DIN–rail or panel mounting.
Current transformer 1-phase AC; operating frequency: 40 to 60 Hz; max system voltage: 0.72 kV; rated insulation level: 3kV/1min @ 50Hz; security factor: ≤5;
rated secondary current: 5A standard (1A on request).
A full range of split-core current transform-
ers is available from 100A to 6000A
18
Accuracy of the main variables
Front housing protection degree
Display digits and (sampling rate)
3-colour display
Excitation output
“Traffic light” function. Alarm level
connected to the display colour
Pulse measuring input
Peak and valley function
Digital filter with action on the display
and signal outputs
Integration time
Linearization
Instantaneous variables displaying
Analogue output for variable retrans-
mission
Alarm outputs for variable control
Digital inputs for external command
Communication port
OUR SALES NETWORK
Carlo Gavazzi GmbH - AUSTRIA Carlo Gavazzi OY AB - FINLAND Carlo Gavazzi SpA - ITALY Carlo Gavazzi SA - SPAIN
Ketzergasse 374, A-1230 Wien Petaksentie 2-4, FI-00630 Helsinki Via Milano 13, I-20020 Lainate Avda. Iparraguirre, 80-82,
Tel: +43 1 888 4112 Tel: +358 9 756 2000 Tel: +39 02 931 761 E-48940 Leioa (Bizkaia)
Fax: +43 1 889 10 53 Fax: +358 9 756 20010 Fax: +39 02 931 763 01 Tel: +34 94 480 4037
[email protected] [email protected] [email protected] Fax: +34 94 480 10 61
[email protected]
Carlo Gavazzi NV/SA - BELGIUM Carlo Gavazzi Sarl - FRANCE Gavazzi Automation Sdn Bhd
Schaarbeeklei 213/3, B-1800 Vilvoorde Zac de Paris Nord II, 69, rue de la Belle No. 1, Jalan Pendidik U1/31, Sek. U1, Carlo Gavazzi AB - SWEDEN
Tel: +32 2 257 4120 Etoile, F-95956 Roissy CDG Cedex Hicom Glenmarie Industrial Park Nattvindsgatan 1, S-65221 Karlstad
Fax: +32 2 257 41 25 Tel: +33 1 48 38 98 60 40150 Shah Alam, Selangor, - MALAYSIA Tel: +46 54 85 1125
[email protected] Fax: +33 1 48 63 27 43 Tel: +60 3 5569 4212 Fax: +46 54 85 11 77
[email protected] Fax: +60 3 5568 0004 [email protected]
Carlo Gavazzi Inc. - CANADA [email protected]
2660 Meadowvale Boulevard, Carlo Gavazzi GmbH - GERMANY Carlo Gavazzi AG - SWITZERLAND
CDN-Mississauga Ontario L5N 6M6, Rudolf-Diesel-Strasse 23, Carlo Gavazzi BV - NETHERLANDS Verkauf Schweiz/Vente Suisse
Tel: +1 905 542 0979 D-64331 Weiterstadt Wijkermeerweg 23, Sumpfstrasse 32,
Fax: +1 905 542 22 48 Tel: +49 6151 81000 NL-1948 NT Beverwijk CH-6312 Steinhausen
Carlo Gavazzi LTEE - CANADA Fax: +49 6151 81 00 40 Tel: +31 251 22 9345 Tel: +41 41 747 4535
3777 Boulevard du Tricentenaire [email protected] Fax: +31 251 22 60 55 Fax: +41 41 740 45 40
Montreal, Quebec H1B 5W3 [email protected] [email protected]
Tel: +1 514 644 2544 Carlo Gavazzi UK Ltd - GREAT BRITAIN
Fax: +1 514 644 2808 7 Springlakes Industrial Estate, Carlo Gavazzi AS - NORWAY Carlo Gavazzi Inc. - USA
[email protected] Deadbrook Lane, Hants GU12 4UH, Melkeveien 13, N-3919 Porsgrunn 750 Hastings Lane,
GB-Aldershot Tel: +47 35 93 0800 USA-Buffalo Grove, IL 60089,
Carlo Gavazzi Handel A/S - DENMARK Tel: +44 1 252 339600 Fax: +47 35 93 08 01 Tel: +1 847 465 6100
Over Hadstenvej 42, DK-8370 Hadsten Fax: +44 1 252 326 799 [email protected] Fax: +1 847 465 7373
Tel: +45 89 60 6100 [email protected] [email protected]
Fax: +45 86 98 15 30 Carlo Gavazzi Lda - PORTUGAL
[email protected] Rua dos Jerónimos 38-B,
P-1400-212 Lisboa
Tel: +351 21 361 7060
Fax: +351 21 362 13 73
[email protected]
OUR PRODUCTION SITES
Carlo Gavazzi Industri A/S Carlo Gavazzi Ltd Carlo Gavazzi Controls SpA SAIET Elettronica SpA Carlo Gavazzi Industri A/S
Hadsten - DENMARK Zejtun - MALTA Belluno - ITALY Castel Maggiore (BO) - ITALY Hadsten - DENMARK
Tel: +45 89 60 6100 Tel: +356 23601 100 Tel: +39 0437 931 000 Tel: +39 051 417 8811 Tel: +45 89 60 6100
8028090 BRO DPM ENG REV.06-2004
Inductive and Capacitive Solid States Relays. Energy Management. Safety Modules, Safety Magnetic Dupline Field and
Proximity Sensors in full metal Versions for PCB and Timers and Sensors, Safety Mats, Safety Light Installation Bus.
and plastic housings. panel mounting. Monitoring Relays. Curtains, Intrinsic Safety, Electrical Building Automation Systems.
Photoelectric Sensors. AC Semiconductor Digital Panel Meters and Protections
Level Sensors: Optical, Motor Controllers Temperature Controllers.
Conductive and Capacitive. Soft starters.
Ultrasonic Sensors and Industrial and PCB Relays.
Magnetic Switches.
Limit Switches.
Further information on www.carlogavazzi.com/ac
CARLO GAVAZZI
Automation Components