Design of Syphon

This document provides the design details for the reinforced concrete barrels of a canal syphon. It includes calculations for determining the distribution factors, dead loads, earth pressures, fixing moments, design moments, required member thicknesses, and reinforcement details. The syphon consists of two 3m x 2.5m barrels. Design moments, fixing moments, and required reinforcement are calculated for each of the three spans - AB, CD, and AD. Reinforcement is specified as 16mm bars spaced 12.5cm, 11.25cm, and 16.25cm respectively for the three spans.

Uploaded by

raghurmi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
441 views

Design of Syphon

This document provides the design details for the reinforced concrete barrels of a canal syphon. It includes calculations for determining the distribution factors, dead loads, earth pressures, fixing moments, design moments, required member thicknesses, and reinforcement details. The syphon consists of two 3m x 2.5m barrels. Design moments, fixing moments, and required reinforcement are calculated for each of the three spans - AB, CD, and AD. Reinforcement is specified as 16mm bars spaced 12.5cm, 11.25cm, and 16.25cm respectively for the three spans.

Uploaded by

raghurmi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Hydraulic Structures Structural Design of Syphon

1

Design of Syphon Barrels
Design barrels of the canal syphon as reinforced concrete box. The data is given below:
1. Number of barrels =2
2. Size of barrel =3 m 2.5 m
3. Bank level =254 m
4. Drain H.F.L =253.25 m
5. Uplift at base of barrel =4.5 t/m
2

6. Unit weight of dry earth =1.6 t/m
3

7. Unit weight of saturated earth =2.0 t/m
3

8. Weight of submerged earth =1.0 t/m
3

9. Angle of internal friction in all
conditions
=30
Design
Assume the thickness of the frame 30 cm all through so that the effective length of horizontal
and vertical members are 3.3 m and 2.8 m.




Hydraulic Structures Structural Design of Syphon
2

1. Distribution factors
At joint A
For
2.8
0.46
2.8 3.3
AB = =
+

For
3.3
0.54
2.8 3.3
AD = =
+


At joint D
For D A=0.54
D C=0.46
2. Dead loads
Consider one meter of barrel:
Depth of dry earth over barrel 254 253.25 0.75m = =
Depth of saturated earth 253.25 251.4 1.85m = =
Weight of dry and saturated earth
2
0.75 1.6 1.85 2 4.9t m = + =

Weight of top slab (0.3 m thick)
2
0.3 2.4 0.72t m = =
Weight on the top slab including its own weight
=
2
4.9 0.72 5.62t m + =

Weight of barrels per meter of length
( ) 4 3.3 3 2.8 0.3 2.4 15.6t m = + =
Total dead load/mof length of barrels
15.6 4.9 6.9 49.4t m = + =

Uplift per one meter length
4.5 6.9 31.05t m = =
Net vertical load acting on foundation
49.4 31.05 18.35t m = =
Pressure on foundation soil (Soil reaction)
2
18.35
2.66
6.9
t m = =
Pressure acting on the base slab + uplift =Soil reaction

2
2.66 4.5 7.16t m = + =
Net upward pressure on the base slab
2
2
7.16 0.72 6.44
Say 6.5
t m
t m
= =





For A B,
For A D,
Therefore, distribution factors:
For
Hydraulic Structures Structural Design of Syphon
3

3. Earth pressure
The earth pressure shall comprise of the following:
a. Dry earth pressure above saturation line (from R.L. 253.25 m to R.L. 254.00 m)
b. Saturated earth pressure (from R.L. 253.25 m to R.L. 248.45 m).
Corresponding to 30 | = ,
1 sin 1
1 sin 3
p
c
|
|

= =
+

Pressure at A = Surcharge due to dry earth+ surcharge due to saturated earth

( ) ( ) ( )
2
254 253.25 253.25 251.25 253.25 251.25
1 1
1.6 0.75 1.0 2 1 2 3.07
3 3
p p s
c c
t m
e e e = + +
= + + =

Pressure at D ( ) ( )
2
3.07 251.25 248.45 251.25 248.45
1
3.07 1 2.8 1 2.8 6.8
3
p s
c
t m
e e = + +
= + + =



4. Fixing moments
a. On span
2 2
5.62 3.3
5.1
12 12
w
AB t m

= = =
b. On span
2
6.5 3.3
5.9
12
CD t m

= =
c. On span AD

2 2
2 2
3.07 2.8 3.73 2.8
2.985
12 30
3.07 2.8 3.73 2.8
3.475
12 20
AD
DA
M t m
M t m

= + =

= + =

Hydraulic Structures Structural Design of Syphon
4

Joint C D A B
Member CD DC DA AD AB BA
D. factor 0.46 0.54 0.54 0.46
F.E.M. -5.9 +5.9 -3.475 +2.985 -5.1 +5.1
Balance -1.115 -1.31 +1.142 +0.973
C.O. -0.5575 +0.57 -0.655 +0.485
Balance -0.2622 -0.3078 +0.3537 +0.3013
C.O. -0.1311 +0.177 -0.1539 +0.151
Balance -0.081 -0.096 +0.083 +0.0708
C.O. -0.041 +0.042 -0.048 +0.035
Balance -0.019 -0.023 +0.026 +0.022
-6.630 +4.423 -4.423 +3.733 -3.733 +5.771

5. Design moments
a. Span AB
Net moments at center and face of span AB
Sagging moment at face
2
5.62 3.3 5.62 0.15
0.15 1.33
2 2
t m

= =
Fixing moment at face ( )
3.15
3.73 5.771 3.73 5.68
3.3
t m = + =
Net fixing moments at face 5.68 1.33 4.35t m = =

Sagging moment at center
2
5.62 3.3
7.65
8
t m

= =
Fixing moment at center
3.73 5.771
4.75
2
t m
+
= =
Net sagging moment at center 7.65 4.75 2.9t m = =
b. Span CD
Sagging moment at face
2
6.5 3.3 6.5 0.15
0.15 1.54
2 2
t m

= =
Fixing moment at face ( )
3.15
4.423 6.63 4.423 6.529
3.3
t m = + =
Net fixing moment at face 6.529 1.54 4.98t m = =

Hydraulic Structures Structural Design of Syphon
5

Sagging moment at center
2
6.5 3.3
8.85
8
t m

= =
Fixing moment at center
6.63 4.423
5.53
2
t m
+
= =
Net sagging moments at center 8.85 5.53 3.32t m = =
c. Span AD

Sagging moment at face:
i. Due to rectangular portion
2
3.07 2.8 3.07 0.15
0.15 0.61
2 2
t m

= =
ii. Due to triangular portion
3.73 2.8 2
2.8 2.8
2 3
3.73 2.8
3
D
D
R
R

=

Sagging moment
2
3.73 2.8 3.53 0.15
0.15 0.483
3 2
t m

= =
Total sagging moments 0.61 0.483 1.09t m = + =
Fixing moment at face ( )
2.65
3.73 4.423 3.73 4.39
2.8
t m = + =
Net fixing moment at face 4.39 1.09 3.3t m = =
Sagging moment at center
i. Due to rectangular portion
2
3.07 2.8
3.01
8
t m

= =
ii. Due to triangular portion
3.73 2.8 2.8
2.8
2 3
3.73 2.8
6
3.73 2.8 2.8 1.865 1.4 1.4
1.83
6 2 2 3
A
A
C
R
R
M t m

=

= =

Total Sagging moment at center 3.01 1.83 4.84t m = + =
Fixing moment at center
4.423 3.73
4.08
2
t m
+
= =
Net sagging moment at center 4.84 4.08 0.76t m = =


Hydraulic Structures Structural Design of Syphon
6

Span Fixing moment (-ve) at face (t.m) Sagging moment (+ve) at center (t.m)
AB 4.35 2.9
16 mm bars@ 12.5cm c/c (up) 12 mm bars@ 10 cm c/c (down)
CD 4.98 3.32
16 mm bars@ 11.25cm c/c 16 mm bars@ 16.25cm c/c
AD 3.3 0.76
16 mm bars@ 16.25cm c/c 12 mm bars@ 25cm c/c


6. Thickness of members
Maximum moment in the barrels=4.98 t.m
The minimum effective thickness (d) required for bending moment is
4.98 1000 100
23.29
100 9.18
M
d
bQ
cm
=

= =



Adopt 27.5 cm effective depth and 30 cm overall thickness for all members.
7. Reinforcement
a. Span AB and BE
At face (hogging moment, -ve steel)
2
4.35 1000 100
15.38
6
1200 27.5
7
t
A cm

= =


Provide 16 mm bars @ 12.5 cm c/c (up)
At center (sagging moment, +ve steel)
2
2.9 1000 100
10.25
6
1200 27.5
7
t
A cm

= =


Provide 12 mm bars @ 10 cm c/c (down)

b. Span CD and CF
At face
2
4.98 1000 100
17.6
6
1200 27.5
7
t
A cm

= =


Provide 16 mm bars @ 11.25 cm c/c
At center
2
3.32 1000 100
11.74
6
1200 27.5
7
t
A cm

= =


Provide 16 mm bars @ 16.25 cm c/c

c. Span AD and EF
Hydraulic Structures Structural Design of Syphon
7

At face
2
3.3 1000 100
11.7
6
1200 27.5
7
t
A cm

= =


Provide 16 mm bars @ 16.25 cm c/c
At center
2
0.764 1000 100
2.70
6
1200 27.5
7
t
A cm

= =


Provide 12 mm bars @ 25 cm c/c
Table: Cross-sectional area for steel bars of different diameters
Diameter | (mm)
Cross-sectional area
( )
2
2
4
s
A cm
t|
=
12 1.13
14 1.54
16 2.01
18 2.54