SFP-5UD/SFP-10UD (E) : Five Zone Fire Alarm Control Panel Ten Zone Fire Alarm Control Panel

These control panels provide reliable fire signaling protection for small to medium-sized commercial, industrial, and institutional buildings. The SFP-5UD is a five-zone FACP and the SFP-10UD(E) is a ten zone FACP. Both panels include built-in communicators for Central station Service and remote upload / download.

Uploaded by

Naree250
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
152 views

SFP-5UD/SFP-10UD (E) : Five Zone Fire Alarm Control Panel Ten Zone Fire Alarm Control Panel

These control panels provide reliable fire signaling protection for small to medium-sized commercial, industrial, and institutional buildings. The SFP-5UD is a five-zone FACP and the SFP-10UD(E) is a ten zone FACP. Both panels include built-in communicators for Central station Service and remote upload / download.

Uploaded by

Naree250
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

dn-60185:c 07/10/08 Page 1 of 4

SFP-5UD/SFP-10UD(E)
Five Zone Fire Alarm Control Panel
Ten Zone Fire Alarm Control Panel
Conventional Fire Alarm Control Panels
dn-60185:c
6
0
1
8
5
c
o
v
.
j
p
g
General
The SFP-5UD is a five-zone FACP (Fire Alarm Control Panel)
and the SFP-10UD(E) is a ten-zone FACP. These control pan-
els provide reliable fire signaling protection for small to
medium-sized commercial, industrial, and institutional build-
ings. Both panels include built-in communicators for Central
Station Service and remote upload/download.
Each of these FACPs is compatible with System Sensors
microprocessor-based i
3
series detectors. These conventional
smoke detectors can transmit a maintenance trouble signal to
the FACP indicating the need for cleaning and a supervisory
freeze signal when the ambient temperature falls below the
detector rating. Additionally, both the SFP-5UD and SFP-
10UD are compatible with conventional input devices such as
two- and four-wire smoke detectors, pull stations, waterflow
devices, tamper switches, and other normally-open contact
devices. Refer to the Notifier Device Compatibility Document
for a complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits),
three programmable Form-C relays (factory programmed for
Alarm, Trouble, and Supervisory) and 24 VDC special applica-
tion resettable and nonresettable power outputs. The FACPs
supervise all wiring, AC voltage, battery level and telephone
line integrity.
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicating LED, sound the
piezo sounder at the FACP, activate the communicator and
FACP alarm relay, and operate an optional module used to
notify a remote station or initiate an auxiliary control function.
NOTE: The SFP-10UDE offers the same features as the SFP-
10UD but allows connection to 240 VAC. Unless otherwise speci-
fied, the information in this data sheet applies to both the 120 VAC
and the 240 VAC versions of these panels.
Features
Listed to UL Standard 864, 9th edition.
Built-in DACT (Digital Alarm Communicator/Transmitter).
Style B (Class B) IDC (Initiating Device Circuit)
SFP-5UD - five IDCs.
SFP-10UD - ten IDCs.
Style Y (Class B) NAC (Notification Appliance Circuit) - spe-
cial application power
SFP-5UD - four NACs.
SFP-10UD - four NACs.
Notification Appliances may be programmed as
Silence Inhibit.
Auto-Silence.
Strobe Synchronization for System Sensor, Wheelock,
Gentex, Faraday, or Amseco devices.
Selective Silence (horn-strobe mute).
Temporal or Steady Signal.
Silenceable or Nonsilenceable.
Optional N-CAC-5X Style Z (Class A) Converter Module for
NACs and IDCs (2 required for SFP-10UD).
Form-C Relays for Alarm, Trouble and Supervisory - Con-
tact Ratings 2.0 A@ 30 VDC or 30 VAC (resistive).
3.0 A total system current for SFP-5UD.
7.0 A total system current for SFP-10UD.
Optional Dress Panel DP-51050 (red)
Optional Dress Panel DP-51050B (black).
Optional Trim Ring TR-CE/-B for semi-flush mounting.
24 volt operation.
Low AC voltage sense.
Alarm Verification.
PAS (Positive Alarm Sequence).
Automatic battery trickle charger.
Up to eight ANN-BUS annunciators:
Optional 8 zone Relay Module N-ANN-RLY.
Optional LED Annunciator Module N-ANN-LED,
Optional Remote Annunciator N-ANN-80.
Optional Remote Printer Gateway N-ANN-S/PG.
Optional LED Annunciator Driver N-ANN-I/O.
Optional 4XTM module (conventional reverse polarity/city
box transmitter).
PROGRAMMING AND SOFTWARE:
Can be programmed at the panel with no special software
or additional equipment.
Programmable Make/Break Ratio.
Upload/Download (local or remote) of program and data via
integral DACT.
USER INTERFACE:
Built-in DACT (Digital Alarm Communicator/Transmitter).
Integral 80-character LCD display with backlighting and
keypad.
Real-time clock/calendar with automatic daylight savings
adjustments.
ANN-BUS for connection to remote annunciators.
Page 2 of 4 dn-60185:c 07/10/08
Audible or silent walk test capabilities.
Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
FIRE ALARM (red)
SUPERVISORY (yellow)
TROUBLE (yellow)
AC POWER (green)
ALARM SILENCED (yellow)
CONTROL BUTTONS
ACKNOWLEDGE
ALARM SILENCE
SYSTEM RESET (lamp test)
DRILL
Terminal Blocks
AC Power TB1:
SFP-5UD (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.
SFP-10UD (FLPS-7 Power Supply): 120 VAC, 50/60 Hz,
3.8 A.
SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size: minimum 14 AWG (2.00 mm) with 600 V insulation.
Supervised, nonpower-limited.
Battery (sealed lead acid only) J12:
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
Maximum Charger Capacity: 18 AH battery for SFP-5UD,
and 26 AH battery for SFP-10UD(E). [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or NFS-
LBB.]
Minimum Battery Size: 7 AH.
Cabinet Measurements
5
2
4
1
6
c
a
b
.
w
m
f
dn-60185:c 07/10/08 Page 3 of 4
Initiating Device Circuits TB4 (and TB 6 on SFP-10UD
only):
Alarm Zones 1 - 5 on TB 4 (SFP-5UD and SFP-10UD).
Alarm Zones 6 - 10 on TB6 (SFP-10UD only).
Supervised and power-limited circuitry.
Operation: All zones Style B (Class B).
Normal Operating Voltage: Nominal 20 VDC.
Alarm Current: 15 mA minimum.
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms.
End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL-
listed).
Standby Current: 2 mA.
Refer to the Notifier Device Compatibility Document for listed
compatible devices.
Notification Appliance Circuits TB5 (and TB 7 on SFP-
10UD only):
Four NACs
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 3.0 A for SFP-5UD, 2.5 A
maximum per NAC; 7.0 A for SFP-10UD(E), 3.0 A maxi-
mum per NAC.
End-of-Line Resistor: 4.7K ohm, 1/2 watt (Part #71252)
Max. Wiring Voltage Drop: 2 VDC
Refer to the Notifier Device Compatibility Document for com-
patible listed devices
Form C Relays TB8:
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble
Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Special Application Resettable Power TB9:
Jumper selectable by JP31 for resettable or nonresettable
power.
Operating voltage: 24 VDC nominal.
Maximum available current: 500 mA - appropriate for pow-
ering four-wire smoke detectors.
Power-limited circuit.
Refer to the Notifier Device Compatibility Document for listed
compatible devices.
Remote Sync Output - TB2: Remote power supply synchro-
nization output, only required for the SFP-5UD. 24 VDC nomi-
nal special application power. Maximum current is 40 mA.
End-of-Line Resistor: 4.7K ohm. Supervised and power-lim-
ited circuit.
Ordering Information
SFP-5UD: Five-zone, 24-volt Fire Alarm Control Panel
(includes black backbox, FLPS-3 power supply, technical man-
ual, and a frame & post operating instruction sheet).
SFP-5UDR: Same as above in a red backbox.
SFP-10UD: Ten-zone, 24-volt Fire Alarm Control Panel
(includes black backbox, FLPS-7 power supply, technical man-
ual, and a frame & post operating instruction sheet).
SFP-10UDE: Same as above with 220 VAC FLPS-7.
SFP-10UDR: Same as SFP-10UD in a red backbox.
OPTIONAL MODULES
N-CAC-5X: Optional (Class A) Converter Module. Converts
Style B (Class B) Initiating Device Circuits to Style D (Class A);
and Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). Connects to J2 on the SFP-5UD and SFP-10UD
main circuit board and to J7 on the SFP-10UD.
NOTE: Two Class A Converter Modules are required for the ten-
zone panel.
4XTM: Transmitter module. Provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. Includes a disable switch and disable trouble
LED. A module jumper option allows the reverse polarity circuit
to open with a system trouble condition if no alarm conditions
exists. Mounts to the main circuit board connectors J4 and J5.
COMPATIBLE ANNUNCIATORS
N-ANN-80: Remote LCD Annunciator. Mimics the information
displayed on the FACPs LCD. Red. (A white version is also
available: N-ANN-80-W.)
N-ANN-LED: Mounts in the DP-51050(B) dress panel and pro-
vides three LEDs for each zone: Alarm, Trouble, and Supervi-
sory.
N-ANN-RLY: Relay module. Mounts inside the cabinet. Pro-
vides ten Form C relays.
N-ANN-S/PG: Serial/parallel printer gateway. Provides a con-
nection for a serial or parallel printer.
N-ANN-I/O: Driver module. Provides connections to a user-
supplied graphic annunciator.
ACCESSORIES
DP-51050: Optional dress panel. Restricts access to the sys-
tem wiring while allowing access to the membrane switch
panel. Red.
DP-51050B: Same as DP-51050 except black.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
NFS-LBB: Battery backbox, holds up to two 55 AH batteries.
Black.
NFS-LBBR: Same as above in red.
TR-CE-B: Optional black trim-ring for semi-flush mounted cab-
inets.
TR-CE: Same as above in red.
PRN-6: UL listed printer.
Page 4 of 4 dn-60185:c 07/10/08
System Capacity
Annunciators ...................................................................... 8
Electrical Specifications
SFP-5UD (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.0 A
SFP-10UD (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.8 A
SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50/60 HZ,
2.2 A
Wire size: minimum 14 AWG (2.0 mm
2
) with 600 V insula-
tion, supervised, nonpower-limited
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring
(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Dimensions:
20.00" (50.80 cm.) high
22.5" (57.15 cm.) wide
8.5" (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0
49C/32 120F and at a relative humidity 93% 2% RH
(noncondensing) at 32C 2C (90F 3F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 27C/60 80F.
Agency Listings and Approvals
The listings and approvals below apply to the basic SFP-5UD
and SFP-10UD control panels. In some cases, certain mod-
ules or applications may not be listed by certain approval
agencies, or listing may be in process. Consult factory for lat-
est listing status.
UL Listed: File S635
FM Approved
CSFM: 7165-0028:246
MEA: MEA: 333-07-E
NFPA Standards
The SFP-5UD/SFP-10UD(E) complies with the following NFPA
72 Fire Alarm Systems requirements:
LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTM).
REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTM is required.)
PROPRIETARY (Automatic, Manual and Waterflow).
CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
NOTIFIER and System Sensor are registered trademarks of Honeywell
International Inc.
2008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

Made in the U.S. A.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
SYSTEM SPECIFICATIONS