MCB/MCCB/ Elcb /rcbo/ RCCB
MCB/MCCB/ Elcb /rcbo/ RCCB
HOME ABSTRACT ELECTRICAL NOTES ELECTRICAL Q&A ELECTRICAL TOOLS EXCEL TOOLS POSTS COMMENTS
MCB/MCCB/ELCB/RCCB
MARCH 20, 2011 54 COMMENTS
A 300/500 mA RCCB may be used where only fire protection is required. eg., on lighting circuits, where the risk of electric shock is small RCDs are an extremely effective form of shock protection
Limitation of RCCB:
Standard electromechanical RCCBs are designed to operate on normal supply waveforms and cannot be guaranteed to operate where none standard waveforms are generated by loads. The most common is the half wave rectified waveform sometimes called pulsating dc generated by speed control devices, semi conductors, computers and even dimmers.
Specially modified RCCBs are available which will operate on normal ac and pulsating dc. RCDs dont offer protection against current overloads: RCDs detect an imbalance in the live and neutral currents. A current overload, however large, cannot be detected. It is a frequent cause of problems with novices to replace an MCB in a fuse box with an RCD. This may be done in an attempt to increase shock protection. If a live-neutral fault occurs (a short circuit, or an overload), the RCD wont trip, and may be damaged. In practice, the main MCB for the premises will probably trip, or the service fuse, so the situation is unlikely to lead to catastrophe; but it may be inconvenient.
It is now possible to get an MCB and and RCD in a single unit, called an RCBO (see below). Replacing an MCB with an RCBO of the same rating is generally safe. Nuisance tripping of RCCB: Sudden changes in electrical load can cause a small, brief current flow to earth, especially in old appliances. RCDs are very sensitive and operate very quickly; they may well trip when the motor of an old freezer switches off. Some equipment is notoriously `leaky, that is, generate a small, constant current flow to earth. Some types of computer equipment, and large television sets, are widely reported to cause problems.
RCD will not protect against a socket outlet being wired with its live and neutral terminals the wrong way round. RCD will not protect against the overheating that results when conductors are not properly screwed into their terminals. RCD will not protect against live-neutral shocks, because the current in the live and neutral is balanced. So if you touch live and neutral conductors at the same time (e.g., both terminals of a light fitting), you may still get a nasty shock.
Phase (line), Neutral and Earth wire connected through ELCB. ELCB is working based on Earth leakage current. Operating Time of ELCB: The safest limit of Current which Human Body can withstand is 30ma sec. Suppose Human Body Resistance is 500 and Voltage to ground is 230 Volt. The Body current will be 500/230=460mA. Hence ELCB must be operated in 30maSec/460mA = 0.65msec
Finally both are working for same, but the thing is connectivity is difference. RCD does not necessarily require an earth connection itself (it monitors only the live and neutral).In addition it detects current flows to earth even in equipment without an earth of its own. This means that an RCD will continue to give shock protection in equipment that has a faulty earth. It is these properties that have made the RCD more popular than its rivals. For example, earth-leakage circuit breakers (ELCBs) were widely used about ten years ago. These devices measured the voltage on the earth conductor; if this voltage was not zero this indicated a current leakage to earth. The problem is that ELCBs need a sound earth connection, as does the equipment it protects. As a result, the use of ELCBs is no longer recommended.
MCB Selection:
The first characteristic is the overload which is intended to prevent the accidental overloading of the cable in a no fault situation. The speed of the MCB tripping will vary with the degree of the overload. This is usually achieved by the use of a thermal device in the MCB.
The second characteristic is the magnetic fault protection, which is intended to operate when the fault reaches a predetermined level and to trip the MCB within one tenth of a second. The level of this magnetic trip gives the MCB its type characteristic as follows:
Tripping Current 3 To 5 time full load current 5 To 10 times full load current 10 To 20 times full load current
The third characteristic is the short circuit protection, which is intended to protect against heavy faults maybe in thousands of amps caused by short circuit faults. The capability of the MCB to operate under these conditions gives its short circuit rating in Kilo amps (KA). In general for consumer units a 6KA fault level is adequate whereas for industrial boards 10KA fault capabilities or above may be required.
If the fuse is marked `30 amps, but it will actually stand 40 amps for over an hour, how can we justify calling it a `30 amp fuse? The answer is that the overload characteristics of fuses are designed to match the properties of modern cables. For example, a modern PVC-insulated cable will stand a 50% overload for an hour, so it seems reasonable that the fuse should as well.
Supplier provides a separate earth connection, usually direct from the distribution station and via the metal sheath of the supply cable.
Supplier provides a combined earth/neutral connection; your main earth terminal is connected to their neutral Supplier provides no earth; you have an earth spike near your premises.
About these ads