The document discusses different methods for controlling the level in a boiler drum, including single, two, and three element controls. The three element control is best for systems with multiple boilers or fluctuating feedwater pressure/flow. Enhanced three element control provides tighter control and can fallback to simpler methods if inputs fail.

Uploaded by

sekhar_ntpc
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
242 views

Boiler Drum Level Control

The document discusses different methods for controlling the level in a boiler drum, including single, two, and three element controls. The three element control is best for systems with multiple boilers or fluctuating feedwater pressure/flow. Enhanced three element control provides tighter control and can fallback to simpler methods if inputs fail.

Uploaded by

sekhar_ntpc
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

12/6/13

Boiler Drum Level Control

Contact Us

Search

Products Downloads Industry Systems

Boiler Drum Level Control


The purpose of the drum level controller is to bring the drum up to level at boiler start-up and maintain the level at constant steam load. A dramatic decrease in this level may uncover boiler tubes, allowing them to become overheated and damaged. An increase in this level may interfere with the process of separating moisture from steam within the drum, thus reducing boiler efficiency and carrying moisture into the process or turbine.

The functions of this control module can be broken down into the following

Operator adjustment of the setpoint for drum level Compensation for the shrink & swell effects Automatic control of drum level Manual control of the feedwater valve Bumpless transfer between auto and manual modes Indication of drum level and steam flow
www.eurotherm.com/industries/boiler/boiler-drum-level-control/ 1/9

12/6/13

Boiler Drum Level Control

Indication of feedwater valve position and feedwater flow Absolute/deviation alarms for drum level

The three main options available for drum level control are

Single element drum level control

The simplest but least effective form of drum level control.

Figure 1 Single-element drum level control

This consists of a proportional signal or process variable (PV) coming from the drum level transmitter. This signal is compared to a setpoint and the difference is a deviation value.

www.eurotherm.com/industries/boiler/boiler-drum-level-control/

2/9

12/6/13

Boiler Drum Level Control

This signal is acted upon by the controller which generates corrective action in the form of a proportional output. The output is then passed to the boiler feedwater valve, which then adjusts the level of feedwater flow into the boiler drum.

Notes:

Only one analogue input and one analogue output required Can only be applied to single boiler / single feedpump configurations with relatively stable loads since there is no relationship between drum level and steam- or feedwater flow Possible inadequate control option because of the swell effect

Two element drum level control

The two-element drum level controller can best be applied to a single drum boiler where the feedwater is at a constant pressure.

www.eurotherm.com/industries/boiler/boiler-drum-level-control/

3/9

12/6/13

Boiler Drum Level Control

Figure 2 Two-element drum level control

The two elements are made up of the following

Level Element: a proportional signal or process variable (PV) coming from the drum level transmitter. This signal is compared to a setpoint and the resultant is a deviation value. This signal is acted upon by the controller which generates corrective action in the form of a proportional value.

Steam Flow Element: a mass flow rate signal (corrected for density) is used to control the feedwater flow, giving immediate corrections to feedwater demand in response to load changes. Any imbalance between steam mass flow out and feedwater mass flow into the drum is corrected by the level controller. This imbalance can arise from

Blowdown variations due to changes in dissolved solids Variations in feedwater supply pressure Leaks in the steam circuits
www.eurotherm.com/industries/boiler/boiler-drum-level-control/ 4/9

12/6/13

Boiler Drum Level Control

Notes:

Tighter control of drum level than with only one element Steam flow acts as feed forward signal to allow faster level adjustments Can best be applied to single boiler / single feedpump configurations with a constant feedwater pressure

Three-element drum level control

The three-element drum level control is ideally suited where a boiler plant consists of multiple boilers and multiple feedwater pumps or where the feedwater has variations in pressure or flow.

www.eurotherm.com/industries/boiler/boiler-drum-level-control/

5/9

12/6/13

Boiler Drum Level Control

Figure 3 Three-element drum level control

The three-elements are made up of the following

Level Element & Steam Flow Element: corrects for unmeasured disturbances within the system such as

Boiler blowdown Boiler and superheater tube leaks

Feedwater Flow Element: responds rapidly to variations in feedwater demand, either from the

Steam flow rate feedforward signal Feedwater pressure or flow fluctuations

In order to achieve optimum control, both steam and feedwater flow values should be corrected for density.
www.eurotherm.com/industries/boiler/boiler-drum-level-control/ 6/9

Ask a Question

12/6/13

Boiler Drum Level Control

Notes:

The three-element system provides tighter control for drum level with fluctuating steam load. Ideal where a system suffers from fluctuating feedwater pressure or flow More sophisticated level of control required Additional input for feedwater flow required

Enhanced three element drum level control

The enhanced three-element drum level control module incorporates the standard three element level components with the following improvements

The three-element mode is used during high steam demand. The twoelement mode is used if the steam flow measurement fails and the module falls
www.eurotherm.com/industries/boiler/boiler-drum-level-control/ 7/9

12/6/13

Boiler Drum Level Control

back to single element level control if the feedwater flow measurement should fail or if there is a low steam demand. The drum level can be derived from up to three independent transmitters and is density compensated for pressure within the boiler drum.

Notes:

Tighter control through a choice of control schemes. Drum level maintained on failure of steam or feedwater flow measurements This module introduces an additional level control loop Boiler drum level control

www.eurotherm.com/industries/boiler/boiler-drum-level-control/

8/9

12/6/13

Boiler Drum Level Control

Products Temperature and Process Control Graphic and Chart Recording Solid State Relays and Power Cotrol Plasic Machine Control System Alarm and Indication products I/O Signal Conditioners Programmable Automation Control System

Support Technical Support Online Tools Repairs Training User Manuals Video Tutorials Software

Contact us USA Headquarters Find a Local Distributor Eurotherm Worldwide Our values Careers

New Video

Latest blog post

Eurotherm Insider

Community

Invensys Eurotherm, 44621 Guilford Drive, Suite 100, Ashburn, Virginia 20147. Tel 703-724-7300
2013 Eurotherm | General Terms & Conditions | Warranty | Cancellation | Legal Information | Privacy Policy | Trading Disclosure | Site Map

www.eurotherm.com/industries/boiler/boiler-drum-level-control/

9/9