0% found this document useful (0 votes)
962 views5 pages

Fire Sprinkler System Specifications

This document provides product information on the Model A PS015/PS016/PS017/PS018 glass bulb sprinklers. It includes details on the design, operation, coverage areas, technical specifications, ratings, dimensions, discharge curves and distribution patterns of the sprinklers. The sprinklers use a frangible glass bulb containing heat-responsive liquid that breaks at a specific temperature, clearing the waterway. They are available in various temperature ratings and finishes to meet design requirements.

Uploaded by

jonnyh85
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
962 views5 pages

Fire Sprinkler System Specifications

This document provides product information on the Model A PS015/PS016/PS017/PS018 glass bulb sprinklers. It includes details on the design, operation, coverage areas, technical specifications, ratings, dimensions, discharge curves and distribution patterns of the sprinklers. The sprinklers use a frangible glass bulb containing heat-responsive liquid that breaks at a specific temperature, clearing the waterway. They are available in various temperature ratings and finishes to meet design requirements.

Uploaded by

jonnyh85
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

-1-

PRODUCT DESCRIPTION
The Model A PS015/PS016/PS017/PS018 (Glass Bulb Type)Standard Orifice Standard Upright, Pendent and Recessed Pendent Standard and Quick Response. The Model A Pendent Sprinkler Identification Number (SIN).PS016(standard) PS018(quick) Recessed Pendent. The Model A Upright Sprinkler Identification Number (SIN) PS015(standard) PS017(quick). The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings (see chart on page 2) and finishes to meet many design requirements. The recessed pendent should be utilized with a Model A recessed escutcheon which provides up of adjustments. All Protector Sprinklers are manufactured using the time proven Belleville seal used exclusively by all major manufactures to ensure long life and safe operation.

Sprinkler Operation
The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire, the ambient temperature rises causing the liquid in the bulb to expand. When the ambient temperature reaches the rated temperature of the sprinkler, the bulb shatters. As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire.

Maximum Coverage
Standard spray coverage is up to:Light Hazard = 230 square feet(21.2 sq.m); Ordinary Hazard = 153 square feet(13.8 sq.m)per NFPA 13. see page 4 for distribution patterns.

PS015

PS016

PS017

PS018

-2-

TECHNICAL SPECIFICATION
SINStandard PS015PS016 (bulb 5mm),Quick Response PS017PS018 (bulb 3mm) StyleUpright Sprinkler PS015PS017Pendent Sprinkler PS016PS018 K-Factor8.0Imp.(115S.I) Response Time Index(RTI)Standard 50Quick Response 30 Norminal Thread SizeNPT(20mm) Max. Working Pressure175PSI(1200kPa) Factory Hydrostatic Test100%@500PSI(3450 kPa) Min. Operation Pressure7 PSI(48 kPa)

RATINGS
SPRINKLRE TEMPERATURE CLASSIFICATION NORMINAL SPRINKLER TEMPERATURE RATING N.F.P.A MAXIMUM AMBIENT (CEILING) TEMP.(ALLOWED) GLASS BULB COLOR

Ordinary Intermediate Intermediate

155/68 175/79 200/93

100/38 150/65 150/65

Red Yellow Green

DIMENSIONS

-3-

DISCHARGE CURVE

-4-

DISTRIBUTION PATTERNS
K8.0 PENDENT SPRINKLER DISTRIBUTION PATTERNS - TRAJECTORY

K8.0 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS - TRAJECTORY