PAS3 Instruction Manual
PAS3 Instruction Manual
Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone : +81-42-585-6201, 6202 INP-TN1PAS3-E Fax : +81-42-585-6187, 6189 http://www.fic-net.co.jp
Thank you for your purchasing Fuji DIGITAL THERMOSTAT. Please check that the product is exactly the one you ordered and use it according to the following instructions. (Please refer to a separate operation manual for details.) Dealers are cordially requested to ensure the delivery of this Instruction Manual to hands of the end-users. NOTICE The contents of this document may be changed in the future without prior notice. We paid the utmost care for the accuracy of the contents. However, we are not liable for direct and indirect damages resulting from incorrect descriptions, omission of information, and use of information in this document.
CONTENTS
Safety Precautions ............................................... 2 For normal usage ................................................. 7 1. Installation/mounting ...................................... 8 2. Wiring ............................................................. 9 3. Usage ............................................................. 10 4. Operation ....................................................... 11 5. Display shifting method .................................. 6. Functions ....................................................... 7. List of parameters .......................................... 8. Alarm function ................................................ 9. Error indications ............................................. Specification ......................................................... PAS3 Model Code ................................................ 12 13 15 17 19 19 19
Digital thermostat mian unit 1 unit Instruction manual 1 copy Mounting bracket 1 pce. Watertight packing 1 pce. Thermister sensor (only for the type that the input signal is thermistor) Note: The provided thermistor sensor is the sensor dedicated to this equipment.
Safety Precautions
Before using this product, the user is requested to read the following precautions carefully to ensure the safety. Safety precautions must be taken by every user to prevent accidents. The safety requirements are classified into warning and caution according to the following interpretations:
Warning
Suggesting that the user's mishandling can result in personal death or serious injury. Suggesting that the user's mishandling can result in personal injury or damage to the property.
Caution
1.
Warning
This product designed to be installed at the conditions shown in the right table. If there is a danger of a serious accident resulting from a failure or a defect in this unit, provide the unit with an appropriate external protective circuit to prevent an accident. The unit is supplied without a power switch and fuses. Make wiring so that the fuse is placed between the main power supply switch and this product. (Main power supply: 2 pole breaker, fuse rating: 250V, 1A) When wiring the power supply terminal, use vinyl insulated 600 volt cable or equivalent. To avoid the damage and failure of this product, supply the power voltage fitting to the rating. To avoid an electric shock and this product failure, do not turn ON the power before all wiring is completed. Be sure to check that the distance is kept to avoid electric shock or firing before turning the power ON. Keep away from terminals while the circuit is energized in order to avoid an electric shock and a malfunction. Never attempt to disassemble, fabricate, modify, or repair this unit because tampering with the unit may result in a malfunction, electric shock, or a fire.
2.
Caution
Installation
Packing Unit Unit
Packing Packing
Front
Case
Panel
Panel
Mounting braclet
Screw
Figure 1
Figure 2
Figure 3
(Caution) Dont block the openings around this product, or radiation effect will be reduced. Dont block the ventilation openings at the top of the terminal block.
4
Standard : Vertical mounting, flush on the panel. (This product is horizontal.) When mounting this product on tilted surface, the maximum tilt angle is 30 (degree) from vertical.
Z-Trap connection
2.5 Others
Do not use organic solvents such as alcohol and benzine to wipe this controller. Use a neutral detergent for wiping this product. Do not bring any mobile phone close to the main unit (50 cm). Malfunction will occur. Noise may be produced if this equipment is brought close to a radio. Use this equipment as fully spaced apart from radios. Do not push the display unit (LCD) on the front face of this equipment with force. Observation of the display (LCD) will become hard. This equipment issues an LCD as the front display. There are cases where the display can be hardly observed at a slant because of the characteristics of LCD. Observation of the display (LCD) will become hard when the ambient temperature drops to a level close to 0C.
6
<Description>
Confirming that the delivered product is equal to the ordered one. Outline dimensions Panel cutout dimensions Mounting method on the panel Terminal connection diagram
<Remarks>
To start the operation, wait for about 15 minutes after the power-on for warm up.
Installation/mounting
Watertight packing 1 48
PV SET1 SET2
24
45.0
+0.3 0
22.2
50 MAX.
Number of units
57 MIN.
22.2
+0.3 0
2 93
3 141
4 189
22 5 237
ALM1 ALM2
34.2
6 285
Wiring
10 11
12 13
14
15 16
17
18
Thermocouple
1 2 3
Power supply
AC100-240V
8 9
Note 1) Check the power supply voltage before installation. Note 2) Tighten the terminal screw securely with fastening torque of 0.4Nm.
PV
r t
!0
Display/Indication Name
q Process value (PV) indicator w Alarm set value 1 (SET 1) e Alarm set value 2 (SET 2) r Alarm 1 (ALM1) indicator t Alarm 2 (ALM2) indicator y Display of process value (PV)/
Function
The lamp is lit while a process value (PV) is displayed. The lamp is lit while an alarm set value 1 is displayed. The lamp is lit while an alarm set value 2 is displayed. The lamp is lit when the alarm 1 occured. The lamp is lit when the alarm 2 occured. 1) Process value, alarm set value 1 or alarm set value 2 is displayed in the Operation mode (level 1). 2) Parameter name or set value is displayed at the time of setup of various parameters (level 2, 3, 4). 3) Various warnings are displayed on occurrence of errors. See 9. Error indications for the display on occurrence of errors. Note: Process value and alarm set value are of 1C units. Lit only in the running state (level 1). Note) Alarm output 2 is optional.
alarm set value 1 (SET1)/ alarm set value 2 (SET2)/ parameter name or parameter set value
u Unit display
Function
Used for switching of display between process value and alarm set value, level move, switching to parameter setting mode and for data registration. Used for parameter shifting (returning) or data changing (increasing). The numerical value is increased by pressing the key once. The numerical value keeps on increasing by pressing the key continuously. Used for parameter shifting (to next) or data changing (decreasing). The numerical value is decreased by pressing the key once. The numerical value keeps on decreasing by pressing the key continuously.
!0 Down key
10
Operation
Set value display
3)
SEL
4) 3)
<Parameter setting procedure> 1) Select a parameter you want to set by pressing the 2) Press the
SEL
or
key.
key to display the parameter set value. or key, to change the parameter set value. key for registration.
3) Pressing the
SEL
<Method for move of level 1> 1) To move to the running state (level 1) from the parameter setting state (level 2, 3, 4), press the SEL key for 3 seconds in the parameter name displayed state.
Caution
1) When a period of 3 seconds has elapsed since the parameter set value was changed, the data is registered even if the SEL key is not pressed.
11
Caution 1) Select the level to which move is to occur by the length of time during which the SEL key is pressed.
2) Setup of the alarm set value cannot be changed at level 1. Change the alarm set value by parameters ST1, ST2 of level 2. 3) The display returns to the running state (level 1/PV display) if the non-operated state continues for 30 seconds. Press SEL for about 3 second. Then, returns to the process value (PV) indication. Press SEL for about 3 second. Then, returns to the process value (PV) indication. Press SEL for about 3 second. Then, returns to the process value (PV) indication.
12
Functions
Caution Turn OFF/ON the power for the main unit once after the alarm type was changed.
(How to read activation diagram) area: Range in which "ALM1 or ALM2" indicator is displayed on the LCD on the front face area: Range in which the alarm relay is energized point: Alarm set value The horizontal represents PV.
13
14
7
Level Level 2
List of parameters
Parameter indication ST1 ST2 Parameter name Alarm set value 1 setup Alarm set value 2 setup Input type Range lower limit setup Range upper limit setup Alarm type 1 Alarm type 2 Alarm 1 hysteresis width Alarm 2 hysteresis width Alarm 1 ON delay time Alarm 2 ON delay time Burn-out direction Function Set the alarm 1 activation value. It may be set within the input range. Set the alarm 2 activation value. It may be set within the input range. Selection of input type Setup of lower limit of the input range (set range: 0-1999) Setup of upper limit of the input range (set range: 0-1999) Select the type of alarm activation. (set range: 0-8) Set the ON/OFF hysteresis width of the alarm output. (set range: 0-110%FS of the input range) Set ON delay of the alarm output. (set range: 0-120 seconds) Set the swinging direction at the time of burn-out. (set range: upper limit = H, lower limit = L) Setup of power ON delay time power ON delay: Delay time until output inhibition is canceled after power ON (set range: 0-120 seconds) Select whether parameter setup change is permitted or not. LoC = 0: Setup change is permitted for all parameters. LoC = 1: No setup change is permitted for all parameters. LoC = 2: Alarm set value 1 (ST1) and alarm set value 2 (ST2) only may be set. Set the time constant. (set range: 0-90 seconds) Shift the display of the process value (PV). (set range: -10-10%FS of the input range) Shift the input ZERO side. (set range: -50-50%FS of the input range) Shift the input SPAN side. (set range: -50-50%FS of the input range) Default Remarks setting Note1 100% Table2 0% 3 0 1200 1 2 1 1 0 0 H Table1 Table1 Note2 Note2 Note1 Table2
Level 3
Pn2 PSL PSU PA1 PA2 HY1 HY2 Pd1 Pd2 brn
oPd
LoC
Setup lock
Level 4
Input filter time constant PV offset User ZERO adjustment User SPAN adjustment
15
Caution 1) If the unit of setup of a parameter is engineering value or deviated engineering value, the value of such a parameter changes accompanying change to PSL and PSU. (Indicated by .) * Values of input range 100% = PSU, input range 0% = PSL 50 2) FS (full scale) means the value of PSU - PSL. (Example: 50% FS = (1200 0) , 100 when PSL = 0 and PSU = 1200)
3) There are parameters that are not displayed depending on the type. (Indicated by 4) The accuracy of alarm delay time and of power ON delay time is less than 1 second. 5) A difference of 1C may arise between the indication and the alarm output depending on the range setup. (Example: If the alarm set value is 200C, an alarm occurs when the indication is 200C in some cases, but an alarm occurs when the indication is 201C in other cases.) 6) There are cases where over-range (UUU) or under-range (LLL) display is not made, if a large value is set as a PV offset, user zero or user span. Be careful. .)
16
Alarm function
1) Kinds of alarm Absolute value upper limit alarm or absolute lower limit alarm is available. (For details, see Table 1 Alarm action type codes.)
ON delay function
ON
Energizing/de-energizing function Alarm judgement Relay output Without De-energizing function With De-energing function
ON OFF ON OFF ON OFF
17
2) Function of alarm
Caution Detail description about functions of alarm of Digital Thermostat is prepared. Please inquire us when you use this function. No. Function name Hysteresis function Alarm ON delay function Energize/ non-energize function Function Activation dead zone (hysteresis) may be set at alarm activation. The alarm is ON when the ON delay set time has elapsed after the alarm ON conditions were satisfied. Relay output energize or non-energize can be selected on occurrence of alarm. (See [Table 1] Alarm activation type codes.) Parameters to set
Alarm1 : Alarm2 : Alarm1 : Alarm2 : Alarm1 : Alarm2 :
Power ON Alarm judgment is not made during the power ON delay time after delay function power ON. (This equipment will not issue an alarm even if the alarming state arises during the power ON delay time.)
Point
What is alarm with hold? The alarm is not turned ON immediately even when the mesauredvalue is in the alarm band. It turns ON when it goes out the alarm band and enters again. Output band of lower limit alarm
PV (Process value)
Power ON
Power OFF on
off off
No output is produced while the power is OFF, even if the non-energize function is ON. (It is OFF.) The HOLD function is also value while the PV value is located in the hysteresis area at the time of power ON. Before HOLD is canceled, HOLD is canceled immediate upon entry to the alarm OFF area. After HOLD was canceled, however, ON delay is applied upon entry to the alarm ON area. Alarm delay is also applied on occurrence of an alarm due to burn-out.
18
Error indications
Error indications
This product has a display function to indicate several types of error code shown below. If any of the error codes is displayed, please eliminate the cause of error immediately. After the cause is eliminated, turn off the power once, and then re-start this product.
Error code
Possible cause
Alarm output
<Case of upper limit alarm setup> q Thermocouple burnt out. q When burn-out direction (brn) is set at lower w PV value exceeds the range upper limit (L) .... OFF limit by 5% FS. w When burn-out direction (brn) is set at upper limit (H) ..... ON <Case of lower limit alarm setup> q When burn-out direction (brn) is set at lower limit (L) ...... ON w When burn-out direction (brn) is set at upper limit (H) ... OFF OFF
q PV value is below the range lower limit by 5%FS. w Thermistor sensor burnt out.
Specification
Power voltage: Power consumption: Alarm output (Max. 2 points): Operating ambient temperature: Preservation temperature: Thermistor sensor: 100 (-15%) to 240 (+10%), 50/60Hz 3VA or less (100V AC), 6VA or less (220V AC) Relay contact (SPST contact) 220V AC / 30V DC 2A (resistive load) 0 to 50C, 90%RH or less (no condensation) -20 to 60C Allowable deviation/ 2C or less, constant value B/3390K1%, resistance/6k (0C)
Thermistor
0 to 100C
19