Lightning Protection Calculation
Lightning Protection Calculation
ANNUAL THREAT OF OCCURANCE, FROM NFPA 780 2011 APPENDIX L6.6.1 DIRECT STRIKES TO STRUCTURE (SECTION L.6.6.1.1) = USER INPUT REQUIRED
10/15/2012
Figure L.4.1(a) Calculation of the equivalent collective area for a rectangular structure.
Nd
0.0037
yearly average flash density in the region where structure is located lighting ground flash density in flashes/km2/year (See Figure L.2) environmental coefficient (see Table L.4.2) equivalent collection area of structure (m2) (choose from below)
Ng
1.0
C1
0.25
Figure L.4.1(b) Calculation of the equivalent collective area for a structure where a prominent part encompasses all portions of the lower part of the structure.
Ae
14702.42
STRUCTURE COLLECTIVE AREA CALCULATION (SECTION L.4) Length (L) Width (W) Height (H) Figure H.4.2(a) Results Figure H.4.2(b) Results 200 ft 100 ft 45 ft
2 5319.2 m 2 14702.4 m
1 of 14
10/15/2012
NM
0.0573
annual threat of occurrence due to strikes near structure (min of 0) collection area of flashes near structure (m2)
Am
243815.4
STRIKES TO AN ADJACENT BUILDING (SECTION L.6.6.1.4) ADJ. BLDG. COLLECTIVE AREA CALCULATION Nda = 0.0059 annual threat of occurrence due to strikes near structure lighting ground flash density in flashes/km2/year (See Figure L.2) environmental coefficient of adj. bldg. (see Table L.4.2) correction factor for presence of an HV/LV transformer located b/t strike point and structure (0.2 if one present, otherwise 1.0) equivalent collection area of adj. bldg. (m2) (choose from below) Length (L) Width (W) Height (H) 300 ft 200 ft 45 ft
2 5319.2 m 2 23435.3 m
Ng
1.0
C1
0.25
Ct
1.0
Ae
23435.3
2 of 14
10/15/2012
NL
0.02236
annual threat of occurrence due to strikes near structure lighting ground flash density in flashes/km2/year (See Figure L.2) environmental coefficient of incoming service (see Table L.4.2) correction factor for presence of an HV/LV transformer located b/t strike point and structure (0.2 if one present, otherwise 1.0)
Ng
1.0
C1
1.0
Ct
1.0
SERVICE COLLECTIVE AREA CALCULATION Hc lc Ha Hb r 0m 1000 m 0m 0m 500 Wm Aerial 0.0 m2 1000000.0 m2 Buried 22360.7 m2 559017.0 m2
Al
22360.7
collection area of flashes striking the service (m2) (see Table 6.7.1)
Al Ai
3 of 14
10/15/2012
NI
0.2795
annual threat of occurrence due to flashes near a service lighting ground flash density in flashes/km2/year (See Figure L.2) environmental coefficient of incoming service (see Table L.6.7.2) correction factor for presence of an HV/LV transformer located b/t strike point and structure (0.2 if one present, otherwise 1.0) collection area of flashes striking near service (m2) (see Table 6.7.1)
Ng
1.0
Ce
0.5
Ct
1.0
Ai
559017.0
4 of 14
10/15/2012
PROBABILITY OF PHYSICAL DAMAGE DUE TO DIRECT STRIKE (SECTION L.6.6.2.2) PB = 0.001 probability of physical damage due to direct strike to a structure (see Table L.6.7.4)
PROBABILITY OF INTERNAL SYSTEM FAILURE AS FUNCTION OF SPD PROTECTION (SECTION L.6.6.2.3) PC = 1 probability of failure of internal systems as function of SPD protection (see Table L.6.7.5) Sec. L.6.6.2.3
5 of 14
10/15/2012
KS
0.0648
For continuous metal shields with a thickness of 0.1 to 0.5 mm, K S1 and K S2 should be assigned the value of 10-4 to 10-5 (scaled linearly). Where not otherwise known, the value of K S1 and K S2 can be evaluated by the following relationship as long as the equipment is located a distance, w from the boundary shield:
w = distance measured in meters and given by a mesh grid spacing, the spacing between down conductors, or the spacing between structural steel columns. In those structures where it is ensured that steel reinforcing bars are interconnected and terminated by approved grounding electrodes, w is the spacing between the reinforcing bars. If the equipment is located closer to the applicable boundary than the distance, w , the values of K S 1 and K S 2 should be doubled. In those cases where multiple internal boundaries exist, the resulting value of K S2 is the product of each individual value of K S2 . KS1 KS2 = = 1.8 1.8 structural shielding efficiency factor internal shielding efficiency factor
6 of 14
10/15/2012
U W = lowest withstand voltage of the hardware in the system under consideration KS4 = 1 system voltage factor
PROBABILITY OF INJURY FROM STRIKE TO INCOMING SERVICE (SECTION L.6.6.2.5) PU = 0.8 probability as a function of the resistance of cable shield and impulse withstand voltage of equipment (see Table L6.7.8) 1.5 based on P U = 1
Where SPDs are provided for equipotential bonding, the value of P U to be used in the equation for the risk of injury to humans due to flashes to a service is the lower value between P C and P U . For unshielded services, a value of P U = 1 is used. Where physical restrictions, warning notices, etc., are used, the value of P U can be further reduced by multiplying it by P A .
PROBABILITY OF PHYSICAL DAMAGE FROM STRIKE TO INCOMING SERVICE (SECTION L.6.6.2.6) PV = 0.8 probability of physical damage from strike to incoming service
Where SPDs are not provided, the value of P V is equal to the value of P U . Where SPDs are provided, the value of P V to be used in the equation for the risk of physical damage due to a strike to a service is the lower value between P C and P U .
7 of 14
10/15/2012
PROBABILITY OF INTERNAL SYSTEM FAILURE DUE TO STRIKE TO INCOMING SERVICE (SECTION L.6.6.2.7) PW = 0.8 probability of physical damage from strike to incoming service
Where SPDs are installed, the value of P W is the lower value of P C or P U . Where SPDs are not installed, the value of P W to be used in the equation for the risk of failure of internal systems due to a strike to a service is equivalent to the value of P U .
PROBABILITY OF INTERNAL SYSTEM FAILURE DUE TO STRIKE NEAR AN INCOMING SERVICE (SECTION L.6.6.2.8) PZ = 0.1 probability of internal system failure due to strike near an incoming service
Where SPDs are not installed, the probability of failure of internal systems due to a flash near the connected service (P Z ) can be taken from Table L.6.7.9. Where SPDs are installed, the value of PZ can be taken to be the lower value of PC or PZ.
8 of 14
10/15/2012
LOSS FACTORS, FROM NFPA 780 2011 APPENDIX L6.6.3 LOSS OF LIFE TO HUMANS (SECTION L.6.6.3)
LA np nt tp
= = = =
estimated, mean, value number of possible endangered persons (victims) expected total number of persons (in the structure) time in hours per year for which the persons are present in a dangerous place, outside of the structure (Lt) or inside the structure (Lt, Lf, Lo)
Typical mean values of Lt, Lf , and Lo, for use when the determination of np, nt, and tp is uncertain or difficult, are given in Table L.6.7.10. INJURY TO HUMANS (SECTION L.6.6.3.1)
LA LU ra
= = =
value for loss of human life value of loss of living being reduction factor for type of surface soil or floor (see Table L.6.7.11) mean value of loss of life (see Table L.6.7.10) 9 of 14
Lt
0.00001
10/15/2012
LB LV rp
= = =
value of loss due to direct strike to the structure value of loss due to strike to incoming service reduction factor for provisions take to reduce consequences of fire (see Table L.6.7.12) reduction factor for risk of fire to structure (see Table L.6.7.13) factor for the kinds of hazard in the structure (see Table L.6.7.14) mean value of physical damage loss (see Table L.6.7.10) Calculated value based on number of people at risk. value of loss due to direct strike to the structure, based on number of people at risk value of loss due to strike to incoming service, based on number of people at risk
rf
0.01
hZ
= = = =
10 of 14
10/15/2012
LC LM LW
= = =
value of loss due to direct strike to the structure value of loss due to a strike near the structure value of loss due to a strike to a service connected to the structure value of loss due to a strike near a service connected to the structure mean value of loss of internal system (see Table L.6.7.10)
LZ
0.001
LO
0.001
11 of 14
10/15/2012
RISK COMPONENTS (SECTION L.6.4) SUMMARY OF NUMBER OF STRIKES (SECTION L.6.6.1) Nd NM Nda NL NI = = = = = 0.0037 0.0573 0.0059 0.0224 0.2795
SUMMARY OF PROBABILITY OF DAMAGE (SECTION L.6.6.2) PA PB PC PM PU PV PW PZ = = = = = = = = 0.000001 0.001 1 1 0.8 0.8 0.8 0.1
SUMMARY OF LOSS FACTORS (SECTION L.6.6.3) Alternate, based on number of people at risk 0.0000 0.00046 0.001 0.001 0.0000 0.00046 0.001 0.001 Difference 0% 91% 0% 0% 0% 91% 0% 0% 12 of 14
LA LB LC LM LU LV LW LZ
= = = = = = = =
10/15/2012
SUMMARY OF RISK COMPONENTS (SEE TABLE L.6.6) RA RB RC RM RU RV RW RZ = = = = = = = = 3.68E-16 1.47E-10 3.68E-06 5.73E-05 2.26E-09 9.03E-07 2.26E-05 2.57E-05 3.68E-16 1.68E-09 3.68E-06 5.73E-05 2.26E-09 1.03E-05 2.26E-05 2.57E-05 Difference 0% 91% 0% 0% 0% 91% 0% 0%
13 of 14
10/15/2012
+ RM*, + RU + RV + RW* + RZ* Alternate 1.03124E-05 0.000119557 * applicable only for structures with risk of explosion, for structures with life-critical electrical equipment (such as hospitals), or other structures where the failure of internal systems immediately endangers human life.
9.05429E-07 0.00011015
R2 = RB + RC + RM + RV + RW + RZ R2 = 0.000110147 0.000119554
R3 = RB + RV R3 = 9.03171E-07 1.03102E-05
R 4 = R A ** + R B + R C + R M + R U ** + R V + RW + R Z R4 R4** = = 0.000110147 0.00011015 0.000119554 0.000119557 ** applicable only for structures where animals might be injured.
TOTAL OVERALL RISK (SECTION L.6.2 & L.6.5) R = R1 + R2 + R3 + R4 R R* R** = = = 0.000222103 0.000331348 0.000222106 0.000259731 0.000368976 0.000259734 RT - Loss of Life or Injury R R R Lightning Protection IS required for Loss of Life IS NOT required for Loss of Service IS NOT required for Loss of Historical Significance Detailed Risk Assessment 14 of 14 0.000001 RT - Loss of Service NR NR NR 0.001 RT - Loss of Historical Significance NR NR NR 0.001