Steam
Steam
Table of Contents
Introduction Recommendation Charts and Instructions for Use Steam Tables Flash Steam Steam...Basic Concepts The Inverted Bucket Steam Trap The Float & Thermostatic Steam Trap The Controlled Disc Steam Trap The Thermostatic Steam Trap The Automatic Differential Condensate Controller Steam Trap Selection HOW TO TRAP: Steam Distribution Systems Steam Tracer Lines Space Heating Equipment Process Air Heaters Shell and Tube Heat Exchangers Evaporators Jacketed Kettles Closed Stationary Steam Chamber Equipment Rotating Dryers Requiring Syphon Drainage Flash Tanks Steam Absorption Machines Trap Selection and Safety Factors Installation and Testing Troubleshooting Pipe Sizing Steam Supply and Condensate Return Lines Useful Engineering Tables Conversion Factors Specific Gravity-Specific Heat Complete Index Gatefold A Gatefold B 2 3 4-7 8-9 10-11 11 12 13 14-15 16-19 20-21 22-24 25 26-27 28-29 30-31 32-33 34-35 36-37 38 39 40-43 44 45-47 48 49 50 Inside Back Cover
IMPORTANT: This Handbook is intended to summarize general principles of installation and operation of steam traps, as outlined above. Actual installation and operation of steam trapping equipment should be performed only by experienced personnel. Selection or installation should always be accompanied by competent technical assistance or advice. This Handbook should never be used as a substitute for such technical advice or assistance. We encourage you to contact Armstrong or its local representative for further details.
Abbreviations
IB IBLV F&T CD DC CV T PRV Inverted Bucket Trap Inverted Bucket Large Vent Float and Thermostatic Trap Controlled Disc Trap Automatic Differential Condensate Controller Check Valve Thermic Bucket Pressure Relief Valve
Alternate Choice
F&T or Thermostatic IBLV
How Various Types of Steam Traps Meet Specific Operating Requirements Feature Inverted F&T Characteristic Code Bucket
A B C D E F G H I J K L M N O P Q Method of Operation Energy Conservation (Time in Service) Resistance to Wear Corrosion Resistance Resistance to Hydraulic Shock Vents Air and CO2 at Steam Temperature Ability to Vent Air at Very Low Pressure ( Ability to Handle Start-up Air Loads Operation Against Back Pressure Resistance to Damage from Freezing (6) Ability to Purge System Performance on Very Light Loads Responsiveness to Slugs of Condensate Ability to Handle Dirt Comparative Physical Size Ability to Handle Flash Steam Mechanical Failure (OpenClosed) (1) Intermittent Excellent Excellent Excellent Excellent Yes Poor Fair Excellent Good Excellent Excellent Immediate Excellent (7) Large Fair Open Continuous Good Good Good Poor No Excellent Excellent Excellent Poor Fair Excellent Immediate Poor Large Poor Closed
Disc
Intermittent Poor Poor Excellent Excellent No (5) NR Poor Poor Good Excellent Poor Delayed Poor Small Poor (8) Open
Thermostatic
(2) Intermittent Fair Fair Good (4) Poor No Good Excellent Excellent Good Good Excellent Delayed Fair Small Poor (9)
Differential Controller
Continuous (3) Excellent Excellent Excellent Excellent Yes Excellent Excellent Excellent Good Excellent Excellent Immediate Excellent Large Excellent Open
psig)
1. Drainage of condensate is continuous. Discharge is intermittent. 2. Can be continuous on low load. 3. Excellent when secondary steam is utilized. Gatefold
4. Bimetallic and wafer trapsgood. 5. Not recommended for low pressure operations. 6. Cast iron traps not recommended.
7. In welded stainless steel construction medium. 8. Can fail closed due to dirt. 9. Can fail either open or closed depending upon the design of the bellows.
Steam Tables
What They AreHow to Use Them
The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Total Heat of Steam (Column 6). The sum of the Heat of the Liquid (Column 4) and Latent Heat (Column 5) in Btu. It is the total heat in steam above 32F. Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound. Specific Volume of Steam (Column 8). The volume per unit of mass in cubic feet per pound.
Properties of Saturated Steam (Abstracted from Keenan and Keyes, THERMODYNAMIC PROPERTIES OF STEAM, by permission of John Wiley & Sons, Inc.)
Col. 1 Gauge Pressure
29.743 29.515 27.886 19.742 9.562 7.536 5.490 3.454 1.418 0.0 1.3 2.3 5.3 10.3 15.3 20.3 25.3 30.3 40.3 50.3 60.3 70.3 80.3 90.3 100.0 110.3 120.3 125.3 130.3 140.3 150.3 160.3 180.3 200.3 225.3 250.3
PSIG
Inches of Vacuum
The heat absorbed by the water in raising its temperature to boiling point is called sensible heat or heat of saturated liquid. The heat required to convert water at boiling point to steam at the same temperature is called latent heat. The unit of heat in common use is the Btu which is the amount of heat required to raise the temperature of one pound of water 1F at atmospheric pressure. If water is heated under pressure, however, the boiling point is higher than 212F, so the sensible heat required is greater. The higher the pressure, the higher the boiling temperature and the higher the heat content. If pressure is reduced, a certain amount of sensible heat is released. This excess heat will be absorbed in the form of latent heat, causing part of the water to flash into steam.
Condensate at steam temperature and under 100 psig pressure has a heat content of 308.8 Btu per pound. (See Column 4 in Steam Table.) If this condensate is discharged to atmospheric pressure (0 psig), its heat content instantly drops to 180 Btu per pound. The surplus of 128.8 Btu re-evaporates or flashes a portion of the condensate. The percentage that will flash to steam can be computed using the formula: % flash steam = SH - SL x 100 H SH = Sensible heat in the condensate at the higher pressure before discharge. SL = Sensible heat in the condensate at the lower pressure to which discharge takes place. H = Latent heat in the steam at the lower pressure to which the condensate has been discharged. % flash steam = 308.8 - 180 x 100 = 13.3% 970.3 For convenience Chart 3-1 shows the amount of secondary steam which will be formed when discharging condensate to different pressures. Other useful tables will be found on page 48.
Chart 3-1. Percentage of flash steam formed when discharging condensate to reduced pressure
30
400
Chart 3-2. Volume of flash steam formed when one cubic foot of condensate is discharged to atmospheric pressure
25
300
A
20
200
B C
15
D E F G
CURVE
A B C D E F G
100
10
100
200
300
400
0 20
50
100
150
200
250
300
SteamBasic Concepts
Steam is an invisible gas generated by adding heat energy to water in a boiler. Enough energy must be added to raise the temperature of the water to the boiling point. Then additional energy without any further increase in temperaturechanges the water to steam. Steam is a very efficient and easily controlled heat transfer medium. It is most often used for transporting energy from a central location (the boiler) to any number of locations in the plant where it is used to heat air, water or process applications. As noted, additional Btu are required to make boiling water change to steam. These Btu are not lost but stored in the steam ready to be released to heat air, cook tomatoes, press pants or dry a roll of paper. The heat required to change boiling water into steam is called the heat of vaporization or latent heat. The quantity is different for every pressure/temperature combination, as shown in the steam tables.
Condensate
1 lb water at 70F
Steam
+ 142 Btu =
1 lb water at 212F
+ 270 Btu =
+ 880 Btu =
Figure 4-2. These drawings show how much heat is required to generate one pound of steam at 100 pounds per square inch pressure. Note the extra heat and higher temperature required to make water boil at 100 pounds pressure than at atmospheric pressure. Note, too, the lesser amount of heat required to change water to steam at the higher temperature.
Definitions
Figure 4-1. These drawings show how much heat is required to generate one pound of steam at atmospheric pressure. Note that it takes1 Btu for every 1 increase in temperature up to the boiling point, but that it takes more Btu to change water at 212F to steam at 212F. I The Btu. A BtuBritish thermal unitis the amount of heat energy required to raise the temperature of one pound of cold water by 1F. Or, a Btu is the amount of heat energy given off by one pound of water in cooling, say, from 70F to 69F. I Temperature. The degree of hotness with no implication of the amount of heat energy available. I Heat. A measure of energy available with no implication of temperature. To illustrate, the one Btu which raises one pound of water from 39F to 40F could come from the surrounding air at a temperature of 70F or from a flame at a temperature of 1,000F.
The need to drain the distribution system. Condensate lying in the bottom of steam lines can be the cause of one kind of water hammer. Steam traveling at up to 100 miles per hour makes waves as it passes over this condensate (Fig. 5-2). If enough condensate forms, high-speed steam pushes it along, creating a dangerous slug which grows larger and larger as it picks up liquid in front of it. Anything which changes the directionpipe fittings, regulating valves, tees, elbows, blind flangescan be destroyed. In addition to damage from this battering ram, high-velocity water may erode fittings by chipping away at metal surfaces.
The need to drain the heat transfer unit. When steam comes in contact with condensate cooled below the temperature of steam, it can produce another kind of water hammer known as thermal shock. Steam occupies a much greater volume than condensate, and when it collapses suddenly, it can send shock waves throughout the system. This form of water hammer can damage equipment, and it signals that condensate is not being drained from the system. Obviously, condensate in the heat transfer unit takes up space and reduces the physical size and capacity of the equipment. Removing it quickly keeps the unit full of steam (Fig. 5-3). As steam condenses, it forms a film of water on the inside of the heat exchanger.
Non-condensable gases do not change into a liquid and flow away by gravity. Instead, they accumulate as a thin film on the surface of the heat exchanger along with dirt and scale. All are potential barriers to heat transfer (Fig. 5-1). The need to remove air and CO2. Air is always present during equipment start-up and in the boiler feedwater. Feedwater may also contain dissolved carbonates which release carbon dioxide gas. The steam velocity pushes the gases to the walls of the heat exchangers where they may block heat transfer. This compounds the condensate drainage problem because these gases must be removed along with the condensate.
STEAM
FLUID TO BE HEATED
yyyyy ,,,,, ,,,,, yyyyy ,,,,, yyyyy ,,,,, yyyyy ,,,,, yyyyy ,,,,, yyyyy ,,,,, yyyyy
COIL PIPE CUTAWAY
Figure 5-1. Potential barriers to heat transfer: steam heat and temperature must penetrate these potential barriers to do their work. Figure 5-3. Coil half full of condensate cant work at full capacity.
Figure 5-2. Condensate allowed to collect in pipes or tubes is blown into waves by steam passing over it until it blocks steam flow at point A. Condensate in area B causes a pressure differential that allows steam pressure to push the slug of condensate along like a battering ram. Condensate Steam Vapor
50.3 psig 297.97F 100 psig 337.9F PRV Trap Trap Trap Trap
Trap
Trap
Vent
Figure 5-4. Note that heat radiation from the distribution system causes condensate to form and, therefore, requires steam traps at natural low points or ahead of control valves. In the heat exchangers, traps perform the vital function of removing the condensate before it becomes a barrier to heat transfer. Hot condensate is returned through the traps to the boiler for reuse.
SteamBasic Concepts
Effect of Air on Steam Temperature
When air and other gases enter the steam system, they consume part of the volume that steam would otherwise occupy. The temperature of the air/steam mixture falls below that of pure steam. Figure 6-1 explains the effect of air in steam lines. Table 6-1 and Chart 6-1 show the various temperature reductions caused by air at various percentages and pressures.
acid. Extremely corrosive, carbonic acid can eat through piping and heat exchangers (Fig. 7-2). Oxygen enters the system as gas dissolved in the cold feedwater. It aggravates the action of carbonic acid, speeding corrosion and pitting iron and steel surfaces (Fig. 7-3).
Figure 6-1. Chamber containing air and steam delivers only the heat of the partial pressure of the steam, not the total pressure.
When non-condensable gases (primarily air) continue to accumulate and are not removed, they may gradually fill the heat exchanger with gases and stop the flow of steam altogether. The unit is then air bound.
Corrosion
Two primary causes of scale and corrosion are carbon dioxide (CO2) and oxygen. CO2 enters the system as carbonates dissolved in feedwater and when mixed with cooled condensate creates carbonic
Steam chamber 100% steam Total pressure 100 psia Steam pressure 100 psia Steam temperature 327.8F
Steam chamber 90% steam and 10% air Total pressure 100 psia Steam pressure 90 psia Steam temperature 320.3F Table 6-1. Temperature Reduction Caused by Air
Pressure (psig) Temp. of Steam, No Air Present (F) Temp. of Steam Mixed with Various Percentages of Air (by Volume) (F)
10% 10.3 25.3 50.3 75.3 100.3 240.1 267.3 298.0 320.3 338.1 234.3 261.0 291.0 312.9 330.3
Chart 6-1. Air Steam Mixture Temperature reduction caused by various percentages of air at differing pressures. This chart determines the percentage of air with known pressure and temperature by determining the point of intersection between pressure, temperature and percentage of air
by volume. As an example, assume system pressure of 250 psig with a temperature at the heat exchanger of 375F. From the chart, it is determined that there is 30% air by volume in the steam.
steam at any time and especially on start-up. Air must be vented for efficient heat transfer and to prevent system binding. 5. CO2 venting. Venting CO2 at steam temperature will prevent the formation of carbonic acid. Therefore, the steam trap must function at or near steam temperature since CO2 dissolves in condensate which has cooled below steam temperature. 6. Operation against back pressure. Pressurized return lines can occur both by design and unintentionally. A steam trap should be able to operate against the actual back pressure in its return system. 7. Freedom from dirt problems. Dirt is an ever-present concern since traps are located at low points in the steam system. Condensate picks up dirt and scale in the piping, and solids may carry over from the boiler. Even particles passing through strainer screens are erosive and,
therefore, the steam trap must be able to operate in the presence of dirt. A trap delivering anything less than all these desirable operating/design features will reduce the efficiency of the system and increase costs. When a trap delivers all these features the system can achieve: 1. Fast heat-up of heat transfer equipment 2. Maximum equipment temperature for enhanced steam heat transfer 3. Maximum equipment capacity 4. Maximum fuel economy 5. Reduced labor per unit of output 6. Minimum maintenance and a long trouble-free service life Sometimes an application may demand a trap without these design features, but in the vast majority of applications the trap which meets all the requirements will deliver the best results.
Condensate
Steam
Figure 7-1. Steam condensing in a heat transfer unit moves air to the heat transfer surface where it collects or plates out to form effective insulation.
Figure 7-2. CO2 gas combines with condensate allowed to cool below steam temperature to form carbonic acid which corrodes pipes and heat transfer units. Note groove eaten away in the pipe illustrated.
Figure. 7-3. Oxygen in the system speeds corrosion (oxidation) of pipes, causing pitting such as shown here. Figs. 7-2 and 7-3 courtesy of Dearborn Chemical Company.
Table 7-1. Cost of Various Sized Steam Leaks at 100 psi (assuming steam costs $5.00/1,000 lbs)
Size of Orifice (in)
1/2 7
Lbs Steam Wasted Per Month 835,000 637,000 470,000 325,000 210,000 117,000 52,500
Total Cost Per Month $4,175.00 3,185.00 2,350.00 1,625.00 1,050.00 585.00 262.50
Total Cost Per Year $50,100.00 38,220.00 28,200.00 19,500.00 12,600.00 7,020.00 3,150.00
/16 /8
3 5
/16 /4
1 3
/16 /8
The steam loss values assume clean, dry steam flowing through a sharp-edged orifice to atmospheric pressure with no condensate present. Condensate would normally reduce these losses due to the flashing effect when a pressure drop is experienced.
Corrosion-Resistant Parts
The valve and seat of Armstrong inverted bucket traps are high chrome stainless steel, ground and lapped. All other working parts are wear- and corrosionresistant stainless steel.
Reliable Operation
The Armstrong inverted bucket trap owes much of its reliability to a design that makes it virtually free of dirt problems. Note that the valve and seat are at the top of the trap. The larger particles of dirt fall to the bottom where they are pulverized under the up-and-down action of the bucket. Since the valve of an inverted bucket is either closed or fully open, there is free passage of dirt particles. In addition, the swift flow of condensate from under the buckets edge creates a unique self-scrubbing action that sweeps
Figure 8-1. Operation of the Inverted Bucket Steam Trap (at pressures close to maximum) Steam Condensate Air 123 123 Flashing Condensate
123 123
Valve Closed
1. All-Stainless Steel Traps. Sealed, tamper-proof stainless steel bodies enable these traps to withstand freeze-ups without damage. They may be installed on tracer lines, outdoor drips and other services subject to freezing. For pressures to 650 psig and temperatures to 800F. 2. Cast Iron Traps. Standard inverted bucket traps for general service at pressures to 250 psig and temperatures to 450F. Offered with side connections, side connections with integral strainers and bottom inlettop outlet connections.
3. Forged Steel Traps. Standard inverted bucket traps for high pressure, high temperature services (including superheated steam) to 2,700 psig at 1,050F. 4. Cast Stainless Steel Traps. Standard inverted bucket traps for high capacity, corrosive service. Repairable. For pressures to 700 psig and temperatures to 506F.
Forged Steel
1/2"
Cast Steel
1/2"
thru 1"
thru 2"
thru 1"
thru 2"
Screwed
0 thru 250
To 20,000
To 4,400
To 19,000
To 4,400
To 19,000
Valve Closed
4. As the valve starts to open, the pressure force across the valve is reduced. The bucket then sinks rapidly and fully opens the valve. Accumulated air is discharged first, followed by condensate. The flow under the bottom of the bucket picks up dirt and sweeps it out of the trap. Discharge continues until more steam floats the bucket, and the cycle repeats.
Steam
Condensate
Air
1. On start-up low system pressure forces air out through the thermostatic air vent. A high condensate load normally follows air venting and lifts the float which opens the main valve. The remaining air continues to discharge through the open vent.
2. When steam reaches the trap, the thermostatic air vent closes in response to higher temperature. Condensate continues to flow through the main valve which is positioned by the float to discharge condensate at the same rate that it flows to the trap.
3. As air accumulates in the trap, the temperature drops below that of saturated steam. The balanced pressure thermostatic air vent opens and discharges air.
NOTE: These operational schematics of the F&T trap do not represent actual trap configuration.
10
SHEMA Ratings
Float and thermostatic traps for pressures up to 15 psig may be selected by pipe size on the basis of ratings established by the Steam Heating Equipment Manufacturers Association (SHEMA). SHEMA ratings are the same for all makes of F&T traps as they are an established measure of the capacity of a pipe flowing half full of condensate under specific conditions of pressure, length of pipe, pitch, etc.
Various specification writing authorities indicate different procedures for sizing traps by SHEMA ratings, and their procedures must be followed to assure compliance with their specifications. However, as SHEMA ratings provide for continuous air elimination when the trap operates at maximum condensate capacity rating and provision is made for overload conditions, no trap safety factor is necessary.
Table 11-1. Typical Design Parameters for Float and Thermostatic Traps
Cast Iron
Connections Type Connections Operating Pressure (psig) Capacity (lbs/hr)
1
Cast Steel
2" thru 3" Screwed, Socketweld or Flanged 0 thru 450
To 208,000
To 280,000
thru 1"
y @ P , @ P , y @y P , y @ P ,
Condensate Air
High Velocity Flow Seat
Outlet Passages
1. On start-up, condensate and air entering the trap pass through the heating chamber around the control chamber and through the inlet orifice. This flow lifts the disc off the inlet orifice, and the condensate flows through to the outlet passages.
2. Steam enters through the inlet passage and flows under the control disc. The flow velocity across the face of the control disc increases, creating a low pressure that pulls the disc toward the seat.
3. The disk closes against two concentric faces of the seat, closing off the inlet passage and also trapping steam and condensate above the disc. There is a controlled bleeding of steam from the control chamber; flashing condensate helps maintain the pressure in the control chamber. When the pressure above the disc is reduced, the incoming pressure lifts the disc off the seat. If condensate is present, it will be discharged, and the cycle repeats.
11
Bronze
1/2", 3/4"
Carbon Steel
1/2",3/4"
Bronze
1/2", 3/4",
1"
Thermostatic Operation
Thermostatic steam traps operate on the difference in temperature between steam and cooled condensate and air. Steam increases the pressure inside the thermostatic element, causing the trap to close. As condensate and non-condensable gases back up in the cooling leg, the temperature begins to drop and the thermostatic element contracts and opens the valve. The amount of condensate backed up ahead of the trap depends on the load
conditions, steam pressure and size of the piping. It is important to note that an accumulation of non-condensable gases can occur behind the condensate backup.
NOTE: Thermostatic traps can also be used for venting air from a steam system. When air collects, the temperature drops and the thermostatic air vent automatically discharges the air at slightly below steam temperature throughout the entire operating pressure range.
Figure 12-2. Operation of Thermostatic Wafer Steam Condensate and Air Condensate
Alcohol Vapor
Wafer
Alcohol Liquid
Bulkhead
Alcohol Chamber
1. On start-up, condensate and air are pushed ahead of the steam directly through the trap. The thermostatic bellows element is fully contracted and the valve remains wide open until steam approaches the trap.
2. As the temperature inside the trap increases, it quickly heats the charged bellows element, increasing the vapor pressure inside. When pressure inside the element becomes balanced with system pressure in the trap body, the spring effect of the bellows causes the element to expand, closing the valve. When temperature in the trap drops a few degrees below saturated steam temperature, imbalanced pressure contracts the bellows, opening the valve.
Balanced Pressure Thermostatic Wafer operation is very similar to balanced pressure bellows described in Fig. 12-1. The wafer is partially filled with a liquid. As the temperature inside the trap increases, it heats the charged wafer, increasing the vapor pressure inside. When the pressure inside the wafer exceeds the surrounding steam pressure, the wafer membrane is forced down on the valve seat and the trap is closed. A temperature drop caused by condensate or non-condensable gases cools and reduces the pressure inside the wafer, allowing the wafer to uncover the seat.
12
Figure 13-1.
DC
Condensate Discharge Valve
Condensate Return
For the most efficient use of steam energy, Armstrong recommends the piping arrangement when secondary steam is collected and reused in heat transfer equipment.
DC
Condensate Return
Piping arrangement when flash steam and non-condensables are to be removed and discharged directly to the condensate return line.
, , , , , , , , , , , , , , , , , , , , , , , , ,
Inlet Bucket Secondary Steam Manual Metering Valve Condensate Live and Flash Steam Condensate and Secondary Steam Outlet
Dotted Lines Indicate Field Piping
13
Trap Selection
To obtain the full benefits from the traps described in the preceding section, it is essential to select traps of the correct size and pressure for a given job and to install and maintain them properly. One of the purposes of this Handbook is to supply the information to make that possible. Actual installation and operation of steam trapping equipment should be performed only by experienced personnel. Selection or instal-lation should always be accompanied by competent technical assistance or advice. This Handbook should never be used as a substitute for such technical advice or assist-ance. We encourage you to contact Armstrong or its local representative for further details. Rely on experience. Select traps with the aid of past experience. Either yours, the know-how of your Armstrong Representative or what others have learned in trapping similar equipment. Do-it-yourself sizing. Do-it-yourself sizing is simple with the aid of Armstrong Software Program I (Steam Trap Sizing and Selection). Even without this computer program, you can easily size steam traps when you know or can calculate: 1. 2. 3. 4. Condensate loads in lbs/hr The safety factor to use Pressure differential Maximum allowable pressure 2. Safety Factor or Experience Factor to Use. Users have found that they must generally use a safety factor in sizing steam traps. For example, a coil condensing 500 lbs/hr might require a trap that could handle up to 1,500 for best overall performance. This 3:1 safety factor takes care of varying condensate rates, occasional drops in pressure differential and system design factors. Safety factors will vary from a low of 1.5:1 to a high of 10:1. The safety factors in this book are based on years of user experience.
Basic Considerations
Unit trapping is the use of a separate steam trap on each steam-condensing unit including, whenever possible, each separate chest or coil of a single machine. The discussion under the Short Circuiting heading explains the why of unit trapping versus group trapping.
1. Condensate load. Each How To section of this Handbook contains formulas and useful information on steam condensing rates and proper sizing procedures.
Configuration affects safety factor. More important than ordinary load and pressure changes is the design of the steam heated unit itself. Refer to Figs. 14-3, 144 and 14-5 showing three condensing units each producing 500 pounds of condensate per hour, but with safety factors of 2:1, 3:1 and 8:1.
Short Circuiting
If a single trap connects more than one drain point, condensate and air from one or more of the units may fail to reach the trap. Any difference in condensing rates will result in a difference in the steam pressure drop. A pressure drop difference too small to register on a pressure gauge is enough to let steam from the higher pressure unit block the flow of air or condensate from the lower pressure unit. The net result is reduced heating, output and fuel waste (See Figs. 14-1 and 14-2).
WRONG
RIGHT
Figure 14-1. Two steam consuming units drained by a single trap, referred to as group trapping, may result in short circuiting.
Figure 14-2. Short circuiting is impossible when each unit is drained by its own trap. Higher efficiency is assured.
Steam
Condensate
10"-12" 6"
Figure 14-3. Continuous coil, constant pressure gravity flow to trap. 500 lbs/hr of condensate from a single copper coil at 30 psig. Gravity drainage to trap. Volume of steam space very small. 2:1 safety factor.
Figure 14-4. Multiple pipes, modulated pressure gravity flow to trap. 500 lbs/hr of condensate from unit heater at 80 psig. Multiple tubes create minor short circuiting hazard. Use 3:1 safety factor at 40 psig.
Figure 14-5. Large cylinder, syphon drained. 500 lbs/hr from a 4' diameter 10' long cylinder dryer with 115 cu ft of space at 30 psig. The safety factor is 3:1 with a DC and 8:1 with an IB.
14
Economical steam trap/orifice selection. While an adequate safety factor is needed for best performance, too large a factor causes problems. In addition to higher costs for the trap and its installation, a needlessly oversized trap wears out more quickly. And in the event of a trap failure, an oversized trap loses more steam which can cause water hammer and high back pressure in the return system.
3. Pressure differential. Maximum differential is the difference between boiler or steam main pressure or the downstream pressure of a PRV and return line pressure. See Fig. 15-1. The trap must be able to open against this pressure differential. NOTE: Because of flashing condensate in the return lines, dont assume a decrease in pressure differential due to static head when elevating.
Modulated control of the steam supply causes wide changes in pressure differential. The pressure in the unit drained may fall to atmospheric or even lower (vacuum). This does not prevent condensate drainage if the installation practices in this handbook are followed.
Inlet pressure can be reduced below its IMPORTANT: Be sure to read the discussion normal value by: to the right which deals with less common but 1. A modulating control valve or important reductions in pressure differential. temperature regulator. 2. Syphon drainage. Every two feet of lift 4. Maximum allowable pressure. between the drainage point and the trap The trap must be able to withstand the reduces the inlet pressure (and the maximum allowable pressure of the system differential) by one psi. See Fig. 15-2. or design pressure. It may not have to operate at this pressure, but must be able to contain it. As an example, the maximum inlet pressure is 350 psig and the return line pressure is 150 psig. This results in a differential pressure of 200 psi, however, the trap must be able to withstand 350 psig maximum allowable pressure. See Fig. 15-1. Discharge pressure can be increased above its normal value by: 1. Pipe friction. 2. Other traps discharging into a return system of limited capacity. 3. Elevating condensate. Every two feet of lift increases the discharge pressure (and the differential) by one psi when the discharge is only condensate. However, with flash present, the extra back pressure could be reduced to zero. See Fig. 15-3, noting the external check valve.
Operating differential. When the plant is operating at capacity, the steam pressure at the trap inlet may be lower than steam main pressure. And the pressure in the condensate return header may go above atmospheric.
If the operating differential is at least 80% of the maximum differential, it is safe to use maximum differential in selecting traps.
Steam
Condensate
4psi
9'
Trap
8'
3psi
2psi
4'
Differential Pressure or Maximum Operating Pressure (MOP)
3'
1psi Pressure drop over water seal to lift cold condensate
Steam Main
A
Inlet Pressure or Maximum Allowable Pressure (MAP) Trap
B
Back Pressure or Vacuum
2' 1'
Trap
Water Seal
Lift in feet
Figure 15-1. A minus B is Pressure Differential: If B is back pressure, subtract it from A. If B is vacuum, add it to A.
Figure 15-2. Condensate from gravity drain point is lifted to trap by a syphon. Every two feet of lift reduces pressure differential by one psi. Note seal at low point and the traps internal check valve to prevent backflow.
Figure 15-3. When trap valve opens, steam pressure will elevate condensate. Every two feet of lift reduces pressure differential by one psi.
15
1. Let condensate escape by gravity from the fast-moving steam. 2. Store the condensate until the pressure differential can discharge it through the steam trap.
Steam traps which serve the header must be capable of discharging large slugs of carryover as soon as they are present. Resistance to hydraulic shock is also a consideration in the selection of traps. Trap selection and safety factor for boiler headers (saturated steam only). A 1.5:1 safety factor is recommended for virtually all boiler header applications. The required trap capacity can be obtained by using the following formula: Required Trap Capacity = Safety Factor x Load Connected to Boiler(s) x Anticipated Carryover (typically 10%). EXAMPLE: What size steam trap will be required on a connected load of 50,000 lbs/hr with an anticipated carryover of 10%? Using the formula: Required Trap Capacity = 1.5 x 50,000 x 0.10 = 7,500 lbs/hr. The ability to respond immediately to slugs of condensate, excellent resistance to hydraulic shock, dirt-handling ability and efficient operation on very light loads are features which make the inverted bucket the most suitable steam trap for this application. Installation. If steam flow through the header is in one direction only, a single steam trap is sufficient at the downstream end. With a midpoint feed to the header (Fig. 16-2), or a similar two-directional steam flow arrangement, each end of the boiler header should be trapped.
Boiler Headers
A boiler header is a specialized type of steam main which can receive steam from one or more boilers. It is most often a horizontal line which is fed from the top and in turn feeds the steam mains. It is important to trap the boiler header properly to assure that any carryover (boiler water and solids) is removed before distribution into the system.
The properly sized drip leg will capture condensate. Too small a drip leg can actually cause a venturi piccolo effect where pressure drop pulls condensate out of the trap. See Table 18-1.
Drip leg same as the header diameter up to 4". Above 4", 1/2 header size, but never less than 4".
Trap
Alternate Choice
*F&T
*On superheated steam never use an F&T type trap. Always use an IB with internal check valve and burnished valve and seat.
Equipment Being Trapped
Steam Mains and Branch Lines Non-freezing Conditions Steam Mains and Branch Lines Freezing Conditions
0-30 psig
*IB F&T *IB
Above 30 psig
*IB **F&T *IB
Thermostatic Thermostatic or CD or CD
*Provide internal check valve when pressures fluctuate. **Use IBLV above F&T pressure/temperature limitations. NOTE: On superheated steam, use an IB with internal check valve and burnished valve and seat.
16
Steam Mains
One of the most common uses of steam traps is the trapping of steam mains. These lines need to be kept free of air and condensate in order to keep steamusing equipment operating properly. Inadequate trapping on steam mains often leads to water hammer and slugs of condensate which can damage control valves and other equipment. There are two methods used for the warmup of steam mainssupervised and automatic. Supervised warm-up is widely used for initial heating of large diameter and/or long mains. The suggested method is for drip valves to be opened wide for free blow to the atmosphere before steam is admitted to the main. These drip valves are not closed until all or most of the warm-up condensate has been discharged. Then the traps take over the job of removing condensate that
may form under operating conditions. Warm-up of principal piping in a power plant will follow much the same procedure. Automatic warm-up is when the boiler is fired, allowing the mains and some or all equipment to come up to pressure and temperature without manual help or supervision. CAUTION: Regardless of warm-up method, allow sufficient time during the warm-up cycle to minimize thermal stress and prevent any damage to the system. Trap selection and safety factor for steam mains (saturated steam only). Select trap to discharge condensate produced by radiation losses at running load. Sizing for start-up loads results in oversized traps which may wear prematurely. Size drip legs to collect condensate during low-pressure, warm-up conditions.
(See Table 18-1.) Condensate loads of insulated pipe can be found in Table 17-1. All figures in the table assume the insulation to be 75% effective. For pres-sures or pipe sizes not included in the table, use the following formula: C = A x U x (t1-t2)E H
Where: C = Condensate in lbs/hr-foot A = External area of pipe in square feet (Table 17-1, Col. 2) U = Btu/sq ft/degree temperature difference/hr from Chart 17-1 T1 = Steam temperature in F T2 = Air temperature in F E = 1 minus efficiency of insulation (Example: 75% efficient insulation: 1-.75 = .25 or E = .25) H = Latent heat of steam (See Steam Table on page 2)
Table 17-1. Condensation in Insulated Pipes Carrying Saturated Steam in Quiet Air at 70F (Insulation Assumed to be 75% Efficient)
Pressure, psig
Pipe Size (in)
1
1 /4 11/2
1
700 900 1050 11 10 9 8 7 6 5 4.5 4.0 3.5 3.3 3.0 2.8 2.6
15
30
60
125
180
250
450
600
900
BTU PER SQ FT PER HOUR PER F TEMPERATURE DIFFERENCE
sq ft per Lineal ft
.344 .434 .497 .622 .753 .916 1.047 1.178 1.456 1.735 2.260 2.810 3.340 3.670 4.200 4.710 5.250 6.280 .05 .06 .07 .08 .10 .12 .13 .15 .18 .20 .27 .32 .38 .42 .47 .53 .58 .68
15
30
60
125
180
1500.3 2400.3
2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
3"
5" 6"
10"
TS LA
AC RF
ES
2.2 2.15
5.3
10.3
15.3
25.3
50.3
75.3 100.3
150.3
250.3
PSIG
XX Strong
3.66 5.21 6.41 9.03 13.69 18.58 22.85 27.54 38.55 53.16 72.42
17
For traps installed between the boiler and the end of the steam main, apply a 2:1 safety factor. Apply a 3:1 safety factor for traps installed at the end of the main or ahead of reducing and shutoff valves which are closed part of the time. Divide the warming-up load from Table 17-2 by the number of minutes allowed to reach final steam temperature. Multiply by 60 to get pounds per hour. For steam pressures and pipe schedules not covered by Table 17-2, the warmingup load can be calculated using the following formula: C = W x (t1 - t2) x .114 H
t1 = t2 = .114= H =
Final temperature of pipe in F Initial temperature of pipe in F Specific heat of steel pipe Btu/lb-F Latent heat of steam at final temperature in Btu/lb (See Steam Tables)
Installation. Both methods of warm-up use drip legs and traps at all low spots or natural drainage points such as: Ahead of risers End of mains Ahead of expansion joints or bends Ahead of valves or regulators Install drip legs and drain traps even where there are no natural drainage points (See Figs. 18-1, 18-2 and 18-3). These should normally be installed at intervals of about 300' and never longer than 500'. On a supervised warm-up, make drip leg length at least 11/2 times the diameter of the main, but never less than 10". Make drip legs on automatic warm-ups a minimum of 28" in length. For both methods, it is a good practice to use a drip leg the same diameter as the main up to 4" pipe size and at least 1/2 of the diameter of the main above that, but never less than 4". See Table 18-1.
A more conservative approach is as follows: Determine the warming-up load to reach 219F or 2 psig. Divide by the number of minutes allowed to reach 219F and multiply by 60 to get pounds per hour. Size the trap on the basis of 1 psi pressure differential for every 28" of head between the bottom of the main and the top of the trap. The inverted bucket trap is recommended because it can handle dirt and slugs of condensate and resists hydraulic shock. In addition, should an inverted bucket fail, it usually does so in the open position.
Where: C = Amount of condensate in lbs W = Total weight of pipe in lbs (See Table 17-3 for pipe weights)
Steam Mains
M D H Drip leg same as the header diameter up to 4". Above 4", 1/2 header size, but never less than 4". Figure 18-1. Trap draining strainer ahead of PRV. Figure 18-2. Trap draining drip leg on main. Figure 18-3. Trap draining drip leg at riser. Distance H in inches 28 = psi static head for forcing water through the trap. Table 18-1. Recommended Steam Main and Branch Line Drip Leg Sizing
M D H Drip Leg Length Min. (in)
Steam Main Drip Leg Diameter Supervised Automatic Size (in) (in) Warm-Up Warm-Up
/2 3/4
/2 3/4
*DC
1 2 3 4 6 8 10 12 14 16 18 20 24
1 2 3 4 4 4 6 6 8 8 10 10 12
10 10 10 10 10 10 10 12 15 18 21 24 27 30 36
28 28 28 28 28 28 28 28 28 28 28 28 28 30 36
18
Branch Lines
Branch lines are take-offs from the steam mains supplying specific pieces of steamusing equipment. The entire system must be designed and hooked up to prevent accumulation of condensate at any point. Trap selection and safety factor for branch lines. The formula for computing condensate load is the same as that used for steam mains. Branch lines also have a recommended safety factor of 3:1. Installation. Recommended piping from the main to the control is shown in Fig. 19-1 for runouts under 10' and Fig. 19-2 for runouts over 10'. See Fig. 19-3 for piping when control valve must be below the main. Install a full pipe size strainer ahead of each control valve as well as ahead of the PRV if used. Provide blowdown valves, preferably with IB traps. A few days after starting system, examine the strainer screens to see if cleaning is necessary.
Separators
Steam separators are designed to remove any condensate that forms within steam distribution systems. They are most often used ahead of equipment where especially dry steam is essential. They are also common on secondary steam lines, which by their very nature, have a large percentage of entrained condensate. Important factors in trap selection for separators are the ability to handle slugs of condensate, provide good resistance to hydraulic shock and operate on light loads. Trap selection and safety factors for separators. Apply a 3:1 safety factor in all cases, even though different types of traps are recommended, depending on condensate and pressure levels. Use the following formula to obtain the required trap capacity:
Required trap capacity in lbs/hr = safety factor x steam flow rate in lbs/hr x anticipated percent of condensate (typically 10% to 20%). EXAMPLE: What size steam trap will be required on a flow rate of 10,000 lbs/hr? Using the formula: Required trap capacity = 3 x 10,000 x 0.10 = 3,000 lbs/hr. The inverted bucket trap with large vent is recommended for separators. When dirt and hydraulic shock are not significant problems, an F&T type trap is an acceptable alternative. An automatic differential condensate controller may be preferred in many cases. It combines the best features of both of the above and is recommended for large condensate loads which exceed the separating capability of the separator.
Installation
Branch Lines 10' or Less Pitch 1/2" per 1 ft Connect traps to the separator drain line 10" to 12" below the separator with the drain pipe running the full size of the drain connection down to the trap take-off (Fig. 19-4). The drain pipe and dirt pocket should be the same size as the drain connection.
Figure 19-1. Piping for runout less than 10 ft. No trap required unless pitch back to supply header is less than " per ft.
Steam Separator
Steam Separator
Shutoff Valve
10"-12"
6" IBLV or DC Figure 19-2. Piping for runout greater than 10'. Drip leg and trap required ahead of control valve. Strainer ahead of control valve can serve as drip leg if blowdown connection runs to an inverted bucket trap. This will also minimize the strainer cleaning problem. Trap should be equipped with an internal check valve or a swing check installed ahead of the trap. Figure 19-3. Regardless of the length of the runout, a drip leg and trap are required ahead of the control valve located below steam supply. If coil is above control valve, a trap should also be installed at downstream side of control valve. Figure 19-4. Drain downstream side of separator. Full size drip leg and dirt pocket are required to assure positive and fast flow of condensate to the trap.
19
Check Valve Freeze Protection Drain Table 20-1. Pipe Size Conversion Table (Divide lineal feet of pipe by factor given for size and type of pipe to get square feet of surface.)
Iron Pipe 4.55 3.64 2.90 2.30 2.01 1.61 1.33 1.09 .848
Copper or Brass Pipe 7.63 5.09 3.82 3.05 2.55 1.91 1.52 1.27 .954
/4
1 1 /4
1
* IB
Tracer Lines
*Select a " steam trap orifice to conserve energy and avoid plugging with dirt and scale.
A, B, C, L, J, N, I, K
Thermostatic or CD
11/2 2 21/2 3 4
20
EXAMPLE: Three tracer lines at 100 psig steam pressure are used on a 20" diameter, 100' long insulated pipe to maintain a temperature of 190F with an outdoor design temperature of -10F. Assume further the pipe insulation is 75% efficient. What is the condensate load?
On most tracer line applications, the flow to the steam trap is surprisingly low, therefore, the smallest trap is normally adequate. Based on its ability to conserve energy by operating reliably over a long period of time, handle light loads, resist freezing
Installation
Install distribution or supply lines at a height above the product lines requiring steam tracing. For the efficient drainage of condensate and purging of noncondensables, pitch tracer lines for gravity drainage and trap all low spots. This will also help avoid tracer line freezing. (See Figs. 20-1, 20-2 and 21-1.) To conserve energy, return condensate to the boiler. Use vacuum breakers immediately ahead of the traps to assure drainage on shutdown on gravity drain systems. Freeze protection drains on trap discharge headers are suggested where freezing conditions prevail.
Using the formula: Q = 100 ft x 2.44 Btu/sq ft - F - hr x 200F x .25 = 72 lbs/hr 0.191 lin ft/sq ft x 880 Btu/lb Now divide by three in order to get the load per tracer line24 lbs/hr. and purge the system, an inverted bucket trap is recommended for tracer line service. Safety factor. Use a 2:1 safety factor whether exposure to ambient weather conditions is involved or not. Do not oversize steam traps or tracer lines. Select a 5/64"steam trap orifice to conserve energy and avoid plugging with dirt and scale.
Chart 21-1. Btu Heat Loss Curves Unit heat loss per sq ft of surface of uninsulated pipe of various diameters (also flat surface) in quiet air at 75F for various saturated steam pressures or temperature differences.
150 160 11 10 9 8 7 6 5 4.5 4.0 3.5 3.3 3.0 2.8 2.6 2.5 2.4 2.3
1" 2"
700 900 1050 11 10 9 8 7 6 5 4.5 4.0 3.5 3.3 3.0 2.8 2.6
Vacuum Breaker
3"
5" 6"
10"
S AT FL
FA UR
S CE
2.2 2.15
PSIG
21
MULTIPLIER
10 8 7 6 5 4 2 5
10 8 7
ORDIN
ARY S
PACE
HEATI
NG
5 4
10
15
25
50
100 125
180
250
Constant Pressure
0-30 psig IBLV F&T IBLV F&T IBLV Above 30 psig IBLV *F&T IBLV *F&T IBLV
MULTIPLIER
12
FORCED
AIR CIR
12
Variable Pressure
Above 30 psig *F&T IBLV *F&T IBLV F&T IBLV
*Use IBLV above F&T pressure/temperature limitations. PLEASE NOTE: 1. Provide vacuum breaker wherever subatmospheric pressures occur. 2. Do not use F&T traps on superheated steam.
22
2. From Chart 22-1 find the multiplier for your service conditions. 3. Multiply normal condensate load by multiplier to get trap required continuous discharge capacity. Note that the safety factor is included in the multiplier. Finned radiation. When Btu output is not known, condensing rates can be computed from Tables 24-2 and 24-4 with sufficient accuracy for trap selection purposes. To enter Table 24-4, observe size of pipe, size of fins, number of fins and material. Determine condensing rate per foot under standard conditions from Table 24-4. Convert to actual conditions with Table 24-2. Safety factor recommendations are to: 1. Overcome the short circuiting hazard created by the multiple tubes of the heater. 2. Ensure adequate trap capacity under severe operating conditions.
In extremely cold weather the entering air temperature is likely to be lower than calculated, and the increased demand for steam in all parts of the plant may result in lower steam pressures and higher return line pressuresall of which cut trap capacity. 3. Ensure the removal of air and other non-condensables. WARNING: For low pressure heating, use a safety factor at the actual pressure differential, not necessarily the steam supply pressure, remembering the trap must also be able to function at the maximum pressure differential it will experience.
Installation
In general, follow the recommendations of the specific manufacturer. Figs. 23-1, 23-2, 23-3, and 23-4 represent the consensus of space heating manufacturers. NOTE: For explanation of safety drain trap, see Fig. 42-1.
Strainer
10" to 12"
Gate Valve
Check Valve
IB Trap
Return
Return Main
Primary Trap
Figure 23-3. Generally approved method of piping and trapping high pressure (above 15 psi) horizontal discharge heaters. Figs. 23-3 and 23-4 drip leg should be 10"-12" minimum.
Strainer
10" to 12"
IB Trap
Return
Primary Trap
Figure 23-4. Generally approved method of piping and trapping low pressure (under 15 psi) vertical discharge heaters.
23
Table 24-1. A Table of Constants for determining the Btu output of a unit heater with conditions other than standardstandard being with 2 lbs steam pressure at 60F entering air temperature. To apply, multiply the standard Btu capacity rating of heater by the indicated constant. (Reprinted from ASHRAE Guide by special permission.)
Steam Pressure lbs per sq in 2 5 10 15 20 30 40 50 60 70 75 80 90 100 Latent Heat of Steam 966.3 960.7 952.4 945.5 939.3 928.5 919.3 911.2 903.9 897.3 893.8 891.1 885.4 880.0 Entering Air Temperature F -10 1.640 1.730 1.799 1.861 1.966 2.058 2.134 2.196 2.256 2.283 2.312 2.361 2.409 0 1.550 1.639 1.708 1.769 1.871 1.959 2.035 2.094 2.157 2.183 2.211 2.258 2.307 10 1.456 1.545 1.614 1.675 1.775 1.862 1.936 1.997 2.057 2.085 2.112 2.159 2.204 20 1.370 1.460 1.525 1.584 1.684 1.771 1.845 1.902 1.961 1.990 2.015 2.063 2.108 30 1.289 1.375 1.441 1.498 1.597 1.683 1.755 1.811 1.872 1.896 1.925 1.968 2.015 40 1.155 1.206 1.290 1.335 1.416 1.509 1.596 1.666 1.725 1.782 1.808 1.836 1.880 1.927 50 1.078 1.127 1.211 1.275 1.333 1.429 1.511 1.582 1.640 1.696 1.721 1.748 1.792 1.836 60 1.000 1.050 1.131 1.194 1.251 1.346 1.430 1.498 1.555 1.610 1.635 1.660 1.705 1.749 70 0.926 0.974 1.056 1.117 1.174 1.266 1.349 1.416 1.472 1.527 1.552 1.577 1.621 1.663 80 0.853 0.901 0.982 1.043 1.097 1.190 1.270 1.338 1.393 1.447 1.472 1.497 1.541 1.581 90 0.782 0.829 0.908 0.970 1.024 1.115 1.194 1.262 1.314 1.368 1.392 1.418 1.461 1.502 100 0.713 0.760 0.838 0.897 0.952 1.042 1.119 1.187 1.239 1.293 1.316 1.342 1.383 1.424
Table 24-2. Finned Radiation Conversion Factors for steam pressures and air temperatures other than 65F air and 215F steam.
Steam Pressure (psig)
.9 5 10 15 30 60 100 125 175
Table 24-4. Finned Radiation Condensing Rates with 65F Air and 215F Steam (for trap selection purposes only).
Pipe Size (in) 11/4 Fin Size (in) 31/4 Fins per Inch 3 to 4 No. of Pipes High on 6" Centers 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Condensate lbs/hr per Foot of Pipe 1.1 2.0 2.6 1.6 2.4 3.1 1.5 2.4 3.1 1.6 2.2 2.8 2.2 3.0 3.6
55
1.11 1.22 1.33 1.43 1.66 2.00 2.31 2.47 2.74
65
1.00 1.11 1.22 1.31 1.54 1.87 2.18 2.33 2.60
70
.95 1.05 1.17 1.26 1.48 1.81 2.11 2.27 2.54
75
.90 1.00 1.11 1.20 1.42 1.75 2.05 2.21 2.47
80
.84 .95 1.05 1.14 1.37 1.69 2.00 2.16 2.41
90
.75 .81 .91 1.00 1.21 1.51 1.81 1.96 2.21
11/4
41/4
3 to 4
41/4
2 to 3
31/4
11/4
41/4
sq ft per Lineal ft
.220 .275 .344 .434 .497 .622 .753 .916 1.047 1.178
30 204
.15 .19 .23 .28 .32 .40 .47 .56 .63 .70
60 237
.19 .24 .28 .36 .41 .50 .59 .70 .80 .89
125 283
.26 .33 .39 .49 .55 .68 .81 .96 1.08 1.21
180 310
.30 .38 .46 .57 .65 .80 .95 1.13 1.27 1.43
250 336
.35 .45 .54 .67 .76 .93 1.11 1.31 1.50 1.72
/2
3 /4
24
EXAMPLE: What would be the condensate load on a tunnel dryer coil handling 2,000 CFM of air and requiring a 100F temperature rise? The steam pressure is 45 psig. Using the formula: Q = 2,000 x .24 x .075 x 60 x 100 915 Q = 236 lbs/hr Multiplying by a safety factor of 2which is recommended for all constant pressure process air heatersindicates that a trap with a capacity of 472 lbs/hr will be required. This is based on one coil. For higher air temperature rises, additional coils in series may be required.
Where: Q = Condensate load in lbs/hr F = Cubic feet of air per minute Cp = Specific heat of air in Btu/lbF (from Table 50-2) d = Density of air.075 lbs/cu ft T = Temperature rise in F H = Latent heat of steam in Btu/lb (Steam Tables, page 2)
Safety Factors
For constant steam pressure, use a safety factor of 2:1 at operating pressure differential. For modulating steam pressure, use a safety factor of 3:1 at of maximum pressure differential across the trap.
Installation
Air Vent Give piping for an entire piece of process air heating equipmentincluding all steam trap connectionsadequate allowance for expansion due to the wide temperature variations. Mount traps 10"-12" below the coils with a dirt pocket of at least 6". On both constant and modulated pressure heaters, install a vacuum breaker between the coil and the steam trap. Install an air vent on each coil to remove air and other non-condensables that can cause rapid corrosion. See Fig. 25-1. Consider a safety drain if condensate is elevated after the trap or if back pressure is present. See page 42 for piping diagram and explanation.
Air Vent
Constant Pressure
0-30 psig IB *F&T Above 30 psig IB IB
Variable Pressure
0-30 psig F&T IBLV Above 30 psig *F&T IBLV
* The pressure break point for F&T traps may be somewhat different in some models and sizes. PLEASE NOTE: 1. Provide vacuum breaker wherever subatmospheric pressures occur. 2. Do not use F&T traps on superheated steam.
25
How to Trap Shell & Tube Heat Exchangers & Submerged Coils
Submerged coils are heat transfer elements which are immersed in the liquid to be heated, evaporated or concentrated. This type of coil is found in virtually every plant or institution which uses steam. Common examples are water heaters, reboilers, suction heaters, evaporators, and vaporizers. These are used in heating water for process or domestic use, vaporizing industrial gases such as propane and oxygen, concen-trating in-process fluids such as sugar, black liquor and petroleum and heating fuel oil for easy transfer and atomization. dirt and slugs of condensate. Three standard methods of sizing help determine the proper type and size traps for coils. III. For constant or modulating steam pressure with syphon drainage. An automatic differential condensate controller with a safety factor of 3:1 should be used. An alternate is an IBLV with a 5:1 safety factor. Apply the safety factor at full differential on constant steam pressure. Apply the safety factor at one half maximum differential for modulating steam pressure.
Safety Factor
I. Constant Steam Pressure. INVERTED BUCKET TRAPS OR F&T TRAPSuse a 2:1 safety factor at operating pressure differentials. II. Modulating Steam Pressure. F&T TRAPS OR INVERTED BUCKET TRAPS. 1. 0-15 psig steam2:1 at psi pressure differential (on F&T traps SHEMA ratings can also be used). Different application requirements involving 2. 16-30 psig steam2:1 at 2 psi constant or variable steam pressure deterpressure differential. mine which type of trap should be used. 3. Above 30 psig steam3:1 at of Trap selection factors include the ability to maximum pressure differential handle air at low differential pressures, across the trap. energy conservation and the removal of
Figure 26-1. Shell And Tube Heat Exchangers (Typical Piping Diagram)
Steam Main By-Pass Strainer Modulating Steam Control Valve Heat Exchanger (Steam in Shell) Cold Water In Use Safety Drain F&T Trap When Going to Overhead Return. See Page 42 for Explanation. Air Vent Drain Alternate to Overhead Return To Low Pressure Return
To Drain
Primary Trap
Constant Pressure
0-30 psig IBLV DC F&T Above 30 psig IBLV DC *F&T
Variable Pressure
0-30 psig F&T3 DC IBT Above 30 psig *F&T3 DC IBLV
Alternate Choice
* Use IBLV above Pressure/Temperature Limitations PLEASE NOTE: 1. Provide vacuum breaker wherever subatmospheric pressures occur. 2. Provide a safety drain when elevating condensate on modulating service. 3. If dirt and large volumes of air must be handled, an inverted bucket trap with an external thermostatic air vent can be used effectively.
26
Rule of Thumb for Computing Condensing Rate for Water Heaters: Raising the temperature of 100 gallons of water 1F will condense one pound of steam.
Logarithmic mean temperature difference can be determined with slightly less accuracy using the nomograph, Chart 29-1. U values are determined by tests under controlled conditions. Tables 27-1 and 27-2 show the commonly accepted range for submerged embossed coils. For trap selection purposes, use a U value that is slightly greater than the conservative U value selected for estimating actual heat transfer. EXAMPLE: A = 20 sq ft of coil surface U = 175 Btu/sq ft-hr-F Conditions: Water in: 40F Water out: 150F Steam pressure: 125 psig or 353F D1 = 353 - 40, or 313 D2 = 353 - 150, or 203 Dividing by 4 to get within range of Chart 29-1, we have: D1 = 78.25 D2 = 50.75 Mean difference from chart is 63F. Multiplying by 4, the mean temperature difference for the original values is 252F. Substituting in the equation: Q = 20 x 175 x 252 = 882,000 Btu/hr Btu transferred per hour. Latent heat of steam at 125 psig = 867.6 882,000 = 1,016 lbs condensate per hr 867.6 Table 27-2. Embossed Coil U Values in Btu/hr-sq ft-F
Type of Service
Steam to Watery Solutions Steam to Light Oil Steam to Medium Oil Steam to Bunker C Steam to Tar Asphalt Steam to Molten Sulphur Steam to Molten Paraffin Steam to Molasses or Corn Syrup Dowtherm to Tar Asphalt
To determine trap capacity required, multiply condensing rate by the recommended safety factor.
Pipe Coils
Pipe coils are heat transfer tubes immersed in vessels which are large in volume compared to the coils themselves (Fig. 27-2). This is their primary difference when compared to shell and tube heat exchangers. Like embossed coils, they may be drained by gravity or syphon drained, depending on the conditions prevailing at the installation site. Unlike embossed coils, most pipe coils are installed in closed vessels.
Embossed Coils
Very often open tanks of water or chemicals are heated by means of embossed coils (Fig. 27-1). Upsetting grooves in the sheet metal of the two halves produce the spaces for the steam. When welded together the halves form the passages for steam entry, heat transfer and condensate evacuation. Trap Selection for Embossed Coils Calculate the condensate load on embossed coils with the following formula: Q = A x U x Dm Where: Q = Total heat transferred in Btu per hour A = Area of outside surface of coil in sq ft U = Overall rate of heat transfer in Btu per hr-sq ft-F. See Tables 27-1 and 27-2. Dm = Logarithmic mean temperature difference between steam and liquid (as between inlet and outlet of a heat exchanger) in F Dm = D1 - D2 Loge (D1)
(D2)
Installation
When gravity drainage is utilized on shell and tube heat exchangers, embossed coils and pipe coils, locate the steam trap below the heating coil. Under modulating pressure, use a vacuum breaker. This can be integral in F&T traps or mounted off the inlet piping on an inverted bucket trap. Place an ample drip leg ahead of the trap to act as a reservoir. This assures coil drainage when there is a maximum condensate load and a minimum steam pressure differential. Avoid lifting condensate from a shell and tube heat exchanger, embossed coil or pipe coil under modulated control. However, if it must be done, the following is suggested: 1. Do not attempt to elevate condensate more than one foot for every pound of normal pressure differential, either before or after the trap. 2. If condensate lift takes place after the steam trap, install a low pressure safety drain. (See page 42.) 3. If condensate lift takes place ahead of the steam trap (syphon lift), install an automatic differential condensate controller to efficiently vent all flash steam.
Type of Service
Steam to Water 1 " Tube Heaters
1/2 3/4
DC
IB Trap
IB Trap
Water Seal
For Pounds of Steam Condensed per sq ft per Hour of Submerged Coil Surface, see Chart 29-2.
dations
27
Single Effect
While the product is being forced through the tubes of the evaporator, heat is added to remove a specific amount of moisture. After this is completed, both the product vapor and the concentrated product are forced into the separating chamber where the vapor is drawn off and may be used elsewhere. The concentrate is then pumped off to another part of the process (Fig. 28-2).
Multiple Effect
In using the multiple effect method, there is a conservation of heat as steam from the boiler is used in the first effect, and then vapor generated from the product is used as the heat source in the second effect. The vapor generated here is then used as the heat source in the third effect and finally heats water for some other process or preheats the incoming feed (Fig. 28-1).
Steam
Concentrate
0-30 psig
DC IBLV F&T DC IBLV F&T
Above 30 psig
DC IBLV F&T DC IBLV F&T
Steam
Concentrate Feed
28
Installation
Because an evaporator is basically a shell and tube heat exchanger with the steam in the shell, there should be separate steam air vents on the heat exchanger. Place these vents at any area where there is a tendency for air to accumulate, such as in the quiet zone of the shell. Install a separate trap on each effect. While the condensate from the first effect may be returned to the boiler, condensate from each successive effect may not be returned to the boiler due to contamination from the product.
Use the following formula to compute heat transfer for constant steam pressure continuous flow heat exchangers. Q = A x U x Dm Where: Q = Total heat transferred in Btu per hour A = Area of outside surface of coil in sq ft U = Overall rate of heat transfer in Btu/hr-sq ft-F (See Charts 29-1 and 29-2) Dm = Logarithmic mean temperature difference between steam and liquid (as between inlet and outlet of a heat exchanger) in F Dm = D1-D2 Loge (D1)
(D2)
EXAMPLE: A = Heat transfer tubes: eight " OD tubes 12' long 8 x 12' = 20 sq ft of coil surface 5.09 (from Table 29-3)
Where: D1 = Greatest temperature difference D2 = Least temperature difference Logarithmic mean temperature difference can be estimated by using the nomograph, Chart 29-1.
U = 500 Btu/hr-sq ft-F Conditions: Water in: 40F Water out: 150F 125 psig or 353F steam pressure: D1 = 353F - 40F, or 313F D2 = 353F - 150F, or 203F Dividing by 4 to get within range of Chart 29-1, we have: D1 = 78.25F D2 = 50.75F Mean difference from chart is 63F. Multiplying by 4, the mean temperature difference for the original value is 252F. Substituting in the equation: Q = 20 x 500 x 252 = 2,520,000 Btu/hr transferred per hour Latent heat of steam at 125 psig = 867.6 2,520,000 = 2,900 lbs condensate per hour 867.6 To determine trap capacity required, multiply the condensing rate by the recommended safety factor.
Chart 29-1. Mean Temperature Difference Chart for Heat Exchange Equipment
D1 Equipment
100 90 80 70
LOGARITHIC MEAN TEMPERATURE DIFFERENCE
Chart 29-2. Pounds of Steam Condensed per sq ft per Hour of Submerged Coil Surface (See Conditions conversion factors below chart)
20 30 40 50 80 100 400 300 250 200 150 250 125 200 300 400 300 250 200 150 125 100 90 80 70 60 50 40 30 25
D2
100 90 80 70 60 55 50 45 40 35 30 25 20 15
POUNDS PER HR PER SQ FT OF SURFACE
100 90 80 70 60 55 50 45 40 35 30 25 20 15
60 55 50 45 40 35 30 25 20 15
Table 29-3. Pipe Size Conversion Table (Divide lineal feet of pipe by factor given for size and type of pipe to get square feet of surface)
Pipe Size (in)
1 /2 3
20 15
10
10
10
10
8 6
Iron Pipe
4.55 3.64 2.90 2.30 2.01 1.61 1.33 1.09 .848
30
50
100
/4
Connect greatest temperature difference on scale D1 with least temperature difference on scale D2 to read logarithmic mean temperature difference on center scale.
Condition Factors (Divide chart figures by proper factor) CONDITION FACTOR Will remain bright ___________________ 1 Moderate scale _____________________ 2 Liquid contains up to 25% solids _____ 3-5 Thick viscous liquids _______________ 4-8
29
EXAMPLE: What would be the recommended trap capacity for a 34" gravity drained kettle at 40 psig steam? Reading directly from the chart, a trap with a capacity of 1,704 lbs/hr at the operating pressure is required. For an alternative method of determining condensate, use the following formula: G x sg x Cp x T x 8.3 Q = Hxt Where: Q = Condensate loads (lbs/hr) G = Gallons of liquid to be heated sg = Specific gravity of the liquid Cp = Specific heat of the liquid T = Temperature rise of the liquid F 8.3= lbs/gal of water H = Latent heat of the steam (Btu/lb) t = Time in hours for product heating
A second basic concern in the use of steam jacketed kettles is the need for a steady, thorough removal of condensate. An accumulation of condensate in the jacket leads to unreliable temperature control, reduces the output of the kettle and causes water hammer.
Figure 30-1. Fixed Gravity Drained Kettle Control Valve Thermostatic Air Vent Strainer Air Discharge to Drain or Return Line Steam In
Rotary Joint
Steam Trap
DC Steam In
To Return Line
Alternate Choice
F&T or Thermostatic IBLV
30
EXAMPLE: Select a trap for a 250-gallon kettle using 25 psig steam to heat a product with a specific gravity of 0.98 and a specific heat of 0.95 Btu/lb-F. Starting at room temperature of 70F, the product will be heated to 180F in one-half hour. (Assume 3:1 safety factor.) Using the formula: Q = 250 gal x 0.98 x 0.95 Btu/lb-F x 110F x 8.3 lbs/gal = 212,500 = 455 lbs/hr 933 Btu/lb x 0.5 hr 466.5 Now simply multiply by a safety factor of 3 to get 1,365 lbs/hr of condensate and select the proper type and capacity trap. Based on the standard requirements and problems involved with fixed gravity drain kettles, the most efficient type trap to use is the inverted bucket. The inverted bucket trap vents air and CO2 at steam temperature and provides total efficiency against back pressure. The primary recommendation for tilting syphon drain kettles is the automatic differential condensate controller. In addition to providing the same features as the IB, the DC offers excellent air venting ability at very low pressure and excellent flash steam handling ability. If an IB trap is selected for syphon drained service, use a trap one size larger.
Installation
Install traps close to the kettle. You can further increase the dependability and air-handling capability by installing a thermostatic air vent at high points in the jacket. See Figs. 30-1 and 30-2. Never drain two or more kettles with a single trap. Group drainage will invariably result in short circuiting.
Table 31-1. Condensate Rates In lbs/hr For Jacketed KettlesHemispherical Condensing Surface Safety factor 3:1 is included Assume U = 175 Btu/hr-sq ft-F, 50F starting temperature
Kettle Diameter (in) 18 19 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 54 60 72 Heat Transfer Surface (sq ft) U.S. Gallons of Water in Hemisphere 7 8 9 12 16 20 25 31 37 45 53 62 73 84 97 110 123 178 245 423 U.S. Gals. Water per in. of Height Above Hemisphere 1.10 1.20 1.35 1.65 1.95 2.30 2.65 3.05 3.50 3.95 4.40 4.90 5.45 6.00 6.60 7.20 7.85 9.90 12.30 17.70 STEAM PRESSURE 5 psig 227F 339 378 420 513 609 717 822 948 1086 1221 1365 1521 1686 1860 2043 2229 2451 3076 3798 5469 10 psig 240F 366 408 456 555 660 774 891 1026 1173 1320 1476 1644 1821 2010 2208 2409 2649 3324 4104 5910 15 psig 250F 387 432 483 588 699 822 942 1089 1242 1398 1566 1743 1932 2130 2343 2553 2808 3523 4350 6264 25 psig 267F 426 477 531 648 768 903 1038 1197 1368 1539 1722 1917 2124 2343 2577 2808 3087 3875 4785 6890 40 psig 287F 474 528 588 717 852 1002 1149 1326 1515 1704 1908 2124 2355 2598 2856 3111 3423 4296 5304 7638 60 psig 307F 522 582 651 792 942 1107 1269 1464 1674 1881 2106 2346 2601 2868 3153 3435 3780 4743 5856 8433 80 psig 324F 564 630 702 855 1017 1194 1371 1581 1809 1944 2277 2535 2808 3099 3405 3711 4083 5125 6327 9111 100 psig 338F 603 669 747 912 1083 1272 1461 1686 1926 2166 2424 2700 2991 3300 3627 3954 4350 5458 6738 9703 125 psig 353F 642 714 798 972 1155 1356 1557 1797 2052 2310 2586 2877 3189 3519 3867 4215 4638 5820 7185 10346
3.50 3.90 4.35 5.30 6.30 7.40 8.50 9.80 11.20 12.60 14.10 15.70 17.40 19.20 21.10 23.00 25.30 31.70 39.20 56.40
31
Installation
Although the condensate load on each platen is small, individual trapping is essential to prevent short circuiting, Fig. 32-1. Individual trapping assures maximum and uniform temperature for a given steam pressure by efficiently draining the condensate and purging the non-condensables.
Alternate Choices
CD and Thermostatic
Where: Q = Condensate load in lbs/hr W = Weight of the material in lbs C = Specific heat of the material in Btu/lb-F (See page 50) T = Material temperature rise in F H = Latent heat of steam in Btu/lb (See Steam Tables on page 2) t = Time in hours EXAMPLE: What will be the condensate load on an autoclave containing 300 lbs of rubber product which must be raised to a temperature of 300F from a starting temperature of 70F? The autoclave operates at 60 psig steam pressure and the heat-up process takes 20 minutes. Using the formula: Q = 300 lbs x .42 Btu/lb-F x 230F = 96 lbs/hr 904 Btu/lb x .33 hr Multiply by a recommended safety factor of 3:1 to get the required capacity288 lbs/hr.
*IB B, N, K, E, A
*IB B, K, E, A
*An auxiliary air vent is recommended. **First choice on large volume vessels.
32
Since steam is in contact with the product you can anticipate dirty condensate. In addition, the vessel is a large volume chamber which requires special consideration in the purging of condensate and non-condensables. For these reasons an inverted bucket trap with an auxiliary thermostatic air vent installed at the top of the chamber is recommended. Where no remote thermostatic air vent can be installed, incorporate the large volume air purging capabilities in the steam trap itself. An automatic differential condensate controller should be considered a possible first choice on large chambers. As an alternative, an F&T or thermostatic trap should be used and be preceded by a strainer, the latter receiving regular checks for free flow.
Installation
As the steam and condensate is in contact with the product, the trap discharge should almost always be disposed of by some means other than return to the boiler. In virtually all cases this equipment is gravity drained to the trap. However, very often there is a condensate lift after the trap. As steam pressure is usually constant, this does not present a problem. For thorough air removal and quicker warm-up, install a thermostatic air vent at a high point of the vessel. See Fig. 33-1.
Trap Selection and Safety Factor Size steam traps for product in chambersteam in jacket equipment by using the same formula outlined for direct steam injection. The safety factor is also 3:1. The inverted bucket trap is recommended because it conserves steam, purges the system and resists hydraulic shock. Use the IB trap in combination with a thermostatic air vent at the top of the chamber for greater air-handling capability. As an alternate an F&T or thermostatic trap could be used. On large chambers, where its not possible to install the air vent, an automatic differential condensate controller should be considered a possible first choice.
Installation
With product in chambersteam in jacket equipment, the steam and condensate do not come in contact with the product and can be piped to the condensate return system. Where possible, install an auxiliary thermostatic air vent at a remote high point on the steam chamber. See Fig. 33-2.
Figure 33-1. Direct Steam Injection Into Product Chamber Steam Control Valve Air Vent
Figure 33-2. Product in ChamberSteam in Jacket Steam Control Valve Air Vent
Strainer
Steam Trap
Steam Trap
33
Trap Selection Condensate loads can be determined by use of the following formula: Q = 3.14D x R x W Where: Q = Condensate load in lbs/hr D = Diameter of the dryer in ft R = Rate of condensation in lbs/sq ft-hr W = Width of dryer in ft EXAMPLE: Determine the condensate load of a dryer 5 ft in diameter, 10 ft in width and a condensing rate of 7 lbs/sq ft-hr. Using the formula: Condensate load = 3.14(5) x 7 x 10 = 1,100 lbs/hr Based on its ability to handle flash steam, slugs of condensate and purge the system, a DC is the recommended first choice. An IBLV may be adequate if proper sizing procedures are followed.
Rotary Joint
10"-12"
Steam Trap
6"
A revolving cylinder drained with a syphon an internal syphon surrounded by steam. Some condensate flashes back to steam due to the steam jacketed syphon pipe and syphon lifting during evacuation.
Alternate Choice
IBLV*
*On constant pressure use 8:1 safety factor, and on modulated pressure use 10:1.
34
Trap Selection The condensate load generated by these dryers can be determined through use of the following formula: Q = NxLxR P Where: Q = Condensate in lbs/hr N = Number of tubes L = Length of tubes in ft R = Condensing rate in lbs/sq ft-hr (typical 6-9 lbs/sq ft-hr) P = Lineal feet of pipe per sq ft of surface (see Table 35-1)
EXAMPLE: What will be the condensate load on a rotary cooker containing 30 1 " steel pipes 12' in length with a condensing rate of 8 lbs/sq ft-hr? Using the formula:
Q = 30 x 12 x 8 = 1,252 lbs/hr 2.30 A differential controller is recommended on these dryers for its purging and flash steam handling ability. The IBLV again requires proper sizing for certain applications.
Installation
In all cases, condensate drainage is accomplished through a rotary joint, Figs. 34-1 and 35-1. The DC should then be located 10"-12" below the rotary joint with an extended 6" dirt pocket. These provide a reservoir for surges of condensate and also a pocket for entrained scale.
Table 35-1. Pipe Size Conversion Table (Divide lineal feet of pipe by factor given for size and type of pipe to get square feet of surface)
Pipe Size (in)
1 /2 3/4
Iron Pipe 4.55 3.64 2.90 2.30 2.01 1.61 1.33 1.09 .848
Copper or Brass Pipe 7.63 5.09 3.82 3.05 2.55 1.91 1.52 1.27 .954
Rotary Joint
10"-12"
1 11/4 11/2
DC
6"
2 21/2 3 4
A revolving cylinder drained with a syphon an internal syphon surrounded by steam. Some condensate flashes back to steam due to the steam jacketed syphon pipe and syphon lifting during evacuation.
35
Where: Q = Condensate load in lbs/hr (to be handled by steam trap) L = Condensate flow into flash tank in lbs/hr P = Percentage of flash EXAMPLE: Determine the condensate load of a flash tank with 5,000 lbs/hr of 100 psig condensate entering the flash tank held at 10 psig. From page 3, the flash percentage is P = 10.5%. Using the formula: Q = 5,000 - (5,000 x .105) = 4,475 lbs/hr Due to the importance of energy conservation and operation against back pressure, the trap best suited for flash steam service is the inverted bucket type with large bucket vent. In addition, the IB operates intermittently while venting air and CO2 at steam temperature. In some cases, the float and thermostatic type trap is an acceptable alternative. One particular advantage of the F&T is its ability to handle heavy start-up air loads.
Alternate Vent Location CV Relief Valve Gauge To Low Pressure Steam Use
Air Vent To Drain Flash steam tank with live steam make-up, showing recommended fittings and connections. The check valves in the incoming lines prevent waste of flash when a line is not in use. The by-pass is used when flash steam cannot be used. Relief valves prevent pressure from building up and interfering with the operation of the high pressure steam traps. The reducing valve reduces the high pressure steam to the same pressure as the flash, so they can be combined for process work or heating. High Pressure Condensate Return Line
Flash Tank
Refer to Chart 3-1 (page 3) for percentage of flash steam formed when discharging condensate to reduced pressure.
A third type of device which may be the preferred selection in many cases is the automatic differential condensate controller. It combines the best features of both of the above and is recommended for large condensate loads which exceed the separating capability of the flash tank.
Safety Factor
The increased amount of condensate at start-up and the varying loads during operation accompanied by low pressure differential dictates a safety factor of 3:1 for trapping flash tanks.
Flash Tanks
F&T or *DC
*Recommended where condensate loads exceed the separating capability of the flash tank.
36
Installation
Condensate return lines contain both flash steam and condensate. To recover the flash steam, the return header runs to a flash tank, where the condensate is drained, and steam is then piped from the flash tank to points of use, Fig. 36-1. Since a flash tank causes back pressure on the steam traps discharging into the tank, these traps should be selected to ensure their capability to work against back pressure and have sufficient capacity at the available differential pressures. Condensate lines should be pitched toward the flash tank and where more than one line feeds into a flash tank, each line should be fitted with a swing check valve. Then, any line not in use will be isolated from the others and will not be fed in reverse with resultant wasted flash steam. If the trap is operating at low pressure, gravity drainage to the condensate receiver should be provided. Generally the location chosen for the flash tank should meet the requirement for maximum quantity of flash steam and minimum length of pipe. Condensate lines, the flash tank, and the low pressure steam lines should be insulated to prevent waste of flash through radiation. The fitting of a spray nozzle on the inlet pipe inside the tank is not recommended. It may become choked, stop the flow of condensate, and produce a back pressure to the traps. Low pressure equipment using flash steam should be individually trapped and discharged to a low pressure return. Large volumes of air need to be vented from the flash tank, therefore, a thermostatic air vent should be used to remove the air and keep it from passing through the low pressure system. The important dimension is the inside diameter. This should be such that the upward velocity of flash to the outlet is low enough to ensure that the amount of water carried over with the flash is small. If the upward velocity is kept low, the height of the tank is not important, but good practice is to use a height of two to three feet. It has been found that a steam velocity of about 10 feet per second inside the flash tank will give good separation of steam and water. On this basis, proper inside diameters for various quantities of flash steam have been calculated; the results are plotted in Chart 37-1. This curve gives the smallest recommended internal diameters. If it is more convenient, a larger size of tank may be used. Chart 37-1 does not take into consideration pressureonly weight. Although volume of steam and upward velocity are less at a higher pressure, because steam is denser, there is an increased tendency for priming. Thus it is recommended that, regardless of pressure, Chart 37-1 be used to find the internal diameter.
Figure 37-1. Flash Steam Recovery from an Air Heater Battery Flash is taken from the flash tank and combined with live steam, the pressure of which is reduced to that of the flash by a reducing valve.
Chart 37-1. Determination of Internal Diameter of Flash Tank to Handle a Given Quantity of Flash Steam Find amount of available flash steam (in pounds per hour) on bottom scale, read up to curve and across to vertical scale, to get diameter in inches.
30
25
Heater Battery
Air Flow
20
15
Flash Tank
10
1,000
Condensate
6,000
37
Installation
Mount the steam trap below the steam coil of the absorption machine with a drip leg height of at least 15" (Fig. 38-1). This assures a minimum differential pressure across the trap of 1/2 psi. Whichever trap is used, a standby trapping system is recommended for this service. In the event that a component in the drainage system needs maintenance, the absorption machine can operate on the standby system while the repairs are being made. This ensures continuous, uninterrupted service. In some cases very heavy condensate loads may require the use of two traps operating in parallel to handle the normal load.
Figure 38-1. Generally approved method of piping steam absorption machine with standby trapping system. Steam Supply 15 psig Single Stage 150 psig Two Stage H2O Vapor Steam
15"
*IB
NOTE: Vacuum breaker and standby system should be provided. *With external thermostatic air vent. F&T Trap w/Integral Vacuum Breaker Draining to Gravity Return
38
factors ensure proper operation under varying conditions. For more specific information on recommended traps
2nd Choice
F&T Wafer
1st Choice
IBLV IBCV Burnished
Safety Factor
1.5:1 Start-up Load
3:1 2:1 @ 1/2 psi Differential 2:1 @ 2 psi Differential 3:1 @ 1/2 Max. Pressure Differential
IB F&T
Thermostatic IB
3:1 for quick heating 2:1 normally 3:1 for quick heating 2:1 normally
IB F&T F&T
IB F&T
2:1 <15 psi 2:1 @ 1/2 psi, 16-30 psi 2:1 @ 2 psi, >30 psi 3:1 @ 1/2 Max. Pressure Differential 2:1, If Load 50,000 lbs/hr use 3:1 3:1 3:1 3:1 for DC, 8:1 for IB constant pressure, 10:1 for IB variable pressure 3:1
DC
IBLV DC DC IBLV
Use an IB with external air vent above the F&T pressure limitations or if the steam is dirty. All safety factors are at the operating pressure differential unless otherwise noted.
39
Check Valve
40
Strainers. Install strainers ahead of traps if specified or when dirt conditions warrant their use. Some types of traps are more susceptible to dirt problems than others see Recommendation Chart on gatefold. Some traps have built-in strainers. When a strainer blowdown valve is used, shut off steam supply valve before opening strainer blowdown valve. Condensate in trap body will flash back through strainer screen for thorough cleaning. Open steam valve slowly. Dirt Pockets are excellent for stopping scale and core sand, and eliminating erosion that can occur in elbows when dirt pockets are not provided. Clean periodically.
Syphon Installations require a water seal and, with the exception of the DC, a check valve in or before the trap. Syphon pipe should be one size smaller than nominal size of trap used but not less than 1/2" pipe size. Elevating Condensate. Do not oversize the vertical riser. In fact, one pipe size smaller than normal for the job will give excellent results. Check Valves are frequently needed. They are a must if no discharge line shutoff valve is used. Fig. 41-2 shows three possible locations for external check valvesArmstrong inverted bucket traps are available with internal check valves, while disc traps act as their own check valve. Recommended locations are given below. Figure 41-2. Possible Check Valve Locations A
Discharge Line Check Valves prevent backflow and isolate trap when test valve is opened. Normally installed at location B. When return line is elevated and trap is exposed to freezing conditions, install check valve at location A, Fig. 41-2. Inlet Line Check Valves prevent loss of seal if pressure should drop suddenly or if trap is above drip point in IB traps. Armstrong Stainless Steel Check Valve in trap body, location D, is recommended. If swing check is used, install at location C, Fig. 41-2.
B D
Valve Test Valve Test Valve Union Plug Check Valve Valve Valve Union
Test Valve
Dirt Pocket
41
A safety drain trap should be used whenever there is a likelihood that the inlet pressure will fall below the outlet pressure of a primary steam trap, especially in the presence of freezing air. One such application would be on a modulated pressure heating coil that must be drained with an elevated return line. In the event of insufficient drainage from the primary trap, condensate rises into the safety drain and is discharged before it can enter the heat exchanger. An F&T trap makes a good safety drain because of its ability to handle large amounts of air and its simplicity of operation. Safety drain trap should be same size (capacity) as primary trap. The proper application of a safety drain is shown in Fig. 42-1. The inlet to the safety drain must be located on the heat exchanger drip leg, above the inlet to the primary trap. It must discharge to an open sewer. The drain plug of the safety drain is piped to the inlet of the primary trap. This prevents the loss of condensate formed in the safety drain by body radiation when the primary trap is active. The safety drain has an integral vacuum breaker to maintain operation when pressure in the heat exchanger falls below atmospheric. The inlet of the
vacuum breaker should be fitted with a goose neck to prevent dirt from being sucked in when it operates. The vacuum breaker inlet should be provided with a riser equal in elevation to the bottom of the heat exchanger to prevent water leakage when the vacuum breaker is operating, but the drip leg and trap body are flooded.
Anti-Freeze Precautions. 1. Do not oversize trap. 2. Keep trap discharge lines very short. 3. Pitch trap discharge lines down for fast gravity discharge. 4. Insulate trap discharge lines and condensate return lines. 5. Where condensate return lines are exposed to ambient weather conditions, tracer lines should be considered. 6. If the return line is overhead, run vertical discharge line adjacent to drain line totop of return header and insulate drain line and trap discharge line together. See Fig. 42-2. NOTE: A long horizontal discharge line invites trouble. Ice can form at far end eventually sealing off the pipe. This prevents the trap from operating. No more steam can enter the trap, and the water in the trap body freezes.
Figure 42-2.
Check Valve
A 4" Typical
Outdoor installation to permit ground level trap testing and maintenance when steam supply and return lines are high overhead. Drain line and trap discharge line are insulated together to prevent freezing. Note location of check valve in discharge line and blowdown valve A that drains the steam main when trap is opened for cleaning or repair.
42
How to Test
The test valve method is best. Fig. 40-1 shows correct hookup, with shutoff valve in return line to isolate trap from return header. Here is what to look for when test valve is opened:
1. Condensate DischargeInverted bucket and disc traps should have an intermittent condensate discharge. F&T traps should have a continuous condensate discharge, while thermostatic traps can be either continuous or intermittent, depending on the load. When an IB trap has an extremely small load it will have a continuous condensate discharge which causes a dribbling effect. This mode of operation is normal under this condition. 2. Flash SteamDo not mistake this for a steam leak through the trap valve. Condensate under pressure holds more heat unitsBtuper pound than condensate at atmospheric pressure. When condensate is discharged, these extra heat units reevaporate some of the condensate. See description of flash steam on page 3. How to Identify Flash: Trap users sometimes confuse flash steam with leaking steam. Heres how to tell the difference: If steam blows out continuously, in a blue stream, its leaking steam. If steam floats out intermittently (each time the trap discharges) in a whitish cloud, its flash steam. 3. Continuous Steam BlowTrouble. Refer to page 44. 4. No FlowPossible trouble. Refer to page 44.
Listening Device Test. Use a listening device or hold one end of a steel rod against trap cap and other end against ear. You should be able to hear the difference between the intermittent discharge of some traps and the continuous discharge of others. This correct operating condition can be distinguished from the higher velocity sound of a trap blowing through. Considerable experience is required for this method of testing as other noises are telegraphed along the pipe lines. Pyrometer Method Of Testing. This method may not give accurate results depending on the return line design and the diameter of the trap orifice. Also, when discharging into a common return, another trap may be blowing through causing a high temperature at the outlet of the trap being tested. Better results can be obtained with a listening device. Request Armstrong Bulletin 310.
Test Valve
Test Valve
43
44
Pipe Sizing
Two principal factors determine pipe sizing in a steam system: 1. The initial pressure at the boiler and the allowable pressure drop of the total system. The total pressure drop in the system should not exceed 20% of the total maximum pressure at the boiler. This includes all drops line loss, elbows, valves, etc. Remember, pressure drops are a loss of energy.
6 15 31 68 100 210 350 650 970 1,370 2,540 4,170 8,680 15,840 25,420
9 21 44 97 150 300 500 920 1,370 1,940 3,600 5,910 12,310 22,460 36,050
11 26 54 120 180 370 610 1,130 1,680 2,380 4,410 7,250 15,090 27,530 44,190
13 30 62 140 210 430 710 1,300 1,940 2,750 5,090 8,360 17,400 31,760 50,970
8 20 40 89 139 282 465 853 1,275 1,800 3,320 5,475 11,360 20,800 33,300
/4 12 28 57 127 197 282 660 1,205 1,800 2,550 4,710 7,725 16,100 29,400 47,100
/2 17 40 81 179 279 565 930 1,690 2,550 3,610 6,660 10,950 22,800 41,500 66,700
3/4
1 25 57 115 253 395 800 1,318 2,410 3,605 5,100 9,440 15,450 32,200 58,900 94,500
2 35 81 163 358 558 1,130 1,860 3,410 5,090 7,220 13,300 21,900 45,550 83,250 133,200
5 55 128 258 567 882 1,790 2,940 5,400 8,060 11,400 21,100 34,600 72,100 131,200 210,600
21 49 100 219 342 691 1,140 2,090 3,120 4,462 8,150 13,420 27,900 51,000 81,750
1
16 37 76 160 260 520 860 1,570 2,350 3,330 6,160 10,120 21,060 38,430 61,690
5 13 27 59 91 180 300 560 830 1,180 2,180 3,580 7,450 13,600 21,830
8 18 38 83 130 260 430 790 1,180 1,660 3,080 5,060 10,530 19,220 30,840
11 26 53 120 180 370 600 1,110 1,660 2,350 4,350 7,150 14,880 27,150 43,570
14 32 65 140 220 450 740 1,360 2,040 2,880 5,330 8,750 18,220 33,250 53,370
23 52 110 230 360 740 1,210 2,220 3,320 4,700 8,700 14,290 29,740 54,270 87,100
21 50 100 220 340 690 1,140 2,090 3,120 4,420 8,170 13,420 27,930 50,970 81,810
1 30 70 140 310 480 980 1,620 2,960 4,420 6,260 11,580 19,020 39,580 72,230 115,900
2 43 99 200 440 680 1,390 2,280 4,180 6,250 8,840 16,350 26,840 55,870 101,900 163,600
5 68 160 320 690 1,080 2,190 3,610 6,610 9,870 13,960 25,840 42,410 88,280 161,100 258,500
7 16 32 70 110 223 368 675 990 1,420 2,625 4,315 9,000 16,400 26,350
10 22 45 99 156 316 520 953 1,405 2,020 3,720 6,100 12,700 23,200 37,250
/2 14 32 64 142 220 446 735 1,340 2,010 2,850 5,260 8,650 18,000 33,300 52,500
3/4
1
19 45 91 202 312 630 1,040 1,905 2,850 4,025 7,450 12,200 25,420 46,500 74,500
2
28 64 129 283 440 892 1,472 2,690 4,020 5,700 10,550 17,300 36,000 65,750 105,500
1 33 77 155 341 532 1,075 1,775 3,245 4,850 6,850 12,700 20,800 43,400 79,100 127,100
2 47 109 220 483 751 1,520 2,550 4,590 6,850 9,700 17,950 29,500 61,400 112,000 179,600
5 75 172 347 764 1,185 2,410 3,960 7,260 10,880 15,350 28,400 46,500 97,100 177,000 284,100
17 39 79 174 270 546 900 1,652 2,470 3,490 6,450 10,600 22,000 40,250 64,500
23 54 109 241 375 760 1,250 2,280 3,430 4,840 8,950 14,710 30,650 56,000 89,900
29 66 134 296 460 930 1,535 2,815 4,200 5,930 11,000 18,070 37,550 68,500 110,200
45
Steam Mains The sizing and design of high capacity steam mains is a complex problem that should be assigned to a competent engineer. Tables 45-1 through 46-4 will prove helpful in checking steam main sizes or in determining main size for small plants. An existing 3" steam main may be supplying one department of a plant with 3,200 lbs/hr at 125 psig. Could the steam use of this department be increased to 7,000 lbs/hr without a new supply line? Table 45-6 shows that 1 psi pressure drop is produced in 100 feet of 3" pipe when supplying 3,200 lbs/hr. To increase the flow to 7,000 lbs/hr would produce a pressure drop of 5 psi per 100 feet with a velocity of 8,000 feet per minute. This velocity is acceptable, and if the pressure drop and corresponding decrease in steam temperature are not objectionable, the existing 3" pipe can be used. However, if this much pressure drop is not permissible, an additional 3" main will have to be installed, or the existing 3" main will have to be replaced with a 4" main which can handle 7,000 lbs/hr with a pressure drop of about 1 psi per 100 feet with a velocity of less than 6,000 fpm. Steam Branch Lines When a new heating or process unit is installed in an existing plant, Tables 45-1 through 46-4 are entirely practical for checking the size of pipe to run from the
steam main to the new unit. The use of the tables is best described by solving a typical problem: Assume a boiler operates at a steam pressure of 15 psig and is supplying a 300-ton steam absorption machine which requires a minimum operating pressure of 12 psig. There is a 2 psig pressure drop along the steam mains and the absorption machine is rated to condense 6,000 lbs/hr. The branch line is 50 feet long and has three standard elbows plus a gate valve. Allowable pressure drop is not to exceed 1 psi. Assuming that a 5" pipe will be needed, use Table 48-2 to determine the equivalent length of pipe to be added to compensate for fittings. 35" standard elbows at 11 = 15" gate valve at 2.2 = Total for valve and fittings = 33.0 ft 2.2 ft 35.2 ft
Trap Discharge Lines Trap discharge lines are usually short. Assuming the trap is properly sized for the job, use a trap discharge line the same size as the trap connections. At very low pressure differential between trap and condensate return pipe, trap discharge lines can be increased one pipe size advantageously. Condensate Return Lines For medium and large-sized plants, the services of a consultant should be employed to engineer the condensate return pipe or pipes. Usually it is considered good practice to select return pipe one or two sizes larger to allow for 1) increase in plant capacity and 2) eventual fouling of pipe with rust and scale. Traps and High Back Pressure Back pressures excessive by normal standards may occur due to fouling of return lines, increase in condensate load or faulty trap operation. Depending on the operation of the particular trap, back pressure may or may not be a problem. See Recommendation Chart on Gatefold B. If a back pressure is likely to exist in the return lines, be certain the trap selected will work against it. Back pressure does lower the pressure differential and, hence, the capacity of the trap is decreased. In severe cases, the reduction in capacity could make it necessary to use traps one size larger to compensate for the decrease in operating pressure differential.
Adding this to the 50-foot length of pipe gives a total effective length of 85.2 feet call it .85 hundred feet. Dividing our maximum allowable pressure drop of 1.0 by .85 gives 1.18 psi per 100 feet. Refer to Table 45-2 for 15 psig steam. With a pressure drop of 1.0 psi per 100 feet, a 5" pipe will give a flow of 6,160 lbs/hr. On the basis of pressure drop only, a 5" pipe could be selected, however, the velocity will be between 10,000 and 12,000 fpm. Because of this, it may be wise to consider the next size pipe, 6", as velocity will then be less than 8,000 fpm.
^
28 64 129 283 441 895 1,470 2,675 4,040 5,700 10,500 17,300 36,000 65,800
1 39 90 182 400 624 1,260 2,080 3,805 5,695 8,500 14,900 24,420 50,850 93,000
2 56 128 258 566 882 1,785 2,940 5,390 8,050 11,400 21,080 34,600 72,000 131,300
5 88 202 407 895 1,394 2,820 4,650 8,550 12,740 18,000 33,300 54,600 113,900 207,000
1 330 640 1,100 1,990 3,150 5,900 15,000 24,500 38,000 80,000
2 460 910 1,350 2,850 4,600 8,500 18,500 33,000 56,000 115,000
5 800 1,400 2,350 4,650 7,800 15,000 31,000 56,000 90,000 200,000
10 1,150 2,200 3,300 6,850 11,500 22,000 46,000 80,000 130,000 285,000
/4
34 78 158 347 540 1,092 1,800 3,300 4,930 6,980 12,900 22,200 44,100 80,500
200 415 700 1,350 2,200 4,100 8,800 15,900 27,500 56,000
1 45 105 210 470 720 1,470 2,410 4,420 6,610 9,340 17,290 28,380 59,100
2 64 150 300 660 1,020 2,070 3,410 6,250 9,340 13,210 24,440 40,100 83,500
32 74 150 330 510 1,040 1,710 3,130 4,670 6,600 12,220 20,060 41,750
39 91 180 400 620 1,270 2,090 3,820 5,710 8,080 14,950 24,540 51,100
5 102 230 470 1,160 1,620 3,280 5,400 9,880 14,770 20,890 38,650 63,400 132,000
^
270 550 820 1,600 2,750 4,800 9,900 18,500 30,500 68,000
46
240 510 1,000 2,100 3,170 6,240 10,000 18,000 37,200 110,500 228,600
95 210 400 840 1,270 2,500 4,030 7,200 14,900 44,300 91,700
60 130 250 520 780 1,540 2,480 4,440 9,180 27,300 56,400
/4
1
11/4 11/2
2
21/2
3 4 6 8 P/L psi/100' D, in
1/2 3
56 120 240 500 750 1,470 2,370 4,230 8,730 25,900 53,400
120 260 500 1,060 1,600 3,100 5,000 8,860 18,200 53,600 110,300
93 200 390 800 1,210 2,350 3,780 6,710 13,800 40,600 83,600
/4
1
11/4 11/2
2
21/2
3 4 6 8
a
For these sizes and pressure losses the velocity is above 7,000 fpm. Select another combination of size and pressure loss. Reprinted by permission from ASHRAE Handbook 1985 Fundamentals.
47
Internal (in)
0.845 1.114 1.549 1.954 2.589 3.296 4.335 5.058 6.494 7.757 9.638 11.146 12.648 15.856 19.054 25.073 31.479 37.699 41.217 47.123 52.998 59.093 71.063
/8 /4
1
11/4 11/2
2
21/2
3
31/2
4 5 6 8 10 12 14 16 18 20 24
Length in Feet to be Added Run Standard Elbow 1.3 1.8 2.2 3.0 3.5 4.3 5.0 6.5 8.0 9.0 11.0 13.0 17.0 21.0 27.0 Side Outlet Tee 3 4 5 6 7 8 11 13 15 18 22 27 35 45 53 Gate Valve* 0.3 0.4 0.5 0.6 0.8 1.0 1.1 1.4 1.6 1.9 2.2 2.8 3.7 4.6 5.5 Globe Valve* 14 18 23 29 34 46 54 66 80 92 112 136 180 230 270 Angle Valve* 7 10 12 15 18 22 27 34 40 45 56 67 92 112 132
Table 48-3. Thermal Expansion of Pipe *From Piping Handbook, by Walker and Crocker, by special permission. This table gives the expansion from -20F to temperature in question. To obtain the amount of expansion between any two temperatures take the difference between the figures in the table for those temperatures. For example, if cast iron pipe is installed at a temperature of 80F and is operated at 240F, the expansion would be 1.780 - 0.649 = 1.13 in.
Temp. (F)
-20 0 20 40 60 80 100 120 140 160 180 200 240 280 320 360 400 500 600
Elongation in Inches per 100 Ft from -20F Up Wrought Steel Pipe Iron Pipe
0.000 0.145 0.293 0.430 0.593 0.725 0.898 1.055 1.209 1.368 1.528 1.691 2.020 2.350 2.690 3.029 3.375 4.296 5.247 0.000 0.152 0.306 0.465 0.620 0.780 0.939 1.110 1.265 1.427 1.597 1.778 2.110 2.465 2.800 3.175 3.521 4.477 5.455
Copper Pipe
0.000 0.204 0.442 0.655 0.888 1.100 1.338 1.570 1.794 2.008 2.255 2.500 2.960 3.422 3.900 4.380 4.870 6.110 7.388
Dia.
.0469 .0520 .0550 .0595 .0625 .0635 .0670 .0700 .0730 .0760 .0781 .0785 .0810 .0820 .0860 .0890 .0935 .0938 .0960 .0980 .0995 .1015 .1040 .1065 .1094 .1100 .1110 .1130 .1160 .1200 .1250 .1285 .1360 .1405 .1406
Area
.00173 .00212 .00238 .00278 .00307 .00317 .00353 .00385 .00419 .00454 .00479 .00484 .00515 .00528 .00581 .00622 .00687 .00690 .00724 .00754 .00778 .00809 .00850 .00891 .00940 .00950 .00968 .01003 .01039 .01131 .01227 .01242 .01453 .01550 .01553
Drill Size
27 26 25 24 23
5
Area
.01629 .01697 .01705 .01815 .01863 .01917 .01936 .01986 .02036 .02164 .02256 .02320 .02351 .02461 .02545 .02602 .02688 .02761 .02806 .02865 .02941 .03017 .03110 .03173 .03241 .03268 .03317 .03431 .03563 .03758 .03836 .04083 .04301 .04314 .04449
Drill Size
C D
1
Dia.
.2420 .2460 .2500 .2500 .2570 .2610 .2656 .2660 .2720 .2770 .2810 .2812 .2900 .2950 .2969 .3020 .3125 .3160 .3230 .3281 .3320 .3390 .3438 .3480 .3580 .3594 .3680 .3750 .3770 .3860 .3906 .3970 .4040 .4062 .4130
Area
.04600 .04753 .04909 .04909 .05187 .05350 .05515 .05557 .05811 .06026 .06202 .06213 .06605 .06835 .06881 .07163 .07670 .07843 .08194 .08449 .08657 .09026 .09281 .09511 .10066 .10122 .10636 .11045 .11163 .11702 .11946 .12379 .12819 .12962 .13396
Drill Size
/64 7 /16 29/64 15 /32 31/64 1/2 33/64 17/32 9 /16 19/32 5 /8 21/32 11 /16 23/32 3 /4 25/32 13/16 27 /32 7/8 29/32 15 /16 31/32
27
Dia.
.4219 .4375 .4531 .4688 .4844 .500 .5156 .5312 .5625 .5937 .6250 .6562 .6875 .7187 .7500 .7812 .8125 .8437 .8750 .9062 .9375 .9687 1.0000 1.0625 1.1250 1.1875 1.2500 1.3125 1.3750 1.4375 1.5000 1.6250 1.7500 1.8750 2.0000
Area
.13920 .15033 .16117 .17257 .18398 .19635 .20831 .22166 .24850 .27688 .30680 .33824 .37122 .40574 .44179 .47937 .51849 .55914 .60132 .64504 .69029 .73708 .78540 .88664 .99402 1.1075 1.2272 1.3530 1.4849 1.6230 1.7671 2.0739 2.4053 2.7612 3.1416
55 54 53
1/16
/4
52 51 50 49 48
5/64
/32
E F G
17/64
22 21 20 19 18
11
H I J K
9
47 46 45 44 43 42
3
/64
/32
17 16 15 14 13
3
L M
19
/64
N
5
/16
/32
/16
41 40 39 38 37 36
7/64
12 11 10 9 8 7
13/64
O P
21/64
Q R
11/32
S T
23/64
35 34 33 32 31
1/8
6 5 4 3
7/32
U
3/8
V W
25/64
30 29 28
9/64
2 1 A
15/64
X Y
13/32
1 11/16 11/8 13/16 11/4 15/16 13/8 17/16 11/2 15/8 13/4 17/8 2
48
Conversion Factors
Power
Multiply Boiler hp Boiler hp Horsepower Horsepower Horsepower Horsepower Horsepower Kilowatts Kilowatts Watts Watts Watts Tons refrig. Tons refrig. Btu/hr lbs H2O evap. at 212F Btu/hr ft-lbs/sec ft-lbs/min Btu/min Kilowatts Btu/hr Btu/min ft-lbs/min ft-lbs/sec Btu/min Btu/hr Btu/min By 33,472 34.5 2,540 550 33,000 42.42 0.7457 3,415 56.92 44.26 0.7378 0.05692 12,000 200 0.00002986 0.0290 0.000393 0.00182 0.0000303 0.0236 1.341 0.000293 0.01757 0.02259 1.355 1.757 0.0000833 0.005 ToGet Btu/hr lbs H2O evap. at 212F Btu/hr ft-lbs/sec ft-lbs/min Btu/min Kilowatts Btu/hr Btu/min ft-lbs/min ft-lbs/sec Btu/min Btu/hr Btu/min Boiler hp Boiler hp Horsepower Horsepower Horsepower Horsepower Horsepower Kilowatts Kilowatts Watts Watts Watts Tons refrig. Tons refrig. Multiply atmospheres atmospheres atmospheres atmospheres atmospheres in. H2O} (at 62F) ft H2O} (at 62F) ft H2O} (at 62F) ft H2O} (at 62F) in. Mercury} (at 62F) in. Mercury} (at 62F) in. Mercury} (at 62F) in. H2O} (at 62F) ft. H2O} (at 62F) lbs/in2 ton/ft2 in. Mercury} (at 62F) in. Mercury} (at 62F) lbs/in2 lbs/ft2 lbs/ft2 lbs/in2 lbs/in2 lbs/in2
Pressure
By 29.92 406.8 33.90 14.70 1.058 0.0737 0.881 0.4335 62.37 70.73 0.4912 0.03342 0.002458 0.0295 0.0680 0.945 13.57 1.131 2.309 0.01603 0.014138 2.042 0.0689 0.0703 ToGet {in Mercury (at 62F) {in H2O (at 62F) {ft. H2O (at 62F) lbs/in2 ton/ft2 {in. Mercury (at 62F) {in. Mercury (at 62F) lbs/in2 lbs/ft2 lbs/ft2 lbs/in2 atmospheres atmospheres atmospheres atmospheres atmospheres {in. H2O (at 62F) {ft H2O (at 62F) {ft H2O (at 62F) {ft H2O (at 62F) {in. Mercury (at 62F) {in. Mercury (at 62F) Bar kg/cm2 Multiply lbs lbs H2O (60F) lbs H2O (60F) tons (long) tons (short) grains cu ft H2O gal H2O lbs lbs
Weight
By 7,000 0.01602 0.1198 2,240 2,000 0.000143 62.37 8.3453 0.000446 0.000500 ToGet grains cu ft H2O gal H2O lbs lbs lbs lbs H2O (60F) lbs H2O (60F) tons (long) tons (short)
Circular Measure
Multiply By Degrees 0.01745 Minutes 0.00029 Diameter 3.142 Radians 57.3 Radians 3,438 Circumference 0.3183 ToGet Radians Radians Circumference Degrees Minutes Diameter
Volume
Multiply Barrels (oil) cu ft cu ft cu in gal (oil) cu in gal gal By 42 1,728 7.48 0.00433 0.0238 0.000579 0.1337 231 ToGet gal (oil) cu in gal gal barrels (oil) cu ft cu ft cu in
Energy
Multiply Btu Btu Btu By 778 0.000393 0.000293 ToGet ft-lbs hp-hrs kw-hrs {lbs H2O evap. at 212F Tons refrig. Watt-hrs Watt-hrs Btu/lb H2O kw-hrs hp-hrs Btu Btu Btu Btu Btu Btu ft-lbs {Latent heat of ice {lbs H2O evap. at 212F {lbs. H2O evap. at 212F
Btu 0.0010307 Btu 0.00000347 Btu 0.293 ft-lbs 0.3765 Latent heat} of ice 143.33 lbs H2O evap.} at 212F 0.284 lbs H2O evap.} at 212F 0.381 ft-lbs 0.001287 hp-hrs 2,540 kw-hrs 3,415 lbs H2O evap.} at 212F 970.4 Tons refrig. 288,000 Watt-hrs 3.415 Watt-hrs 2,656 Btu/lb H2O kw-hrs hp-hrs 0.006977 3.52 2.63
Temperature
F = (C x 1.8) + 32 C = (F - 32) 1.8
Velocity of Flow
Multiply ft/min ft/min cu ft/min cu ft/sec miles/hr ft/sec gal/sec gal/min By 0.01139 0.01667 0.1247 448.8 88 60 8.02 0.002228 ToGet miles/hr ft/sec gal/sec gal/min ft/min ft/min cu ft/min cu ft/sec
Heat Transmission
Multiply Btu/in} /sq ft /hr/F Btu/ft} /sq ft /hr /F By 0.0833 ToGet {Btu/ft /sq ft /hr/F {Btu/in /sq ft /hr/ F
12
49
0.19 0.94 0.33 0.78 0.84 0.24-0.33 0.11 0.12 0.74 0.66 0.30 0.203 0.27 0.35 0.52 0.84 0.13 0.42 0.215 0.21 0.42 0.73-0.94 1.00 0.90 0.90 0.325 0.095
0.73 2.25 0.072 1.09 1.26 1.15 1.05 0.90 0.92 11.34 0.86-1.02 0.93 0.208
1.03 8.90 1.50 1.37 1.05 0.81 0.86 0.88 0.90 0.93 0.95
50
Alphabetical Index
Abbreviations, Gatefold B Air cause of slow heating, low temperatures, 6 effect on steam temperature, 6 Air venting, 12 Automatic differential condensate controller, 13 Boiler headers, 16 Branch lines, 18 By-passes, 40 Charts Btu heat loss from bare pipe, 17, 21 Mean temperature difference, 29 Multiplier for selecting traps for draining pipe coils, 22 Percentage of flash steam, 3 Recommendations, Gatefold, 16, 18, 20, 22, 25, 26, 28, 30, 32, 34, 36, 38 Circles, areas, 48 Closed, stationary steam chamber equipment, 32, 33 Controlled disc trap, 11 Conversion factors, 49 Drip leg sizing, 16 Embossed coils, 26, 27 Evaporators, 28, 29 Finned radiation, 23 Flash steam, 3 Flash tanks, 36, 37 Float & thermostatic traps, 10, 11 Freezing, protecting traps, 42 Individual trapping, 14 Inspection of traps, 43 Installation, 40, 41, 42, 43 Inverted bucket principle, 8, 9 Jacketed kettles, 30, 31 Leaks, steam, cost of, 7 Maintenance of traps, 43, 44 Mains Returns, 45 Steam, 16, 17, 18, 46 Pipe coils, 22, 23, 27 Pressure differential, 15 Process air heaters, 25 Recommendation chart, Gatefold, 16, 18, 20, 22, 25, 26, 28, 30, 32, 34, 36, 38 Rotating dryers, 34, 35 Safety drain trap, 42 Safety factors explanation, 14, 15 for different jobs, 16-39 Secondary steam, 3 Shell and tube heat exchangers, 26, 27 Short circuiting, 14 Sizing, pipe and condensate return lines, 45, 46, 47 Sizing, traps for: air handling units, 22 autoclaves, 32 boiler headers, 16 branch lines, 18, 19 closed, stationary steam chamber equipment, 32, 33 coils embossed, 26, 27 finned, 23 pipe, 22, 23, 27 space heating, 22, 23 submerged, 26, 27 combustion air preheaters, 25 concentrators, 30, 31 dryers, rotating, 34, 35 evaporators, 28, 29 finned radiation, 23 flash tanks, 36, 37 heat exchangers, 26, 27 jacketed kettles, 30, 31 kettles, jacketed, 30, 31 pipe coils, 22, 23, 27 platen press, 32 process dryers, 25 reboilers, 26 retorts, 32, 33 separators, 19 space heating equipment, 22, 23 steam absorption machine, 38 steam distribution system, 5, 16, 17, 18, 19 steam mains, 16, 17, 18, 46 steam separators, 19 steam tracer lines, 20, 21 submerged coils, 26, 27 suction heaters, 26 tracer lines, 20, 21 tunnel dryers, 25 unit heaters, 22 vaporizers, 26 water heaters, 26 Space heating equipment, 22, 23 Specific gravity, 50 Specific heat, 50 Steam basics, 4-7 flash, 3 how heat is used, 4 leaks, cost of, 7 leaks, testing for, 43, 44 need for draining, 5 tables, 2 Steam absorption machine, 38 Steam distribution systems, 16, 17, 18, 19 Steam mains, 16, 17, 18, 46 Steam tables, 2 Steam tracer lines, 20, 21 Steam traps automatic differential condensate controller, 13 controlled disc, 11 float & thermostatic, 10, 11 inverted bucket, 8, 9 thermostatic, 12 Submerged coils, 26, 27 Tables, technical, useful information air, effect on steam temperature, 6 circles, area, 48 condensing rates in bare pipe, 24 constants for determining unit heater Btu output, 24 finned radiation, condensing rates, 24 finned radiation, conversion factors, 24 leaks, steam, cost of, 7 pipe capacity condensate, 47 steam, 45, 46, 47 conversion factors, 49 conversion, lineal feet to square feet of surface, 29, 35 dimensions, schedule 40, 48 equivalent, length of fittings, 48 expansion, thermal, 48 steam condensed in, due to normal radiation, 17 steam condensing during warm-up, 17 steam, saturated properties of, 2 temperature reduction caused by air, 6 U values, embossed coils, 27, 29 pipe coils, 27, 29 warming up, Schedule 40, 17 weight per foot, 19 Testing, trap, 43, 44 Thermostatic steam traps, 12 Tracer lines, 20, 21 Trap selection, 14, 15 Troubleshooting, 44 Unit trapping, 14 U values embossed coils, 27, 29 pipe coils, 27, 29 Water hammer, 5
51
Other Products
Y-Type Strainers
Armstrong Y-type strainers are manufactured in a wide choice of sizes and materials to meet the bulk of all pipeline straining requirements. Request Bulletin No. 171.
Pumping Traps
Armstrongs pumping traps are an ideal non-electric solution for returning condensate in special applications such as evacuating a vacuum, entering a pressurized return line or elevating condensate. Request Bulletin No. 230.
Manifolds
Armstrongs condensate collection and steam distribution manifolds are designed especially for the low loads common in the chemical, petrochemical and rubber industries. Request Bulletin No. 615.
Application assistance is a most important part of the complete service provided by Armstrong International. Armstrong Representatives are qualified by factory training and extensive experience to assist you. Backing the Representatives are Armstrong specialists who are available to assist with especially difficult or unusual requirements.