Hid Troubleshooting Guide PDF
Hid Troubleshooting Guide PDF
High Intensity
Discharge
Lamp Ballasts
Ballast Components - 22
Capacitors - 22
Dry Metalized Film - 22
Oil Filled - 23
Ignitors (Starters) - 23
Application and Installation Information - 25
Remote Mounting - 27
Input Wiring - 27
Bi-Level Operation - 27
Warranty - 28
Troubleshooting - 28
Safety - 28
Instruments and Test Equipment - 29
Troubleshooting Procedures - 29
Normal End of Lamp Life - 29
Mercury and Metal Halide Lamps - 30
High Pressure Sodium Lamps - 30
Low Pressure Sodium Lamps - 30
Electronic Ballasts - 30
Troubleshooting Charts - 32
Measuring Line Voltage - 36
Measuring Open Circuit Voltage - 36
Short Circuit Lamp Current Test - 40
Capacitor Testing - 42
Ballast Continuity Checks - 43
Continuity of Primary Coil - 43
Continuity of Secondary Coil - 44
Ignitor Testing - 45
Further Magnetic Ballast Checks - 46
Electronic HID Ballasts - 47
Electronic Troubleshooting Flow Chart - 48
TABLE OF CONTENTS
Description of HID Lamp Types - 5
Mercury Vapor - 5
Low Pressure Sodium - 5
High Pressure Sodium - 6
Metal Halide - 6
Pulse Start Metal Halide - 7
General Ballast Description - 8
Ballast Circuitry - 9
Lamp/Ballast Regulation Characteristics - 9
Ballast Circuits - 10
Reactor - 10
High Reactance Autotransformer - 11
Constant Wattage Autotransformer (CWA) - 12
Constant Wattage Isolated (CWI) - 13
Regulated Lag - 14
Electronic HID Ballasts - 15
Standards and Safety Agencies - 16
ANSI American National Standards Institute - 16
UL Underwriters Laboratories - 16
UL Bench Top Temperature Rise - 16
CSA- Canadian Standards Association - 17
Ballast Design Applications - 18
Magnetic Ballasts - 18
Core & Coil - 18
Encapsulated Core & Coil - 19
Indoor Enclosed - 19
F-Can - 19
Outdoor Weatherproof - 20
Postline - 21
Electronic HID (e-HID) - 21
e-Vision Low Frequency - 21
DynaVision - 21
TABLE OF CONTENTS
DESCRI PTI ON OF HI D LAMP TYPES
5
There are four basic types of lamps considered as HID light
sources: mercury vapor, low pressure sodium, high pressure
sodium and metal halide. All are arc discharge lamps. Light is
produced by an arc discharge between two electrodes at
opposite ends of the arc tube within the lamp. Each HID lamp
type has its own characteristics that must be individually
considered for any lighting application.
There are four key parameters:
1. System efficiency (lumens per watt and ballast efficiency)
2. Lamp life
3. Lumen maintenance
4. Color rendition and stability over the life of the lamp
Mercury Vapor
Mercury vapor lamps are the least efficient
HID source with an efficacy of 25 to 55 lumens
per watt. They were developed as a more
efficient alternative to incandescent light with
lamp life 20 to 30 times longer. Mercury vapor
light color is bluish and lumen maintenance is
only fair when compared to other HID
sources. Its benefits are low cost and long life
(in the range of 16,000 to 24,000 hours or
more) and a wide range of wattages from 50W to 1000W.
Mercury vapor lamps require 3-6 minutes to cool down before
they can be restarted. This interval is known as the re-strike
time. Mercury vapor lamps are most commonly used for
roadway lighting with a strong niche in landscape applications.
Low Pressure Sodium
Low pressure sodium (LPS) lamps are grouped with HID
lamps, but in fact do not have a compact, high intensity arc.
They are more like a fluorescent lamp with a long stretched-out
arc. These lamps are the most efficient light source with an
4
I NTRODUCTI ON
High Intensity Discharge (HID) lighting sources are important
for commercial, industrial and outdoor locations, such as high
bay, parking lot and street lighting. HID lighting sources
include mercury vapor, low pressure sodium (LPS), high
pressure sodium (HPS), and metal halide (MH) ballast and
lamp systems. Since the introduction of HID lighting, steady
improvements in lamp and ballast technology have increased
efficiency and other performance characteristics of HID
systems. The improved systems include pulse start (both
quartz, ceramic arc tubes and ballasts), as well as electronic
HID ballasts.
The purpose of this booklet is to provide technical information
with a major focus on troubleshooting techniques for all HID
systems including pulse start and electronic systems. The
booklet is physically designed to fit in your pocket or tool bag
as a technical and troubleshooting ready reference.
For more detailed operational descriptions and specifications,
refer to the Advance Atlas, ABCs of HID Ballasts, or
www.advancetransformer.com.
Note: The information in this pocket guide is written based on our experience
to date and believed to be reliable. It is a guide intended for use by persons
having the necessary technical skills at their own discretion and risk. We do not
guarantee favorable results or assume any liability in connection with its use.
This information is not intended to conflict with existing code, ordinances and
regulations. Existing codes, ordinances and regulations should be observed at
all times.
Customer Support/Technical Services: 800.372.3331
Advance A Division of Philips Electronics North America Corporation 2005
DESCRI PTI ON OF HI D LAMP TYPES
7
lighting, and have lamp life ratings of only 3000 to 5000
hours. The advantage of metal halide lighting is its bright,
crisp, white light output suitable for commercial, retail, and
industrial installations where light quality is important.
However, lumen maintenance over the life of the lamps is less
than optimal relative to other HID sources.
The arc tube material for metal halide lamps was quartz until
1995 when ceramic arc tube technology was developed.
Ceramic arc tubes are now predominantly used in low
wattage (20W to 150W) lamps, though new designs up to
400W have emerged in recent years. Ceramic arc tubes
provide improved color consistency over lamp life. This
technology is ideal for lamp applications requiring truer color
as in fruit, vegetable, clothing and other accent lighting in
retail displays.
Pulse Start Metal Halide
In the mid 1990s lamp manufacturers sought to improve
standard probe start metal halide lighting (175W to 1000W).
They did so by changing the chemistry and fill pressure in the
lamp arc tube to increase lumen efficacy (lumens per watt).
These lamp improvements required introduction of an ignitor
or starter to provide a high voltage starting pulse eliminating
the internal starting probe and its bi-metallic switch.
Removal of the starting probe and switch from the arc tube
construction allowed an optimized arc tube design and
manufacturing process.
This technology improved the overall performance of metal
halide systems. Lumen output per watt consumed can
increase by 25%. Lumen maintenance is improved as much as
15%, lamp life is extended, warm-up time is reduced to two
minutes and there is some improvement in color rendition.
Adding an ignitor reduced re-strike time to 4 to 5 minutes
6
DESCRI PTI ON OF HI D LAMP TYPES
efficacy of 100 to 185 lumens per watt. LPS
lamps have no color rendering index as the
color output is monochromatic yellow.
Consequently, LPS has few viable applications
beyond street, parking lot and tunnel lighting.
Low pressure sodium lamps range in size from
18W to 180W and average 14,000 to 18,000
hour lifetimes. They have excellent lumen
maintenance but the longest warm up times,
from 7 to 15 minutes. LPS lamps feature the
shortest re-strike time among HID sources
only 3 to 12 seconds.
High Pressure Sodium
High pressure sodium lamps have an efficacy
of 80 to 140 lumens per watt, a long lamp life
of 20,000 to 24,000 hours, and the best lumen
maintenance of all HID sources. Wattages
range from 35W to 1000W and the warm-up
time is from 2 to 4 minutes. Re-strike time is
approximately 1 minute. The biggest drawback
of high pressure sodium is the yellowish color
light output, but it is acceptable for use in many
industrial and outdoor applications (e.g.
roadway lighting). High pressure sodium and metal halide
lamps comprise the majority of HID lighting applications.
Metal Halide
Metal Halide lamps have an efficacy of 60 to
110 lumens per watt and have a warm-up time
of 2 to 5 minutes. They have a re-strike time of
10 to 20 minutes. Lamp wattages range from
20W to 1000W with lamp life of 6,000 to
20,000 hours. Wattages from 1500W to
2000W are specialty lamps used for sports
GENERAL BALLAST DESCRI PTI ON
9
For many years all HID ballasts were magnetic ballasts
operating at the power line frequency of 50 or 60 Hertz to
provide proper lamp operation. In the past few years
electronic ballasts have been developed, primarily for metal
halide lamps, using integrated circuits that monitor and
control lamp operation. Electronic ballast circuits sense lamp
operation characteristics and regulate lamp current to operate
the lamp at constant wattage, thus providing a more uniform
light output and color rendition throughout lamp life. They
also sense lamp end of life and other circuit conditions and
shut down the ballast when the lamp operating characteristics
fail to meet operating specifications. These characteristics
present more complicated troubleshooting conditions that will
be discussed later.
BALLAST CIRCUITRY
Lamp/Ballast Regulation Characteristics
One of the most important characteristics of each particular
ballast circuit is the degree to which it controls the lamp
wattage, and hence light output, with changes of input line
voltage. Ballast circuit design dictates the lamp wattage
regulation characteristics. As a rule, better lamp regulation
requires larger, more expensive ballasts. The following chart
compares the relationship of the three basic types of ballast
circuits as the input voltage changes.
8
GENERAL BALLAST DESCRI PTI ON
from the standard metal halide lamp time of 10 to 20 minutes.
GENERAL BALLAST DESCRIPTION
HID lamps provide light from an electric discharge or arc and
have a negative resistance characteristic that would cause
them to draw excessive current leading to instant lamp
destruction if operated directly from line voltage. The ballast
is a power supply for arc discharge lamps. Its purpose in HID
lighting is to provide the proper starting voltage to initiate and
maintain the lamp arc and to sustain and control lamp current
once the arc is established.
A ballast design incorporates basic circuitry to provide
specific lamp/ballast operating characteristics. For some
types of lighting applications a particular ballast circuit has
proven the most cost effective and is, therefore, the only
circuit offered. Other applications may require an optimum
ballast selection from two or three available alternatives for
that particular application. Final selection is based upon cost
vs. performance requirements.
As described in the previous section, HID lamps come in
various types and wattage selections. Each lamp type and
wattage requires specific starting and operating conditions to
develop rated light output and operate the lamp within
allowable limits. Ballasts and lamps are designed to meet
standards for interchangeability between lamps and ballasts
of the same type and wattage. A lamp must be operated
by the ballast designed for that lamp, as improper matching
of lamp and ballast may cause damage to the lamp or
ballast or both. The American National Standards Institute
(ANSI) provides specifications to standardize lamp and
ballast compatibility.
475
450
425
400
375
350
325
300
275
0 50 60 70 80 90 100 110 120 130 140 150 160 170
LAMP VOLTS
L
A
M
P
W
A
T
T
S
VOLT-WATT
TRACES
INPUT
VOLTAGE
TRAPEZOID BOUNDARY
NOMINAL LAMP VOLTAGE
NOMINAL
+10%
-10%
112
110
102
100
98
95
88
87 90 95 100 105 110 113
REACTOR (R)*
CWA**
CONSTANT
WATTAGE
(CW)***
PRIMARY VOLTAGE (%)
L
A
M
P
W
A
T
T
S
(
%
)
BALLAST CI RCUI TS
11
The reactor ballast is electrically in series with the lamp.
There is no capacitor involved with the operation of the lamp.
Because of that, the lamp current crest factor is desirably low,
in the 1.4 to 1.5 range.
Without a capacitor, the reactor ballasts are inherently normal
power factor devices (50%). When desired to reduce the
ballast input current required during lamp operation, a
capacitor may be utilized across the input line to provide high
power factor (90%) operation, but the addition of the capacitor
will not affect how the ballast operates the lamp.
Reactor ballasts with power factor correction capacitors, can
limit the number of fixtures that can be used on a circuit
because they draw substantially more current during lamp
starting (warm-up) and/or open-circuit operation (burned-out or
missing lamp), than when the lamp is operating normally.
Typical Reactor
Circuit with
Optional
Capacitor
High Reactance Autotransformer (HX) - When the input
voltage does not meet the starting and operating voltage
requirements of the HID lamp, a high reactance autotransformer
ballast can be used. In addition to limiting the current to the
lamp, an HX ballast transforms the input voltage to the lamps
required level. Two coils, called the primary and secondary,
are employed within the ballast. The operating characteristics,
such as lamp wattage regulation are similar to the reactor.
10
BALLAST CI RCUI TRY
As an example, the CWA line indicates that at 90% of line
voltage, the ballast will operate the lamp at 90% of it nominal
wattage. Similarly, at 110% of line voltage, the ballast will
operate the lamp at 110% of nominal wattage.
The voltage of a typical mercury or metal halide lamp remains
relatively constant throughout its operational life for this
reason, the lamp wattage regulation of these ballasts can be
defined as a simple percent wattage change. High pressure
sodium lamps, however, see significant arc tube voltage
increases during their operational life; therefore, the high
pressure sodium lamp ballast must compensate for this
changing lamp voltage (even with stable input voltages) to
maintain constant lamp wattage. Consequently, a simple
percent wattage change is not an adequate definition for high
pressure sodium lamp regulation. Instead, a trapezoid,
established by the American National Standards Institute
(ANSI), is defined, which restricts the operation of the lamp to
certain acceptable limits with respect to lamp voltage and
resulting lamp wattage. The ballast is designed to operate a
high pressure sodium lamp throughout its life within the
trapezoid for any input voltage within the rated input voltage
range of the ballast. The resultant value of the lamp's actual
operation wattage over the life of the lamp when shown on a
graph follows a rising-then-falling path called a volt-watt trace.
BALLAST CIRCUITS
Reactor (R) A single coil ballast can be used when the
input voltage to a fixture meets the starting and operating
voltage requirements of an HID lamp. In this situation, the
reactor ballast performs only the current-limiting function since
the voltage necessary to initiate the ignitor pulses, and start
and sustain the lamp comes directly from the input voltage to
the fixture.
LAMP
CAP LAMP
LINE V
BALLAST CI RCUI TS
13
The CWA ballast provides greatly improved lamp wattage
regulation over reactor and high reactance circuits. A 10%
line voltage variation will result in a 10% change in lamp
wattage for metal halide. The metal halide and high pressure
sodium ballasts also incorporate wave shaping of the open
circuit voltage to provide a higher peak voltage than a normal
sine wave. This peak voltage (along with a high voltage
ignition pulse when an ignitor is used) starts the lamp and
contributes to the lamp current crest factor (typically 1.60 -1.65).
With the CWA ballast, input current during lamp starting or
open circuit conditions does not exceed the input current
when the lamp is normally operating. CWA ballasts are
engineered to tolerate 25-30% drops in line voltage before the
lamp extinguishes (lamp dropout), thus reducing accidental
lamp outages.
Typical Constant
Wattage
Autotransformer
Circuit
Constant Wattage Isolated (CWI) The CWI ballast is a
two-coil ballast similar to the CWA ballast except that its
secondary coil is electrically isolated from the primary coil.
This isolated design permits the socket screw shell to be
grounded for phase-to-phase input voltage applications such
as 208, 240 and 480 volt inputs. The use of the CWI ballast
for these voltages is a CSA safety requirement in Canada.
12
BALLAST CI RCUI TS
The high reactance autotransformer ballast is also inherently
a normal power factor (50%) ballast but can be corrected to
a high power factor (90%) with the addition of a capacitor
across the primary coil. As with the reactor ballast, the
addition of this capacitor does not affect the lamps operation.
Both reactor and high reactance ballasts provide the same
degree of lalmp wattage regulation. For example, a simple
5% change in line voltage results in a 10-12% change in lamp
operating wattage. However, this fair degree of lamp
regulation is acceptable for many applications.
Typical High
Reactance
Autotransformer
Circuit without
Capacitor
Constant Wattage Autotransformer (CWA), also
referred to as a Peak Lead Autotransformer To
correct the higher input current associated with reactor and
high reactance ballasts, and to provide a greater level of lamp
wattage regulation, the 2-coil CWA ballast was developed. It is
the most commonly used ballast circuit for medium and high
wattage (175W 2000W) applications and typically represents
the best compromise between cost and performance. The
CWA is a high power factor ballast utilizing a capacitor in
series with the lamp rather than across the input. The
capacitor works with the core-and-coil to set and regulate the
lamp current to the prescribed level.
LAMP
LAMP
LINE V
COM COM
LINE V
LINE V
LINE V
CAP
CAP
BALLAST CI RCUI TS
15
Electronic HID (e-HID) Ballasts
There are two basic designs for electronic HID ballasts; low
frequency square wave (typically used for low-wattage lamps
or with ceramic arc tube lamps in the 250W-400W range)
and high frequency (for medium wattage lamps in the 250W
to 400W range). Both make use of integrated circuit
technology to provide closer regulation and control of lamp
operation over a variety of input voltage and lamp aging
conditions. The integrated circuits in both types of ballasts
continuously monitor input line voltage and lamp conditions
and regulate lamp power to the rated wattage. If any power
line or lamp circuit condition exists that will cause the lamp or
ballast to operate beyond their specified limits the ballast
shuts down (removes power from the lamp) to prevent
improper operation. Electronic HID ballasts improve lamp life,
lamp lumen maintenance, and system efficiency.
Integrated circuit control allows most electronic ballasts to
operate at multiple input line voltages and, in some cases,
operate more than one lamp wattage. The lamps are operated
with constant lamp power that provides better light output
regulation and more consistent light color over the life of the
lamp. Some electronic HID ballasts also offer a continuous
dimming function that will dim the lamp to 50% (minimum)
lamp power using zero to ten volt (dc) dimming control voltage.
All functions required to correct power factor, line current
harmonics, and to start and control lamp operation are
inherent in the ballast. The lamp socket must be pulse rated
(4kV) because there is an ignition pulse supplied to start
the lamp.
14
BALLAST CI RCUI TS
Typical Constant
Wattage Isolated
Circuit
Regulated Lag (REG-LAG), also referred to as
Magnetic Regulator or MAG-REG This three-coil
ballast circuit consists of a reactor ballast with a two-coil
voltage regulator circuit all assembled on one core. The
primary coil works with the tertiary coil and its capacitor to
regulate the current through the lamp coil, and hence, the
lamp. The lamp current crest factor is typically 1.5, similar to
that of single-coil reactor ballast.
The lamp coil portion of the ballast is essentially isolated from
line voltage variations and deviations from nominal. This
circuit provides the best lamp wattage regulation for magnetic
ballasts, (a 10% change in input voltage yields only a 4%
change in lamp wattage) but carries an increase in ballast
size, ballast losses and cost.
Typical
Regulated Lag
Circuit
LAMP 1
CAP
LAMP
COM
LINE V
LINE V
LINE V
IGNITOR
X1
X3
X2
LINE V
CAP
CAP
LAMP 2
LAMP 1
LAMP
LINE V
COM
LINE V
LINE V
CAP
CAP
LAMP 2
STANDARDS AND SAFETY AGENCI ES
17
1029 is the UL standard for HID ballasts and the X is the
temperature letter code. This temperature information should
be used when ballast replacements are required. A ballast
with a lower or equal letter rating may be used as a
replacement without affecting UL listing of the fixture. For
example, if a fixture is UL listed for 1029C then, automatically,
electrically equivalent ballasts with an A, B, or C temperature
classification are acceptable for use within that same fixture.
A table is shown below giving the letter code and the
temperature range.
UL approves maximum temperature ratings for insulation
systems that include the wire insulation and the ballast
impregnation material. Advance ballasts may have one or
both of two temperature ratings, Class H - 180C or Class
N - 200C. These temperature ratings are maximum opera-
tion temperatures. However, greater ballast reliability will be
realized when the operating temperatures are lower than the
maximum. The rule of thumb is: Ballast life can double for
each 10C decrease in operating temperature.
CSA Canadian Standards Association is the Canadian
equivalent to UL. They generate performance and safety
standards for many Canadian industries. When a product has
the CSA symbol on the label, it has been investigated and
approved for use in Canada.
16
STANDARDS AND SAFETY AGENCI ES
STANDARDS AND SAFETY AGENCIES
ANSI American National Standards Institute is a
non-profit organization that generates voluntary product
performance standards for many U.S. industries, including
ballasts and lamps. ANSI lighting committees consist of
members from ballast, lamp, and fixture designers and
manufacturers that meet periodically to provide consistent
product performance requirements. There are specific
performance standards for each lamp and ballast type.
UL Underwriters Laboratories, Inc sets safety
standards for building materials, electrical appliances and
other products, including ballasts and lighting fixtures. These
standards include prescribed requirements for insulation
systems and maximum operating temperatures.
UL provides, through testing, two different approvals for
ballasts, UL Listed and UL-Recognized. UL Listing
indicates the ballast is approved as a stand-alone unit and no
further safety testing of the ballast is required by the fixture
manufacturer. UL Listed ballasts are manufactured in an
enclosure and the fixture manufacturer cannot change the
internal components. UL-Recognized is a limited approval
given to individual components that are not enclosed when
manufactured. The fixture manufacturer must obtain UL
Listing for the fixture enclosure that includes meeting
temperature and insulation requirements of the ballast and
associated components. The ballast manufacturer provides
temperature and insulation rating information to the fixture
manufacturer.
UL Bench Top Temperature Rise information is provided
as a letter code for each core and coil ballast in the Advance
Atlas and on the ballast label to facilitate UL inspection. The
temperature rise code is shown on the label as 1029X, where
UL Bench Top Rise
Letter Code
Temperature Range for
Class H (180C) Ballasts
Temperature Range for
Class N (200C) Ballasts
A less than 75C less than 95C
B 75C < 80C 95C < 100C
C 80C < 85C 100C < 105C
D 90C < 95C 105C < 110C
E 90C < 95C 110C < 115C
F 95C < 100C 115C < 120C
etc. etc. etc.
BALLAST DESI GN APPLI CATI ONS
19
are UL-Recognized. A description of the various encased
ballasts follows.
Encapsulated Core & Coil (73B)
In this configuration the capacitor is mounted separately in
the luminaire, as is the ignitor (where required). Typical
applications are installations requiring minimum ballast noise,
including indoor installations such as offices, schools and
retail stores. For a given
application the encapsulated
core & coil ballast also
operates about 10C cooler
than the open core & coil.
Encapsulated core & coil
ballasts are UL-Recognized.
Indoor Enclosed (78E)
Indoor enclosed ballasts are UL-Listed for indoor use where
the ballast must be mounted remotely from the luminaire.
These ballasts are typically used in applications where the
luminaire may be mounted in an
area with very high ambient
temperatures. The ballast can be
mounted remotely in a cooler
location. The case contains the
core-and-coil ballast potted in a
heat-dissipating resin (Class H,
180C max.) within the ballast
compartment. The capacitor and
ignitor (where used) are also
included within the case.
F-Can (72C)
F-Can ballasts are also UL-Listed for indoor use and are
commonly used with recessed downlighting fixtures to
18
BALLAST DESI GN APPLI CATI ONS
BALLAST DESIGN APPLICATIONS
Magnetic Ballasts
Advance HID ballasts are available in a variety of shapes and
sizes for the most popular lighting applications. Six basic
designs are available for magnetic ballasts.
Core & Coil (71A)
The electromagnetic or magnetic ballast is an inductor
consisting of one, two or three copper or aluminum coils
assembled on a core (or stack) of electrical-grade steel
laminations commonly referred to as a core-and-coil ballast
(71A). This assembly transforms electrical power into a form
appropriate to start and operate HID lamps. Ballasts for high
pressure sodium and pulse start metal halide lamps also
include an ignitor to start the lamp. The third major component
is the capacitor, which improves the power factor,
subsequently reducing line current draw, and in some
ballasts circuits works with the core-and-coil to set the lamp
operating wattage.
Typically, all three components the basic open core-and-
coil, capacitor, and ignitor are assembled directly into the
lighting fixture by the lighting luminaire manufacturer.
However, some ballast core-and-coil assemblies are encased
in a container to meet specific needs. Core-and-coil ballasts
BALLAST DESI GN APPLI CATI ONS
21
UL Listed for operation remote from the lighting fixture.
Postline (74P)
Lantern-type, post-top fixtures mounted on slender poles
often require ballasts which fit in the poles. Postline ballasts
include a special, elongated core & coil encased and potted
in high temperature resin (Class H, 180C
max.) in cylindrical housings of a diameter
to accommodate being placed within 3 or
4 diameter poles. The capacitor and ignitor
(where required) are included within the
housing. Postline ballasts are often supplied
with hanger chain for mounting and a spring
clip designed to press the ballast against
the pole wall for added heat sinking.
Postline ballast are UL-Recognized.
Electronic HID (e-HID)
Note: e-HID ballast development is a rapidly expanding
segment of the lighting industry. Consult Advance often for
the latest specifications on currently available ballasts.
e-Vision Low Frequency
e-Vision ballasts are available in
several case sizes for 20W to
200W metal halide, 150W high
pressure sodium and 100W Mini
whiteSON lamps.
DynaVision
Just as electronic ballasts for low
wattage ceramic lamps provide
critical lamp parameter control,
electronic ballasts for medium
wattage lamps serve similar
critical functions.
20
BALLAST DESI GN APPLI CATI ONS
minimize inherent ballast noise. F-Can ballasts are
stand-alone products encased and potted in larger fluorescent
ballast-style housings. F-Can ballasts utilize Class A (105C
rating, 90C maximum case temperature) insulating materials
for normal indoor ambients. Each ballast unit has an integral
auto-reset thermal protector, which disconnects the ballast
from the power line in the event of overheating to protect the
ballast and prevent melting and dripping of the asphalt fill. All
ballasts include the capacitor within the housing. All models
for high pressure
sodium, and medi-
um and low wattage
pulse start metal
halide ballasts also
include the ignitor
within the housing.
Outdoor Weatherproof (79W)
Outdoor weatherproof ballasts are designed for remote
mounting outdoors under all weather conditions. They may
also be placed inside a pole base, but care must be taken to
avoid areas prone to flood situations as weatherproof ballasts
are not water-submersible. They must also be mounted base
(nipple) down, with a drip loop for the wiring, when exposed
to weather. A core & coil, with
capacitor and ignitor (where
required) are firmly mounted to the
heat-sink base. This assembly is
then protected with an aluminum
cover, gasketed and bolted to the
base. The most common
applications are billboard, road sign
lighting and some outdoor sports
facilities, such as tennis courts.
Outdoor weatherproof ballasts are
BALLAST COMPONENTS
23
oil-filled capacitors. The discharge resistors (when required)
are installed within the capacitor case. Dry film capacitors are
UL-Recognized and contain no PCB material.
The maximum allowed dry film capacitor case temperature
is 105C.
Oil-Filled capacitors supplied today contain non-PCB oil and
are a UL-Recognized component. Oil-filled capacitors are
only supplied with ballasts where the capacitor operating
voltage cannot be satisfied by dry film capacitors. When
required, the capacitor discharge resistor is connected across
the capacitor terminals.
Additional precautions must be taken
when an oil filled capacitor is installed.
Underwriters Laboratories, Inc. (UL)
requires clearance of at least 3/8 inch
above the terminals to allow for
expansion of the capacitor in the event
of failure.
The maximum case temperature for
oil-filled capacitors is 90C.
Ignitors (Starters)
An ignitor is an electronic component that must be included in
the circuitry of all high pressure sodium, low wattage metal
halide (35W to 150W) and pulse start metal halide
(175W to 1000W) lighting systems. The ignitor provides a
pulse of at least 2500 volts peak to initiate the lamp arc. It is
important to note that ignitors are specifically designed
to operate properly with specific ballasts and cannot
be interchanged with other ignitors or different brands
of ignitors and ballasts. The ignitor should always be
mounted near the ballast but not on the ballast.
22
BALLAST COMPONENTS
The Advance DynaVision electronic ballasts are designed for
operation of 320W, 350W and 400W quartz arc tube, pulse
start metal halide lamps, and provide dramatic lumen
maintenance improvement over magnetically ballasted probe
start MH and pulse start MH systems.
BALLAST COMPONENTS
Capacitors
All high power factor (HPF) Reactor (R) and High Reactance
(HX) ballasts, as well as all Constant Wattage Autotransformer
(CWA), Constant Wattage Isolated (CWI) and Regulated
Lag ballasts require a capacitor. With core and coil and
encapsulated core-and-coil units the capacitor is a separate
component and must be properly connected electrically.
The capacitor for outdoor weatherproof, indoor enclosed,
F-can and postline types are already properly connected
within the assembly.
Two types of capacitors are currently in use: dry metalized
film and oil-filled. Present capacitor technology has allowed
all but a few capacitor applications to be dry film. Oil-filled
capacitors are used only when dry film technology cannot
satisfy capacitor voltage requirements.
Dry Metalized Film Capacitors are available to fill almost
all needs for HID ballast applications.
Advance dry film capacitors typically
require only half the space used by oil
filled capacitor and do not require
additional spacing for safety. The
compact, light weight, cylindrical
non-conductive case and two insulated
wires or terminals reduce the required
mounting space as compared with
BALLAST COMPONENTS
25
of 50 feet for reliable starting. The list of ballasts that can be
used with this extended range ignitor is in the ignitor section
of the Atlas. There are also other long range ignitors for
applications not satisfied by the Xtenza
.
Some lighting applications require instant restarting of lamps
after a momentary loss of power to the fixtures. When an
HID lamp is hot after operation and power is removed and
reapplied, it will not restart with a standard ignitor until the
lamp sufficiently cools. When instant restrike of a hot lamp
is required, a special ignitor is necessary that will provide
a pulse with much greater peak voltage. Advance has
developed an instant restrike ignitor for low wattage
mogul-based high pressure sodium lamps with a maximum
ballast-to-lamp distance of 2 feet .
APPLICATION AND INSTALLATION
INFORMATION
Remote Mounting of ballasts is often done to reduce ballast
audible noise in sensitive applications and requires special
attention to ballast spacing and temperature considerations,
distance to the lamp, and wire sizing.
Remote mounted ballasts are often mounted in groups in a
panel box or room away from the lamp location. Ballasts
dissipate heat that must be removed to prevent the ballasts
from overheating.
Spacing between ballasts and the mounting surface must be
considered when the ballasts are remote-mounted. Twelve
inches between ballasts must be maintained. If multiple rows
vertically are used, there should be at least 12 inches
between rows. In addition to ballast and row spacing, the
ballast must not be directly mounted to a non-metallic surface.
24
BALLAST COMPONENTS
When the lighting
system is energized,
the ignitor provides the
required high voltage
pulse until the lamp arc
is established and
automatically stops
pulsing once the lamp has started. It also furnishes the pulse
continuously when the lamp has failed or the socket is empty.
All lighting systems requiring ignitors must be
supplied with special pulse rated lamp sockets to
prevent voltage breakdown and arcing from the high
voltage ignitor pulse. If a lighting system is being converted
to a lamp and ballast requiring an ignitor from a system
without an ignitor, the lamp socked must be changed to a
pulse rated lamp socket or the lamp may not start reliably.
Ballasts that include an ignitor to start the HID lamp are
limited in the distance they may be mounted remotely from
the lamp because the ignitor pulse attenuates as the wire
length between the ballast and lamp increases. All Advance
open core and coil ballasts listed in the Atlas include a
standard ignitor that provides the proper electrical pulse to
start lamps when the ballast is mounted within the lighting
fixture. For most of these ballast/ignitor combinations, the
typical maximum ballast-to-lamp distance is listed in the
Atlas as 2 feet. When this distance is exceeded the lamp
may not start reliably and a long range ignitor is required. The
Atlas lists the proper long range ignitor required for various
high pressure sodium and metal halide ballasts.
Advance has developed a long range ignitor called the
Xtenza