Prelab (To Be Completed INDIVIDUALLY) : Lab 2 - Transformer Characteristics
Prelab (To Be Completed INDIVIDUALLY) : Lab 2 - Transformer Characteristics
From this transformers voltage and current ratings shown on the face of this module, determine the following and have the answers ready to show the instructor before you begin your in-lab work: What is the rated (maximum operating) voltage of this transformers primary winding (between terminals 1 and 2) ? _________________ What is the rated (maximum operating) current of this transformers primary winding ? _________________
Find and open the LVDAC-EMS program on the PC. Find and open the Metering application. Set up the transformer circuit as shown in the Figure 7-3 below. Connect meter inputs E1 and I1 of the data acquisition module as shown, and use input E2 to measure the different secondary voltages.
Figure 7-3. Transformer circuit connection. Turn on the power and slowly adjust the voltage control to obtain 60 V for the value of Es shown in Figure 7-3. Measure the transformer primary current (by I1) and the different voltages across the various terminals of the transformer secondary windings, as listed below. Change the connections of input E2 to measure each secondary voltage, making sure to turn off the Power Supply before modifying the connections of input E2. After recording the measurements, rotate the voltage control fully ccw to 0 and then turn off the power.
Do the secondary voltages compare well with the rated values written on the front panel? If they do not, then let your instructor know.
~
Turn on the power and slowly adjust the voltage control to apply rated voltage, as Eoc, to the primary winding. Measure Ioc, and Poc, the current and real power supplied to the primary winding. To obtain the Poc reading, find and click the Meter settings icon, then for meter M1, change its measurement setting from E1 to PQS(E1, I1). Record all three "open-circuit" parameters Eoc, Ioc, and Poc.
Eoc = ________ V;
Ioc = ________ A;
Poc = ________ W
Lower the supply voltage to zero and turn OFF the power supply, but do not disassemble the circuit.
Check to be sure that the supply voltage is set to zero, and then turn ON the supply. Carefully increase the voltage (should not exceed 10 V) until rated current, as Isc, is applied to the primary winding. Measure Esc, and Psc, the voltage and real power supplied to the primary winding. Record all three "short-circuit" parameters Esc, Isc, and Psc. Esc = ________ V; Isc = ________ A; Psc = ________ W
Lower the supply voltage to zero and then turn OFF the supply Remove all cables connected to the transformer, and put away all wires and equipment.
Turns Ratio Investigation Include all measured voltage and current values obtained during this investigation. Calculate the voltage ratios (turns ratios) between the windings for each case shown in the following table and also the percentage errors between the ideal and your measured values: Ideal ratio (## : 1) E5-6 : E1-2 E5-9 : E1-2 E3-4 : E1-2 E3-7 : E1-2 Measured ratio (## : 1) Percent error (%)
Open Circuit Test Include all measured voltage and current values obtained during this test.
Short Circuit Test Include all measured voltage and current values obtained during this test.