Motion Controllers, Users Manual A171-173
Motion Controllers, Users Manual A171-173
User's Manual
A173UHCPU, A172SHCPUN,
A171SHCPUN
Art.-no.: 134383
2000 09 01
Version B
INDUSTRIAL AUTOMATION
INTORODUCTION
WARNING
CAUTION
Note that some items described as cautions may lead to major results depending on the
situation. In any case, important information that must be observed is described.
II
4. Various precautions
Strictly observe the following precautions.
Mistaken handling of the unit may lead to faults, injuries or electric shocks.
CAUTION
Use wires and cables within the length of the range described in the instruction manual.
The ratings and characteristics of the system parts (other than control unit, servo amplifier,
servomotor) must be compatible with the control unit, servo amplifier and servomotor.
Install a cover on the shaft so that the rotary parts of the servomotor are not touched during
operation.
There may be some cases where holding by the magnetic brakes is not possible due to the
life or mechanical structure (when the ball screw and servomotor are connected with a
timing belt, etc.). Install a stopping device to ensure safety on the machine side.
IV
Conditions
Control unit/servo amplifier
Servomotor
0C to +55C
0C to +40C
(With no freezing)
(With no freezing)
According to each instruction
80%RH or less
(With no dew condensation)
manual.
According to each instruction
20C to +65C
manual.
Indoors (where not subject to direct sunlight).
No corrosive gases, flammable gases, oil mist or dust must exist
1000m (3278.69ft.) or less above sea level
According to each instruction manual
CAUTION
When coupling with the synchronization encoder or servomotor shaft end, do not apply
impact such as by hitting with a hammer. Doing so may lead to detector damage.
Do not apply a load larger than the tolerable load onto the servomotor shaft. Doing so may
lead to shaft breakage.
When not using the unit for a long time, disconnect the power line from the control unit or
servo amplifier.
Place the control unit and servo amplifier in static electricity preventing vinyl bags and store.
When storing for a long time, please consult our sales representative.
(4) Wiring
CAUTION
Correctly and securely wire the wires. Reconfirm the connections for mistakes and the
terminal screws for tightness after wiring. Failing to do so may lead to run away of the
servomotor.
After wiring, install the protective covers such as the terminal covers to the original positions.
Do not install a phase advancing capacitor, surge absorber or radio noise filter (option FRBIF) on the output side of the servo amplifier.
Correctly connect the output side (terminals U, V, W). Incorrect connections will lead the
servomotor to operate abnormally.
Do not connect a commercial power supply to the servomotor, as this may lead to trouble.
Do not mistake the direction of the surge absorbing diode
installed on the DC relay for the control signal output of
brake signals, etc. Incorrect installation may lead to signals
not being output when trouble occurs or the protective
functions not functioning.
Do not connect or disconnect the connection cables
between each unit, the encoder cable or sequence expansion cable while the power is ON.
Servo amplifier
VIN
(24VDC)
Control output
signal
RA
Securely tighten the cable connector fixing screws and fixing mechanisms. Insufficient fixing
may lead to the cables combing off during operation.
Do not bundle the power line or cables.
VI
A1S61PN
A1S62PN
100 to 240VAC+10%
(85 to 264VAC)-15%
50/60Hz 5%
Input power
Input frequency
Tolerable momentary
power failure
Within 20ms
VII
(9) Disposal
CAUTION
Dispose of this unit as general industrial waste.
Do not disassemble the control unit, servo amplifier or servomotor parts.
Dispose of the battery according to local laws and regulations.
VIII
Revisions
*The manual number is given on the bottom left of the back cover.
Print Date
*Manual Number
Apr.1998
Sep.2000
IB(NA)-67395-B
IB(NA)-67395-C
Revision
First edition
Addition
Addition of information on the A173UHCPU
Correction
For Sate Operations (4. Various precautions (3), (6), (8)), CONTENTS, 1.1,
1.2.1, 1.2.2, 1.3, 1.4, 1.5.1, 1.5.2 (1), 1.5.3, 1.5.4, 1.5.5, 1.5.6, 2.1, 2.3, 2.3.1,
2.3.2 (2), 4.3, 4.4, 5.4.1, 5.4.1(3), 5.4.1 (4), 5.4.1 (5), APPENDICES
Delete
1.5.7 (2), 5.3.1 (2)
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial
property rights which may occur as a result of using the contents noted in this manual.
2000 Mitsubishi Electric Corporation
CONTENTS
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS..................................................... 1- 1 to 1-57
1.1 Overview of the Motion System ......................................................................................................... 1- 1
1.2 Overall Configuration of Motion System ............................................................................................ 1- 3
1.2.1 A172SHCPUN/A171SHCPUN System Overall Configuration .................................................... 1- 3
1.2.2 A173UHCPU System Overall Configuration ............................................................................... 1- 5
1.3 Equipment in System ......................................................................................................................... 1- 7
1.4 General Specifications ...................................................................................................................... 1-10
1.5 Specifications and Settings of Components ..................................................................................... 1-11
1.5.1 A173UHCPU/A172SHCPUN/A171SHCPUN............................................................................. 1-11
1.5.2 Extension Base Power Supply Module ...................................................................................... 1-25
1.5.3 Base Units and Extension Cables .............................................................................................. 1-28
1.5.4 Manual Pulse Generator/Synchronous Encoder Interface Module............................................ 1-38
1.5.5 Teaching Unit ............................................................................................................................. 1-49
1.5.6 SSCNET Cables and Termination Resistor and Their Connection Method .............................. 1-53
1.5.7 Battery ........................................................................................................................................ 1-57
2. DESIGN...................................................................................................................................... 2- 1 to 2-22
2.1 System Designing Procedure ............................................................................................................ 2- 1
2.2 System Design ................................................................................................................................... 2- 4
2.3 External Circuit Design....................................................................................................................... 2- 5
2.3.1 Power Supply Circuit Design...................................................................................................... 2-10
2.3.2 Safety Circuit Design.................................................................................................................. 2-12
2.3.3 Instructions for External Circuit Wiring Design........................................................................... 2-16
2.4 Layout Design within Enclosure........................................................................................................ 2-17
2.4.1 Location Environment................................................................................................................. 2-17
2.4.2 Installing the Base Units............................................................................................................. 2-18
2.4.3 Installation .................................................................................................................................. 2-19
2.4.4 Calculating Heat Generated by A173UHCPU/A172SHCPUN/A171SHCPUN .......................... 2-20
2.5 Design Checklist ............................................................................................................................... 2-22
3. MOUNTING AND WIRING......................................................................................................... 3- 1 to 3-12
3.1 Mounting and Wiring Methods ........................................................................................................... 3- 1
3.2 Mounting the Base Unit...................................................................................................................... 3- 1
3.2.1 Mounting without DIN Rail........................................................................................................... 3- 2
3.2.2 Mounting with DIN Rail................................................................................................................ 3- 2
3.3 Mounting and Removing Modules ..................................................................................................... 3- 4
3.4 Mounting the Serial Absolute Synchronous Encoder ........................................................................ 3- 7
3.5 Wiring ................................................................................................................................................. 3- 9
3.5.1 How to Run the Power Supply and I/O Wires ............................................................................. 3- 9
3.5.2 Example of Routing the Power Supply and I/O Wires ............................................................... 3-11
3.6 Mounting/Wiring Checklist ................................................................................................................ 3-12
4. TRIAL RUN AND ADJUSTMENT ............................................................................................... 4- 1 to 4- 8
4.1 Checklist before Trial Operation ........................................................................................................ 4- 1
4.2 Trial Run and Adjustment Procedure................................................................................................. 4- 3
I
II
PE, SW
RN-GSV
PE
The following diagram outlines the peripheral devices and programs using a
positioning software package, data creation, and A173UHCPU/A172SHCPUN/
A171SHCPUN processing.
[Peripheral device]
IBM PC
+
SW SRX-GSV
SW RN-GSV
+
SW SRX-SV
SW RN-SV
[Program, data]
[A173UHCPU/A172SHCPUN/A171SHCPUN]
Sequence program
Sequence control
Servo program or motion
program execution
PE,
PE
,
SCPU
Positioning
device
Servo program or
motion program
Positioning
parameter
PCPU
JOG operation
For communication
between SCPU and PCPU
Positioning control
Home position return
Servo monitoring
11
REMARKS
For information about a peripheral device and programming information for
producing a sequence program and a special function unit, refer to each
manual pertaining to the individual unit.
For information about creating motion programs, refer to the programming
manual of the operating system used. For information about the operation of
each peripheral software package, refer to each individual operating manuals.
In this manual, the following abbreviations are used.
Description
Abbreviation
A173UHCPU/A172SHCPUN/
MR-H-BN/MR-J2S-B/MR-J2-B
A172SENC
SSCNET*1
12
Motion CPU
A6BAT
A172 A1S
SENC Y42
Extension cable
(A1SC B for
A1S6 B
and A168B)
(A1S NB
for A6 B)
100/200VAC
B)
IBM PC
(DOS)
RS422
GOT
Power supply
module
Limit switch
output module
Motion slot
A171SHCPUN A172SHCPUN
Communication cable
(A270CDCBL M/
A270BDCBL M)
IBM PC (DOS,Windows)
TRA tracking
RS422
SSCNET2
SSCNET cable
d1
d2
d3
dn
*2
Termination
resistance
SSCNET1
1
2
MR-H-BN/MR-J2S-B/MR-J2-B model
Servo amplifier
SSCNET:Servo System Controller NETwork
POINTS
(1) When using the sequence extension base and bus connection type GOT, select the A168B as the
sequence extension base. When not using the sequence extension base, you can connect the bus
connection type GOT directly to the extension connector of the main base unit.
(2) When using a teaching unit A31TU-E with a dead-man switch, a dedicated connecting cable
A31TUCBL03M is required between the CPU unit and A31TU-E connector. If the A31TU-E is
connected directly to the RS422 connector of the CPU without using a dedicated cable, the
A31TU-E will not operate at all. After disconnecting the A31TU-E, attach a short-circuit connector
A31SHORTCON for A31TUCBL.
(3) In a motion module, a sequence A1S I/O modules can also be installed.
(4) Though the external input signals of A172SENC are reserved for eight axes, for A171SHCPUN,
set those for the first half four axes (PX0 to PX0F).
13
CAUTION
Configure safety circuits external to the controller or servo amplifier if their abnormal operation
could cause axis motion in a direction other than the safe operating direction for the system.
Ensure that the characteristics of other components used in a system match those of the
controllers, servo amplifiers, and servo motors.
Set the parameters to values appropriate for the controllers, servo amplifiers, servo motors,
regenerative resistor types, and system application. The protective functions may not work if the
parameters are set incorrectly.
14
Manual pulse
generator/
synchronous encoder
interface module
Battery
A6BAT
Emergency stop input
100/200VAC
IBM PC
(DOS)
Extension cable
(A1SC B for
A1S6 B
and A168B)
(A1S NB
for A6 B)
E
E
E
Teaching unit
A31TU-E/A30TU-E
RS422
GOT
Power supply
module
Motion slot
RS422
Communication cable
(A270CDCBL M/
A270BDCBL M)
TRA tracking
IBM PC (DOS,Windows)
*3
*2
*2
SSCNET4
SSCNET4
SSCNET cable
SSCNET3
SSCNET2
d1
d9
d8
d17
d16
d25
d24
d32
SSCNET1
1
2
4
8
M
E
MR-H-BN/MR-J2S-B/MR-J2-B model
Servo amplifier, max. 32 axes
SSCNET:Servo System Controller NETwork
POINTS
(1) When using the sequence extension base and bus connection type GOT, select the A168B as the
sequence extension base. When not using the sequence extension base, you can connect the bus
connection type GOT directly to the extension connector of the main base unit.
(2) When using a teaching unit A31TU-E with a dead-man switch, a dedicated connecting cable
A31TUCBL03M is required between the CPU unit and A31TU-E connector. If the A31TU-E is
connected directly to the RS422 connector of the CPU without using a dedicated cable, the
A31TU-E will not operate at all. After disconnecting the A31TU-E, attach a short-circuit connector
A31SHORTCON for A31TUCBL.
(3) In a motion module, a sequence A1S I/O modules can also be installed.
*2 The A173UHCPU can use four channels of the SSCNET. When using the SSCNET card/board
(A30CD-PCF/A30BD-PCF), connect it to the SSCNET4 and the servo amplifiers to the SSCNET1
to 3.
In this case, up to 24 axes of servo amplifiers can be connected.
*3 TRA tracking enable can use any one point.
15
CAUTION
Configure safety circuits external to the controller or servo amplifier if their abnormal operation
could cause axis motion in a direction other than the safe operating direction for the system.
Ensure that the characteristics of other components used in a system match those of the
controllers, servo amplifiers, and servo motors.
Set the parameters to values appropriate for the controllers, servo amplifiers, servo motors,
regenerative resistor types, and system application. The protective functions may not work if the
parameters are set incorrectly.
16
CPU module
Model Name
Description
A173UHCPU(-S1)
A172SHCPUN
A171SHCPUN
A172B
A175B
A178B
Main base unit
A178B-S1
A178B-S2
A178B-S3
A1S65B
Sequence
extension base
unit
A1S68B
A168B
A1SC01B
Current
Consumption
5 VDC (A)
1.90
1.63
1.63
Sequence extension
connector as
accessory
Extension connector
as accessory
For extension to the
right side
A1SC03B
A1SC07B
A1SC12B
Extension cable A1SC30B
A1SC60B
A1SC05NB
A1SC07NB
A1SC30NB
A1SC50NB
Manual pulse
generator
/synchronous
encoder
interface
module
A172SENC
A1SY42
MR-HDP01
For A6
0.93
0.06
0.15
0.22
A31TUCBL03M
A31SHORTCON
A30BD-PCF
A30CD-PCF
MR-HSCBL
Battery
A6BAT
A30TU-E
A31TU-E
0.42
MR-HENC
Serial absolute
synchronous
encoder cable
Teaching unit
Remarks
A31TU-RE
A270BDCBL
A270CDCBL
17
0.22
0.22
For control panel
When A31TU-E is
not connected
MR-H-BN
series
MR-J2S-B
series
MR-J2-B
series
Model Name
MR-H BN
Servo amplifier
MR-H KBN
Battery
MR-BAT
Termination
MR-TM
connector
MR-PB
MR-H KB
Regenerative
Standard accessory
resistor
MR-PB -4
FR-BU
FR-RC
Description
50 W to 22 kW
30 kW to 55 kW
Backup for absolute position detection
Fitted to the last amplifier of SSCNET
External regenerative resistor 10 W to 500 W
Regenerative power 600 W
MR-BAT
MR-A-TM
MR-J2HBUS
SSCNET cable
MR-J2HBUS
Equipment
common to
MR-J2S-B
and
MR-J2-B
Encoder
*2
series
MR-JHSCBL
MR-JHSCBL
cable
MR-ENCBL
MR-JCCBL
MR-JCCBL
Encoder
connector set
50 W to 3.5 kW
MR-J2CNS
MR-ENCNS
MR-J2CNM
For connection of CPU module and MR-J2S-B/MR-J2-B, for connection of MR-HM-A BN and MR-J2S-B/MR-J2-B
0.5 m(1.64 ft), 1 m (3.28ft), 5 m (16.4 ft)
For connection of MR-J2S-B/MR-J2-B and MR-J2S-B/MR-J2-B
M
0.5 m(1.64 ft), 1 m (3.28ft), 5 m (16.4 ft)
For connection of HC-SFS/RFS/UFS (2000r/min) series motor and
Standard
M-L cable
MR-J2S-B, and for connection of HC-SF/RF/UF (2000r/min) series
M-H Long flexing motor and MR-J2-B
2 m (6.56 ft), 5 m (16.4 ft), 10 m (32.8 ft), 20 m (65.6 ft),
M-H life cable
30 m (98.4 ft)
For connection of HC-MFS/KFS/UFS (3000r/min) series motor and
Standard
M-L
MR-J2S-B, and for connection of HC-MF/UF (3000r/min), HA-FF
cable
series motor and MR-J2-B
Long flexing
2 m (6.56 ft), 5 m (16.4 ft), 10 m (32.8 ft), 20 m (65.6 ft),
M-H
life cable
30 m (98.4 ft)
For HC-SF/RF/UF (2000r/min), HC-SFS/RFS/UFS (2000r/min) series motors
Amplifier side connector and encoder side connector set
For HC-MF/UF (3000r/min), HA-FF, HC-MFS/KFS/UFS (3000r/min) series motors
Amplifier side connector and encoder side connector set
18
DOS
assembly
IBM PC/AT
NT/
(SV13)
98
For motion
conveyor
For
A172SH/
A171SH
For
For
For
A173UH
A172SH
Japanese SW2SRX-GSV13P
SW2SRX-
SW0SRX-
SW0SRX-
English
From 00J on
00F or later
SV13B
SV13D
SV13G
From 00F on
00E or later
Without
Without
SW2SRX-
SW2SRX-
SW0SRX-
restriction
restriction
SV13B
SV13D
IBM PC/AT
Teaching
function
A171SH
SV13G
Model Name
SW2SRX-GSV13PE
Japanese SW3RNC-GSV
English
SW3RNC-GSVE
Japanese SW3RNC-GSV
SFCcompatible
Applicable version
Peripheral
Devices
For conveyor
For
A173UH
From 00F on
Yes
Without
restriction
NT/
SW3RN-
SW3RN-
98
SV13B
SV13D
English
assembly
SW3RNC-GSVE
Without
Without
restriction
restriction
(SV13)
Japanese
machinery
English
IBM PC/AT
From 00B on
00B or later
From 00J on
00F or later
Without
Without
SW2SRX-
SW0SRX-
SW0SRX-
restriction
restriction
SV22A
SV22C
SV22F
From 00F on
00E or later
Without
Without
restriction
restriction
SW0IX-CAMPE
(SV22)
NT/
98
For motion
compatible
automatic
machinery
Japanese SW3RNC-GSV
English
SW3RNC-GSVE
Japanese SW3RNC-GSV
SFCIBM PC/AT
SW2SRX-GSV22PE
DOS
For automatic
SW2SRX-GSV22P
SW0SRX-CAMP
From 00F on
Without
restriction
SW3RN-
NT/
98
No
English
SW3RNC-GSVE
Without
Without
restriction
00J or later
SV22C
SW2SRX-
SW0SRX-
SW0SRX-
SV43A
SV43C
SV43F
SW0SRX-
SW0SRX-
SV51D
SV51G
restriction
From 00T on
SW3RN-
SV22A
(SV22)
For machine
tool peripheral IBM PC/AT DOS Japanese SW2SRX-GSV43P
(SV43)
For dedicated
robot (SV51)
00E or later
19
No
Yes
Specification
Operating ambient
0 to 55C
temperature
Storage ambient
-20 to 75C
temperature
Operating ambient
humidity
Storage ambient
humidity
Frequency
Vibration resistance
Conforms to JIS C
0911*2
Acceleration
Noise resistance
Number of Sweeps
0.075mm
10 to 55Hz
(0.003 in)
9.8m/s2
55 to 150Hz
Shock resistance
Amplitude
10
(1 octave/minute)*1
Withstand voltage
2830VAC rms/3 cycles across all inputs/LG and all outputs/FG (altitude 2000m (6557.38ft.))
Insulation resistance
5M
Ground
or more by 500VDC insulation resistance tester across all inputs/LG and all outputs/FG
Operating environment
Cooling method
Natural cooling.
REMARKS
*1 An octave refers to an increase or decrease in frequency by a factor of
two. For example, the following are all octaves: 10 Hz to 20 Hz, 20 Hz to
40 Hz, 40 Hz to 20 Hz, and 20 Hz to 10 Hz.
Refer to CHAPTER 2 DESIGN for the installation environment and
mounting instructions.
*2 JIS: Japan Industrial Standards
WARNING
Class 3 grounding should be used. The motion controller should not share a common ground with
any other equipment. The ground terminal is located on the motion controller module terminal
block. (See Section 1.5.2.)
CAUTION
The motion controller must be stored and operated under the conditions listed in the table of
specifications above.
Disconnect the power cables from the motion controller if it is to remain unused for a long period
of time.
Insert a controller or servo amplifier into the static-proof vinyl bag for storage.
Consult the system service or service station before storing equipment for a long period of time.
1 10
A173UHCPU(-S1)
A172SHCPUN
A171SHCPUN
32-axes
3.5 ms/1 to 20 axes
7.1 ms/21 to 32 axes
8-axes
4-axes
Equivalent to
reinforced I/O
memory of
A2SHCPU
Equivalent to
A2SHCPU
Computing
frequency
SV22
Sequencer CPU
Processing speed
( s) (Sequence
instruction)
Equivalent to A3UCPU
Direct
method
Refresh
method
Standard
Memory capacity (built-in RAM)
-S1
Program capacity
(Main sequence)
No. of file register (R)
No. of extension file register
block *2
8192 points
2048 points
192k bytes (Equivalent to
A3NMCA-24)
768k bytes (Equivalent to
A3AMCA-96)
System
configuration
Outside dimensions
192k bytes
(Equivalent to
A3NMCA-24)
64k bytes
(Equivalent to
A3NMCA-8)
Max. 14k steps
Standard
-S1
Max. 2 blocks
Max. one
A172SENC 4
(Corresponding to external signal input
32-axes)
4CH.
A172SENC 1
(Corresponding to external signal input
8-axes)
2CH.
SSCNET1..... For connection of servo
amplifier
SSCNET2..... For personal computer link
dedicated
Compatibility
System setting
2048 points
1024 points
512 points
0.25 s/step
130
113.3
0.85 (1.87)
*1 The real I/O points can be used within the range of one extension base.
*2 No. of extension file register blocks varies depending on the setting of program capacity, No. of file
registers, and No. of comments.
1 11
1 12
Number of instructions
Processing speed ( s)
(sequence instructions)
No. of I/O points
Sequence instructions
Basic instructions
Special instructions
Motion dedicated instructions
Direct method
Refresh method
Program capacity
Timers (T)
Specifications
A173UHCPU(-S1)
A172SHCPUN
A171SHCPUN
Points
256 points
*4
Device
Normal counter
Interrupt program counter
Counters (C)
Setting range
1 to 32767
Device
C0 to C255
C224 to C255
(No initial value)
1 to 32767
Specifications
2 points (V, Z)
(V, V1 to V6, Z, Z1 to Z6)
1 13
No. of comments
No. of extension comments *2
Self-diagnosis function
Operating mode on error
Output mode selection when switching from STOP to RUN
Clock function
A173UHCPU (-S1)
A172SHCPUN
A171SHCPUN
Max. 10 blocks
Standard (set by memory
*6
*6
capacity)
Max. 3 blocks
Max. 10 blocks
(set by memory capacity)
(set by memory capacity)
Max. 46 blocks
-S1
(set by memory
capacity)
Max. 4032 points (64k bytes), 1 point = 16 bytes (set in 64-point unit)
Max. 3968 points (63k bytes), 1 point = 16 bytes (set in 64-point unit)
Watchdog error monitoring, memory/CPU/input output/battery, etc. error detection
Select stop/continue
Select re-output operation status before STOP (default) or output after operation
execution.
Year, month, day, hour, minute, day of the week (leap year automatic distinction)
*1 Range of positioning dedicated devices differs depending on the OS. Refer to the Programming Manual of each OS.
When shared between M, L and S, the total number of devices points is 8192 for the A173UHCPU or 2048 for the A172SHCPUN/A171SHCPUN.
*2 Extension comments are not stored into the internal memory of the CPU.
*3 For the A173UHCPU, set the times of the extension timers (T256 to T2047) using the word devices (D, W, R).
*4 For the A173UHCPU, set the count values of the extension counters (C256 to C1023) using the word devices (D, W, R).
*5 The real I/O points can be used within the range of one extension base.
*6 SW0GHP-UTLP-FN1 is necessary for using A6GPP and A6PHP.
1 14
Description
! Sets a constant time for one scan of a sequence program which is independent of the sequence
Constant scan
program scan.
! Set the constant scan time between 10 ms and 2000 ms.
Latch (hold on
power interruption)
Remote
RUN/STOP
! The contents of devices set as latch devices are retained when a reset or a power interruption
over 20 ms occurs if the power is turned off.
! Devices L, B, T, C, D, W can be set as latch devices.
! Conducts remote RUN/STOP sequence control from external inputs or peripheral devices when
the RUN/STOP switch is set to RUN.
! Stops the operation and holds the output (Y) ON/OFF status.
PAUSE
Status latch
Sampling trace
Off-line switch
Error indicator
order or priority
! Separates the devices (Y, M, L, S, F, B) used by the OUT instruction from the sequence
program operations.
! Sets order in which the indicators light and go out when an error occurs.
! Executes the CPU module internal clock operations.
Clock
! Clock data is: year, month, day, hour, minute, second, day of week.
! The clock data can be read to D9025 to D9028.
1 15
A173UHCPU/A172SHCPUN
3)
2)
1)
13)
15)
16)
12)
4)
100 240VAC
105VA
100 240VAC
105VA
10)
14)
NC
NC
6)
17)
7)
8)
9)
[A173UHCPU]
18), 19)
FRONT
SSCNET
18)
19)
18)
19)
11)
1:SSCNET1 2:SSCNET2
3:SSCNET3 4:SSCNET4
A171SHCPUN
2)
3)
1)
13)
15)
16)
N
100 240VAC
105VA
4)
3
24VDC 0.6A
100 240VAC
105VA
3
24VDC 0.6A
10)
14)
+24V
5)
12)
24G
6)
17)
7)
8)
9)
18), 19)
No.
11)
Name
1)
2)
POWER indicator
Application
! RUN/STOP: Starts or stops operation of a sequence program.
! RESET: Resets the hardware.
Applies a reset after an operation error occurs and initializes the operations.
! LATCH CLEAR (L. CLR): Clears the latch area data set with the parameters
(to OFF or 0).
(LATCH CLEAR also clears data outside the latch area.)
! Display indicator for 5 VDC power supply.
1 16
Name
3)
RUN indicator
4)
ERROR indicator
5)
24 VDC, 24 GDC
terminals
6)
FG terminal
7)
LG terminal
Power supply input
8)
terminals
9) Terminal screws
10) Terminal cover
11) RS-422 connector
12) Covers
Applications
! Lit: Sequence program operating with RUN/STOP key switch set to RUN.
The indicator remains lit if an operation error occurs in the sequence
program (Refer to section 5.4.1 (10)).
! Not lit: The RUN indicator is not lit in the following cases:
! No 100/200 VAC power supplied to the CPU module.
! RUN/STOP key switch is set to STOP.
! A remote STOP is applied.
! A remote PAUSE is applied.
! Flashing: The RUN indicator flashes in the following cases:
! Self-diagnosis function detected an error which stops sequence
program
operation.
! A latch clear operation is conducted.
! Lit: Self-diagnosis function detected an error.
However, the indicator does not light if it is set not to light for the error
detected in the order of priority settings.
! Not lit: Normal, or error detected by CHK instruction.
! Flashing: Sequence program annunciator (F) is on.
! Internally supplies output modules which require 24 VDC (supplied through external
wiring). (A171SHCPUN only)
! A grounding terminal connected with the shielding pattern on the printed circuit
board.
! Ground for power supply filter, with 1/2 the electrical potential of the input voltage.
! Connect the 100 VAC or 200 VAC power supply to the power supply input
terminals.
! M3.5 7
! A cover to protect the terminal block.
! Connector to read, write, monitor, or test main programs with a peripheral device.
! Covered by a cover when not connected to a peripheral device.
! Open the protective cover for the printed circuit board, RS-422 connector, or
battery to carry out the following operations:
! Set DIP switches.
! Connect the battery connectors.
! Replace the battery.
! Screws to fix the module to the base unit.
! Back-up battery for programs, devices in the latch range, and file registers.
(See Section 1.5.7 for the battery mounting procedure.)
! Installation switch
This switch is used to change the installed CPU module operating system with a
peripheral device.
(See Section 1.5.1 (5) for details about the switch settings.)
ON : Turn ON to install an operating system.
OFF : Turn OFF to enable CPU operation when OS installation is complete.
! This switch selects the I/O control method and enables or disables memory
protection.
(See Section 1.5.1 (5) for details about the switch settings.)
1 17
Name
Applications
! A connector for linking a personal computer and personal computer link SSC.
When using the A172SHCPUN/A171SHCPUN, connect the servo amplifier or
personal computer to SSCNET2, or when using the A173UHCPU, connect it to
SSCNET4.
1 18
OFF
ON : Installation
OFF: Ordinary operation
Not used
SW402
For A172SHCPUN/A171SHCPUN
Not used
I/O control method setting
OFF
ON
1 2
ON : Memory protect ON
OFF: Memory protect OFF
* SW402-2 is invalid for A171SHCPUN.
* Memory allocation varies depending on the PC memory capacity
setting.
SW402
OFF
For A173UHCPU
SCPU built-in RAM memory protect range setting
1 2 3 4
ON
A17 SHCPUN
ON : Memory protect ON
OFF: Memory protect OFF
* Memory allocation varies depending on the PC memory capacity
setting.
1 19
CAUTION
Switch SW1-2 is for use by the manufacturer only.
Leave this switch set OFF.
Operation cannot be guaranteed if this switch is set to ON.
POINTS
(1) Turn off the power supply before setting the install switch.
(2) After using this switch, check the switch status before turning on the power supply.
(3) The switch settings shipped from the factory are as shown above. The switch settings are
indicated by a mark ( ).
(4) Whenever the switch settings are changed, be sure to reset the key of the CPU once or turn on the
power again.
(5) Turn off the power before setting the I/O control changeover switch.
(6) After using this switch, check the switch status before turning on the power supply.
(7) A BIN value corresponding to the selected I/O control method is input in special-function register
D9014 and can be monitored from a peripheral device. (A172SHCPUN/A171SHCPUN)
! Direct method for inputs and outputs......... 0
! Refresh method for inputs and outputs ..... 3
(8) When executing the sampling trace and/or the status latch, do not protect the memory. If the
memory is protected, the result of execution cannot be stored in the memory.
1 20
Specifications
Model name
A173UHCPU/A172SHCPUN
100 to 240 VAC
Input frequency
50/60 Hz
Overcurrent protection *1
Overvoltage protection *2
5%
105VA
Rush current
Rated output current
A171SHCPUN
+10%
-15%
5A
3A
10%
5VDC
0.6A
5.5 A min.
3.3 A min.
24VDC
0.66 A min.
5VDC
5.5 to 6.5 V
24VDC
Efficiency
65% min.
Power indicator
M3.5
0.75 to 2mm
RAV 1.25-3.5
RAV 2-3.5
59 to 88 Ncm
20ms max.
time
POINTS
*1: Overcurrent protection
When current in excess of the specifications flows through the 5 VDC or
24 VDC circuits, the overcurrent protection device breaks the circuit and
stops the system.
A drop in voltage will extinguish or dim the CPU module indicator
POWER display.
After overcurrent protection operates, start up the system after
eliminating the cause, such as insufficient current capacity or short
circuit.
The system initial start commences when the current returns to the
normal level.
*2: Overvoltage protection
When an overvoltage of 5.5 V to 6.5 V is applied to a 5 VDC circuit, the
overvoltage protection device breaks the circuit and stops the system.
The CPU module indicator goes out.
To restart the system, switch the input power supply off, and then turn it
back on. The system initial start commences.
If the system does not start up and the indicator POWER display
remains off, the CPU module must be changed.
1 21
CPU module
Panel computer, etc.
SSCNET cable
SSCNET connector*
Communication cable
(A270CDCBL M/A270BDCBL M)
SSC I/F card/board
(A30CD-PCF/A30BD-PCF)
A172SHCPUN/A171SHCPUN
A173UHCPU
Module
Usable(MELSECNET mode or
MELSECNET (II) MELSECNET II mixed mode
Usable
only)
A1SJ71AP21/R21
A1SJ71LP21/BR11
Usable
In the MELSECNET(II) data link system, the motion CPU module can be used
as the master or local station in each layer. When it is used as the master
station in layer 3 (local station in layer 2), up to two data link modules
(A1SJAP21/R21) may be used.
In the MELSECNET/10 network system, the motion CPU module can be used
as the control or normal station. Up to four network modules
(A1SJ71LP21/BR11) may be loaded to achieve separate network
configurations.
Refer to the following manuals when using the MELSECNET(II) data link system
and MELSECNET/10 network system.
MELSECNET(II), MELSECNET/B data link system reference manual
MELSECNET/10 data link system reference manual (Inter-PC network
manual)
1 22
(a) MELSECNET(II)
Master
station
Fiber-optic or coaxial cable
2nd class
Local station
Local station
Master station
Fiber-optic or coaxial cable
Remote I/O
station
3rd class
Local station
Local station
POINTS
As the instruction for other station access in the MELSECNET(II) data link
system, note that the system is not compatible with other station access via
the motion controller, e.g. access to the motion controller from the peripheral
device connected to the sequencer CPU, access to the sequencer CPU from
the peripheral device connected to the motion controller, and access to the
motion controller from the personal computer on the network.
(b) MELSECNET/10
1) Optical loop network
Master
station
Fiber-optic cable
Normal station
Normal station
Normal station
Normal station
Normal station
Network No.
Coaxial cable
1 23
Normal station
CPU module
RS422 connector
RS422
cable
RS422-RS232C converter
RS232C
cable
*2
SSCNET connector
Invalid Valid
Emergency
Stop
MITSUBISHI
A30TU
*1
Data
Program
Monitor
Test
Instruction
7 :
Write
4 D
Item
8 #
Address
1 A
2 B
Function
Clear
9 SP
Delete Indirect
5 E
6 F
Register
Interval
9 C
Stop
Speed
ratio
Teaching unit
(A30TU-E/A31TU-E)
Step
Step +
Insert
!
Numeri c
input
Shift
Error
Reset
Axis No.
JOG
JOG +
Return
CAN
GO
SSCNET cable
Communication cable
(A270CDCBL M/A270BDCBL M)
*1: The A31TU-E must be connected with the external circuit. For details, refer
to Section 1.5.5 (2).
*2: Use SSCNET2 for A171SHCPUN/A172SHCPUN or SSCNET4 for
A173UHCPU.
1 24
Item
A1S61PN
A1S62PN
50/60 Hz
5%
105VA
Rush current
5A
24VDC
Overcurrent protection *1
2
Overvoltage protection *
3A
10%
5VDC
0.6A
5.5 A min.
3.3 A min.
24VDC
0.66 A min.
5VDC
5.5 to 6.5 V
24VDC
Efficiency
65% min.
Withstand voltage
2,830VAC rms/3 cycles across all inputs/LG and all outputs/FG (altitude 2,000m
(6557.38 ft))
Insulation resistance
5M or more by 500VDC insulation resistance tester across all inputs/LG and all
outputs/FG
Noise immunity
Power indicator
LED indicator
M3.5
0.75 to 2mm2
RAV 1.25-3.5
RAV 2-3.5
59 to 88 Ncm
130
Weight kg (lb)
54.5
3.69)
0.6 (1.32)
20ms max.
POINT
*1: Overcurrent protection
When current in excess of the specifications flows through the 5 VDC or
24 VDC circuits, the overcurrent protection device breaks the circuit and
stops the system.
A drop in voltage will extinguish or dim the power supply module
indicator POWER display.
After overcurrent protection operates, start up the system after
eliminating the cause, such as insufficient current capacity or short
circuit.
The system initial start commences when the current returns to the
normal level.
*2: Overvoltage protection
When an overvoltage of 5.5 V to 6.5 V is applied to a 5 VDC circuit, the
overvoltage protection device breaks the circuit and stops the system.
The power supply module indicator goes out.
To restart the system, switch the input power supply off, and then turn it
back on. The system initial start commences.
If the system does not start up and the indicator POWER display
remains off, the power supply module must be changed.
1 25
1)
6)
2)
(FG)
(LG)
3)
4)
100-240 VAC
5)
No.
Name
Application
1)
POWER indicator
2)
FG terminal
A grounding terminal connected with the shielding pattern on the printed circuit board.
3)
LG terminal
Ground for power supply filter, with 1/2 the electrical potential of the input voltage.
4)
Connect the 100 VAC or 200 VAC power supply to the power supply input terminals.
5)
Terminal screws
M 3.5 7
6)
Terminal cover
7)
1 26
1)
7)
DC24V 0.6A
24V
2)
24G
3)
(FG)
4)
(LG)
5)
100-240 VAC
6)
No.
1)
2)
Name
Application
POWER indicator
24VDC, 24GDC
Supplies output modules which require 24 VDC internally (supplied through external
terminals
wiring).
3)
FG terminal
A grounding terminal connected with the shielding pattern on the printed circuit board.
4)
LG terminal
Ground for power supply filter, with 1/2 the electrical potential of the input voltage.
5)
Connect the 100 VAC or 200 VAC power supply to the power supply input terminals.
6)
Terminal screws
M 3.5 7
7)
Terminal cover
8)
1 27
A172B
Item
A175B
A178B
Extension connections
OK
0.51 (1.12)
Accessories
430 130 28
(10.93 5.12 1.1)
0.75 (1.66)
0.97 (2.14)
Mounting screws M5
25 4 pcs
POINT
Configure a system by choosing the motion modules and MELSEC-A series I/O modules so that the sum
of 5VDC consumed currents of the motion modules, MELSEC-A series I/O modules, synchronous
encoders and manual pulse generators connected to the main base unit is within 5 (A) for the
A172SHCPUN or 3 (A) for the A171SHCPUN.
2) Extension base unit specifications
Table 1.7 Table of Extension Base Unit Specifications
Model Name
A1S65B
Item
Max. I/O modules mountable
A1S68B
5 modules
A168B
8 modules
Must be mounted
Second/subsequent
stage unconnectable
Only GOT
connectable
420 130 28
(16.55 5.12 1.1)
420 130 28
(16.55 5.12 1.1)
0.71 (1.56)
0.95 (2.09)
0.95 (2.09)
Weight kg (lb)
Accessories
Mounting screws M5
25 4 pcs
A1SC01B
A1SC03B
A1SC12B
A1SC30B
0.055 (2.17)
Item
0.33 (12.99)
1.2 (47.24)
3.0 (118.11)
0.22
0.021
0.055
0.121
1 28
0.10 (0.22)
0.20 (0.44)
0.4 (0.48)
7)
4)
1)
Sequencer slot
3)*1 Motion slot
6)
No.
1)
Name
Extension cable
connector
2)
Application
Connects to the signal communications connector on the extension base unit with the
extension cable.
A cover for protecting the extension cable connector. When connecting to an extension
base unit, cut out the area surrounded by the groove under the word OUT on the base
cover with side cutters, or some other tool.
Connectors to mount the CPU module, I/O modules, and special-function modules.
Install the supplied connector cover or blank cover (A1SG60) to prevent dust
penetrating empty connector spaces.
P I/0 : Motion slot
For A172SENC, A1SY42 or MELSEC-A1S series I/O module A1SI61
S I/0 : Sequencer slot
For MELSEC-A1S series module
Screws to fix the unit to the base.
Screw size M4 12.
2)
Base cover
3)
Module connector
4)
5)
Slots for mounting the base unit onto the control board panel (for M5 screws)
6)
7)
Emergency stop
terminal
CAUTION
*1 : Install the supplied blind cap or blank cover (A1SG60) to prevent dust penetrating the empty
connector spaces. Failure to do so can cause malfunctioning.
1 29
5) 7)
2)
OUT
A178B-S2
1)
6)
No.
1)
Motion slot
3)*1
Name
Extension cable
connector
Sequencer slot
Application
Connects to the signal communications connector on the extension base unit with the
extension cable.
A cover for protecting the extension cable connector. When connecting to an extension
base unit, cut out the area surrounded by the groove under the word OUT on the base
cover with side cutters, or some other tool.
Connectors to mount the CPU module, I/O modules, and special-function modules.
Install the supplied connector cover or blank cover (A1SG60) to prevent dust
penetrating empty connector spaces.
P I/0 : Motion slot
For A172SENC, A1SY42 or MELSEC-A1S series I/O module A1SI61
S I/0 : Sequencer slot
For MELSEC-A1S series module
Screws to fix the unit to the base.
Screw size M4 12.
2)
Base cover
3)
Module connector
4)
5)
Slots for mounting the base unit onto the control board panel (for M5 screws)
6)
7)
Emergency stop
terminal
CAUTION
*1 : Install the supplied blind cap or blank cover (A1SG60) to prevent dust penetrating the empty
connector spaces. Failure to do so can cause malfunctioning.
1 30
2)
4)
A1S68B
1)
No.
1)
2)
3)*1
6)
Name
Extension cable
Application
connector
Connects to the signal communications connector on the main base unit with the
extension cable. Remove the connector cover before connecting the extension cable.
Base cover
3)
Module connector
4)
5)
Slots for mounting the base unit onto the control board panel (for M5 screws)
6)
CAUTION
*1 : Install the supplied blind cap or blank cover (A1SG60) to prevent dust penetrating the empty
connector spaces. Failure to do so can cause malfunctioning.
1 31
IN
2)
4)
2)
OUT
OUT
A168B
1)
No.
1)
3)*1
6)
Name
Extension cable
connector
1)
Application
Connects to the signal communications connector on the main base unit or bus
coupling type GOT with the extension cable.
Take off the supplied connector cover before connecting the extension cable.
A cover for protecting the extension cable connector.
When connecting to bus coupling type GOT, cut out the area surrounded by the groove
under the word OUT on the base cover with side cutters, or other appropriate tool.
Connectors to mount the Power module, I/O module, and special-function modules.
Install the supplied connector cover or blank cover (A1SG60) to prevent dust
penetrating empty connector spaces.
Screws to fix the unit to the base.
Screw size M4 12.
2)
Base cover
3)
Module connector
4)
5)
Slots for mounting the base unit onto the control board panel (for M5 screws).
6)
CAUTION
*1 : Install the supplied blind cap or blank cover (A1SG60) to prevent dust penetrating the empty
connector spaces. Failure to do so may cause malfunctioning.
1 32
Choose the extension cable according to the distance between the main base
unit and sequence extension base unit and the type of the sequence extension
base unit. Note that the overall distance should be within 3m (9.84ft.).
Selection of Extension Cable
Extension Cable
Model
A1SC01B
A1SC03B
A1SC07B
A1SC12B
A1SC30B
A1SC60B
A1SC05NB
A1SC07NB
A1SC30NB
A1SC50NB
Length mm (inch)
55 mm (2.17 inch), flat cable for horizontal
extension
330 mm (13 inch)
700 mm (27.58 inch)
1200 mm (47.28 inch)
3000 mm (118.2 inch)
6000 mm (236.4 inch)
450 mm (17.73 inch)
700 mm (27.58 inch)
3000 mm (118.2 inch)
5000 mm (196.9 inch)
Type of Sequence
Extension Base Unit
For A6 B
POINT
Choose the motion modules and MELSEC-A series I/O modules so that the
sum of 5VDC consumed currents of the CPU module, motion modules,
MELSEC-A series I/O modules, synchronous encoders and manual pulse
generators connected to the main base unit is within 5 (A) for the
A173UHCPU/A172SHCPUN or 3 (A) for the A171SHCPUN.
1 33
OUT
Emergency stop
24VDC
EMG
EMG.COM
(b) Do not use the emergency stop terminals of the separate servo amplifiers.
If an independent emergency stop circuit is also required at a separate
servo amplifier, provide an external circuit that shuts off the power supply to
the separate servo amplifier.
1 34
Power supply
module
8 9 10 11 12 13 14 15
80 90 A0 B0 C0 D0 E0 F0
to to to to to to to to
Vacant, 16 points 60 to 6F
Vacant, 16 points 70 to 7F
0F
Vacant, 16 points 50 to 5F
to
CPU
Vacant, 16 points 40 to 4F
0
00
Vacant, 16 points 30 to 3F
Motion slot
Sequencer slot No.
Vacant, 16 points 20 to 2F
Vacant, 16 points 10 to 1F
Example of using the A172B main base (when a 16-point module is loaded to
each slot)
8F 9F AF BF CF DF EF FF
A1S68B extension base unit
POINT
1) Max. number of actual I/O points
A173UHCPU:2048 points, A172SHCPUN:1024 points, A171SHCPUN:512
points. The real I/O points can be used within the range of one extension
base.
2) When using the bus connection type GOT, use the A168B.
3) Use the extension cable within 3m (9.84ft.) length.
1 35
0F 1F 2F 3F
Power supply
module
7
Vacant, 16 points 70 to 7F
to to to to
CPU
6
Vacant, 16 points 60 to 6F
0 1 2 3
00 10 20 30
5
Vacant, 16 points 50 to 5F
4
Motion slot
Sequencer slot No.
Vacant, 16 points 40 to 4F
8 9 10 11 12 13 14 15
80 90 A0 B0 C0 D0 E0 F0
to to to to to to to to
8F 9F AF BF CF DF EF FF
A168B extension base unit
GOT
2nd extention stage,
slot 0
100
(special unit)
11F
to to to to
Power supply
module
0F 1F 2F 3F
8 9 10 11 12 13 14 15
80 90 A0 B0 C0 D0 E0 F0
to to to to to to to to
8F 9F AF BF CF DF EF FF
A1S68B extension base unit
1 36
7
Vacant, 16 points 70 to 7F
CPU
Vacant, 16 points 60 to 6F
Motion slot
Vacant, 16 points 50 to 5F
Vacant, 16 points 40 to 4F
Vacant, 16 points 10 to 1F
Vacant, 16 points 20 to 2F
Vacant, 16 points 30 to 3F
Vacant, 16 points 40 to 4F
Vacant, 16 points 50 to 5F
Vacant, 16 points 60 to 6F
Vacant, 16 points 70 to 7F
CPU
Power supply
module
Motion slot
Vacant, 16 points 00 to 0F
8 9 10 11 12 13 14 15
80 90 A0 B0 C0 D0 E0 F0
to to to to to to to to
8F 9F AF BF CF DF EF FF
A1S68B extension base unit
1 37
No. of inputs
Motion control
signal input,
tracking input
Brake output
Tracking input
response time
No. of outputs
Rated load voltage
Operating load
voltage range
Maximum load
current
Response time
Manual pulse
generator input or
incremental
synchronous
encoder
No. of modules
H voltage
L voltage
Maximum input
frequency
Applicable type
No. of modules
Applicable types
Position detection
method
Resolution
Power consumption (5 VDC)
Product weight (kg) (lb)
Serial absolute
synchronous
encoder input
Specification
A172SENC
Motion control signals: 32 points
(8 points each for upper stroke limit, lower stroke limit, STOP input, nearzero point DOG/speed-position changeover signal)
Tracking enable signal : 1 point
Total : 33 points
12/24VDC
12VDC 2mA/24VDC 4mA
10.2 to 26.4VDC
7.0 VDC min./1.0 mA min.
1.8 VDC max./0.18 mA max.
OFF
ON 2 ms max.
ON
OFF 3 ms max.
OFF
ON 0.5 ms max.
ON
OFF 0.5 ms max.
1 point
24 VDC
21.6 to 30 VDC (peak voltage 30 VDC)
0.1 A (max. rush current: 0.4A, 10 ms max.)
OFF
ON 2 ms max.
ON
OFF 2 ms max.
1
3.0 to 5.25 V
0 to 1.0 V
100 kpps max.
Voltage-output type (5 VDC), Recommended product: MR-HDP01
Differential-output type: 26LS31 or equivalent
Selectable by connector wiring
1
MR-HENC
Absolute
16384 PLS/rev
0.42
0.22 (0.49)
1 38
1)
3)
2)
4)
No.
Name
Application
Display the input status from external equipment and errors detected by self-diagnosis.
LED
PX0 to
PX1F
TRA
Description
Indicators to display the motion control signal input status of each
axis.
Input start signal from synchronous encoder.
1)
LED indicators
2)
CTRL connector
Connector for motion control signal input and tracking signal input of each axis.
3)
PULSER connector
4)
SY.ENC connector
1 39
Manual pulse
generator/incremental
synchronous encoder
(Voltage/differential output type)
Serial absolute synchronous
encoder
8 points
(for 8 axes)
1 unit
1 unit
OUT
1 40
Synchronous Encoder
A173UHCPU
A172SHCPUN/A171SHCPUN
*3
PIN No.
Signal Name
1
2
3
4
5
6
7
8
9
10
*2
Signal Name
SG
Vacant
HZ1
HA1
SG
P5
HA2P
HB2P
HZ2P
Vacant
11
12
13
14
15
16
17
18
19
20
SG
Vacant
Vacant
HB1
SG
P5
HA2N
HB2N
HZ2N
HPSEL
*1
Applicable connector
model names
10120-3000VE
connector
*2 10320-52F0-008 (Standard
connector cover accessories)
(Manufactured by
Sumitomo 3M)
*3
*Also available as MR-CON1.
*1
Inputs from manual pulse generator switched by HPSEL. Unconnected selects voltage-output type, HPSEL=SG
selects differential-output type.
*2, *3 Connect the manual pulse generator connector cable wires according to the output type of the manual pulse
generator, as described below.
*2 Voltage -output type
Connect the A-phase signal to Pin 4 (HA1) and the B-phase signal to Pin 14 (HB1).
*3 Differential-output type
Connect the A-phase signal to Pin 7 (HA2P) and the A-phase inverse signal to Pin 17 (HA2N), the Bphase signal to Pin 8 (HB2P) and the B-phase inverse signal to Pin 18 (HB2N).
1 41
Signal Name
Pin No.
PULSER
Connector
Voltage-Output
Type
Wiring Example
Internal Circuit
1K
Manual
pulse
generator,
phase A
Manual
pulse
generator,
phase B
A+
B+
14
Manual pulse
generator/
synchronous
encoder
1K
B
Specification
Rated input
voltage 5.5 VDC
max.
HIGH level
3 VDC to 5.25
VDC/2 mA
LOW level
1 VDC max./ 5 mA
min.
Description
To connect manual
pulse generator
phases A,B
Pulse width
10 s min.
5 s min. 5 s min.
(Duty ratio:50%)
Input
P5
SG
6 16
1 5 11 15
5V
0V
1 42
Phase B
2.5 s min.
(1) Positioning
address
increases if
Phase A leads
Phase B.
(2) Positioning
address
decreases if
Phase B leads
Phase A.
Pin No.
PULSER
Connector
Voltage-Output
Type
Signal Name
Manual
pulse
generator,
phase A
A+
Manual
pulse
generator,
phase B
Specification
Description
Rated input
voltage 5.5 VDC
max.
17
B+
Internal Circuit
Wiring Example
To connect manual
pulse generator
phases A,B
Pulse width
18
A
Manual pulse
generator/
synchronous
encoder
HIGH level
3 VDC to 5.25
VDC/2 mA max.
10 s min.
5 s min. 5 s min.
LOW level
1 VDC max./ 5 mA
max.
(Duty ratio:50%)
Input
P5
5V
6 16
Phase B
0V
SG
2.5 s min.
(1) Positioning
address
increases if
Phase A leads
Phase B.
(2) Positioning
address
decreases if
Phase B leads
Phase A.
1 5 11 15
Connection examples
Connection of voltage-output manual pulse generator
A172SENC
Signal name
Manual pulse
generator side
Signal name
Manual pulse
generator side
HA1
HA2P
HA2
HA2N
SG
0V
HB2P
5V
HB2N
SG
SG
0V
P5
P5
SG
*2
*1
*2
*1
5V
SG
HPSEL
CAUTION
*1: The 5 VDC power supply from the A172SENC must not be connected if a separate power
supply is used as the manual pulse generator power supply.
If a separate power supply is used as the manual pulse generator power supply, use a 5 V
stabilized power supply. Any other power supply may cause a failure.
*2: Total connector cable length not to exceed 30 m (98.4 ft.)
1 43
Signal Name
PIN No.
Signal Name
10
9
8
7
6
5
4
3
2
1
Vacant
Vacant
P5
P5
Vacant
Vacant
MR
MRR
SG
SG
20
19
18
17
16
15
14
13
12
10
SD
Vacant
Vacant
SG
P5
SG
BAT
MDR
MD
Vacant
CPU
A172S
ENC
: A173UHCPU/A172SHCPUN/A171SHCPUN
SY.SNC
connector
Serial absolute synchronous encoder cable
(MR-HSCBL M)
1 44
CAUTION
Connect the SY.ENC connector to external equipment using a shielded cable. To reduce
electromagnetic interference, do not position the cable close to, or bundle it with, power or main
circuit cables. A clearance of at least 200 mm (0.66 inch) to other cables is required.
Connect the shield wire of the shielded cable to the FG terminal of the external equipment.
When increasing the cable length, use the cable within 30m (98.36 ft). Note that the cable should
be run in the shortest possible distance to avoid induced noise.
Always wire the cables when power is off. Not doing so can damage the output circuit if any of
the output signal cables makes contact with the power supply or the output signal cables make
contact with each other.
Use extreme care when wiring the cables. Wrong wiring can damage the internal circuitry.
4
3
7
1
P5
SG
8
2
C
D
S
R
MR
MRR
P5
SG
4
3
7
1
C
D
S
R
BAT 14
SG 15
F
G
P5
SG
P5
SG
BAT
SG
8
2
16
17
14
15
F
G
SD
SD
20
20
PCR-S20FS
connector
(SY.ENC end)
MS3106B20-29S
connector
(synchronous
encoder end)
PCR-S20FS
connector
(SY.ENC end)
*1
MR-HSCBL2M , MR-HSCBL5M
(2m (6.56ft.))
(10m (32.79ft))
MS3106B20-29S
connector
(synchronous
encoder end)
*1
MR-HSCBL10M to MR-HSCBL30M
(10m to 30m (98.36ft.) )
1 45
Signal Name
SY.ENC
Connector
MR
Wiring Example
Internal Circuit
MRR
P5
Description
Transmission
method: serial
communications
Serial
synchronous
encoder
Position detection
method: absolute
*3
7, 8, 16
SG
Specification
*3
1, 2, 15, 17
Input
BAT
14
SD
20
*3:
Application
Number of Points on
One A172SENC
8 points each
(1 point/1 axis each)
1 46
1 point each
CTRL connector
PIN No.
External input
signal name
Signal No.
Signal Name
PIN No.
Signal Name
A1
A2
A3
A4
BRK.COM
BRK
Vacant
Vacant
B1
B2
B3
B4
COM
COM
Vacant
TRA
External input
signal name
Signal No.
DOG/CHANGE
STOP
RLS
FLS
A5
A6
A7
A8
PX1F
PX1E
PX1D
PX1C
B5
B6
B7
B8
PXF
PXE
PXD
PXC
DOG/CHANGE
STOP
RLS
FLS
DOG/CHANGE
STOP
RLS
FLS
A9
A10
A11
A12
PX1B
PX1A
PX19
PX18
B9
B10
B11
B12
PXB
PXA
PX9
PX8
DOG/CHANGE
STOP
RLS
FLS
DOG/CHANGE
STOP
A13
A14
PX17
PX16
B13
B14
PX7
PX6
RLS
FLS
A15
A16
PX15
PX14
B15
B16
PX5
PX4
DOG/CHANGE
STOP
RLS
DOG/CHANGE
STOP
RLS
FLS
A17
A18
A19
A20
PX13
PX12
PX11
PX10
B17
B18
B19
B20
PX3
PX2
PX1
PX0
FLS
DOG/CHANGE
STOP
RLS
FLS
(Standard
accessories)
1 47
Pin Number
Signal Name
Wiring Example
CTRL Connector
B20
A20
B16
A16
B12
A12
B8
A8
Upper stroke
limit input
B19
A19
B15
A15
B11
A11
B7
A7
Lower stroke
limit input
B18
A18
B14
A14
B10
A10
B6
A6
Stop signal
input
B5
A5
Internal Circuit
B17
A17
B13
A13
B9
A9
6.8k
Input
TRA signal
TRA
6.8k
6.8k
Specification
Supply voltage
FLS
12 to 24 VDC
(10.2 to 26.4 VDC,
stabilized power
supply)
RLS
HIGH level
7.0 VDC
min./1.0mA min.
STOP
LOW level
1.8 VDC max./0.2
mA max.
Tracking enable
signal input.
Generates
interrupts to
A173UHCPU/
A172SHCPUN/
A171SHCPUN.
Starts counter
operation.
6.8k
B1 B2
BRK
A2
Brake
BRK, COM
A1
24VDC
Output
Common terminals
for motion control
signals, external
signal and TRA.
5VDC to
24VDC
Power
DOG/CHANGE
6.8k
B4
Description
CAUTION
Always use a shielded cable for connection of the SY.ENC connector and external equipment,
and avoid running it close to or bundling it with the power and main circuit cables to minimize the
influence of electromagnetic interference. (Separate them more than 200mm (0.66 inch) away.)
Connect the shield wire of the connection cable to the FG terminal of the external equipment.
Make parameter setting correctly. Incorrect setting may disable the protective functions such as
stroke limit protection or may not provide the brake output, damaging the module.
Always wire the cables when power is off. Not doing so can damage the output circuit if any of
the output signal cables makes contact with the power supply or the output signal cables make
contact with each other.
Use extreme care when wiring the cables. Wrong wiring can damage the internal circuitry.
1 48
Invalid Valid
Emergency
Stop
MITSUBISHI
2)
A30TU-E
A30TU-E SV13
Ve
*Data
*Monitor
*PROG
*Test
Press the mode key.
1)
DATA
TEST
6)
STOP
ITEM
:
CLEAR
SP
WRITE
STEP-
STORE
4)
STEP+
MDI
-
.
SHIFT
AXIS
NO.
No.
ERROR
RESET
CAN
JOG -
JOG +
Name
RETURN
GO
Application
4-line
1)
Display
2)
3)
Valid/Invalid switch
Changes over the operations of the teaching box between valid and invalid.
4)
Operation keys
5)
Internal buzzer
6)
It is also possible to set the buzzer so that it does not sound for key input.
1 49
Valid
Invalid
Schematic
drawing of
front panel
3)
Schematic drawing
of rear panel
2)
Emergency Stop
MITSUBISHI
A31TU-E
A31TU-E SV13
Ve
*Data
*Monitor
*PROG
*Test
Press the mode key.
1)
DATA
TEST
6)
STOP
ITEM
:
CLEAR
SP
WRITE
STEP-
STORE
4)
7)
STEP+
MDI
-
.
SHIFT
AXIS
NO.
No.
ERROR
RESET
CAN
JOG -
JOG +
RETURN
GO
Name
Application
1)
Display
2)
3)
Valid/Invalid switch
Changes over the operations of the teaching box between valid and invalid.
4)
Operation keys
5)
Internal buzzer
6)
7)
Deadman switch
Turns on the switch to enable servo operation: turns off the switch to shut off the servo
power.
POINT
A dead-man switch is used for jogging operated from the teaching box. To operate the switch, press and
hold it down. Releasing the deadman switch turns off servo power, bringing the servo motor to an
immediate stop.
1 50
A30TU-E
Without
With (signal on semiconductor
level)
Emergency stop
A31TU-E
With
With (signal on relay level)
Directly unconnectable
Via A31TUCBL03M
Directly connectable
External circuit required
(In direct connection, CPU
module does not operate.)
*1: Releasing the deadman switch turns off servo power.
(b) Connection of A31TU-E unit (teaching unit with deadman switch) and CPU
module
To connect the A31TU-E teaching unit with deadman switch and the CPU
module, use the A31TUCBL03M for connection within the panel and plug its
A31TU-E side connector into the operator panel surface for A31TU-E
connection. When using the A31TU-E unit, use it by plugging it into the
connector on the operator panel surface. When not using the A31TU-E, fit the
A31SHORTCON into the connector on the operator panel surface.
The A31TUCBL03M's signal wires connected to the external circuit, e.g. EMG
and EMGL, are used for external safety circuit connection for the emergency
stop switch and deadman switch of the A31TU-E. Refer to Section 2.3(2) for
details of the external circuit.
Control panel
CPU module
A31SHORTCON
(Fitted when A31TU-E is not used)
A31TUCBL03M
A31TU-E
External circuit
DED2
DED1
EMG2
EMG1
EMG
EMGL
*2
A31TUCBL03M connector
*2: The CPU module does not operate if the A31TU-E and CPU module are connected directly.
POINT
When using the A31TU-E, be sure to use the A31TUCBL03M.
When the A31TU-E is not connected, be sure to connect the
A31SHORTCON. Failing to do this could result in the system entering an
emergency stop state.
An external circuit is essential to form a safety circuit. (For details of external
circuit configuration, refer to the section 2.3.)
1 51
Applicable Version
A30TU-E
D or later
A31TU-E
B or later
Teaching unit version is marked on the rated name plate at the rear panel of
the unit.
(4) A30TU-E rated name plate
Unit version
A30TU-E
D
DATE
MITSUBISHI ELECTRIC CORPORATION
MITSUBISHI
TEACHING UNIT
MODEL
A31TU-E
DATE B
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
BC370D070H02
Unit version
1 52
Motion controller
CPU module
3)
1)
2)
IN OUT
Servo amplifier
MR-H-BN
MR-J2S-B
MR-J2-B
No.
1)
2)
1)
2)
2)
3)
Product
IN OUT
Servo amplifier
MR-H-BN
MR-J2S-B
MR-J2-B
Model
Description
MR-HBUS05M
MR-HBUS1M
MR-HBUS5M
0.5 (1.64)
1 (3.28)
5 (16.39)
MR-J2HBUS05M
(-A)
MR-J2HBUS1M
(-A)
MR-J2HBUS5M
(-A)
0.5 (1.64)
1 (3.28)
5 (16.39)
1 53
Model Name
MR-HBUS
SSCNET cable
MR-J2HBUS
MR-J2HBUS
M-A
MR-TM
Termination
connector
MR-A-TM
MR-H-BN
MR-H-BN
MR-H-BN
Termination
connector
Battery
MR-BAT,
A6BAT
Battery
MR-BAT,
A6BAT
Battery
MR-BAT,
A6BAT
MR-J2S-B
/MR-J2-B
MR-J2S-B
/MR-J2-B
MR-J2S-B
/MR-J2-B
Termination
connector
Battery
MR-BAT,
A6BAT
1 54
Battery
MR-BAT,
A6BAT
Battery
MR-BAT,
A6BAT
MR-J2S-B
/MR-J2-B
MR-J2S-B
/MR-J2-B
MR-H-BN
Termination
connector
Battery
MR-BAT,
A6BAT
CPU module
Battery
MR-BAT,
A6BAT
Battery
MR-BAT,
A6BAT
MR-H-BN
MR-J2S-B
/MR-J2-B
MR-H-BN
Termination
connector
Battery
MR-BAT,
A6BAT
CPU module
Battery
MR-BAT,
A6BAT
Battery
MR-BAT,
A6BAT
MR-J2S-B
/MR-J2-B
MR-H-BN
MR-J2S-B
/MR-J2-B
Termination
connector
Battery
MR-BAT,
A6BAT
1 55
Battery
MR-BAT,
A6BAT
Battery
MR-BAT,
A6BAT
SSCNET
Line
1
1
1
1
1
1
1
1
Servo Amplifier's
Rotary Switch
0
1
2
3
4
5
6
7
dno. *1
SSCNET
Line
3
3
3
3
3
3
3
3
Servo Amplifier's
Rotary Switch
0
1
2
3
4
5
6
7
dno. *1
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
SSCNET
Line
2
2
2
2
2
2
2
2
Servo Amplifier's
Rotary Switch
0
1
2
3
4
5
6
7
SSCNET
Line
4
4
4
4
4
4
4
4
Servo Amplifier's
Rotary Switch
0
1
2
3
4
5
6
7
*1: dno. is the servo amplifier axis numbers displayed in the system settings of the
positioning software package. Set the axis No. relative to the dno. in system
settings.
1 56
A6BAT
Item
Nominal voltage
3.6 VDC
5 years
The range is as follows. for details, see Section 5.3.
Applications
16(0.63) 30(1.18)
A6BAT
Battery connector
CAUTION
Do not short a battery.
Do not disassemble a battery.
Do not burn a battery.
Do not overheat a battery.
Do not solder the battery terminals.
1 57
2. DESIGN
2. DESIGN
This chapter provides those who will design and manage the motion system with the
procedures and instructions necessary to design the motion system.
For the system and parameter settings and programming method of the motion system,
refer to the operating and programming manuals.
This chapter does not describe the selection of the amplifiers, motors and MELSEC-A
series (I/O modules).
Refer to the corresponding manuals.
2.1 System Designing Procedure
Design the system which uses the motion controller in the following procedure.
Motion system design
Select the CPU module according to the number of control axes and the number of
control I/O points.
Choose the motion functions to be installed according to the machinery and equipment
to be controlled (selection of the motion OS determines the peripheral positioning
packages).
Choose the number of A172SENCs and design connections according to the axis-by-
axis control system and depending on whether servo external signals are required or
not.
When there is mechanical home position and dog type home position return is made:
Near-zero point dog required
For speed control: Speed-position control change signal required
When overrun prevention is necessary: Stroke limits required
When axis-by-axis stop is necessary: STOP signal required
Choose A1SY42 when using the limit output which outputs ON/OFF according to the
present value of the specified axis.
Choose the main base, extension bases, extension power supplies and extension
cables and make I/O assignment according to the necessary number of A172SENCs
and A1SY42s and the number of I/O modules.
Select the servo amplifier and servo motor according to the motor capacity and speed
calculated from the machine mechanism to be controlled axis-by-axis.
Set servo amplifier connection by SSCNET and axis numbers and axis No.s.
Connection of peripheral equipment
Refer to an applicable
servo amplifier manual .
Refer to Appendix 2.
Refer to Section 1.5.6(2).
Select the teaching unit when using the handy unit to perform JOG operation, teaching
or the like. Choose A31TU when the deadman switch is needed or choose A30TU
when not needed.
21
2. DESIGN
Design of system to which GOT and personal computer information control have been added
Choose the GOT when using the graphic panel to perform equipment status monitoring
and equipment operation.
Select the personal computer and related software packages when you want to execute Refer to Section 1.5.1(7).
the digital oscilloscope functions designed for tuning and timing checking and
user-developed software functions (e.g. machining/assembling recipe function and data
supervising collection function) in addition to equipment status monitoring and
equipment operation.
Select MELSECNET modules and carry out MELSECNET system design such as link
allocation when connecting the motion controller to MELSECNET(II) or
MELSECNET/10 for communications with the PC CPU, etc. over the network.
Design the power supply circuit which supplies power to such system components as
the motion controller, I/O equipment and servo amplifiers, taking into consideration the
protective coordination and noise suppression techniques.
Carry out layout design from such aspects as installation environment, e.g.
temperatures and vibrations in consideration of heat generated from modules, and
handling of the modules mounted.
22
2. DESIGN
CAUTION
Provide appropriate circuits external to the servo system CPU to prevent cases where danger
may result from abnormal operation of the overall system in the event of a power supply fault or
servo system CPU failure.
Mount each controller, servo amplifier, servomotor, and regenerative resistor on a nonflammable material. Fire may result if they are mounted on or near a flammable material.
Take measures to cut off the servo amplifier power supply if the controller or servo amplifier fails.
Large currents continuing to flow can cause fires.
If a regenerative resistor is used, ensure that an alarm signal cuts off the power supply,
otherwise damage to the regenerative transistor, overheating of the regenerative resistor, or
even fire may result.
To prevent fires, take flameproofing measures inside the control box where the servo amplifier
and regenerative resistor are located and use non-flammable wiring.
Do not apply a voltage to terminals which exceeds the voltage prescribed in this manual or the
instruction manuals for other products used. Incorrect voltage can cause destruction of, or
damage to, the equipment.
Correct the terminals correctly. Incorrect connection can cause destruction of, or damage to, the
equipment.
Ensure polarity is correct. Incorrect polarity can cause destruction of, or damage to, the
equipment.
The servo amplifier cooling fins, regenerative resistor, and servomotors become hot during
operation and can remain hot for some time after the power is turned off. Do not touch these
parts or burn injuries may result.
To avoid injury, turn off the power before touching servomotor shafts or machinery connected to
them.
To avoid injury, do not approach machinery during trial or teaching operation.
Connect a leak breaker to the controller and servo amplifier power supply.
Provide an electromagnetic contactor for servo amplifiers and other equipment for which the
instruction manual prescribes an electromagnetic contactor to cut off the power in the event of an
error.
Provide an external emergency stop circuit to instantaneously stop operation and cut off power.
Use controllers, servo amplifiers, servomotors, and regenerative resistors in combinations
prescribed in this manual and the instruction manuals for other products used. Incorrect
combinations can cause damage to the system or fire.
If used in systems for which safety standards apply (such as robot systems), all controllers, servo
amplifiers, and servomotors must meet the prescribed safety standards.
Configure safety circuits external to the controller or servo amplifiers if their abnormal operation
could cause axis motion in a direction other than the safe operating direction for the system.
Use dynamic braking on servomotors if free running after an emergency stop, servo OFF, or a
power cut is a problem.
Consider the overrun distances of the system, even if dynamic braking is used.
Use both dynamic braking and electromagnetic braking on servomotors if vertical falling of axes
after an emergency stop, servo OFF, or a power cut is a problem.
Use the dynamic brake module to stop servomotors when an emergency error or other error
occurs to turn off the servomotors. Do not use it to stop the servomotors during normal operation.
The electromagnetic brake incorporated in a servomotor is intended for holding only. Do not use
it during normal operation.
Design systems with sufficient mechanical allowance for a safe stop if an axis passes the strokeend limit switch at maximum speed.
Select cables for the system with appropriate diameter, heat resistance, and bending resistance.
Use wires and cables with lengths in the range prescribed in this manual and the instruction
manuals for other products used.
Ensure that the characteristics of other components used in a system match those of the
controllers, servo amplifiers, and servomotors.
Attach covers to prevent servomotor rotating parts being touched during operation.
The electromagnetic brake may not be able to hold an axis due to age or machine construction
(if a servomotor is linked via a timing belt to a ball screw, for example). As a safety measure,
provide a stopping device on the machine.
23
2. DESIGN
2.2 System Design
To exercise motion control and external I/O equipment control, the motion system
consists of the CPU module, main base unit and various modules such as the
power supply module, pulse generator/synchronous encoder modules and I/O
modules. Each module must be selected, set, and connected according to the
system specifications. Further, the motion system can connect to the graphic
operation system (GOT), exercise information control using a personal computer,
and connect to a control network which uses the MELSECNET so that the system
may be configured up to meet various applications.
Based on the following system configuration, this section explains the ways to
select the modules needed in designing the motion system and to set and connect
the modules, and the designing precautions.
Control network
Monitoring/Operation
Information control
(Such as digital oscilloscope,
monitoring and recipe functions)
Refer to Section 1.5.1(7).
OUT
MELSECNET system
Refer to Section
1.5.1(8).
Personal computer
MELSECNET(II)/10
I/O control
Synchronous encoder
CPU module
Pulse generator/synchronous encoder interface
module (refer to Section 1.5.4(3))
Limit output module
Base, extension cable (refer to Section 1.5.3(3))
MELSEC-A
I/O module
RS422
(CPU front)
Peripheral
device
Motion controller
SSCNET
Servo amplifier
Refer to
Section 1.5.6(2).
SSCNET
Teaching
JOG operation
Stroke limit
Stop signal
Near-zero point DOG/Speed
-position changeover
command
SSCNET
Program development
Personal computer
Teaching unit
Refer to Section 1.5.5(2).
24
Refer to Section
1.5.1(9).
2. DESIGN
2.3 External Circuit Design
As to the ways to design the external circuits of the motion system, this section
explains the method and instructions for designing the power supply and safety
circuits, etc.
(1) Sample system circuit design for motion control
3-phase
200/220VAC
A172SENC
A173UHCPU/
A172SHCPUN/
A171SHCPUN
NFB
T
200VAC
PX0
*1
PX1F
TRA
COM
200VAC
FG
LG
BRAKE
OUT
BRAKE
COM
EMG
EMG. COM.
PX0
Motion control
input for 8 axes
PX1F
TRA
COM
Ra2
24VDC
power
supply
+24V
24G
Operation Ready
Ra1
EMG
OFF
ON
MC
MC
EMG
CPU module
Yn
Ra1
*2
25
SK
2. DESIGN
POINTS
(1) *1 : A 100 VAC power supply can also be used as the power supply to the CPU module.
(2) *2 : Sequence program
M9036
Servo alarm/
M9074 Error detection
Yn
(3) *3 : It is also possible to use a full wave rectified power supply as the power supply for the
electromagnetic brake.
(4) For details on connecting SSCNET cables and termination resistors refer to Sections 1.5.6 (2).
SM
Ra3
*3
Ground Electro-
R1
24 VDC
S1
magnetic
brake
COM
MBR
Ra3
EM1
EM2
L1 MR-J2S-B
L2 /MR-J2-B
L3
SM
Ra4
*3
Ground Electro-
L11
MC
L12
magnetic
brake
COM
MBR
Ra4
EM1
SG
24 VDC
26
2. DESIGN
(2) Example of system circuit configuration compatible with A31TU-E type teaching
unit
3-phase
200/220VAC
A172SENC
A173UHCPU/
A172SHCPUN/
A171SHCPUN
NFB
T
200VAC
PX0
Ym
Ym+1
*1
PX1F
TRA
COM
200VAC
EMG
Ym+n
EMG. COM.
CPU EMG
BRAKE
OUT
CPU EMGL
BRAKE
COM
FG
COM
LG
A31TUCBL
TU EMG1
PX0
Motion control
input for 8 axes
24 VDC
power supply
TU EMG2
DED1
PX1F
TRA
COM
DED2
+DC24V
24G
TU EMG2
(To
Cable)
(To
Cable)
EMG
Operation
Ready
ON
OFF
Ra1
Deadman switch
DED1
Ym
Ra1
SK
Ym:
PCPU Ready Completion
servo normal output
(Servo normal: ON, Alarm: OFF)*2
DED2
Ra2
CPU EMG
(To cable)
(To
(To
Cable) Cable)
Ra2
SK
CPU EMGL
(To cable)
Ra1
Ra2
MC
SK
27
2. DESIGN
POINT
Valid
Invalid
Schematic
drawing of
front panel
Servo alarm/
M9074 Error detection
Emergency Stop
MITSUBISHI
M9036
A31TU-E
A31TU-E SV13
Ve
*Data
*Monitor
*PROG
*Test
Press the mode key.
DATA
Ym
TEST
STOP
A31SHORTCON
short-circuit
connector
(when A31TU-E is not
connected)
ITEM
:
CLEAR
SP
WRITE
STEP-
STORE
STEP+
MDI
-
ERROR
RESET
CAN
JOG -
SHIFT
JOG +
AXIS
NO.
RETURN
GO
OR
R MR-H-BN
S
T
U
W
E
COM
MER
SM
Ra11
Electromagnetic
brake *3
R1
S1
Servo motor
Ra11
EM1
EM2
L1 MR-J2S-B U
/MR-J2-B V
L2
L3
MC
V
W
W
E
L11
L21
Ground
COM
MER
Ra12
EM1
SG
MC
28
Servo motor
SM
Ra12
Electromagnetic
brake *3
2. DESIGN
(c) Sample system circuit designs
Using AC
Using AC and DC
Power supply
Power supply
Transformer
Transformer
Fuse
CPU
Transformer
Fuse
Fuse
M9006
Ym
CPU
DC power supply
established signal input
M9039
DC power
supply
(-) (+)
M9006
Ym
Yn
M9039
XM
Yn
START/STOP circuit
(Starting possible when the
PC RUN output RA1 is ON.)
M9084
Program
Start switch
Stop switch RA1
Set TM to time
to establish
DC input signal
Fuse
XM
TM
TM
M9084
MC
TM
MC
MC1 NO M10
Input module
RA1
M10
XM
MC
MC
Output module
Ym
L
Program
Start switch
Stop switch RA1
Alarm output
(lamp or buzzer)
RA2
Input module
RA2
XM
Yn
A voltage relay
is recommended
RA1
MC
Output module
Alarm output
(lamp or buzzer)
Output module
Ym
MC
MC2
MC1
RA1
Output module
MC
MC1
MC2
MC2
MC1
MC1
MC2
RA1 switched
ON by M9039
Yn
MC
Turns output
equipment
power off when
STOP occurs
(on emergency
stop, on stop at
upper limit)
AC and DC
(1) Set the CPU to RUN.
(2) Turn on the power supply.
(3) Turn ON RA2 when DC power supply is
established.
(4) Turn on timer (TM) when the DC power supply is
100% established. (Set TM set value to the time
from RA2 turning ON until the DC power supply
is 100% established. The set time should be
approximately 0.5 s.)
(5) Turn on the start switch.
(6) Output equipment driven by program when the
electromagnetic contactor (MC) turns on.
(When a voltage relay is used as RA2, the timer
(TM) in the program is not needed.)
29
2. DESIGN
2.3.1 Power Supply Circuit Design
This section describes the protective coordination and noise suppression techniques of
the power supply circuit.
(1) Separation and protective coordination (leakage current protection, overcurrent
protection) of power supply lines
When wiring, separate the lines of CPU module power supplies from those of the
I/O equipment and servo amplifier as shown below.
Main
power
supply
CPU module
power supply
NFB
CP
CPU module
100/200VAC
I/O
power supply
I/O equipment
CP
Main
power
supply
CPU module
power supply
NFB
CP
CPU module
100/200VAC
I/O
power supply
I/O equipment
CP
Servo amplifier
power
Servo amplifier
supply
200VAC
NFB
2 10
2. DESIGN
(2) Power supply noise and lightening surge suppression techniques
If there is a possibility that a malfunction may occur due to a sneak noise from the
main power supply or servo amplifier or due to a lightening surge, use a line noise
filter and lightening surge absorber in the power supply lines of the motion controller
and I/O equipment. Also use an insulating transformer for suppression of common
noises of the power supplies (noises produced between power supplies and earth).
Example of using the line noise filter
Motion
controller I/O
equipment
Line noise
filter
AC
E1
E2
AC
E2
Lightening surge absorber
E1
Motion
controller I/O
equipment
AC
Constantvoltage
transformer
CPU module
CAUTION
Separate the grounding (E1) of the line noise filter and lightening surge absorber from the
grounding (E2) of the motion controller.
Choose the lightening surge absorber which will not cause the maximum permissible circuit
voltage of the power supply module to be exceeded when the power supply voltage rises to the
maximum.
When using the power transformer which will drop the voltage from 200VAC to 100VAC or the
insulating transformer, its capacity should be not lower than the value in the following table.
Power Supply Module Model
Transformer Capacity
A1S61PN
A1S62PN
CPU module
110VA
110VA
110VA
2 11
2. DESIGN
(4) Grounding
The motion system may malfunction as it is affected by various noises such as
electric path noises from the power supply lines, radiated and induced noises
from other equipment, servo amplifiers and their cables, and electromagnetic
noises from conductors. To avoid such troubles, connect the earthing ground of
each equipment and the shield grounds of the shielded cables to the earth.
Also use ferrite cores to prevent the sneak noises of the SSCNET from
entering.
For grounding, use the exclusive ground terminal wire of each equipment or a
single-point earth method to avoid grounding by common wiring, where
possible, since noises may sneak from other equipment due to common
impedances.
Panel computer
100/200VAC
Motion controller
Ferrite cores
SSCNET
Servo amplifier
SM
2 12
2. DESIGN
(2) Main base emergency stop circuit
(a) By opening the EMG circuit of the main base unit, all axes of the external
servo amplifiers (MR-H-BN/MR-J2S-B/MR-J2-B) can be brought to an
emergency stop at once. After an emergency stop, remove the emergency
stop factor and cancel the emergency stop (switch on the EMG circuit) to
switch on the servo amplifiers immediately. (An emergency stop does not
turn on the servo error detection signal.)
An emergency stop wiring example is shown below.
Main base unit
Emergency stop
24VDC
EMG
EMG.COM
(b) Do not use the emergency stop terminals on the external servo amplifier
side.
When the external servo amplifier side requires its own emergency stop circuit,
use an external circuit to power off the external servo amplifiers.
(3) External electromagnetic brake circuit
When configuring an electromagnetic circuit externally, create a sequence program
to turn off the electromagnetic brake output when the servo error detection or servo
OFF command turns off.
Also, write the sequence program to turn on the electromagnetic brake output
200ms after normal detection (servo error detection : OFF and servo OFF
command : ON) on the servo side.
Configure the external circuit to open the electromagnetic brake terminal of the
servo motor when the electromagnetic brake output turns ON.
2 13
2. DESIGN
For A172SHCPUN/A171SHCPUN
M1608+20n
M0
M1815+20n
K20*1
M1608+20n M1815+20n
T200
M0
T200
Yn
M1608+20n
M1815+20n
M0
T200
Yn
For A173UHCPU
M2408+20n
M0
M3215+20n
K20*1
M2408+20n M3215+20n
T200
M0
T200
Yn
M2408+20n
M3215+20n
M0
T200
Yn
:
:
:
:
:
POINT
*1 : T200 is a 10ms timer and has an error produced by the scan time of a sequence program, and that
error is -2/+1 scan.
Actually open the electromagnetic brake and adjust the setting to avoid a servo side error.
CAUTION
For details of the electromagnetic brake circuit and amplifier periphery, refer to the manual of the
servo amplifier used.
For vertical lift applications, make up a system which makes a stop using the mechanical locking
mechanism which will operate at power-off, emergency stop and alarm occurrence, in addition to
the electromagnetic brake, to prevent a drop.
When you want to make a sudden stop at an emergency stop, use the dynamic brake. If it is
used with the electromagnetic brake, the coasting distance will not be so short as expected.
When considering double safety, calculate the coasting distance when the dynamic brake fails,
and examine whether safety is ensured or not. Refer to Appendix 2 and 3 for the brake
characteristics.
2 14
2. DESIGN
(4) Failsafe measures for Motion controller failure
Failure of the CPU module or memory is detected by the self-diagnosis
function, but some abnormalities in the I/O control components cannot be
detected by the CPU.
Some failures can result in situations such as all points turning on or off, where
normal operation and safety of the controlled object cannot be assured.
The manufacturer makes every effort to ensure perfect quality control.
However, external failsafe circuits should be provided to prevent accidents or
damage to machines in the event that a failure does occur in the CPU module.
An example of a failsafe circuit is shown in the diagram below.
On-delay timer
T1
Y00
Internal program
1s
Off-delay timer
M9032
Y00
T2
Y01
Y0F
Y00
External load
L
1s
MC
24V
0.5s 0.5s
0V
24VDC
CPU module
Output
module *1
T1
T2
MC
CAUTION
*1 : Use a non-contact output module for Y00, as it turns ON/OFF at 0.5 s intervals. A transistor
is shown in the example above. Using a contact module for Y00 can cause failures.
2 15
2. DESIGN
2.3.3 Instructions for External Circuit Wiring Design
(1) Wiring
(a) Use the wires of the following diameters for wiring.
Application
I/O equipment
Ground wire
2.0mm or more
(b) Twist the 100VAC, 200VAC and 24VDC wires as closely as possible and
run them to connect modules in the shortest distance.
(c) Instructions for using the 24VDC output of the A1S62PN power supply
module
Do not connect the 24VDC outputs of two or more power supply modules in
parallel to supply power to one I/O module. Parallel connection will damage the
power supply modules.
If one power supply module cannot provide enough 24VDC output capacity, use
an external 24VDC power supply to supply extra power.
CPU module
I/O
module
24VDC
CPU module
24VDC
I/O
module
24VDC
External power supply
CAUTION
Do not connect the 24VDC outputs of two or more power supply modules in parallel to supply
power to one I/O module. Doing so can cause burst, damage or the like.
Do not bundle the 100VAC, 200VAC and 24VDC wires with or run them close to the main circuit
(high-voltage, large-current) wires and I/O signal wires.
Separate them more than 100mm (3.94inch) where possible.
2 16
2. DESIGN
2.4 Layout Design within Enclosure
2.4.1 Location Environment
Avoid locating the motion controller system in environments subject to:
(1) Ambient temperature outside the range 0C to 55C
(2) Ambient humidity outside the range 10% to 90% RH
(3) Condensation resulting from sudden temperature changes
(4) Corrosive or inflammable gas
(5) Large amounts of conducting dust or iron filings, oil mist, salt, organic solvents
(6) Direct sunlight
(7) Strong electrical or magnetic fields
(8) Direct vibrations or shocks on the unit.
CAUTION
The storage conditions are listed in the table below.
Environment
Conditions
0 C to 55 C
Ambient temperature
Ambient humidity
10% to 90% RH
No condensation resulting from sudden temperature changes
No corrosive or inflammable gas
Atmosphere
Low levels of conducting dust or iron filings, oil mist, salt, organic solvents
Not subject to direct sunlight
No strong electrical or magnetic fields
No direct vibrations or shocks on the equipment.
2 17
2. DESIGN
2.4.2 Installing the Base Units
This section describes the precautions related to mounting a motion controller in
an enclosure.
(1) To improve ventilation and permit easy mounting of the unit, leave a space of
at least 30 mm (1.18 inch) between the top of the unit and any other object.
(2) Provide a wiring duct, if required.
Consider the following points if the dimensions from the top or bottom of the
motion controller are less than those shown in Fig. 2.1.
(a) If the duct is above the motion controller, limit the duct height to 50 mm
(1.97 inch) max. to improve ventilation.
Leave sufficient clearance above the motion controller to allow the
mounting screws on top of the unit to be tightened or removed. It is
impossible to replace the unit if the screws cannot be removed.
(b) If the duct is below the motion controller, leave sufficient clearance to
eliminate effects on the CPU module 100/200 VAC input cables, the I/O
module input wires, and 12/24 VDC wires.
CAUTION
Due to ventilation problems, do not install the base units vertically or horizontally.
Install the base units on a flat surface. Unevenness or warping of the surface can apply undue
force to printed circuit boards and lead to malfunctions.
Avoid installing the base units close to a vibration source, such as a large electromagnetic
contactor or no-fuse breaker. Mount them on a separate panel or at a safe distance.
To limit the effects of reflected noise and heat, leave at least 100 mm (3.94 in) clearance to
instruments mounted in front of the motion controller (on the rear of the door).
Similarly, leave at least 50 mm (1.97 in) clearance between instruments and the left and right
sides of the base units.
2 18
2. DESIGN
2.4.3 Installation
The mounting positions of the main base unit and extension base unit are shown
below.
Top of enclosure, wiring duct, or other components
40mm (1.57inch)
Fig.2.1 Parallel Installation
*1: If a DIN rail is used, consider the mounting position of the DIN rail.
70mm
(2.76inch)
min.
30mm
(1.18inch) min.
70mm
(2.76inch) min.
30mm
(1.18
inch)
min. *2
70mm
(2.76inch) min.
Fig.2.2 Series Installation
Enclosure, etc.
CPU module
Door
Contactor,
relay, etc.
100mm
(3.94 inch)
min.
2 19
2. DESIGN
2.4.4 Calculating Heat Generated by A173UHCPU/A172SHCPUN/A171SHCPUN
If a motion controller is installed in an enclosure, the temperature inside the
enclosure must be restricted to the operation ambient temperature of 55 C .
The average power consumption (heat generation) of the equipment and
instruments in the enclosure must be known to design the heat dissipation of the
enclosure.
This section describes how to calculate the motion controller system power losses
and average power consumption. Calculate the temperature rise in the enclosure
from the power consumption.
5VDC line
CPU
(power
supply)
module
Output module
24VDC line
Exaternal
24 VDC
power supply
Special-function
module
Relay transistor
I24V
Input module
Input current
(IIN) E
Power supply
Output current
(IOUT) Vdrop
AC
DC
Output
power
supply
(IOUT)
LOAD
AC
Input
power
supply
(IIN)
DC
AC
DC
2 20
2. DESIGN
(4) Average power consumption from voltage drop in output circuits of the output
modules (power consumption of simultaneously ON points)
W OUT = IOUT Vdrop No. output points Simultaneously ON ratio (W)
IOUT : IOUT is the output current(actual operation current) (A)
Vdrop: Vdrop is the voltage drop of each output module (V)
(5) Average power consumption from voltage drop in input circuits of the input
modules (power consumption of simultaneously ON points)
W IN = IIN E No. input points Simultaneously ON ratio (W)
IIN : IIN is the input current (effective value for AC) (A)
E
: E is the input voltage (actual operation voltage) (V)
(6) Power consumption of special-function module power supply circuits
W S = I5V 5 + I24V 24 I100v 100(W)
The total power consumption of each block described above is the power
consumption of the entire PC system.
W = W PW + W 5V + W 24V + W OUT + W IN + W S (W)
Use the overall calculated power consumption (W) to calculate the heat
generation and temperature rise inside the enclosure.
The following equation approximately calculates the temperature rise in the
enclosure:
W
T = ( C)
UA
W : W is the overall power consumption of the motion controller (calculated
above)
2
A : internal surface area of the enclosure (m )
U : if a fan is used to make enclosure temperature uniform ............6
if air is not circulated inside the enclosure ..................................4
CAUTION
If the enclosure temperature rises above the prescribed range, a heat exchanger should be
attached to the enclosure to lower the temperature.
Ventilation of the enclosure with a fan can result in dust problems with the motion controller
because of the dust which is introduced with the ambient air.
2 21
2. DESIGN
2.5 Design Checklist
At the worksite, copy the following table for use as a check sheet.
Item
Sub Item
Design Confirmation
Check
Number of axes
CPU module selection
axes
points
pcs.
Synchronous encoder
pcs.
points
points
points
points
points
points
points
A172SENC
Module/unit
selection
modules
points
modules
Yes / No
Yes / No
modules
modules
modules
mm
A
A
Layout design
2 22
Sub Item
Mounting/Wiring Outline
Refer To
Section 3.2
to base unit
Section 3.3
Synchronous
encoder mounting
Wiring
Running of power
supply and I/O wires
Section 3.4
shaft
Running of power supply and I/O
wires of power supply and I/O
Section 3.5
modules
CAUTION
The terminal block and pin connectors of this base unit are made of resin. Do not drop them or
give them hard impact.
Do not remove the printed circuit boards of the base unit. Doing so can cause a failure.
Wire the cables carefully to ensure that no foreign matter such as wire-offcuts enter the base
unit. Remove them if any.
Tighten the base unit mounting screws within the tightening torque range.
While power is on, do not install or remove the base unit.
While power is on, do not mount or dismount the modules to or from the base unit.
Install the base unit in a weight-bearing place according to this manual.
Do not stand or rest heavy objects on the product.
Always check that the mounting orientation is correct.
31
cm
273 to 361
(Control box, when screws are made of iron)
35mm
(1.38 inch)
32
DIN rail
Base Unit
Base unit
Hook
33
Screwdriver
Direction to
remove the unit
Module lugs
Module fixing holes
End
Module
CAUTION
The lugs must be inserted in the module fixing holes when the module fixing screws are inserted.
Forcibly fixing a module in place without inserting the lugs in the holes will bend the module
connector pins and cause other damage.
Turn off the power supply before mounting or removing a module.
34
Module
connector
Module
End
Module fixing
holes
35
78 to 117
cm
CAUTION
When removing a module, remove the module fixing screws before attempting to remove the
lugs from module fixing holes. Forcing out a module may damage the lugs.
Turn off the power supply before mounting or removing a module.
The terminal block and pin connectors of this base unit are made of resin. Do not drop them or
give them hard impact.
Do not remove the printed circuit boards of each module. Doing so can cause a failure.
Wire the cables carefully to ensure that no foreign matter such as wire-offcuts enter from the
module top. Remove them if any.
Tighten the module mounting and emergency stop input terminal screws within the tightening
torque ranges.
When fitting the module to the base, press the module against the base to ensure that the latch
is locked into the base. When removing the module, push the latch until the latch comes out of
the base completely, and pull the module toward you.
36
Radial Direction
Permitted shaft
Thrust Direction
98N max.
49N max.
load
0.2mm
(0.008 inch)
max.
Eccentricity
Angle of deviation
1.5 max.
Axial displacement
0.5mm
(0.02 inch)
max.
37
CAUTION
The MR-HENC contains a glass disk and precision mechanism. Take care when handling it. The
encoder performance may deteriorate if it is dropped or subjected to shocks or vibration
exceeding the prescribed limits.
Do not connect the encoder directly to the rotating machine shaft. Always connect the encoder
through a flexible coupling.
Coupling
MR-HENC
38
24VDC
CPU module
24VDC
I/O
module
24VDC
External power supply
(2) Twist 100 VAC, 200 VAC, and 24 VDC wires together as tightly as possible.
Connect units together over the minimum distance.
(3) To minimize the voltage drop, use the thickest 100 VAC, 200 VAC, and 24
2
VDC wires possible (2 mm max.).
(4) Wiring the I/O equipment
2
2
(a) Wires between 0.75 mm and 1.5 mm can be connected to the terminal
2
block, but 0.75 mm wires are recommended.
(b) If wires pass through a conduit, the conduit must be grounded.
CAUTION
Do not connect 24 VDC outputs from multiple power supply modules in parallel to supply a single
I/O module. This can damage or destroy the power supply modules.
Do not position the 100 VAC, 200 VAC or 24 VDC cables close to, or bundle them with, powercircuit (high-voltage, high-current) cables or I/O signal cables. A clearance of at least 100 mm
(3.94 in) to other cables is required.
39
CPU module
Other
equipment
CPU module
Other
equipment
Class 3 grounding
Class 3 grounding
Other
equipment
CPU module
cm
59 to 88
CAUTION
Connect input and output wires along different routes.
Leave at least 200 mm (7.87 in) clearance between I/O wires and high-voltage, high-current
main-circuit cables.
If the I/O wires cannot be kept separate from the main-circuit or power cables, use shielded
cable for all of them and ground the shield at the CPU module end. However, if appropriate,
ground the other end of the shield
CPU module
Shield cable
Input
Output
RA
Shield
DC
Keep 24 VDC I/O wires separate from 100 VAC and 200 VAC wires.
The leakage current over long-distance wiring connections exceeding 200 m (656.17 ft.) can lead
to problems.
See Section 5.4.2 (9) for appropriate countermeasures.
Ground resistance to be 100 max (class 3 grounding). Do not share a common ground with
other equipment.
3 10
CPU module
AC
Fuse
Select transformer
according to
Section 3.5.1(c)
+24V
-24G
(Only A171SHCPUN)
FG
AC
DC
LG
24VDC
24VDC
INPUT
100 200VAC
Extension cable
I/O
NC
NC
FG
100/110VAC
LG
INPUT
100
200VAC
Ground wire
Ground wire
POINTS
2
(1) Use wires as thick as possible (2 mm max.) for the 100 VAC, 200 VAC, 24 VDC wires. Twist the
wires when connected to the terminals. Use solderless terminals with insulating tubes to prevent
shorting if the screw in the solderless terminal is loose.
(2) Grounding is required if the FG and LG terminals are connected or resistance to noise is reduced.
A shock may be felt when touching the LG terminal as it has a potential of 1/2 input voltage.
3 11
Sub Item
Mounting/Wiring Confirmation
Check for loose or distorted mounting.
Mounting of modules to
Check for loose or distorted mounting.
base unit
Unit/module
mounting
Synchronous encoder
mounting
Wiring
Running of power
supply and I/O wires
3 12
Check
CPU module
Check Item
Reference
1.5.1 (5)
(4) Are the supply voltage and power supply module rated voltage correct?
(5) Are FG and LG wired correctly?
(7) Are cable sizes correct?
(1) Is the module mounted in the correct position (option slot)?
1.5.3 (3)
3.3
I/O module
3.5.1 (6)
3.5.1
1.5.2
3.5.2
A172SENC manual
pulse generator/
synchronous encoder
interface module
1.5.7
1.5.2 (2)
3.5.2
3.5.1 (6)
3.5.1
Special-function
module
Extension cable
41
1.5.3
1.5.3 (3)
1.5.1
3.3
1.5.3
CAUTION
Check and adjust the programs and parameters before starting trial operation. Errors in the
programs or parameters may cause the machine to make unpredicted movements.
Never make very large adjustments as this can make operation unstable.
WARNING
Do not open the front casing or terminal cover during operation or when power is connected.
This can cause electric shocks.
Do not operate with the front case or terminal cover open. This can cause electric shocks from
exposed high-Voltage terminals or charged parts.
Do not operate switches when your hands are wet. This can cause electric shocks.
Do not scratch, apply undue strain to, place heavy weights on, or trap, cables. This can cause
electric shocks.
Do not touch controller, servo-amplifier, or servomotor terminal blocks while power is turned on.
This can cause electric shocks.
Do not touch the controller or servo amplifier internal power supply, internal ground, or signal
wires. This can cause electric shocks.
CAUTION
The machine may make unpredicted movements after a servo amplifier or servomotor is turned
on. Top prevent accidents, check the operation of each individual motor.
Start up servos according to the servo start-up procedure described below.
The servo amplifier cooling fins, regenerative resistor, and servomotors become hot during
operation and can remain hot for some time after power is turned off. Do not touch these parts or
burn injuries may result.
To avoid injury, turn off the power before touching servomotor shafts or machinery connected to
them.
To avoid injury, do not approach machinery during trial or teaching operation.
42
Turn on power
Ensure that the CPU module RUN/STOP key
is set to STOP.
Turn on the CPU module power.
WARNING
Ground controllers, servo amplifiers, and
servomotors to 100W ground resistance,
or less (class 3 grounding). Do not share a
common ground with other equipment.
CAUTION
If a regenerative resistor is used, ensure
that an alarm signal cuts off the power
supply, otherwise damage to the regenerative transistor, overheating of the regenerative resistor, or even fire may result.
To prevent fires, take flameproofing measures inside the control box where the servo
amplifier and regenerative resistor are
located and use non-flammable wiring.
1)
43
CAUTION
Do not connect a phase-advancer
capacitor, surge absorber, or radio noise
filter (FR-BIF option) to the servo amplifier
output.
Ensure output teminals U, V, W, are
correctly connected. Abnomal servomotor
operation may result if the teminals are
incorrctly connected.
[Install Mode]
Install operating system
Install the positioning OS into the
CPU module from the peripheral device.
CAUTION
Set parameter values to match the
controllers, servo amplifiers, servomotors,
and regenerative resistor models used.
Protective functions may not operate
correctly if the parameters are set
incorrectly.
WARNING
Even if the power is tumed off, do not open
the front casing or terminal covers, except
to connect wiring or conduct scheduled
inspections. Charged components in the
controller or servo amplifier can cause
electric shocks.
[Monitor Mode]
Check external inputs to A172SENC
(1) Check the wiring for the following
external inputs by monitoring at a
peripheral device or by using the LED
indicators.
(Input signals' PX0 to PXF)
(a) FLS (upper limit switch input)
(b) RLS (lower limit switch input)
(c) STOP (stop command)
(d) DOG/CHANCE (near-zero point dog,
speed/position switching commad)
CAUTION
Connect a leak breaker to the controller
and servo amplifier power supply.
[Programming Mode]
Write motion programs
Create motion programs from the peripheral
device.
[Programming Mode]
[Sequence Mode]
Write sequence programs
Write the created sequence programs to
CPU module with the peripheral device.
2)
44
CAUTION
[Servo PC Mode]
Write positioning data
Write the created sequence programs and
motion programs to CPU module with the
peripheral device.
3)
45
CAUTION
End
46
End
POINTS
After completion of installation, always turn OFF the installation switch.
47
Item
Check
Before
power-on
Unit/module mounting
and basic wiring
OS installation
Manual operation
CPU module in
RUN status
Automatic operation
Torque check
48
Description
Inspection performed daily.
Inspection performed once or twice every six
months or every year
Clearing up of system trouble cause and its
corrective action
Refer To
Section 5.2
Section 5.3
Section 5.4
WARNING
Do not open the front casing or terminal cover during operation or when power is connected.
This can cause electric shocks.
Do not operate with the front case or terminal cover open. This can cause electric shocks from
exposed high-voltage terminals or charged parts.
Even if the power is turned off, do not open the front casing or terminal covers, except to connect
wiring or conduct scheduled inspections. Charged components in the controller or servo amplifier
can cause electric shocks.
To avoid electric shocks, turn off the power, wait at least ten minutes, then check the voltage with
a tester before starting wiring or inspections.
Ground controllers, servo amplifiers, and servomotors to class 3 grounding resistance, or less.
Do not share a common ground with other equipment.
All wiring and inspections to be conducted by a trained technician.
Install controllers, servo amplifiers, and servomotors before connecting wiring. Otherwise,
electric shocks or injury can result.
Do not operate switches when your hands are wet. This can cause electric shocks.
Do not scratch, apply undue strain to, place heavy weights on, or trap cables. This can cause
electric shocks.
Do not touch controller, servo-amplifier, or servomotor terminal blocks while power is turned on.
This can cause electric shocks.
Do not touch the controller or servo amplifier internal power supply, internal ground, or signal
wires. This can cause electric shocks.
51
CAUTION
Perform daily and periodic inspections in accordance with the directions in this manual and the
instruction manual for the product used.
Make backups of controller and servo amplifier programs and parameters before carrying out
maintenance and inspection.
Be careful not to trap your fingers in the gaps when opening and closing parts that can be
opened and closed.
Replace batteries and other consumable parts at the intervals indicated in this manual and the
instruction manuals for the products used.
Do not touch the IC leads or the contacts of connectors.
Do not place a controller or servo amplifier on a metallic surface where current leakage is
possible, or on surfaces that can become charged with static electricity, such as wood, plastics,
and vinyl.
Do not perform a megger test (insulation resistance measurement) during inspections.
When replacing a controller or servo amplifier, set the settings of the new unit correctly.
On completing maintenance and inspection, check that position detection by the absolute
position sensing function is correct.
Do not charge, heat, burn, or disassemble batteries.
Since electrolytic capacitors can generate gases when faulty, do not put your face close to the
controller or servo amplifier.
The electrolytic capacitor and fan deteriorate over time. Replace them regularly in order to avoid
secondary accidents in the event of their becoming faulty. These parts must be replaced at a
service center or service station.
If the self-diagnostic error of the controller or servo amplifier has occurred, confirm the check
item and recover in accordance with the instruction manual.
If a hazardous condition is supposed to take place at a power failure or product failure, use the
servo motor equipped with an electromagnetic brake or provide an external brake mechanism for
a holding purpose to prevent such a condition.
For the electromagnetic brake operation circuit, make up a double circuit structure so that the
brake is actuated by an emergency stop signal provided externally.
Shut off with servo ON signal OFF,
alarm, magnetic brake signal.
Servo motor
RA1
Magnetic
brakes
Restart operation after removing the cause of alarm occurrence and ensuring safety.
After restoration of power from an instantaneous power failure, stay away from the machine
since a restart may be made suddenly. (Design the machine so that personal safety may be
ensured if a restart is made.)
Before starting operation, check and adjust the programs and parameters. Not doing so can
cause some machines to operate unexpectedly.
Never make extreme adjustment changes as doing so will make operation instable.
Apply only the voltage specified in the instruction manual to each terminal. Not doing so can
cause burst, damage, etc.
Ensure that the wires are connected to the corresponding terminals. Not doing so can cause
burst, damage, etc.
Always make sure that polarity is correct (+, -). Not doing so can cause burst, damage, etc.
While power is on or soon after power-off, do not touch the servo amplifiers' heat sinks,
regenerative brake resistors, servo motors and the like as they may be hot. Doing so can cause
a burn.
Always switch power off before touching the servo motor shaft or the machine connected to it.
Not doing so can cause injury.
Stay away from the machine during trial run or teaching or similar operation. Doing so can cause
injury.
52
Item
Description
Evaluation Standard
Remedy
Tighten loose
screws.
Tighten loose
screws.
Extension cable
connectors
No loose screws
Connectors fully
tightened
Adjust spacing.
Tighten connector
screws
POWER
indicator
Indicator lights
(otherwise abnormal)
See Section
5.4.1 (2)
RUN indicator
Indicator lights
(otherwise abnormal)
See Section
5.4.1 (3) (4)
ERROR
indicator
See Section
5.4.1 (5) (6)
INPUT indicator
See Section
5.4.1 (7)
OUTPUT
indicator
See Section
5.4.1 (7)
Connections
Indicators
53
Item
Ambient
temperature
Ambient
environment
Ambient
humidity
Description
0 C to 55 C
Measure temperature and
humidity.
Measure corrosive gases.
Installation
Remedy
If system is in an
enclosure,
measure
temperature and
humidity inside the
enclosure.
Supply voltage
10% to 90% RH
No corrosive gases
Atmosphere
2
Evaluation Standard
Change power
supply
Looseness
Battery
Tighten screws.
Visual
Clean
No loose screws
Tighten loose
screws
Spacing
between
solderless
terminals
Visual
Adjust spacing
Loose
connectors
Connections
Firmly installed
Loose terminal
screws
Dirt, foreign
matter
Visual
Tighten connector
screws
(Preventative maintenance)
Replace battery if
life is exceeded,
even if no voltage
drop occurs.
Refer to Section
5.3.1.
54
Actual Time
After M9006,
(minimum)
(typical)
M9007 Turns ON
Not used
5400
13000
168
Used (1 module)
3800
9500
168
Synchronous
Encoder Used/Not Used
*The actual time is the average value. The guaranteed time is the minimum value.
Preventative Maintenance Guidelines
1) Replace battery every year, even if total power-interruption time is less than the value in
the table.
2) Replace the battery if the total power-interruption time exceeds the guaranteed time
shown in the table and M9006 is ON.
55
Replacing battery
Actual Time
(Typical)
15
Check M9006
A6BAT
(lithium
battery)
OFF
ON
Battery defective
End
IMPORTANT
Some components mounted on the printed circuit board are sensitive to static electricity. Take the
following precautions before directly handling the printed circuit board:
(1) Ground your body or the work bench.
(2) Do not directly touch the conductive parts or electrical components in the product.
CAUTION
Dispose of batteries according to local government regulations.
56
Error occurs
D9008
57
58
Lit
ERROR indicator lit
Go to Section 5.4.1(5)
"Flowchart when ERROR Indicator is Lit."
Flash/Not lit
Flash Go to Section 5.4.1(6)
"Flowchart when ERROR Indicator is Flashing."
Abnormal
Go to Section 5.4.1(7)/(9)
"Flowchart when Output Module Load Does Not Turn
On." and "Possible Problems with I/O Modules."
Go to Section 5.4.1(8)
"Flowchart when Program Cannot Be Written."
59
NO
Is power supplied?
Supply power.
YES
NO
Is
supply voltage
in range 85 to
264 VAC?
NO
Does
POWER indicator
light?
YES
YES
NO
Is the CPU
(power supply)
module correctly fixed?
NO
Does
POWER indicator
light?
YES
YES
NO
Overcurrent/
overvoltage protection
tripped?
Does
POWER indicator
light?
YES
YES
NO
NO
5 10
Does
POWER indicator
light?
YES
End
Is an
error displayed
when a peripheral device
is connected?
YES
NO
Reset with the CPU module
RUN/STOP key switch.
RUN indicator
lights
RUN indicator
does not light
Set the CPU module
RUN/STOP switch to STOP.
Write END to address 0 from
a peripheral device.
RUN indicator
does not light
RUN indicator
lights
Is sequence program
defective?
5 11
Hardware defect
Does
RUN indicator
light?
YES
End
5 12
NO
NO
NO
Is M9008 ON?
YES
YES
Refer to error code table for
corrective action.
Hardware error
YES
Is
corrective action
available?
NO
YES
Does
ERROR indicator
light?
NO
End
5 13
Does
special register D9124
contain 0?
NO (not 0)
Reset the coil of the
annunciator which is ON
using the RST F instruction.
End
5 14
YES (0)
Is the
indicator LED of the output
module ON?
NO
YES
Is the
indicator LED of the input
module ON?
Is voltage
applied from load power
supply?
NO
0V
YES
Check if input signal is OFF in
monitor mode from peripheral
device.
YES
NO
Supply
voltage
(Monitored
signal OFF)
Check external
wiring and external
equipment.
NG
OK
End
POINT
If the input signal or load does not turn off, refer to Section 5.4.1 (9) "Possible
Problems with I/O Modules."
5 15
Is the
RUN/STOP switch set to
STOP?
RUN
STOP
Can
program be
written?
YES
NO
Reset the CPU.
NO
Is
M.PRO switch set to
OFF?
ON
Can
program be
written?
YES
OFF
NO
Can
program be
written?
YES
End
5 16
Cause
Corrective Action
Example 1
AC input
C
Input signal does not
turn OFF
Input module
Leak current
C
Input module
R
Power supply
Power supply
CR constant : 0.1 to 0.47
W) recommended
Driven using a limit switch with neon lamp.
Example 2
AC input
Input signal does not
turn OFF
Leak current
F + 47 to 120
(1/2
Input module
Power supply
Example 3
AC input
Input module
Input module
Power supply
Power supply
Driven using a limit switch with LED indicator.
DC input (sink)
Example 4
Leak current
DC input (sink)
Input module
Input signal does not
turn OFF
Resistor
Input module
5 17
Cause
Corrective Action
Example 5
E1
Input module
E2
E1
E 1 >E2
E2
Input module
24VDC
1) This circuit does not turn OFF because the A1SX40 OFF current of 1 mA is not
reached. Therefore, the connection of a resistor is required, as shown below.
4mA
IR=3mA
3.6K
A1SX40
IZ=1mA
Input impedance
3.3K
24VDC
2) Resistance calculation
To achieve the A1SX40 OFF current of 1 mA, a resistor should be connected
such that a current of 3 mA min. flows through the resistor.
5 18
Cause
Corrective Action
Example 1
A1SY22
Output module
Overvoltage applied to
load when output turns
OFF
D1
[1]
Load
[2]
With polarity (1), C is charged. With polarity (2),
the C charge voltage plus the power supply
voltage is applied across D1. Max. voltage is
approx. 2.2V.
Leak current due to internal surge suppresor.
Example 2
A1SY22
Output module
Load does not turn
OFF
(Triac output)
Load
Load
Leak current
Example 3
Load
A1SY22
Output module
Resistor
Leak current
CR timer
5 19
Calculate resistor
constant from load.
"INSTRCT
CODE ERR."
"PARAMETER
ERROR"
"MISSING
END INS."
"CAN'T
EXECUTE (P)"
Contents (BIN)
of Special
Register D9008
10
CPU
Status
STOP
Corrective Action
11
STOP
12
STOP
STOP
(1) The jump destination designated (1) Read the error step with the
peripheral device and correct
by the CJ/SCJ/CALL/CALLP/JMP
the program (insert jump
instruction does not exist or is
destination, eliminate duplicate
duplicated.
jump destinations, etc.).
(2) RET instruction exists in program
but no CALL instruction.
(3) The jump destination of a
CJ/SCJ/CALL/CALLP/JMP
instruction is after the END
instruction.
(4) The number of FOR instructions
does not match the number of
NEXT instructions.
(5) A JMP instruction between a FOR
and NEXT instruction jumps out of
the FOR-NEXT loop.
A JMP instruction before the RET
instruction jumps out of the subroutine.
(6) A JMP instruction destination is a
step between a FOR and NEXT
instruction or into a sub-routine.
13
5 20
"CHK FORMAT
ERR."
Contents (BIN)
of Special
Register D9008
14
CPU
Status
STOP
Corrective Action
CJ
(6) The [CHK] [D1] [D2] instruction
D1 device number does not match
the device number of the contacts
before the CJ instruction.
(7) No pointer P254 exists at the start
of the CHK instruction ladder
block.
P254
CHK D1 D2
"CAN'T
EXECUTE (I)"
15
STOP
"RAM ERROR"
20
STOP
"OPE. CIRCUIT
ERR."
21
STOP
"WDT ERROR"
22
STOP
5 21
Error
CPU
Status
Corrective Action
"END NOT
EXECUTE"
24
STOP
"WDT ERROR"
25
STOP
STOP
(RUN)
Problem with I/O module at power on. (1) The bit corresponding the
module causing the verification
(1) During operation, the I/O module
error is set to 1 in special
(induding the special function
register D9116. Monitor the
module) is loose or has come out
contents of this special register
of its slot, or the wrong module is
from the peripheral device.
mounted.
Check the module where the
error occurred and replace, if
necessary.
(2) If the module position is correct,
reset with the RUN/STOP key
switch.
"UNIT VERIFY
ERR."
31
"CONTROL-BUS
ERR."
32
40
41
STOP
(RUN)
STOP
STOP
5 22
Contents (BIN)
of Special
Register D9008
CPU
Status
Corrective Action
43
STOP
(1)
(2)
"SP. UNIT LAY.
ERR."
44
STOP
(3)
(4)
(1)
"SP. UNIT ERROR"
46
STOP
(RUN)
(1)
"LINK PARA.
ERROR"
47
RUN
(2)
(1)
"OPERATION
ERROR"
50
RUN
(STOP)
(2)
(3)
(1)
"BATTERY ERROR"
70
RUN
(2)
APPENDICES
APPENDICES
Appendix 1 Cables
Appendix 1.1 SSCNET Cables
Generally use the SSCNET cables of our options. If the length you need is not
found in our options, fabricate the cable on the customer side.
(1) Selection
The following table indicates the SSCNET cables used with the servo
amplifiers. Make selection according to your operating conditions.
Type
Description
MR-HBUS
SSCNET
cable
MR-J2HBUS
M-A
MR-J2HBUS
Use the following or equivalent twisted pair cables as the SSCNET cables.
Type
Length [m]
MR-HBUS
Wire Model
0.5 to 5
MR-J2HBUS
0.5 to 5
M-A
MR-J2HBUS
A14B2343 6P
UL20276 AWG#28 10 pairs (cream)
Wire Model
Structure
[Number of
wires/mm]
Conductor
resistance
[ /km]
Insulating
sheath OD
d[mm] *1
Finish OD
[mm]*3
0.08
20 (10 pairs)
7/0.127
222 max.
0.38
6.1
A14B2343 6P*2
0.2
12 (6 pairs)
40/0.08
105 max.
0.88
7.2
Conductor
*2: Supplier: Toa Electric Industry
*3: Standard OD. Max. OD is about 10% greater.
CAUTION
When fabricating the bus cable, make correct connection. Wrong connection will cause
runaway/explosion.
APP 1
APPENDICES
(2) MR-HBUS M
(a) Explanation of type
Type: MR-HBUS M
Symbol Cable Length [m]
05
0.5
PCR-S20FS(connector)
PCR-LS20LA1(case)
LG
LG
11
11
RD
RD*
12
12
TD
TD*
14
14
LG
LG
15
15
EMG
EMG* 16
16
BT
SD
20
20
APP 2
APPENDICES
(3) MR-J2HBUS M-A
(a) Explanation of type
Type: MR-J2HBUS M-A
Symbol Cable Length [m]
05
0.5
10120-6000EL(connector)
10320-3210-000(shell kit)
LG
LG
11
11
RD
RD*
12
12
TD
TD*
14
14
LG
LG
15
15
EMG
EMG* 16
17
SD
Plate
20
APP 3
APPENDICES
(4) MR-J2HBUS M
(a) Explanation of type
Type: MR-J2HBUS M
Symbol Cable Length [m]
05
0.5
10120-6000EL(connector)
10320-3210-000(shell kit)
LG
LG
11
11
RD
RD*
12
12
13
13
TD
TD*
14
14
LG
LG
15
15
16
16
EMG
EMG* 17
17
9
19
10
10
20
SD
18
9
19
BAT
18
20
Plate
Plate
APP 4
APPENDICES
Appendix 1.2 Encoder Cables
Generally use the encoder cables of our options. If the length you need is not
found in our options, fabricate the cable on the customer side.
(1) Selection
The following table indicates the encoder cables used with the servo motors.
Make selection according to your operating conditions. Connector sets are also
available for your fabrication.
Encoder Cable
Type
MR-HSCBL
Connector Set
Protective
structure
M
Type
Protective
structure
IP20
MR-JSCNS
IP20
MR-EN1CBL
M-H
IP65
MR-EN1CNS
IP65
MR-JHSCBL
M-L, H
IP20
MR-J2CNS
MR-H compatible
M-H
MR-J2-Super
compatible
HA-LH
K
HC-SF
HC-RF
HC-UF 2000r/min
IP20
MR-ENCBL
MR-J2 compatible
HC-SF
HC-RF
HC-UF 2000r/min
HC-MF
HC-MFS
HA-FF
HC-UF 3000r/min
IP65, IP67
HC-SFS
HC-RFS
HC-UFS 2000r/min
HA-KFS
HC-UFS 3000r/min
HC-MF
MR-HCNM
MR-JCCBL
*1
M-L, H
IP20
IP20
HA-FF
HC-UF 3000r/min
MR-J2CNM
*1: For use of any of the above cables with the MR-H, the MR-HCN2 conversion connector is
required.
Use the following or equivalent twisted pair cables as the encoder cables.
Type
MR-HSCBL
MR-EN1CBL
M
M-H
MR-JCCBL
M-L
MR-JCCBL
M-H
MR-JHSCBL
MR-JHSCBL
MR-ENCBL
M-L
M-H
M-H
Length [m]
Cable Type
2/5
A14B2339 4P
10 to 30
A14B2343 6P
2/5
A14B2339 4P
10 to 30
A14B2343 6P
2 to 10
20/ 30
2/5
10 to 30
A14B2343 6P
A14B0238 7P
2/5
10 to 30
2/5
A14B2339 4P
10 to 30
A14B2343 6P
2/5
A14B2339 4P
10 to 30
A14B2343 6P
CAUTION
When fabricating the encoder cable, make correct connection. Wrong connection will cause
runaway/explosion.
APP 5
APPENDICES
Characteristics of One Core
Wire Model
Core Size
Number of Cores
[mm2]
Conductor
resistance
[ /km]
Insulating
sheath OD
d[mm] *1
Finish OD
[mm]*3
7/0.127
14 (7 pairs)
Structure
[Number of
wires/mm]
222 max.
0.38
5.6
0.08
0.08
8 (4 pairs)
7/0.127
222 max.
0.38
4.7
0.3
12 (6 pairs)
12/0.18
62 max.
1.2
8.2
A14B2343 6P*2
0.2
12 (6 pairs)
40/0.08
105 max.
0.88
7.2
A14B2339 6P*2
0.2
8 (4 pairs)
40/0.08
105 max.
0.88
6.5
A14B0238 7P*2
0.2
12 (6 pairs)
40/0.08
105 max.
0.88
8.0
Conductor
*2: Supplier: Toa Electric Industry
*3: Standard OD. Max. OD is about 10% greater.
APP 6
APPENDICES
(2) MR-HSCBL M (Long flexing life product)
(a) Explanation of type
Type: MR-HSCBL M
Symbol Cable Length [m]
2
10
10
20
20
30
30
11
2
13
14
LG
Servo amplifier
Encoder connector
LG
3
12
MRR
5
BAT
15
MR
16
LG
17
18
P5
8
P5
20
Encoder
T
J
C
D
P
S
SD
10
CN2
R
G
MR
MRR
BAT
LG
LG
P5
H
I
MR-HSCBL2M
MR-HSCBL5M
MR-HSCBL10M to MR-HSCBL30M
Encoder side
MS3106B20-29S(plug)
MS-3057-12A(cable clump)
Encoder side
MS3106B20-29S(plug)
MS-3057-12A(cable clump)
MR
MR
MRR
MRR
P5
P5
LG
LG
P5
P5
LG
LG
P5
16
*1
SHD
E
G
E
F
30m max.
MDR
Encoder connector
P5
19
Encoder cable
(Optional or fabricated)
MD
P5
Servo motor
LG
17
BAT
14
*1
BAT
14
LG
15
LG
15
SD
20
SD
20
*1: Always make connection for use in the absolute position detection system.
Wiring is not needed for use in the incremental system.
APP 7
APPENDICES
(3) MR-EN1CBL M-H (Long flexing life product)
(a) Explanation of type
Type: MR-EN1CBL M-H
Symbol Cable Length [m]
2
10
10
20
20
30
30
11
2
LG
Encoder connector
13
Servo amplifier
LG
MRR
5
12
14
BAT
15
MR
16
LG
17
18
P5
8
P5
20
Encoder
C
D
P
S
SD
K
J
10
CN2
E
F
MDR
MR
Encoder connector
P5
19
Encoder cable
(Optional or fabricated)
MD
P5
Servo motor
MRR
BAT
LG
LG
P5
30m max.
SHD
MR-EN1CBL10M-H to MR-EN1CBL30M-H
MR-EN1CBL2M-H
MR-EN1CBL5M-H
Servo amplifier side
Servo amplifier side
Encoder side
Encoder side
PCR-S20FS(connector)
PCR-S20FS(connector)
MS3106A20-29S(D190)(plug)
MS3106A20-29S(D190)(plug)
PCR-LS20LA1(case)
CE3057-12A-3(D265)(cable clump) PCR-LS20LA1(case)
CE-3057-12A-3(D265)(cable clump)
CE02-20BS-S(back shell)
CE02-20BS-S(back shell)
P5
LG
P5
LG
P5
LG
P5
LG
MR
P5
MRR
16
LG
17
BAT
14
MR
LG
15
MRR
SD
20
BAT
14
LG
15
SD
20
*1
*1
AWG24 used
(for less than 10m)
*1: Always make connection for use in the absolute position detection system.
Wiring is not needed for use in the incremental system.
APP 8
AWG24 used
(for 10m to 30m)
APPENDICES
(4) MR-JHSCBL M-L/MR-JHSCBL M-H
(a) Explanation of type
Type: MR-JHSCBL MSymbol Specifications
Symbol Cable Length [m]
2
10
20
20
30
10
30
11
2
13
14
LG
Servo amplifier
Encoder connector
LG
3
12
MRR
5
BAT
15
MR
16
LG
17
18
P5
8
P5
20
Encoder
T
J
R
G
10
P5
19
LG
11
P5
20
LG
12
MR
MRR
17
P5
MRR
SHD
BAT
LG
LG
P5
H
I
MR-JHSCBL10M-L to MR-JHSCBL30M-L
Servo amplifier side
10120-3000VE
(connector)
10320-52F0-008
(shell kit)
MR
E
F
30m max.
MR-JHSCBL2M-L, MR-JHSCBL5M-L,
MR-JHSCBL2M-H, MR-JHSCBL2M-H
Encoder side
Servo amplifier side
MS3106B20-29S
10120-3000VE
(plug)
(connector)
MS3057-12A
10320-52F0-008
(cable clump)
(shell kit)
C
E
P
S
SD
CN2
MDR
Encoder connector
P5
19
Encoder cable
(Optional or fabricated)
MD
P5
Servo motor
Encoder side
MS3106B20-29S
(plug)
MS3057-12A
(cable clump)
MR-JHSCBL10M-H to MR-JHSCBL30M-H
Servo amplifier side
10120-3000VE
(connector)
10320-52F0-008
(shell kit)
P5
19
P5
19
LG
11
LG
11
P5
20
P5
20
LG
12
LG
12
P5
18
P5
18
LG
LG
Encoder side
MS3106B20-29S
(plug)
MS3057-12A
(cable clump)
18
LG
BAT
MR
MR
LG
MRR
17
MRR
17
SD
Plate
BAT
BAT
LG
LG
SD
Plate
SD
Plate
AWG24 used*1
(for less than 10m)
*1: AWG28 can be used for 5m or less.
AWG22 used
(for 10m to 30m)
APP 9
AWG22 used
(for 10m to 30m)
APPENDICES
(5) MR-ENCBL M-H (Long flexing life product)
(a) Explanation of type
Type: MR-ENCBL M-H
Long flexing life
Symbol Cable Length [m]
2
10
10
20
20
30
30
11
2
LG
Encoder connector
13
Servo amplifier
LG
MRR
5
12
14
BAT
15
MR
16
LG
17
18
P5
8
P5
20
Encoder
C
D
P
S
SD
K
J
10
CN2
R
G
E
F
MDR
MR
Encoder connector
P5
19
Encoder cable
(Optional or fabricated)
MD
P5
Servo motor
MRR
BAT
LG
LG
P5
30m max.
SHD
MR-ENCBL2M-H
MR-ENCBL10M-H to MR-ENCBL30M-H
MR-ENCBL5M-H
Servo amplifier side
Encoder side
Servo amplifier side
Encoder side
10120-3000VE(connector)
MS3106A20-29S(D190)(plug)
10120-3000VE(connector)
MS3106A20-29S(D190)(plug)
10320-52F0-008(shell kit)
CE-3057-12A-3(D265)(cable clump)
CE3057-12A-3(D265)(cable clump) 10320-52F0-008(shell kit)
CE02-20BS-S(back shell)
CE02-20BS-S(back shell)
P5
19
LG
11
P5
19
LG
11
P5
20
LG
12
P5
20
LG
MR
12
P5
MRR
17
18
LG
P5
18
LG
BAT
MR
LG
MRR
17
SD
Plate
BAT
LG
SD
Plate
AWG24 used
(for less than 10m)
*1
AWG22 used
(for 10m to 30m)
APP 10
APPENDICES
(6) MR-JCCBL M-L/MR-JCCBL M-H
(a) Explanation of type
Type: MR-JCCBL MSymbol Specifications
Symbol Cable Length [m]
2
10
20
20
30
10
30
11
2
12
13
14
LG
Servo amplifier
LG
3
Encoder cable
(Optional or fabricated)
MRR
Servo motor
Encoder connector
172161-9(AMP make)
Encoder
MR-HCNS2
MR MRR BAT
Encoder connector
BAT
15
MR
16
LG
P5
17
18
P5
P5
19
P5
20
1
7
CN2
MD MDR
30cm
10
SD
MR-JCCBL2M-L, MR-JCCBL5M-L,
MR-JCCBL2M-H, MR-JCCBL2M-H
Encoder side
Servo amplifier side
1-172161-9
10120-3000VE
(plug)
(connector)
170359-1
10320-52F0-008
(connector pin)
(shell kit)
P5
50m max.
LG
SHD
MR-JCCBL10M-L to MR-JCCBL30M-L
Encoder side
1-172161-9
(plug)
170359-1
(connector pin)
MR-JCCBL10M-H to MR-JCCBL30M-H
Encoder side
1-172161-9
(plug)
170359-1
(connector pin)
P5
19
P5
19
P5
19
LG
11
LG
11
LG
11
P5
20
P5
20
P5
20
LG
12
LG
12
LG
12
P5
18
P5
18
P5
18
LG
LG
LG
MR
MR
MR
MRR
17
MRR
17
MRR
17
MD
MD
MD
MDR
16
MDR
16
MDR
16
BAT
BAT
BAT
LG
LG
LG
*1
SD
Plate
*1
9
SD
*1
9
Plate
*1: Always make connection for use in an absolute position detection system.
Wiring is not needed for use in an incremental system.
APP 11
SD
Plate
APPENDICES
Appendix 1.3 A31TU-E Teaching Unit Cable
(1) A31TUCBL03M cable
(a) A31TUCBL03M cable appearance
EMG1
EMG2
EMG
DED1
EMGL
DED2
A31TU-E side
Signal name
BA
BAL
CA
CAL
BB
BBL
CB
CBL
+5V
BA
BAL
CA
CAL
BB
BBL
CB
CBL
+5V
Pin No.
3
16
5
18
2
15
4
17
12
+5V
13
+5V
13
SG
+5V
7
24
SG
+5V
7
24
+5V
25
+5V
25
SG
SG
AB
FG
8
20
21
1
SG
SG
AB
FG
8
20
21
1
EMG
EMGL
22
9
EMG1
EMG2
DED1
DED2
22
9
6
14
Signal name
Case
CPU module side
Connector
17JE-23250-02(D8A)
Manufactured by DDK
(Red)
(White)
(Red)
(White)
(Red)
(White)
A31TU-E side
Connector
DB-25SF-N
Manufactured by JAE
APP 12
APPENDICES
A31SHORTCON
BA
BAL
CA
CAL
BB
BBL
CB
CBL
+5V
+5V
SG
+5V
+5V
SG
SG
AB
FG
EMG1
EMG2
DED1
DED2
Pin No.
3
16
5
18
2
15
4
17
12
13
7
24
25
8
20
21
1
22
9
6
14
Connector
17JE-23250-02(D8A)
Manufactured by JAE
APP 13
APPENDICES
Appendix 2 Outside Dimensions
Appendix 2.1 CPU Modules
(1) A173UHCPU Module
OUTPUT
5VDC 5A
(5.12)
INPUT
100 - 240VAC
105VA
50 / 60Hz
! WARNING
(0.16)
Hazardous
voltage
(3.69)
(4.46)
(0.25)
(0.66)
Unit=mm (inch)
OUTPUT
5VDC 5A
(5.12)
INPUT
100 - 240VAC
105VA
50 / 60Hz
! WARNING
(0.16)
Hazardous
voltage
(3.69)
(0.25)
(4.46)
(0.66)
APP 14
Unit=mm (inch)
APPENDICES
(3) A171SHCPUN Module
OUTPUT
5VDC 3A
24VDC 0.6A
(5.12)
INPUT
100 - 240VAC
105VA
50 / 60Hz
! WARNING
(0.16)
Hazardous
voltage
(3.69)
(0.25)
(4.46)
(0.66)
APP 15
Unit=mm (inch)
APPENDICES
130 (5.12)
71.6 (2.82)
6.5
93.6 (3.69)
34.5 (1.36)
22
(0.87)
23
(0.91)
(0.26)
APP 16
Unit=mm (inch)
APPENDICES
Appendix 2.3 Main Base Unit
(1) A172B main base unit
mounting screws
(M5 25)
110(4.33)
130(5.12)
16.4
(0.65)
28
(1.1)
200(7.87)
220(8.66)
Unit = mm(inch)
mounting screws
(M5 25)
130(5.12)
110(4.33)
OUT
305(12.02)
16.4
325(12.81)
(0.65)
28
(1.1)
Unit = mm(inch)
APP 17
APPENDICES
mounting screws
(M5 25)
110(4.33)
130(5.12)
OUT
A178B
410(16.15)
430(16.94)
16.4
(0.65)
28
(1.1)
Unit = mm(inch)
APP 18
APPENDICES
Appendix 2.4 Extension Base Units
(1) A1S65B extension base unit
mounting screws
(M5 25)
110(4.33)
130(5.12)
16.4
(0.65)
28
(1.1)
295(11.61)
315(12.4)
Unit = mm(inch)
110(4.33)
130(5.12)
16.4
(0.65)
28
(1.1)
400(15.75)
420(16.54)
Unit = mm(inch)
APP 19
APPENDICES
(3) A168B extension base unit
4
mounting screws
(M5
25)
OUT
OUT
110(4.33)
130(5.12)
IN
1
2
3
1
2
3
400(15.75)
420(16.54)
16.4
(0.65)
28
(1.1)
Unit = mm(inch)
APP 20
APPENDICES
Appendix 2.5 Teaching Unit
(1) A30TU-E teaching unit
10
(0.39)
7)
(8.6
227
Invalid Valid
Emergency
Stop
MITSUBISHI
A 3 0 T U -E
TEST
STOP
225(8.87)
ITEM
:
CLEAR
SP
WRITE
STEP-
STORE
STEP+
MDI
-
.
SHIFT
AXIS
NO.
ERROR
RESET
CAN
JOG -
JOG +
RETURN
GO
27
(1.06)
1(0.04)
5
(0.2)
CONTRACT
DATA
95(3.74)
5000(197)
Unit = mm(inch)
APP 21
APPENDICES
36.5(1.44)
95(3.74)
236(9.30)
TEST
STOP
ITEM
:
C O N T R AC T
DATA
CLEAR
SP
WRITE
STEP-
STORE
STEP+
MDI
-
.
SHIFT
CAN
JOG -
JOG +
RETURN
GO
5000(197)
AXIS
NO.
ERROR
RESET
Unit = mm(inch)
APP 22
APPENDICES
Appendix 2.6 Connector
(1) Honda Tsushin Kogyo make
PCR-LS20LA1
PCR-LS20LA1
13.0
(0.51)
10.4
(0.41)
23.0
(0.91)
20.6
(0.81)
14.2
(0.56)
1
12.2
1
(0.04) (0.48) (0.04)
38.5
(1.52)
HONDA
38.5
(1.52)
HONDA
27.4
(1.08)
32.0
(1.26)
27.4
(1.08)
32.0
(1.26)
1
12.2
1
(0.04) (0.48) (0.04)
1.9
(0.07)
Unit: mm (inch)
Type
Number of Pins
20
Connector
Case
PCR-LS20LA1
PCR-LS20LA1W
12.0
(0.47)
14.0
(0.55)
Position
where e.g.
logo is
indicated
23.8
(0.93)
39.0
(1.52)
22.0
(0.86)
10.0
(0.39)
33.3
(1.3)
12.7
(0.5)
APP 23
Unit: mm (inch)
APPENDICES
12.0
(0.47)
14.0
(0.55)
27.4
(1.08)
5.7
(0.22)
23.8
(0.93)
39.0
(1.52)
22.0
(0.86)
10.0
(0.39)
33.3
(1.3)
12.7
(0.5)
Unit: mm (inch)
11.5
(0.45)
29.7
(1.17)
Unit: mm (inch)
33.0
(1.30)
42.0
(1.65)
20.9
(0.82)
APP 24
APPENDICES
Appendix 2.7 Manual Pulse Generator Specifications
3.6(0.14)
70(2.76)
50(1.97)
60(2.36) 0.5
80(3.15) 1
NP
Packing, t=2.0
+5 to
12V 0V
M3
16
20
(0.63) (0.79)
8.89
(0.35)
7.6
(0.3)
4.8(0 to 19)dia.,
equi-spaced
72(2
.83)
0.2
62
(2.
44
+2
0
27.0 0.5
(1.06)
Unit = mm (inch)
Item
Model name
Pulse resolution
Specification
MR-HDP01
25 PLS/rev (100 PLS/rev after magnigication by 4 in
A172SENC
Output method
Supply voltage
4.5 to 13.2VDC
Current consumption
60 mA max.
Life
Weight kg (lb)
0.4 (0.88)
APP 25
APPENDICES
-0.006
91(3.58)
4- 5.4(0.21)
Effective dimension
21(0.83)
-0.012
5(0.2) -0.042
Shaft cross-section
+0.1
0
28(1.1)
3(0.12)
33(1.3)
3(0.12)
102(4.02)
135(5.31)
56(2.2)
-0.009
1.15(0.05)+0.14
6
2(0.08)
20(0.79)
1.15(0.05)+0.14
0
19.5
(0.77)
56(2.2)
50(1.97) -0.025
68(2.68)
2(0.08)
5(0.2)
68(2.68)
68(2.68)
15(0.59) -0.017
14.3(0.56) -0.11
0
14.3(0.56) -0.11
N.P
16(0.63)
Cross-section B-B
Item
Specification
Model name
MR-HENC
Resolution
16384 PLS/rev
Operation temperature
-5 to 55 C
Weight kg (lb)
1.5 (3.3)
Communications method
Transmission distance
Connecting cables
APP 26
Printed in Japan