Auto Start
Auto Start
1. "TDBFP Tripped " contact is generated from trip oil pressure very low (2 out of 2 logic). Turbine running contact(Derived from Turbine speed > 500 RPM) is used for runback in CMC. 2. " Scoop tube at minimum" permissive will be bypassed if MDBFP Auto/Manual switch is in Auto mode. 2(a) If MDBFP Auto/Manual switch is kept in MAN mode and if pump is not running , scoop tube will drive to minimum position without human intervention and permissive will also present. 3. Recirculation valve will be in auto and in full open condition and it will be regulated with MDBFP Pump suction flow. 4. 2TF3 is a time delay to drop out relay and set for 7 sec .This relay contacts were used for Energizing /De-energising the hydraulic coupling rapid start solenoid valves. 5. 2TF2 is also a time delay to drop out relay whose contacts are going to close the MDBFP breaker .Auto start command is parallel to the Manual start command. 6. "Pump not running and drive scoop to minimum" interlock will be bypassed and scoop is to be kept in auto, so that it will track FW pump Master command. 7. When unit is not running / MDBFP not available , MDBFP Auto /Manual Switch is to be kept in "Manual" position.
7 8
4A
MANUAL BFP-C START COMMAND
M A
5 6
5 6 2K88
10
4B
MDBFP NOT RUNNING L1
2LR8
2K87
2TF3
L2
BFP-C ON AUTO
BFP-A/B TRIPPED
X2395 / 9
ARP 3S/K41
ARP3S/59
SBF31J
4A MDBFP START SWITCH HS-0699A 4B X2395 / 10
ARP 3S/K42 L
START(S)
ARP3S/59
1 5
2 6 2TF3
SV91
SV92
PR9
3P38
2TF2
Modification for Manual Starting of MDBFP even when Auto/Manual switch is kept in Auto position Requirement: 2 cables (cores) from ARP-3 to UCB (Near) switch-HS0699A) Existing available cable:
X2452 X2453
BF31J 14C
ARP-3
ARP-3R 13 TO 22
ARP-3 S59
X2395 / 9
S41
START
10
S42
S60