Fire Alarm System Requirements
Fire Alarm System Requirements
C. Low pressure and low temperature alarms on fire sprinkler systems shall be monitored by the fire alarm system. D. Separate alarm zones and signals on the panel, annunciator and at the central station are required. E. All fire protection systems, i.e. sprinkler, FM 200, kitchen hood, must interface with the system as separate alarm zones and signals. F. All fire sprinkler system control valves including the PIV must be tampered and supervised on the system. System Components and Hardware: A. Monitoring must comply with NFPA 72, including panel requirement for audible trouble signals and must have two means of signal transmission. B. Remote visual alarm indicating devices with labels are required on the ceiling or wall directly below duct detectors that are not visible from the floor. C. An approved cover is required on all pull stations. D. The system AC power supply circuit breaker must be labeled and red in color. E. All devices on addressable systems shall be labeled to coincide with the annunciator panel. F. All indicating sprinkler control valves must be secured and electronically supervised. G. An approved Fire Alarm Panel sign is required on the door access to the room where the panel is located. H. An approved 11 x 17 system plan and building floor plan is required at the panel and annunciator locations. I. Smoke damper detector locations in accordance with State Building Code provisions. J. Zoning shall be approved by the Fire Inspector. Inspections Required: Call 763 509 5449 between 8:00 a.m. to 4:30 p.m. to arrange for an inspection. Please provide the permit number with your request. Allow 24 hours for all inspections. A. The system must be 100% tested prior to calling for inspection. If an acceptance test of a system fails, a reinspection must be scheduled. B. All devices will be tested for proper operation. Smoke detectors, heat detectors, pull stations, etc. C. All sprinkler control valves shall be tested. D. Test all horns and strobes. The decibel level and light intensity must be set correctly and synchronized. E. Test primary and secondary phone lines. F. A 24 hour AC power loss test is required. G. Magnetic door devices release, doors close and latch on activation of any device. H. Ventilation system shutdown upon activation of duct smoke detectors. I. Smoke dampers close on detector activation. J. Central station verification of signals received at test and submittal of signal received documentation required. L. Completed and signed NFPA 72 inspection/test record forms and a UL certificate must be submitted to the Protective Inspection Division at time of, or prior to final acceptance approval.
IB\APPS HANDOUTS INFO\Fire Alarm System Requirements.docx