SYSTEM DATA
00.01: Language:
English
00.02: Password:****
00.04: Description:
DISTANCE PROTN
00.05: Plant Reference: 66KV LINE
00.06: Model Number:
P442316B6M0550K
00.08: Serial Number:
477769U
00.09: Frequency:
50 Hz
00.0A: Comms Level:
2
00.0B: Relay Address:
1
00.0C: Plant Status:
0000000000000000
00.0D: Control Status:
0000000000000000
00.0E: Active Group:
1
00.10: CB Trip/Close:
No Operation
00.11: Software Ref. 1: D4.4_A
00.20: Opto I/P Status: 0000000000000000
00.21: Relay Status 1:
000000000000000000000
00.22: Alarm Status 1:
00000000000000000000000000000100
00.40: Relay Status 1:
000000000000000000000
00.50: Alarm Status 1:
00000000000000000000000000000100
00.51: Alarm Status 2:
00000000000000000000000000000000
00.52: Alarm Status 3:
00000000000000000000000000000001
00.D0: Access Level:
2
00.D1: Password Control: 2
00.D2: Password Level 1: ****
00.D3: Password Level 2: ****
CB CONTROL
07.01: CB Control by:
Disabled
DATE AND TIME
08.01: Date/Time:
1994-01-01 00:43:05.78
08.06: Battery Status:
Dead
08.07: Battery Alarm:
Enabled
08.13: SNTP Status:
Disabled
08.20: LocalTime Enable: Fixed
08.21: LocalTime Offset: 0 min
08.22: DST Enable:
Enabled
08.23: DST Offset:
60.00 min
08.24: DST Start:Last
08.25: DST Start Day:
Sunday
08.26: DST Start Month: March
08.27: DST Start Mins:
60.00 min
08.28: DST End: Last
08.29: DST End Day:
Sunday
08.2A: DST End Month: October
08.2B: DST End Mins:
60.00 min
CONFIGURATION
09.01: Restore Defaults: No Operation
09.02: Setting Group:
Select via Menu
09.03: Active Settings:
Group 1
09.04: Save Changes:
No Operation
09.05: Copy From:
Group 1
09.06: Copy To: No Operation
09.07: Setting Group 1: Enabled
09.08: Setting Group 2: Disabled
09.09: Setting Group 3: Disabled
09.0A: Setting Group 4: Disabled
09.0D: Dist. Protection: Enabled
09.10: Power-Swing:
Disabled
09.11: Back-up I>:
Disabled
09.12: Neg Sequence O/C:
Disabled
09.13: Broken Conductor: Disabled
MiCOM S1 Agile
Page: 2
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
MiCOM S1 Agile
Page: 3
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
11111111111111111111111111111111
33.30 %
Single
VA
VB
VC
VN
IA
IB
MiCOM S1 Agile
Page: 4
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
0C.0A:
0C.0B:
0C.0C:
0C.0D:
0C.0E:
0C.0F:
0C.10:
0C.11:
0C.12:
0C.13:
0C.14:
0C.15:
0C.16:
0C.17:
0C.18:
0C.19:
0C.1A:
0C.1B:
0C.1C:
0C.1D:
0C.1E:
0C.1F:
0C.20:
0C.21:
0C.22:
0C.23:
0C.24:
0C.25:
0C.26:
0C.27:
0C.28:
0C.29:
0C.2A:
0C.2B:
0C.2C:
0C.2D:
0C.2E:
0C.2F:
0C.30:
0C.31:
0C.32:
0C.33:
0C.34:
0C.35:
0C.36:
0C.37:
0C.38:
0C.39:
0C.3A:
0C.3B:
0C.3C:
0C.3D:
0C.3E:
0C.3F:
0C.40:
0C.41:
0C.42:
0C.43:
0C.44:
0C.45:
0C.46:
AnalogChannel7:
AnalogChannel8:
DigitalInput1:
Input1Trigger:
DigitalInput2:
Input2Trigger:
DigitalInput3:
Input3Trigger:
DigitalInput4:
Input4Trigger:
DigitalInput5:
Input5Trigger:
DigitalInput6:
Input6Trigger:
DigitalInput7:
Input7Trigger:
DigitalInput8:
Input8Trigger:
DigitalInput9:
Input9Trigger:
DigitalInput10:
Input10Trigger:
DigitalInput11:
Input11Trigger:
DigitalInput12:
Input12Trigger:
DigitalInput13:
Input13Trigger:
DigitalInput14:
Input14Trigger:
DigitalInput15:
Input15Trigger:
DigitalInput16:
Input16Trigger:
DigitalInput17:
Input17Trigger:
DigitalInput18:
Input18Trigger:
DigitalInput19:
Input19Trigger:
DigitalInput20:
Input20Trigger:
DigitalInput21:
Input21Trigger:
DigitalInput22:
Input22Trigger:
DigitalInput23:
Input23Trigger:
DigitalInput24:
Input24Trigger:
DigitalInput25:
Input25Trigger:
DigitalInput26:
Input26Trigger:
DigitalInput27:
Input27Trigger:
DigitalInput28:
Input28Trigger:
DigitalInput29:
Input29Trigger:
DigitalInput30:
IC
IN
Any Start
Trigger L/H
Any Trip
Trigger L/H
DIST Fwd
Trigger L/H
DEF Rev
Trigger L/H
Z1
Trigger L/H
Z2
Trigger L/H
Z3
Trigger L/H
Z4
Trigger L/H
SOTF Enable
Trigger L/H
SOTF/TOR Trip
Trigger L/H
VT Fail Alarm
Trigger L/H
Any Pole Dead
Trigger L/H
All Pole Dead
Trigger L/H
SOTF Enable
Trigger L/H
SOTF/TOR Trip
Trigger L/H
T3
Trigger L/H
T4
Trigger L/H
Brk.Conduct.Trip
Trigger L/H
Brok.Cond. Alarm
Trigger L/H
Power Swing
Trigger L/H
VT Fail Alarm
Trigger L/H
MCB/VTS Main
Trigger L/H
MCB/VTS Synchro
No trigger
DEF. Chan Recv
No trigger
DEF Rev
No trigger
DEF Fwd
No trigger
DEF Start A
No trigger
DEF Start B
No trigger
DEF Start C
No trigger
Unused
MiCOM S1 Agile
Page: 5
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
0C.48: DigitalInput31:
Unused
0C.4A: DigitalInput32:
Unused
MEASURE'T SETUP
0D.01: Default Display: U - I - Freq
0D.02: Local Values:
Primary
0D.03: Remote Values: Primary
0D.04: Measurement Ref: VA
0D.05: Measurement Mode:
0
0D.06: Demand Interval: 30.00 min
0D.07: Distance Unit:
Kilometres
0D.08: Fault Location:
Distance
COMMUNICATIONS
0E.01: RP1 Protocol:
Courier
0E.02: RP1 Address:
255
0E.03: RP1 InactivTimer: 15.00 min
COMMISSION TESTS
0F.01: Opto I/P Status: 0000000000000000
0F.02: Relay Status 1:
000000000000000000000
0F.04: Test Port Status: 00000000
0F.06: Monitor Bit 1:
Relay Label 01
0F.07: Monitor Bit 2:
Relay Label 02
0F.08: Monitor Bit 3:
Relay Label 03
0F.09: Monitor Bit 4:
Relay Label 04
0F.0A: Monitor Bit 5:
Relay Label 05
0F.0B: Monitor Bit 6:
Relay Label 06
0F.0C: Monitor Bit 7:
Relay Label 07
0F.0D: Monitor Bit 8:
Relay Label 08
0F.0E: Test Mode:
Disable
0F.0F: Test Pattern 1:
000000000000000000000
0F.11: Contact Test:
No operation
0F.12: Test LEDs:
No operation
0F.13: Autoreclose Test: No Operation
0F.16: Red LED Status: 000000000100000000
0F.17: Green LED Status: 000000000000000000
CB MONITOR SETUP
10.01: Broken I^:
2.000
10.02: I^ Maintenance: Alarms Disabled
10.04: I^ Lockout:
Alarms Disabled
10.06: No CB Ops Maint: Alarms Disabled
10.08: No CB Ops Lock: Alarms Disabled
10.0A: CB Time Maint:
Alarms Disabled
10.0C: CB Time Lockout: Alarms Disabled
10.0E: Fault Freq Lock: Alarms Disabled
10.11: Lockout Reset:
No
10.12: Reset Lockout By: CB Close
OPTO CONFIG
11.01: Global Nominal V: 110/125V
11.50: Opto Filter Cntl: 1111111111111111
11.80: Characteristic:
Standard 60%-80%
CTRL I/P CONFIG
13.01: Hotkey Enabled: 11111111111111111111111111111111
13.10: Control Input 1: Latched
13.11: Ctrl Command 1: SET/RESET
13.14: Control Input 2: Latched
13.15: Ctrl Command 2: SET/RESET
13.18: Control Input 3: Latched
13.19: Ctrl Command 3: SET/RESET
13.1C: Control Input 4: Latched
13.1D: Ctrl Command 4: SET/RESET
13.20: Control Input 5: Latched
13.21: Ctrl Command 5: SET/RESET
MiCOM S1 Agile
Page: 6
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
MiCOM S1 Agile
Page: 7
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
MiCOM S1 Agile
Page: 8
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
MiCOM S1 Agile
Page: 9
Settings File Report
Substation:
File: AS PER SITE.set
Model Number: P442316B6M0550K
MiCOM S1 Agile