Boiler Trip Protection: Master Fuel Trip Protections
Boiler Trip Protection: Master Fuel Trip Protections
Both ID Fans
OFF
--
--
--
Both FD Fans
OFF
--
--
--
3 hardwired contacts for each ID fan (2/3) (HT Switchgear) 3 hardwired contacts for each FD fan (2/3) (HT Switchgear)
4 5 6 7 8 9 10
UCP: EMG PB MFT1 and MFT 2 Any OWS: EMG trip command Furnace Pressure Furnace Pressure Drum Level Drum Level Total Air Flow
----5 sec 10 sec 2/3 Pressure Switches 2/3 Pressure Switches 2/3 Transmitter 2/3 Transmitter Flow Transmitters
11 12
--
10 sec 2 sec
Arming: 220V DC for LOTV/ HOTV and HORV solenoids & Scanner air Emergency Damper 24V for MFT Panel Hardwired trip 110V AC for nozzle valve solenoids Arming: All feeders off Arming: Any feeder proven Arming: Any LO/HO nozzle valve not closed
13 14
Unit 24V DC (FSSS internal) Loss of FB & loss of AC in any elevation i/s Unit Flame Failure Trip Loss of All Fuel Trip
---
---
-2 sec
15 16
---
---
---
NOTE: All Trip Conditions are individually sensed by each MFT panel. Final 2/3 Logic for Master Fuel Trip is hardwired in Purge Panel.
Sl.No. 01. 02. 03. 04. 05. 06. 07. 08. 09. 10. 11. 12. 13. 14. 15. 16. 17.
Description Emergency push button trip from desk & OWS Fire Protection 1 & 2 from control desk & OWS and MBLD 1 & 2 (from MOT room & TG 17m) FCS trip optd 2/3. (arming > 540rpm) Lub Oil pressure very low 2/3. HP exhaust steam temp. Very high 2/3. Axial shift Very high 2/3. Cold gas temp. after H2 cooler high AB 2/3. Cold gas temp. after H2 cooler CD 2/3. Seal oil temp. after cooler high 2/3. Liquid level in main leads high 2/3. Hot air temp. exciter high 2/3. Turbine / Generator brg Temp ATRS Trip Over Speed Trip Boiler trip to Turbine trip. Generator trip to Turbine trip. MOT level very low (2/3) (Through Fire Protection logic)
Set Value < -0.7 kg/cm2 < 1.2 kg/cm2 > 450oC > .5 mm > 55oC > 55oC > 55oC > 90 mm > 85oC >90 deg / > 130 deg