DPM b100 Modbus Map User
DPM b100 Modbus Map User
Modbus Map
P&C Tech
V1.1 2004-03-04
Modbus Map
1. Scope
This document describes the Modbus RTU register map for the DPM-B100
2. Applicable Document
Modicon Modbus Protocol Reference Guide DWG#:PI-MBUS-300 Rev.E
This document describes the Modicon Modbus RTU communication protocol used by the DPM-B100.
The device configuration parameters, such as baud rate, is only accessible via debug port on the device. Because MODBUS is a multidrop network, the operator is responsible to make sure no 2 devices have the same ID on the network, The device ID can range from 1~254. BPS : 1200, 2400, 4800, 9600
Data Format
INT16U : 0~65535
V1.1 2004-03-04
Modbus Map
Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose without the express written permission of P&C Technologies Co., Ltd.
P&C Technologies Co, Ltd. #401, Anyang Megavelley,799 Kwangyang-dong, Dongahn Ku, Anyang-shi, Kyongki Do, 431-767, Korea
V1.1 2004-03-04
Modbus Map
DI
IF = CT (2026) / 1,000 VF = PT 1(2023) * PT Scale(2024) / PT 2(2025) / 10 WF = IF * VF * 10,000 = CT (2026) * PT 1(2023) * PT Scale(2024) / PT 2(2025)
A 1 (A) 3 (W)
= 2000 * IF = 2006 * WF
1) 3 (kWh) = {(2012)*65536*65536)+((2011) *65536) +(2010)} * WF / 5000 2) 3 (kVarh) = {(2015)*65536*65536)+((2014) *65536) +(2013)} * WF / 5000