Electronic Watt-Hour Meter

Modbus Map

P&C Tech

MODBUS PROTOCOL & MEMORY MAP DOCUMENT


DPM-B100
Rev Date: Revision 24-Feb-06 Document: 1.0 Firmware: Hardware:

V1.1 2004-03-04

P&C Technologies Co.,LTD

Electronic Watt-Hour Meter

Modbus Map

1. Scope
This document describes the Modbus RTU register map for the DPM-B100

2. Applicable Document
Modicon Modbus Protocol Reference Guide DWG#:PI-MBUS-300 Rev.E

This document describes the Modicon Modbus RTU communication protocol used by the DPM-B100.

The device configuration parameters, such as baud rate, is only accessible via debug port on the device. Because MODBUS is a multidrop network, the operator is responsible to make sure no 2 devices have the same ID on the network, The device ID can range from 1~254. BPS : 1200, 2400, 4800, 9600

3. Functions and message parsing


The DPM-B100 supports a subset of Modbus commands. All the supported commands are listed below.
Function Code 0x03 0x04 03 04 Read Holding Registers Read Input Registers Read Actual Values of Set-points Read Actual Values of Set-points Set-point & Control registers Dynamic values, fixed values, faults, events, and reports 0x05 0x06 0x10 05 06 16 Force Single Coil Preset Single Register Preset Multiple Register Execute Operation Program Set-points Program Multiple Set-points Coil registers Set-point registers Set-point registers Modbus Definition P&C Definition Register Groups

Data Format
INT16U : 0~65535

V1.1 2004-03-04

P&C Technologies Co.,LTD

Electronic Watt-Hour Meter

Modbus Map

Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose without the express written permission of P&C Technologies Co., Ltd.

Copyright 2002 P&C Technologies Co., Ltd. All rights reserved

For further information, contact:

P&C Technologies Co, Ltd. #401, Anyang Megavelley,799 Kwangyang-dong, Dongahn Ku, Anyang-shi, Kyongki Do, 431-767, Korea

Tel:+82-31-420-5791 Fax:+82-31-420-5793 Website:www.pnctech.co.kr

V1.1 2004-03-04

P&C Technologies Co.,LTD

Electronic Watt-Hour Meter

Modbus Map

REVISIONS User Map


Format name Type DO Description Address 500 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010~2012 2013~2015 2023 2024 2025 2026 1999 Function Code 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 0x04 Description DO A B C A B C Watt Var PF(3) WattHr VarHr -PT 1 -PT Scale -PT 2 -CT DI R/W R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O R/O Access Format Data Type WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD ON : 0xFF00 OFF :0x00FF * IF * IF * IF * VF * VF * VF * WF * WF * 100 * 100 1) 2) Unit/Facter

DI

Facter = IF , Facter = VF ,(//) Facter = WF ,

IF = CT (2026) / 1,000 VF = PT 1(2023) * PT Scale(2024) / PT 2(2025) / 10 WF = IF * VF * 10,000 = CT (2026) * PT 1(2023) * PT Scale(2024) / PT 2(2025)

A 1 (A) 3 (W)

= 2000 * IF = 2006 * WF

A 1 (V) = 2003 * VF 3 (Var ) = 2007 * WF

1) 3 (kWh) = {(2012)*65536*65536)+((2011) *65536) +(2010)} * WF / 5000 2) 3 (kVarh) = {(2015)*65536*65536)+((2014) *65536) +(2013)} * WF / 5000