Instrument Transformer Basics
Instrument Transformer Basics
Turns Ratio
Current Transformer TR= Primary Current/ Secondary Current Example: What is the TR of a CT marked 600:5? TR=600/5= 120
Voltage Transformer TR= Primary Voltage/ Secondary Voltage Example: What is the TR of a PT marked 13200:120? TR=13200/120=110 Example: What is the TR of a PT marked 110:1? TR= 110/1=110
Polarity The Primary Terminals of an instrument transformer is marked H1 and H2. The secondary side is marked X1 and X2. The rule is that whenever the AC wave shape of the H1 is high, then the X1 will also be high. Some transformers use dots in lieu of characters. In this case H1 and X1 are marked with a dot. H2 and X2 have no marking.
The second number this the maximum burden (load) that you can put on the transformer and still get the accuracy percent!
Selecting a CT Both of these CTs are rated 600:5 How do you decide which one is right for you?
Current Transformer Relay accuracy Example: A 600:5 CT is rated C20, 0.3 B 0.9. Can it produce enough voltage to trip a relay 50 feet away if connected to the relay with #14 awg. wire? The voltage required is the sum of the voltage drop in the wire plus the relay burden (but most electronic relays have near zero burden), so lets look a the wire resistance: Wire resistance= 50* 2* .0025 ohms/ ft = .25 ohms Required voltage= I*R= 5*20*.25= 25 volts 25 volts > 20 volts
Current Transformer Relay accuracy Example: A 600:5 CT is rated C20. Can it produce enough voltage to trip a relay 50 feet away if connected to the relay with #14 awg. wire? 25 volts > 20 volts, so this CT is to small!! How could this be fixed?
Current Transformer Metering Accuracy Example: A 600:5 CT is rated C20, 0.3 B 0.9. Can it produce enough voltage to meter 50 feet away if connected to the relay with #14 awg. Wire? The voltage required is the sum of the voltage drop in the wire plus the relay burden (but most electronic relays have near zero burden), so lets look a the wire resistance: Wire resistance= 50* 2* .0025 ohms/ ft = 0.25 ohms
Current Transformer Metering Accuracy Example: A 600:5 CT is rated C20, 0.3 B 0.9. Can it produce enough voltage to meter 50 feet away if connected to the relay with #14 awg. Wire? Since 0.25 ohms < 0.9 ohms Even with the addition of a small meter burden, the CTs will perform fine.
INSTRUMENT TRANSFOMERS,INC. CURRENT TRANSFORMER RATIO 1200:5 A. CAT 623-122MR RF 1.33 ACC CLASS C100 50-400 HZ 600V INS CLASS 10kV BIL
INSTRUMENT TRANSFOMERS,INC. CURRENT TRANSFORMER RATIO 400:5 A. CAT 115-401 RF 2.0 ACC CLASS 0.3B0.9 C50 50-400 HZ 600V INS CLASS 10kV BIL
INSTRUMENT TRANSFOMERS,INC. VOLTAGE TRANSFORMER PRI 2400V. 20:1 BIL 60kV 60 HZ 0.3Y 750VA @ 30 DEG C PTG3-2-60-SD0331
Transformer Label
INSTRUMENT TRANSFOMERS,INC. VOLTAGE TRANSFORMER PRI 12000V. 100:1 BIL 110kV 60 HZ 0.3WXMYZ 1.2ZZ 1200VA @ 30 DEG C PTG5-2-110-SDXXXXXFF
Never open circuit a current transformer secondary while the primary is energized
CTs are intended to be proportional current devices. Very high voltages can result from open circuiting the secondary circuit of an energized CT. Even very small primary currents can cause damage
VTs are intended to be used as proportional voltage devices. Damaging current will result from short circuiting the secondary circuit of an energized VT.
The Rule Book: ANSI/ NETA MTSSTANDARD FOR MAINTENANCE TESTING SPECIFICATIONS
Smell
If you suspect a recent event, sniff the CT or PT. An internally shorted transformer can produce a lot of heat that can burn insulation. And, by all means, do not re-energize a transformer that does not pass the sniff test- even if it tests good! Caution: Dont sniff test PVC dipped CTs
Is my PT good?
Test #2 Continuity test to look for broken internal wires Measure the resistance from X1 to X2 and H1 to H2. You should always see some resistance, but the H1 to H2 might be high on medium voltage transformers. The resistance from X1 to X2 should always be less than H1 to H2!
If you cant measure resistance the PT is bad, dont do any more testing!
Is my CT good?
Test #2 Continuity test to look for broken internal wires Measure the resistance from X1 to X2. Make sure all leads and shorting wires are removed form the terminals.
If resistance cant be measured or it shows very high, the CT is bad. All 5 amp secondary CTs have a low secondary resistance. The exact value can be found on the manufactures specification sheet.
If you cant measure resistance the CT is bad, dont do any more testing!
2.
Loop a wire through the CT window one or more times and measure the voltage.
The voltage measured should be: V(X1 to X2) * # of loops / Turns ratio
STOP: NEVER connect the variac across the X1 to X2 terminals. Very high voltage may be present across H1 and H2 if this is done!
3. Slowly raise the voltage on the variac to about 50 volts maximum. You dont need more! 4. Measure voltage across H1 to H2, and then across X1 to X2. 5. V(H1 to H2)/ V(X1 to X2) should equal the Transformer Turns Ratio
Insulation resistance test levels and test values are recorded in Table 100.1 of the NETA/ANSI MTS standard. For example 1000v rated equipment should be tested with 1000VDC and 100 Megohms should be the lowest acceptable resistance.
Keep them Clean Wipe them clean when you inspect them with a clean dry cloth.
If you have transformers on medium voltage systems, look for treeing.
(Treeing is carbon tracks that forms on the surface of the transformer due to partial discharge and/or corona.) Clean it off!! The tracks will only grow larger, and can eventually break down.
Questions?