Ea448 Manual en

This document provides an operation manual for an automatic voltage regulator (EA448) that can be used with permanent magnet generators or auxiliary excitation systems. It includes: 1) An introduction describing the regulator's specifications such as voltage and current output ranges, response time, and dimensions. 2) Procedures for adjustment including jumper settings for phase detection, response time, frequency selection and more. It also describes potentiometer adjustments for droop, output voltage, stability and overcurrent. 3) Wiring diagrams and notes on connecting the regulator to an excitation system and power inputs.

Uploaded by

roozbehxox
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
265 views

Ea448 Manual en

This document provides an operation manual for an automatic voltage regulator (EA448) that can be used with permanent magnet generators or auxiliary excitation systems. It includes: 1) An introduction describing the regulator's specifications such as voltage and current output ranges, response time, and dimensions. 2) Procedures for adjustment including jumper settings for phase detection, response time, frequency selection and more. It also describes potentiometer adjustments for droop, output voltage, stability and overcurrent. 3) Wiring diagrams and notes on connecting the regulator to an excitation system and power inputs.

Uploaded by

roozbehxox
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

EA448

Generator Automatic Voltage Regulator Operation Manual

Permanent Magnet Generator or A.R.E.P or Auxiliary Winding Type Compatible with Leroy Somer R448* * Use for reference purpose only and not a genuine Leroy Somer product.

Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw

1. INTRODUCTION
Sensing Input Terminal 0 ~ 110V = 95 ~ 140V 0 ~ 220V = 170 ~ 260V 0 ~ 380V = 340 ~ 520V 50 / 60 Hz, selectable External Volts Adjustment 10% @ 1K ohm Response Time 0.3 ~ 1sec @ 20% Voltage Vibration Current Droop 2 sec. Max 4% @ P.F. = 0.8 Auxiliary Winding 6~150VAC (No load rms) LAM Voltage Drop Rate 10% and 15% selectable Dimensions 203mm L * 153mm W * 60.5mm H Weight 970g 2%

Frequency Power Input Voltage

40 ~ 150 VAC, 3 phase

Voltage Output Max 160VDC @120VAC Current Output Max 10 A Voltage Regulation < 0.5% ( with 4% engine governing ) Voltage Build-up Residual voltage at AVR terminal > 5 VAC

2. OPERATION PROCEDURE
2.1 Jumper Adjustment
1. ST1 Connected wire ST1 for Single phase measurement. Cut wire ST1 for three phase measurement. 2. ST2 Response Time Fast(disconnected) / Slow(Connected) Select. PSIt should do stable adjustment with P3. 3. ST3For 50/60HZ selection use Jumper.ST3. 4. ST4 Remove wire ST4 to Connect external potentiometer (1K). Connect wire ST4 when it is not necessary to connect external potentiometer. 5. ST6Instantaneous Compensation for Voltage. PS Remove wire ST6 when the regulator is used in higher 600KVA. 6. ST7Jumpers connected. 7. J1Connected with LAM protection. Discounted without LAM protection. No LAM protection, for knee frequency adjustment use P4. 8. J2LAM Voltage DROP RATE, 1-2 about 12%, 2-3 about 20%.

3. P3Stability. 4. P4Under-speed (U/F) and LAM protection: for knee frequency adjustable us P4. 5. P5Excitation over current adjustment use P5 3.5A ~ 10A.

2.3 Wiring
1. X1-X2Excitation power auxiliary winding input, single phase 2 wires. 2. Z1-Z2Harmonic Power input (Multi-Harmonic). 3. E+Positive Output Terminal for Excitation power. 4. E- Negative Output Terminal for Excitation power. 5. 0 ~ 110Measure Power Input 110VAC. 6. 0 ~ 220Measure Power Input 220VAC. 7. 0 ~ 380Measure Power Input 380VAC. Note 1. When excitation power is three phase input, connect X2, X1, Z2. See Figure 3. 2. Fuse capacity10A / 250V. 3. When the regulator works normal, the LED will keep Light condition. The LED will be turned off when Stand-by power works in normal usual. In this condition, the rated voltage will decrease automatically and the voltage adjustment will failure.

2.2 Adjustment
1. P1 Adjustment of quadrature droop. (MAX 12%).

2. P2Output Voltage adjustment by using P2. ______________________________________________________________________________________ 2 EA448

Exciter field Armature

Stator wires

C.T N:1A

R S T

FU FV FW S2 S4 S1 S3

Fuse 10A

50HZ 60HZ X2 Z1 X1 Z2 E+ E0V 110V 220V 380V

AVR EA448

S2 S1

3ph in

EXT.VR 1k Ohm

Figure 1

Power and Wiring for Harmonic Power

Exciter field Armature

Stator wires

C.T N:1A

R S T

FU FV FW S2 S4 S1 S3

Fuse 10A

50HZ 60HZ X2 Z1 X1 Z2 E+ E0V 110V 220V 380V

AVR EA448

S2 S1

3ph in

EXT.VR 1k Ohm

Figure 2 Three phase wiring

______________________________________________________________________________________ EA448 3

ST3

Fuse 10A

50HZ 60HZ P5 J1
123

LED

J2

P4 ST2 P3

ST6 ST7 P2 ST1 P1

X2 Z1 X1 Z2 E+ E0V 110V 220V 380V

3ph in

S2 S1 VR 1k ST4

Figure 3

Adjustment and Jumper Diagram

P.S. Please use the fuse of the original plant.

______________________________________________________________________________________ 4 EA448