Generator Capability Curve
Generator Capability Curve
- K. Arputharaju, Assistant Executive Engineer / Operation, Basin Bridge Gas Turbine Power Station, TANGEDCO, TNEB Ltd., Chennai 600 012.
1
REAL POWER (P): The real power, P is defined as the average value of P and therefore, physically, means the useful power being transmitted. Its magnitude depends very strongly on the power factor cos. REACTIVE POWER (Q): The reactive power, Q is by definition equal to the peak value of that power component that travels back & forth on the line, resulting in zero average, and therefore capable of no useful work.
3
TYPE OF LOADS:
TYPE OF LOAD I V R I V PHASOR PHASE ANGLE POWER ABSORBED BY THE LOAD P Q P>0 Q=0
= 0
I V I L I
= +90
P=0
Q>0
= - 90
P=0
Q<0
I V
R V L
0<<+90
P>0
Q>0
L
4
TYPE OF LOADS:
TYPE OF LOAD I V R C V R C I V -90<<0 P>0 Q<0 PHASOR PHASE ANGLE POWER ABSORBED BY THE LOAD P Q
Tuned to
Resonance I V C Ic L IL = Ic PL = Pc Energy travels
-90<=<=+90
IL
P=0
Q=0
TYPE OF LOADS
Inductive load absorbs positive Q. i.e., an inductor consumes reactive power. Capacitive load absorbs negative Q. i.e., a capacitor generates reactive power. Sign change in Q simply means a 180 phase shift. Resistive load consumes real power. Inductive load consumes positive reactive power Capacitive load consumes negative reactive power. Combination of R & L load consumes real & positive reactive power. Combination of R & C load consumes real & negative reactive power. Reactive power is bi-directional power. It travels from source to load as well as load to source.
6
V1
V2 jX P jQ
1. 2. 3.
Bus Voltage V1 is kept at constant magnitude. Transmission line has reactance only i.e. jX. Power flow is P jQ.
Take V1 as reference. V2=V1-jXI -----------------------------------(1) V1 * I = P jQ I = (P-jQ) / V1 ------------------------------(2) Substitute (2) in (1) V2 = V1 jX [(P/V1) j(Q/V1)] V2 = [V1 (X/V1)Q] j(X/V1)P]
VECTOR DIAGRAMS:
V2 = V1- X Q V1
-j X P V1
DOUBLE P DOUBLE Q
V1
X Q V1 X P V1
V1
X
V1
V1
Q
X P V1 2X Q V1
V2
V2
V2
2X P V1
DOUBLE P : VOLTAGE ANGLE WILL CHANGE. NO CHANGE IN MAGNITUDE. DOUBLE Q : VOLTAGE MAGNITUDE IS VERY MUCH RELATED TO REACTIVE POWER. MORE Q FLOW WILL AFFECT THE VOLTAGE EXCITATION MORE EXCITATION LESS LAGGING MVAR LAGGING MVAR GEN. VOLTAGE GEN. VOLTAGE 10
REACTIVE POWER INJECTION AT LOAD SIDE BY USING SHUNT CAPACITORS, IMPROVES THE VOLTAGE. UNDER LIGHT LOAD CONDITIONS, RECEIVING END VOLTAGE > SENDING END VOLTAGE (FERRANTI EFFECT) DUE TO CAPACITIVE LOAD. CONNECT SHUNT REACTORS TO CONTROL VOLTAGE. PEAK LOAD CONDITION CONNECT CAPACITORS TO CONTROL VOLTAGE
CONNECT REACTORS
SYNCHRONOUS CONDENSER IS USED TO ABSORB or TO DELIVER THE REACTIVE POWER. SYNCHRONOUS MOTOR UNDER NO-LOAD CONDITION IS SYNCHRONOUS CONDENSER.
11
1.0
C
E
AD AE AC DE BC
AB
o
SCR = o Fo o Fs c Fo b Fs c Fo a Fo
Fo
Fs
FIELD CURRENT
1 Per unit voltage on open circuit Corresponding per unit current on short circuit 12 1 Xd
1 a Fo / c Fo
SCR
AIR GAP
WEIGHT
SIZE
Present trend is to build low value of SCR since fast acting excitation system available.
13
CASE-I: In ABC, BC=E Sin B In BCD, BC=IXd Cos E E Sin = IXd Cos MW A Multiply both sides by V V D C Xd I MVAR EV Sin = VI Cos = REAL Xd POWER At =90, We get the maximum power i.e. the theoritical stability line.
In ABC, CD=AC AD; In BCD, CD=IXd Sin In ABC, AC=E Cos & AD = V IXd Sin = E Cos - V ; Multiply both sides by V , We get Xd EV Cos V2 = VI Sin = REACTIVE POWER Xd Xd CASE-I I:
14
OE : No-load Field Current OD : Field Current required for Armature Reaction FGDHF : Capability Diagram of the 110 MW Alternator
=90
1.0 0.9 0.9
B
P.F.= 0.8 LAGGING
G
THEORITICAL STABILITY LIMIT LINE
0.7
ARG IN ( =6 3)
0.8
OR AT ST
%M
IT W ITH 12.5
AT UR
0.5
0.5
0.4 0.3
ST AT OR
.87
L TA 0.3 TO
0.2
R) 0.4 R (O TO RO
AR M
D EL FI
CU
RR
T EN
CU
0.6
0.6
RR
EN T
CU
RR T EN LIM
CUR OR ROT
(O R)
IT
REN IT T LIM
A
1.0 0.9 0.8 0.7 0.6 SCR
E
0.5
PRA C
0.1
0.1
F
0.3 0.2 0.1
=3 6
0.2
TO TA L
H O
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
C
1.0
0.4
16
OE : No-load Field Current OD : Field Current required for Armature Reaction FGDHF : Capability Diagram of the 110 MW Alternator
=90
1.0 0.9 0.9
B
P.F.= 0.8 LAGGING
G
THEORITICAL STABILITY LIMIT LINE
0.7
ARG IN ( =6
3)
0.8
OR AT ST
%M
IT W ITH 12.5
AT UR
0.5
0.5
0.4 0.3
ST AT OR
=36 .87
L TA 0.3 TO
0.2
R) 0.4 R (O TO RO
AR M
D EL FI
CU
RR
T EN
CU
0.6
0.6
RR
EN T
CU
RR T EN LIM
CUR OR ROT
(O R)
IT
REN IT T LIM
0.2
PRA C
0.1
0.1
TO TA L
0.5
0.4
0.6
0.2
0.3
0.7
0.8
0.9
1.0
A
1.0 0.9 0.8 0.7 0.6 SCR
E
0.5
0.1
0.3
H
0.9
C
1.0
0.4
0.2
0.1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
17
III) COMPARISON
Actual MW=50 (i.e. 50/137.5=0.364p.u.) Actual MVAR=6 (i.e. 6/137.5=0.044p.u.) Arm. Current = 0.36p.u. X 7220A=2599A Field Current=0.475p.u. X 1500A=712.5A p.f.=cos(6.5)=0.994 lag Load Angle =33.4 V=(MVA X 106)/(3 X
Iarm.) Iarm.)
=((MW2+MVAR2) X 106)/(3 X
18
A.
CAPABILITY CURVE
B.
C.
D.
MW load limit
Turbine limit (steam power generation capability) Turbine is designed for MW load only .
E.
Stressing stator winding & heating of stator 10 to 20 MVAR (leading p.f.) is safe Rotor is relieved from stress Stator end winding heated due to capacitive effect Remove capacitor banks in load centres In NCTPS 210 MW unit, running the generator at -64 MVAR load for an hour. Not able to reduce the load.
19
USEFULNESS OF CAPABILITY DIAGRAM FOR EXCITATION CONTROL The information given by the capability diagram regarding full load rotor current (excitation), maximum rotor angle during steady state leading p.f. zone operation (<75) etc., are essential for proper setting of the various limiters in the excitation control system. Capability diagram give the basic information regarding the limiting zones of the operation so that limiters can be set / commissioned suitably for safe operation of the units.
20