F SUPPLIED FROM: SMB INCOMING CABLES: 4Cx16 mm2 PVC/PVC + 1Cx10 mm2 ECC
CIRCUIT NUMBER
LOAD DESCRIPTION
R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8 R9 Y9 B9 R10 Y10 B10 R11 Y11 B11 R12 Y12 B12 R13 Y13 B13 R14 Y14 B14
17xD1 LED lights type in main Intrance Through LCP 17xD1+7xD5 LED lights type in Main entrance Through LCP 44xD1 LED lights type in main Intrance Through LCP 8xD5+6xD1 LED lights type in ex. Staircase Through LCP 7xD2+9xD6+2xW1 LED Lights in Intrance Through LCP 34D1 LED Lights in Car Intrance Through LCP 34D1 LED Lights in Car Intrance Through LCP 9xD5+6xD6+3xD2 LED Lights In car park Through LCP 5xD5+1xA4+2xC2 Lights in swimming pool service room Through LCP 9xW1+1xW5 LED Lights in boundary wall Through LCP 13xW1+2xW5 LED Lights in boundary wall Through LCP 6xW1+1xW5 in boundary wall Through LCP 6xD6+1x LED mirror light+3xLED Cove Light 25xD4+12xD6 LED Lights In Intrance 33xD4+16xD6 LED Lights in Majlis 11xD4+12xD6+2xD7 LED Lights in Dinning area 3xD4+21xD6 LED Lights In Intrance 2xA5 + 7xD6+11xD4+1x Mirro light LED Lights in Bathroom+dreesing+sitting area 9xD4+9xD6 In bedroom 18xD4+12xD6+4xD7 in Sitting area 20xD5 LED in staircase 6 x Single socket Outlet weather proof IP 67 boundary wall mount 6 x Single Socket Outlet weather proof IP 67 Boundary wall mount 5 x Single Socket Outlet weather proof IP67 Boundary wall mount Shaver Socket Outlet 3 x Double Socket Outlet in dressing + library area 4 x Double Socket Outlet in Sitting area Bell in Gate entrance Spare 5 x Double Socket Outlet in Bedroom Bell in main entrance 2 x Double socket outlet in Entrance 5 x Double Socket Outlet in Dinning and Majlis EXFAN Spare EXFAN 1.7 TON A/C Spare Spare Spare Spare Spare
TOTAL WATTS PER PHASE TOTAL CONNECTED LOAD MAXIMUM DEMAND NOTE : * denotes ELCB ( 30 mA of sensitivity) TP ELCB to be provided separately with enclosure
PROJECT: VILLA ALQ DISTRIBUTION BOARD : DB - PH LOCATION :PENT HOUSE STORE ROOM SUPPLIED FROM: SMB INCOMING CABLES: 4Cx16 mm2 PVC/PVC + 1Cx10 mm2 ECC
CIRCUIT NUMBER
LOAD DESCRIPTION
R1
12xD5 LED Lights In staircase 6xA4 Lights In Water Tank room and elec room 14xD6 + 3xD7 + 12D4 LED Lights in Intrance and pantry Mirror LED Lights + 7x D6 + 1xD7 + 34X D4 LED Lights in dinning and toilet 6x D6 + 34x D4 + 1xD7 LED Lights in Majlis 7x D6 + 18xD4 LED Lights In Bedroom 8x D6 + 2 Mirror + 2xA5 Lights in toilets and dressing rooms Spare 6 x Single Socket Outlet in Bedroom 6 x Single Socket Outlet in Bedroom 6 x Double Socket Outlet in Majlis and Dinning room 2 NO Floor Box Of 4 Switched socket Outlet (IP67) In Majlis 13 A Single Socket outlet for Fridge at Pantry 13 A Single Socket outlet for mini Chiller at Pantry 2 x Single Socket Outlet In tank yard 4 x Double Socket Outlet in Pantry 4 x Double Socket Outlet in Pantry Booster Pump
SPARE Hot Water Circulation Pump EXFAN Spare EXFAN EXFAN EXFAN 1.7 TON A/C Space 1.7 TON A/C
TOTAL WATTS PER PHASE TOTAL CONNECTED LOAD MAXIMUM DEMAND NOTE : * denotes ELCB ( 30 mA of sensitivity) TP ELCB to be provided separately with enclosure
14W 40A TPN MCB DISTRIBUTION BOARD 415 V,80A, 50 HZ, 3P+N+E INCOMING MCCB: 40 A, 3P (NON TRIP) LOAD (WATTS) R Y B
MCB/ELCB
220 312 572 182 540 442 442 421 367 300 450 320 230 610 810 550 660 380 450 700 260 600 600 500 200 600 800 200 1,000 200 400 1,000 100 100 2,500
10* 10* 10* 10* 10* 10* 10* 10* 10* 10* 10* 10* 10 10 10 10 10 10 10 10 10 20* 20* 20* 20* 20* 20* 15* 20* 20* 15 * 20* 20* 10 * 20* 15* 20 20 20 10 10 10
KW KW
6,174
6,551
12W 40A TPN MCB DISTRIBUTION BOARD 415 V,100A, 50 HZ, 3P+N+E INCOMING MCCB: 40 A, 3P (NON TRIP) LOAD (WATTS) R Y B
MCB/ELCB
390
10
R1
156 228 660 600 560 390 320 600 1,200 1,200 800 500 500 200 800 800 500 500 500 3,000 3,000 3,000
3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 4x4 + 2x4mm2 PVC WIRES 4x4 + 2x4mm2 PVC WIRES 4x4 + 2x4mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 3x4mm2 PVC WIRES 3x4mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 5x4mm2 PVC WIRES
Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4
30*A
3x2.5 mm2 pvc wires 3x2.5 mm2 pvc wires 3x2.5 mm2 pvc wires 3x2.5 mm2 pvc wires 3x4 mm2 pvc wires 3x4 mm2 PVC WIRES
PROJECT: VILLA ALQADI 12W 63A TPN MCB DISTRIBUTION BOARD 415 V,100A, 50 HZ, 3P+N+E INCOMING MCCB : 63 A, 3P (NON TRIP) LOAD (WATTS) R Y B
MCB/ELCB
LOAD DESCRIPTION
12xD6+18xD4+3xD7 LED Lights Type in majlis 10xD5 LED Light at staircase 11xD6 LED Lights + 1 mirror LED lights type in Bedroom 14xD6 LED Lights in corridure and store 9xD6LED Lights+2 LED mirror lights in lobby - wash and toilet 18xD6 + 8xD4 LED Lights in sitting area 12xD6+16xD4 LED Lights in Dinning area 16xD6 in Kitchen + Corridure Spare 4 x Double socket Outlet in Bedroom 4 x Double socket Outlet in Bedroom 1NO 13A Socket Outlet For Refrigrator 5 x Double socket Outlet in Office and Dinning 1NO Flexible outlet Cooker point in Dirty Kitchen 1NO Flexible outlet Cooker point in Kitchen 4 x Double socket Outlet in Kitchen Spare Spare 1NO Flexible outlet for dish washer in kitchen Spare Spare 13 A Single Socket outlet for Freezer at Kitchen EXFAN 13 A Single Socket outlet for Fridge at Kitchen 4 x Double socket Outlet in Kitchen& Dirty Kitchen 1 NO Flex Outlet for Kitchen Hood 1 NO Flex Outlet for Kitchen Hood 2 NO Floor Box Of 4 Switched socket Outlet (IP67) In Sitting Area 1NO Flexible outlet for cloth drayer in laundry 1NO Flexible outlet for Washing Machine in laundry 2 NO Floor Box Of 4 Switched socket Outlet (IP67) Majlis Spare Spare 2 NO Floor Box Of 4 Switched socket Outlet (IP67) in Majlis EXFAN EXFAN
TOTAL WATTS PER PHASE TOTAL CONNECTED LOAD MAXIMUM DEMAND NOTE : * denotes ELCB ( 30 mA of sensitivity) TP ELCB to be provided separately with enclosure
660 130 350 330 310 620 520 480 800 800 500 800 6,000 6,000 800
2,000
500 200 500 800 200 200 800 2,000 2,000 800
10 10 10 10 10 10 10 10 10 20* 20* 20* 20* 50 50 20* 20* 20 20 20 20 20* 10* 20* 20* 15 15 20* 20* 20* 20* 20* 20* 20* 10 * 10 * KW KW
PROJECT: VILLA ALQADI 4W 32A TPN MCB DISTRIBUTION BOARD 415 V, 32A, 50 HZ, 3P+N+E INCOMING MCCB: 32 A, 3P (NON TRIP) LOAD (WATTS) R Y B
MCB/ELCB
LOAD DESCRIPTION
500
15
Spare ROLL UP SHUTTER ISOLATOR. ROLL UP SHUTTER ISOLATOR. Driver Room A/C Unit Water Heater In Driver room 3NOS. socket Outlet in Driver Room Spare Spare 13 A Single Socket outlet for Fridge at Kitchen Spare Spare
TOTAL WATTS PER PHASE TOTAL CONNECTED LOAD MAXIMUM DEMAND NOTE : * denotes ELCB ( 30 mA of sensitivity) TP ELCB to be provided separately with enclosure
500
1,700
1,600
DISTRIBUTION BOARD : DB - FF LOCATION : ELECTRICAL ROOM F.F SUPPLIED FROM: SMB INCOMING CABLES: 4Cx16 mm2 PVC/PVC + 1Cx10 mm2 ECC CABLE SIZE
3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 3x4mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 3x10mm2 PVC WIRES 3x10mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES CIRCUIT NUMBER
LOAD DESCRIPTION
LO R
R1 Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8
9xD4+9xD6 In bedroom 22xD5 in staircase 16xD6 + 21xD4 in Bedroom + 3x A5 + 1 Mirror Light 12xD6 + 1 Mirror + 2xA5 Led Light In toilet and Office 27xD6 +30xD4 LED Light In Lobby 13xD6 + 21xD4 LED Light in Bedroom+1 Mirror light in toilet + 3xA4 14xD6 + 18xD4 + 8x A5 + 2 Mirror Lights in master bedroom 16xD6 + 18xD4 + 4xD7 LED Lights in sitting Area 5 x Double socket Outlet in Master Bedroom 4 x Double socket Outlet in pantry and looby 6 x Double socket Outlet in Bedroom 8 x Double socket Outlet in Bedroom 6 x Double socket Outlet in Bedroom 4 x Double socket Outlet in Office 2 NO Floor Box Of 4 Switched socket Outlet (IP67) In Sitting Area SPARE Spare Spare 1.7 TON A/C 1.7 TON A/C 1.7 TON A/C EXFAN EXFAN EXFAN
TOTAL WATTS PER PHASE TOTAL CONNECTED LOAD MAXIMUM DEMAND NOTE : * denotes ELCB ( 30 mA of sensitivity) TP ELCB to be provided separately with enclosure
450
420
800
800
1,200
2,500
100
6,270
DISTRIBUTION BOARD : DB - ME1 LOCATION : ELECTRICAL ROOM G.F SUPPLIED FROM: SMB INCOMING CABLES: 4Cx35 mm2 PVC/PVC + 1Cx16 mm2 ECC CABLE SIZE
3x2.5mm2 PVC WIRES CIRCUIT NUMBER
LOAD DESCRIPTION
LO R
R1
1,600
3x4mm2 PVC WIRES 3x4mm2 PVC WIRES 3x4mm2 PVC WIRES 3x4mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES
4 TON A/C AT BASEMENT FLOOR 1,833 5 TON A/C AT BASEMENT FLOOR 1,600 4 TON A/C AT BASEMENT FLOOR 1,833 5 TON A/C AT GROUND FLOOR 1,833 5 TON A/C AT GROUND FLOOR 1,600 4 TON A/C AT FIRST FLOOR 1,833 5 TON A/C AT FIRST FLOOR 1,833 5 TON A/C AT PENTHOUSE FLOOR
SPARE
SPARE
SPARE
SPARE
TOTAL WATTS PER PHASE TOTAL CONNECTED LOAD MAXIMUM DEMAND NOTE : * denotes ELCB ( 30 mA of sensitivity) TP ELCB to be provided separately with enclosure 13,965
OAD (WATTS) Y B
MCB/ELCB
CABLE SIZE
3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 3x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES 4x4 + 2x2.5mm2 PVC WIRES
286 690 1,110 680 780 1,000 1,200 1,600 800 800
10 10 10 10 15 10 15 15 20* 20* 20* 20* 20* 20* 20* 10 * 20 10* 20 20 20 10* 10* 10*
KW KW
3x4 mm2 pvc wires 3x4 mm2 pvc wires 3x4 mm2 pvc wires 3x2.5 mm2 pvc wires 3x2.5 mm2 pvc wires 3x2.5 mm2 pvc wires
OAD (WATTS) Y B
CABLE SIZE
CIRCUIT NUMBER
R1
1,600 1,600 1,833 1,834 1,600 1,600 1,833 1,834 1,833 1,834 1,600 1,600 1,833 1,834 1,833 1,834
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
30A TPN
5Cx6mm PVC
Y1 B1 R2 Y2 B2 R3 Y3 B3 R4 Y4 B4 R5 Y5 B5 R6 Y6 B6 R7 Y7 B7 R8 Y8 B8
30A TPN
30A TPN
30A TPN
30A TPN
13,965 41.90 32.68 13,970 KW KW
PROJECT: VILLA ALQADI 8W 32A TPN MCB DISTRIBUTION BOARD 415 V,32A, 50 HZ, 3P+N+E INCOMING MCCB: 32 A, 3P (NON TRIP) LOAD (WATTS) R Y B
MCB/ELCB
LOAD DESCRIPTION
500
LIFT PUMP 767 SUBMERSIBLE PUMP1 767 SUBMERSIBLE PUMP2 500 IRRIGATION PUMP
20A TPN
20A TPN
20A TPN
20A TPN
SPARE
20A TPN
20A TPN
KW KW
CABLE SIZE