Min.distance
3 - 4 x hmax
90 hmax
weir
upstream water
Note Otherwise follow the installation guidelines given by the channel manufacturer.
Sensor
3 - 4 x hmax
90
hmax
Sensor
VEGASON 71 - D
2 Technical Information
Fault:
Min. distance from sensor to hmax not maintained. Problem: The upper range cannot be measured. Solution: Correct min. distance of the sensor to 0,3 m.
hmax
< 300 mm
Fault: Sensor is not directed vertically to the surface. Problem: Sensor receives weak echoes. Solution: Mount sensor vertically.
Fault: Distance from sensor to hmax too large. Problem: Unreliable results due to very weak echoes. Solution: Correct min. distance of the sensor to 0,3 m.
hmax
> 300 mm
Fault: Strong heat fluctuations, e.g. sun. Problem: The measuring accuracy is not constant. Solution: Install a sun shield in the respective position.
Fault:
Sensor too close to the flume wall, i.e. not mounted in the centre. Problem: Build-up and rough flume walls cause measuring problems. Solution: Mount sensor in the centre of the flume.
Fault: Surface has foaming problem. Problem: The surface of the foam is detected as level. The measured value is wrong. Solution: The used measuring principle is not suitable and must be replaced e.g. by a hydrostatic system (pressure transmitter).
10
VEGASON 71 - D