Hydronic System: J.Ilangumaran
Hydronic System: J.Ilangumaran
J.ILANGUMARAN
P.S.
6"Ø 6"Ø
P.S.
5"Ø 10"Ø
5"Ø 10"Ø
5"Ø 5"Ø
CONDENSER
5"Ø
5"Ø 10"Ø
10"Ø
5"Ø 5"Ø
5"Ø CONDENSER
5"Ø
10"Ø 10"Ø
10"Ø 5"Ø
5"Ø 5"Ø
5"Ø
CONDENSER
HYDRONIC SYSTEM
HYDRONIC SYSTEM - BASIC COMPONENTS
EXPANSION
CHAMBER PUMPS
DISTRIBUTION SYSTEM
COMPRESSOR
COIL-CHW
CHILLING MACHINE
AIR FLOW
TO SPACE
55°F CHILLED
WATER RETURN
CONDENSOR
HEAT EXCHANGE
BETWEEN CHILLED
HEAT REJECTED TO WATER & AIR
REFRIGERANT
ie. AT COOLER TERMINAL UNITS
* AHU'S
* FCU'S
HEATING - HOT WATER & COIL
HOT WATER SUPPLY
HEATING COIL
AIR FLOW
TO SPACE
100°F 120°F
HOT WATER
GENERATOR 100°F
HOT WATER RETURN PIPE
TERMINAL UNITS
* AHU'S * FCU'S
AIR OUT
COOLING
TOWER
COMPRESSOR
CONDENSOR
AIR IN CONDENSOR
WATER RETURN
CHILLING MACHINE
MECHANICAL
SOURCE - WATER IS USED AS
GENERATION OF
PLANT ROOM
HIGH SIDE
COOLING/HEATING
A CARRIER OF HEAT,
LOW SIDE IT IS THE COOLANT
CHILLED WATER
F.C.U. F.C.U. SUPPLY OR COOLING
F.C.U. F.C.U. CHILLED WATER
F.C.U. F.C.U.
RETURN MEDIUM.
F.C.U. F.C.U. IT TRANSPORTS THE
BLOCK A
F.C.U. F.C.U. AHU
F.C.U. F.C.U.
SPACE HEAT TO
DISTRIBUTION NETWORK
F.C.U. F.C.U. CHILLING MACHINE.
F.C.U. F.C.U. BLOCK B
AHU
WATER IS A
L SECONDARY
L
AHU
L REFERIGERANT
BLOCK D
BLOCK C
AHU
CHILLER FLOW RATE
HEAT CARRYING CAPACITY OF PIPING
Q = MASS FLOW RATE x SP. HEAT x TEMP.
RANGE
Q BTU/HR = GALLONS/MINUTE x 8.33
POUND/GALLON x 60 x 1 x ∆ T0 F
= GALLON/MINUTE x 500 x ∆ T0 F
∆ T0 F = BTU/HR PER GPM, FLOW RATE
8 = 4000 3.0 GPM / TR.
10 = 5000 2.4 GPM / TR.
15 = 7500
20 = 10,000
CLOSED RECIRCULATING TYPE
STATIC HS = STATIC HD
ATMOSPHERIC
PRESSURE THERE IS NO UNBALANCED
EXPANSION
TANK STATIC HEAD.
EVEN WHEN PUMP IS NOT IN
OPERATION, THE ENTIRE
PIPING IS FILLED WITH
WATER
CHILLED WATER
SUPPLY THE PRESSURE AT THE
HIGHEST POINT =
TERMINAL
UNITS SYSTEM PRESSURE + STATIC
CHILLED
WATER HEIGHT & LIQUID
COOLER
RETURN
(EXPANSION TANK WATER
44°F PUMP 54°F LEVEL )
DIRECT RETURN
D
E
AHU / FCU
10 FT 10 FT
C
F
AHU / FCU
10 FT 10 FT
B
G
AHU / FCU
10 FT 10 FT
PUMP
A COOLER H
40 FT
PARALLEL PATHS
- A-B-G-H ( 100 FT. ) SHORTEST PATH
- A-B-C-F-G-H (120 FT.)
- A-B-C-D-E-F-G-H ( 140 FT. ) LONGEST PATH
SEAMLESS IS EXPENSIVE & HENCE NOT USED
GENERALLY FOR HVAC SYSTEM
COIL
B
CHW / HOT
AB A
WATER OUT
COIL
CHW / HOT
WATER OUT
4"Ø
4"Ø 8"Ø 4"Ø
4"Ø
8"Ø CHILLER 4"Ø
4"Ø
6"Ø 6"Ø
P.S.
5"Ø 10"Ø
5"Ø 10"Ø
5"Ø 5"Ø
CONDENSER
5"Ø
5"Ø 10"Ø
10"Ø
5"Ø 5"Ø
5"Ø CONDENSER
5"Ø
10"Ø 10"Ø
10"Ø 5"Ø
5"Ø 5"Ø
5"Ø
CONDENSER