On Transformer
On Transformer
Transformer
Distribution
Power
Core type
Shell type
Straight cut
Angular cut
Power Transformer
Distribution Transformer
Comparison between power & distribution transformer Power transformer Installation At substation (generation side). - or Y- , 3 wire. MVA. Usually stepped down to 11kv. ONAF, OFAF, ONWF, OFWF Distribution transformer At distribution and transmission (consumer side). -Y, 4wire. KVA. Usually stepped down from 11kv to 415v.
Cooling system
Usually ONAN.
Transformer type
Core type transformer
Winding
Core
The advantages of each type are: core-type (or three limbs) is the most commonly used method of construction, the smaller core means less weight and expense. shell-type (or five limbs) is used for larger transformers because of a reduced height and better mechanical protection to the winding because it is surrounded by core. From a manufacturing standpoint, core-type & shell-type designs are very similar.
Performance
Reduce reluctance against the Provides more reluctance magnetic flux by reducing the to magnetic flux due to gaps between sheets. Hence more number of gaps. So lessen the iron loss and performance is well below betters the performance. angular.
Cost
Cost is more as huge amount of core is wasted due to the cutting off at corner to make it angular. Preferred where efficiency is vital.
Preference
Products / Services:
I ) Transformers:
Power Transformer, 3 Phase, 33/11KV, 1 MVA to 5 MVA Distribution Transformer, 3 Phase, 33/0.415 KV, 100 KVA to 250 KVA Distribution Transformer, 3 Phase, 11/0.415 KV, 50 KVA to 500 KVA Distribution Transformer, 1 Phase, 6.35/0.24 KV, 5 KVA to 50 KVA Distribution Transformer, 1 Phase, 11/0.24 KV, 15 KVA to 25 KVA Apart from these, other rated transformer could manufactured as per requirements of clients up to 5MVA II)Repair & Miscellaneous Works: Damaged Distribution & Power Transformers up to 20 MVA
CPL
Plant
Electrical Mechanical
Name of Raw Materials CRGO Silicon Steel Sheet Copper Strips Super Enameled Copper Wire Mild Steel Sheet HT Insulator Transformer Oil Insulated Paper & Board
Specification of materials Grade M-5 (width 0.3mm, density7.65kg/dm3, Core loss 0.97-1.39 for 1.5-1.7T)
Electrolytic Copper of 99.9% purity SWG -14 to 21 Copper of 99.9% purity Prime Quality Electrical Porcelain Insulator As per IEC-296 Class-1 Electrical Grade 100% Sulphate/Kraft Pulp
Design specification
Raw material specification LT Coil dimension, Thickness=5.6mm, width=11.2mm, insulation=.45mm, density=61.92x10^-6 kg/m3 HT coil type- SWG17 , supper enameled
Design specification
In design calculation The design is usually 6 step core section with Cylindrical coils
Transformer leg
Active Part
Tapping
Core
Insulation Board
Each transformer undergoes following routine tests as per IEC 60076 requirements:
Di-electric strength test of transformer oil.
Testing