Design and Calculation of An Earth Electrode
Design and Calculation of An Earth Electrode
J. Gomez
Abstract
People using electrical installations have to be protected against electrical shock. For purposes of
protection a distinction is made between direct and indirect contact. Direct contact is contact with
a live conductor. Protection is provided by the insulation of cables or the screening of live parts.
An indirect contact happens when someone touches exposed metal parts which are not intended
to carry current but have become live as a result of a fault. In this case metallic parts raise the
metal to a dangerous potential (contact voltage). Here protection is provided by connecting the
exposed metal part (i.e. the case of the electrical machine) to the earthing point of the installation.
A protective device will disconnect the circuit as soon as a fault current flows to earth. The earth
fault value will depend on the impedance of the path taken by the fault current, which is known
as the earth fault loop. The resistance of the earth electrode plays an important role in the final
impedance of the earth fault loop, especially when the neutral of the transformer is earthed
without any impedance. A good earth electrode should have the lowest possible value compared
with the rest of the earth loop (voltage divisor). If this can be achieved, the contact voltage will
be limited and the current that trips the protections will be of a higher value. The maximum
duration of a contact voltage is established according to IEC 60364-4 413.1.1.1. An important
constraint in obtaining a good resistance value for the earth electrode is the resistivity of the soil.
1 SOIL RESISTIVITY
The resistivity of a given type of soil will vary by several orders of magnitude as a result of small changes
in the moisture content, salt concentration, and soil temperature. A broad variation of resistivity occurs as
a function of soil types. Knowledge of exactly what type of soil we have at a given site will help to design
in a precise manner the earth electrode.
x Because we are going to place more than one rod there will be a lower resistance which will be
estimated according to Fig. 3.
If the rods are distributed in a grid pattern, as will frequently be done for substations, use Fig. 2 to
estimate the net resistance instead of Fig. 3.
Figure 3: Effective resistance of ground rods when arranged in a straight line or a large circle.
Therefore, 3 m (10 ft) ground rods are initially selected for evaluation. (Minimum rod diameter
14.8 mm or 3/4 inch.)
First in Fig. 2 we place a straight edge between the point marked 3/4 on line ‘d’ and the point
marked 10 ft on line ‘l’. Indicate on line ‘q’ where the straight edge crosses. Next, place the straight edge
between the point just marked on ‘q’ and the 10 000 ohm-cm point on the vertical line marked as
resistivity. Then read the resistance as 32 ohm-cm at the point where the straight edge crosses the vertical
line tagged resistance.
In order to prevent interactions between rods (placing rods too close increases the expected
resistance) we assume an initial spacing of 7 m (20 m) or twice the rod length. Figure 1 shows that 26 rods
are needed to encircle the building. Then we use Fig. 3 to determine the relative lowering of resistance of
one rod that is produced by 26 rods in parallel. The answer is 5.5%.
The resistance of the 26 rods in a 10 000 ohm-cm soil is:
R = 32 x 0.055 = 1.76 ohms.
Figure 3 applies to ground rods placed in a straight line or around the perimeter of a site whose
dimensions are large with respect to the rod spacing. If the rods are distributed in a grid use Fig. 2.
For this example, we have an area of 16 000 square feet (1450 m2) and 26 rods distributed in it, so
the graph shows a multiplier of 0.056.
R = 32 x 0.056 = 1.9 ohms.
This calculation method does not consider the interconnecting cable between rods because the
effect produced by the rod on the earth resistance is more important than the one produced by 7 m of bare
cable. If the distance between rods is bigger then 7 m should be considered.
Wire resistance should be considered in parallel with the rods.
For this purpose we can use two formulas:
- Buried straight rod or wire
h = depth of burial (cm)
L = total length (cm)
r = ohm-cm
R = 0.366 r/L (log (L/d) + log (L/4h) + 0.34) h < 0.4L
- Buried circle of wire
R = 0.366 r/L (log (L/d) + log (L/4h) + 0.81) h > 0L
- Vertical rod
R = 0.366 r/L (log (3L/d)
When a vertical rod is driven through a high-resistivity superficial layer into a lower resistivity
subsoil, an adjustment can be made to the resistance to earth expression by substituting a reduced
‘effective length’ of the ground rod. Lc will be the effective length.
Lc = L – h (1 – (r2/r1)) where L is the length of the rod, r1 is the resistivity of the upper layer, r2 is
the resistivity of the subsoil, and h is the depth of the upper layer.
4 DESIGN GUIDELINES
a) Where bedrock (meaning an underground layer formed by rocks) or other obstacles prevent the
effective use of vertical rods, horizontal wires, grids, or radials should be used.
b) When other alternatives are not possible or are not cost-effective, chemical enhancement (salting) is
frequently the only choice left.
c) The nominal spacing between rods should be between one and two times the length of the rod;
however, it is necessary for a ground rod to be placed near each lightning down conductor, so
spacings should be limited to not more than 15.2 m.
d) The rods and interconnecting cable comprising the earth electrode subsystem should be positioned
between 0.6 m and 1.8 m outside the dripline of the building or structure to insure that rain, snow, and
other precipitation wets the earth around the rods.
e) Where two or more structures or facilities are located in the same general area (less than 60 m away)
and are electrically interconnected with signal, control, and monitor circuits, either provide a common
earth electrode subsystem or interconnect the separate earth electrode subsystems with two buried
bare cables.
f) To minimize voltage differentials between the two structures, the facilities should effectively share a
common earth electrode subsystem. Separate structures spaced closer than 6 m should have a common
earth electrode subsystem installed that encircles both facilities.
g) Structures or facilities having no interconnecting cables and separated by a distance greater than 60 m
generally do not require their earth electrode subsystems to be interconnected.
h) Metallic structures near the earth electrode subsystem should be connected to reduce the danger of
potential differences during lightning or fault protection; their connection will also reduce the
resistance to earth of the electrode subsystem.
i) To minimize resistance variations caused by surface drying of the soil and by the freezing of the soil
during winter, connections, interconnecting cables, and tops of ground rods should be buried at least
0.3 m below grade level and the interconnecting cable at least 0.45 m below grade level.
j) Access to the earth electrode subsystem should be provided through the installation of one or more
grounding wells at each site. Removable access covers must be provided.
k) More than one grounding well may be necessary depending upon the size of the facility, the extent of
the electrode subsystem, and the degree of accessibility to the electrodes.
l) Locate at least one of the ground wells in an area with access to open soil so that resistance checks of
the earth electrode subsystem can be made once the building is in use.
BIBLIOGRAPHY
[1] Grounding, bonding, and shielding for electronic equipments and facilities – US Department of
Defense handbook.
[2] Grounding principle and practices II – Establishing grounds, Jensen Claude.
[3] Guide de protections des reseaux industriels, Christophe Preve.