Abb Test Switch Catlogue
Abb Test Switch Catlogue
Application The COMBITEST system for testing of pro- i.e. blocking of tripping circuits, short-circuit-
tection relays is built up around the RTXP 8, ing of CT’s, opening of voltage circuits, mak-
RTXP 18 or RTXP 24 test switches. The test ing relay terminals available for secondary
switch can also be used for other testing injection.
needs not directly associated with relays,
such as for switchboards or voltmeters. The test-plug handle may be connected to any
type of test equipment or instrument. When a
The test switch may be used where testing number of protection relays of the same type
would otherwise require disconnection of the are tested, the test-plug handle need to be
instrument transformer’s secondary or control moved only from the test switch of one relay
wiring. It may also be used to advantage in to the test switch of the other, without altering
the testing of other complete relay systems, previously made connections. If different
even when each individual relay has its own types of relays are to be tested, it is a simple
test switch. matter to change the connections on the test-
plug handle and the relay testing set.
When the test-plug handle is inserted into the
test switch, preparations for testing are auto-
matically carried out in the proper sequence,
Test System COMBITEST
1MRK 512 001-BEN
Page 2
Test switch
Fig. 1 Test switch, RTXP 8
The test switch, RTXP, is built up in a light
beige housing containing a number of contact
units. The contact units are of two basic An adapter is used for mounting of the
types. One type is for trip circuits and RTXP 8 in a 4U rack assembly. This allows
designed to open first and close last when the one RX 1 terminal base to be mounted under
test handle is inserted respectively pulled out. the RTXP 8 (see Fig. 2).
The other type is used for all other circuit
functions, current, voltage and auxiliary
power. If the housing is not fully equipped
with contact units, unused space is occupied
by dummies of the same shape as the contact
units.
The test switches are available with different Fig. 2 The assembly of RTXP 8 and terminal
base RX 1 with the 4U adapter.
contact arrangements (see ordering table).
The contact units have guiding slots fitting Test switch RTXP 18
the guides of the test pins, to prevent incor- The test switch RTXP 18 contains maximum
rect insertion of the test-plug handle. The 18 contact units and occupies two seats in the
available contact arrangements and marking COMBIFLEX system with dimensions of 4U
symbols are shown in the ordering table. and 6C. It mounts rigidly to the COMBI-
FLEX apparatus bars.
Test switch RTXP 8
The test switch RTXP 8 contains eight con- The contact blocks are numbered consecu-
tacts. It occupies one seat in the COMBI- tively on the left-hand side with markings 1-
FLEX system with dimensions 2U and 6C. 18, from top to bottom. Similar markings are
arranged on the right-hand side of the contact
block for the function. As standard the con-
tact block for + is placed at the top (position
1) and the contact block for - at the bottom
(position 18) of the housing.
Test System COMBITEST
1MRK 512 001-BEN
Page 3
Fig. 3 Test switch, RTXP 18 The front of the test switch has two doors,
each with a label. The left-hand label has
The front of the test switch has a door with space for protective relay data and test speci-
two face labels having space for the test fied by the customer. On the right-hand label
device and the protection relay data. Space is the type, ordering number and symbol of the
also provided for order specific text. On the test switch are shown.
back of the door there is a label showing the
type and location of the contacts and bypass- Test-plug handle
ing bars used in the test switch. The test-plug handle, RTXH, is fitted with
banana-plug sockets for use with 4 mm
Test switch RTXP 24 banana plugs. Test leads are used to connect
The test switch RTXP 24 consists of two between the banana-plug socket on test-plug
housings screwed together with the base to handle and the relay testing set. Plugs for pos-
one unit. Each housing contains a maximum itive and negative dc auxiliary voltage main-
of 12 contact units. Further, one contact for tain circuit continuity when inserted into the
the signalling of a test under progress, is test switch. The other plugs are test plugs
located on the top right-hand housing. The which disconnect the primary circuits (con-
test switch occupies the front space of nected to the A-side of the test switch) from
3 U 12 C. the relay (connected to the B-side of the test
switch) and connect it to the test leads. To
It mounts rigidly to any standard European prevent unwanted tripping when the handle is
rack system and it can also be installed in withdrawn, latches on the handle secure it in
RHGS, RHGP and RHGX cases and in the half withdrawn position. In this position,
RHGT equipment frames. all voltages and currents are restored to the
relay and any reenergizing transients are
given a chance to decay before the trip cir-
cuits are restored. When the latches are
released, the handle can be completely with-
drawn from the test switch, restoring the trip
circuits to the relay.
Block-plug handle
The block-plug handles, RTXF 8, 18 and 24,
consist of 8, 18 and 24 test-plugs respectively,
(xx04000328.jpg) clipped together. This device completely
blocks the relay by disconnecting all circuits
Fig. 5 Test-plug handle, RTXH 24 routed through the test switch, including the
dc power supply. The signalling contact in
Test leads RTXP 24 is not activated when the block-
Red and black test leads are available in two plug handle is inserted. When the block-plug
types. One type has a cross section of handle is inserted, the door of a COMBI-
2.5 mm2 and is 2.0 m long with a 4 mm banana- FLEX equipment frame can be closed.
plug in each end. The other type has a cross sec-
tion of 1.0 mm2 and is 2.0 m long with a 10 A
COMBIFLEX terminal pin in one end and a
4 mm banana-plug in the other.
Trip-block plug
The trip-block plug, RTXB, is a short red
plug, which can open a trip-type contact only.
It cannot cause any switching action if it is
inadvertently plugged into a wrong position.
It can also be used for measurement purposes
in trip circuits. The plug is red to draw atten-
tion to the fact that blocking has been carried
out. The door of the COMBIFLEX equip- (xx04000329.jpg)
ment frame can be closed while the plug
remains inserted in the test switch. Fig. 6 Block-plug handle, RTXF 24
Test System COMBITEST
1MRK 512 001-BEN
Page 5
(xx04000330.jpg) (832008)
(xx04000331.jpg)
Contact unit for current and voltage circuits Contact unit for trip circuits
(xx04000332.jpg)
dc supply plug
2 plugs for + and – dc auxiliary
voltage supply to the test
equipment.
Not sold separately
Normal position Test position
(96000089)
(xx04000333.jpg)
Test plug
16 or 22 test-plugs, for RTXP 18
or RTXP 24 respectively, which
disconnect the relay and connect
it to the test leads.
Current testing of relay
Not sold separately
Test System COMBITEST
1MRK 512 001-BEN
Page 6
Design (cont’d)
Loose plugs:
(960000890)
(SE840538)
Trip-block plug
The trip-block plug RTXB is short and is
used separately for blocking trip circuits. Interruption or blocking of a dc circuit or for
It can also be used for measurement time measurement of trip pulses etc.
purposes in trip circuits.
(96000091)
(xx04000334.jpg)
Ammeter test-plug
The ammeter test-plug RTXM is used
separately for service current measurement
It incorporates an overvoltage protection. Load current measurement
Extension bases
The extension bases consist of a plug-in plate and a terminal base between which are connected
leads with combination pin-sockets.
(76813)
1-seat
(76812)
(76811)
2H-seat
For RXY-seats
Dimension 4U 4C
The 1-seat extension base can also be used for 2, 2H- and 4-seat relay modules, but then with
2 or 4 mounted side-by-side. The 2H seat extension base can also be used for a 4-seat relay
module.
Test System COMBITEST
1MRK 512 001-BEN
Page 7
Technical data
Test voltage 2.5 kV
Highest system voltage 600 V dc, 500 V ac
Current-carrying capacity
Test contacts:
continuous 20 A
for 1 second 500 A
Signalling contact:
continuous 10 A
for 1 second 150 A
• Type
• Quantity
• Ordering No.
• Desired wording on the face label
• Function designation symbol with location (contact position) and Symbol No. of
each one of these
Wording on the face labels:
Ordering example:
• Description
• Quantity
• Ordering No.
Contact functions
(96000092)
RTXP 8
Ordering
No.
RK 926 002 -AD -AE -AF -AG -AH
RTXP 18
(rk926115-xx)
Ordering No.
Ordering No.
RTXP 24
Ordering No.
Ordering No.
No of labels
Symbol Significance Symbol No.
on a sheet
Unmarked 1 20
+ Positive terminal 2 8
- Negative terminal 3 8
+/~ Positive terminal or ac voltage 60 1
-/~ Negative terminal or ac voltage 61 1
~ Ac voltage 71 2
IN Neutral current 8 25
I Current 10 5
Id Differential current 19 2
U Voltage 29 5
Various:
e.g. signal + outgoing blocking 65 9
Tripping 66 15
Closing 67 3
• Raise 68 1
→
→
• Lower 69 1
Accessories
Description Ordering No.
Test-plug handle
RTXH 8 RK 926 011-BE
RTXH 18 RK 926 011-BC
RTXH 24 RK 926 016-AA
Block-plug handle
RTXF 8 RK 926 007-AC
RTXF 18 RK 926 007-AB
RTXF 24 RK 926 016-AB
Extensions bases with terminal base
RX 1 RK 924 035-AA
RX 2H RK 924 035-AB
RXY 5371 069-A
Trip-block plug, RTXB RK 926 005-AC
Ammeter test-plug RTXM RK 926 006-AB
Test leads *)
2.5 mm2, length 2.0 m, banana plugs in both ends
Black 2639 0605-1
Red 2639 0605-2
Test lead 10 A COMBIFLEX *)
1.0 mm2, length 2.0 m, banana plug in one end and a 10 A pin
in the other
Black 2639 0180-B
Red 2639 0181-B
Mounting kit for RTXP 24 in 4U rack assembly 1MRK 000 020-BT
Adapter for mounting RTXP 8 in 4U rack assembly 1MRK 000 316-19
A tool box containing some of the accessories above and in addition See connection and installation
tools and parts that are useful when testing protection relays and components catalogue.
systems belonging to the COMBIFLEX family.
*) Banana plugs are touch safe according to IEC Class II