Setting Calculation Protocol For IDMT Over Current Relay

This document provides the setting calculation protocol for overcurrent and earth fault protection of a numerical relay on an outgoing feeder. It includes the feeder details, relay and CT data, fault current data, equations to calculate the time multiplier setting (TMS) to achieve a protection operating time of 0.3 seconds, and the adopted settings for TMS, high set, and coordination with upstream and downstream protection.

Uploaded by

refaate
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (4 votes)
11K views2 pages

Setting Calculation Protocol For IDMT Over Current Relay

This document provides the setting calculation protocol for overcurrent and earth fault protection of a numerical relay on an outgoing feeder. It includes the feeder details, relay and CT data, fault current data, equations to calculate the time multiplier setting (TMS) to achieve a protection operating time of 0.3 seconds, and the adopted settings for TMS, high set, and coordination with upstream and downstream protection.

Uploaded by

refaate
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Overcurrent Relay Settings


Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Ratio Prim. Current Sec. Current Burden, VA Class Rct


CT Data:
600/400/1 600 1 15 - 10 5P15 -

Fault Current, If L-L Fault L-G Fault

Fault Data: Min. Fault Current, A 11000 8100

Max. Fault Current, A 22000 16200

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Overload Current: 480 (125% of Full load current of Protected Object)

PMS (Plug Multiplier Setting): 0.8

Curve Selected: Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


2.17 sec .........Eq. 1
[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated 22.92 1.06 .........Eq. 2
Current/PMS)]
Assuming Prot. Op. time, sec:
0.3 sec
(0.3sec)
Grading Margin (0.3sec) 0 sec
Hence TMS: ('= (0.3+0) / (Result
0.139 .........Eq. 3
from Eq.1)
Final TMS set at: 0.125
Operating time at TMS 0.125, sec
0.271 sec
'=0.14*0.125/[(PSM)0.02 - 1]:
Operating time at TMS 0.2, sec
0.433 sec (for Sample)
'=0.14*0.2/[(PSM)0.02 - 1]:

PMS: 0.8

Adopted Settings: TMS: 0.125


High Set
10xIn
(I>>):
Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

42608022.xls/IDMT OC-Outgoing 1/2


ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Earth Fault Relay Settings


Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Ratio Prim. Current Sec. Current Burden, VA Class Rct


CT Data:
600/400/1 600 1 15 - 10 5P15 -

Fault Current, If L-L Fault L-G Fault

Fault Data: Min. Fault Current, A 11000 8100

Max. Fault Current, A 22000 16200

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Earth Fault Current: 0.2 (25% of OC PMS)

PMS (Plug Multiplier Setting): 0.2

Curve Selected: Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


1.59 sec .........Eq. 1
[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated 67.50 1.09 .........Eq. 2
Current/PMS)]
Assuming Prot. Op. time, sec:
0.3 sec
(0.3sec)
Grading Margin (0.3sec) 0 sec
Hence TMS: ('= (0.3+0) / (Result
0.188 .........Eq. 3
from Eq.1)
Final TMS set at: 0.2
Operating time at TMS 0.2, sec
0.319 sec
'=0.14*0.2/[(PSM)0.02 - 1]:

PMS: 0.2

Adopted Settings: TMS: 0.2


High Set
8xIn
(I0>>):
Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

42608022.xls/IDMT EF-Outgoing 2/2