Dali Schematics

The document is a schematic diagram of a DALI lighting control system. It shows a DALI network powered by a DALI power supply and connected to up to 64 light fittings addressed from 00 to 07. It also shows optional connections for sensors, wallplates and an Ethernet controller to monitor and control the system.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views7 pages

Dali Schematics

The document is a schematic diagram of a DALI lighting control system. It shows a DALI network powered by a DALI power supply and connected to up to 64 light fittings addressed from 00 to 07. It also shows optional connections for sensors, wallplates and an Ethernet controller to monitor and control the system.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

MAX. 64 ADDRESSES PER DALI LOOP, MAX.

300m

DALI POWER SUPPLY P


250mA MAX S
DALI-01

00 01 02 03 04 05 06 07 DALI LIGHT FITTINGS


11 12 1
10 2
9
8 4
3 PE
7 6 5

OPTIONAL ETHERNET DALI LIGHT SENSOR DALI OCCUPANCY SENSOR


CONTROLLER/GATEWAY
WITH RTC AND I/O.

DALI WALLPLATE DALI WALLPLATE

NOTES:
DALI IS AN INTERNATIONAL STANDARD LIGHTING CONTROL SYSTEM. THE SCHEMATIC DIAGRAM SHOWS A DALI NETWORK (DALI-01) POWERED BY A DALI POWER SUPPLY.
THE 8 LIGHT FITTINGS (ADDRESSED FROM 00 TO 07) CAN BE ANY LIGHT FITTING FROM ANY MANUFACTURER FITTED WITH A DALI ECG (ELECTRONIC CONTROL GEAR).
DALI ECGS ARE AVAILABLE FOR FL AND CFL LAMPS, DISCHARGE LAMPS, LOW VOLTAGE HALOGEN LAMPS, INCANDESCENT LAMPS, LEDs, EMERGENCY LIGHTS ET C.
THE LIGHT FITTINGS ARE CONTROLLED BY DALI ECDs (ELECTRONIC CONTROL DEVICES) SUCH AS DALI WALLPLATES AND DALI SENSORS FROM ANY MANUFACTURER
INCLUDING DALI CONTROL'S DC100 SERIES OF DALI CONTROL DEVICES.

DALI CAN ALSO CONTROL LEGACY LIGHT FITTINGS INCLUDING FIXED OUTPUT, ANALOG 1 TO 10V AND DSI DIMMABLE FITTINGS. REFER TO DRAWING DALI-1014.

Simple DALI Room Control Schematic


www.dalicontrol.com
DRG NO: DALI-1011 DATE: 30-JUN-2007 REV NO: B
MAX. 64 ADDRESSES PER DALI LOOP. MAX 300m.

DALI POWER SUPPLY P


250mA MAX S
DALI-01

DALI-
00 01 02 03 04 AC 05 EXIT 63

DALI EMG (06)

PE PE

OCCUPANCY &/OR
LIGHT SENSOR
WALLPLATE & SENSORS WALLPLATE
11 12 1
10 2
TO RISER OR HUB 9
8 4
3

FOR OPTIONAL COMPUTER ETHERNET 7 6 5

MONITORING AND CONTROL TO SECURITY OR ACCESS CONTROL PANEL


BM2500-DALI CONTROLLER/
GATEWAY WITH RTC AND I/O.

DALI POWER SUPPLY P


250mA MAX S
DALI-02

00 EXIT 01 02 03 04 63

DALI EMG (60) DALI EMG (61)

DALI SENSOR

DALI WALLPLATE

NOTES:
THE BM2500-DALI CONTROLLER/GATEWAY MANAGES TWO DALI NETWORKS. THE CONTROLLER INCLUDES SCHEDULING, 16 INPUTS, 2 OUTPUTS AND AN RJ45 ETHERNET NETWORK
SOCKET FOR COMPUTER MONITORING AND CONTROL.
INPUTS ON THE BM2500-DALI CAN BE USED FOR WALLPLATES, SENSORS AND INTERFACING TO SECURITY AND ACCESS CONTROL PANELS ETC.
EACH DALI NETWORK REQUIRES A DALI-PS POWER SUPPLY AND A DALI INTERFACE.
THE DALI-AC AREA CONTROLLER CONTROLS A DALI GROUP BASED ON INPUTS FROM STANDARD SWITCHES AND SENSORS.

Floor Control Schematic


www.dalicontrol.com
DRG NO: DALI-1012 DATE: 30-JUN-2007 REV NO: C
RISER TO HIGHER FLOORS

MAX. 64 ADDRESSES PER DALI LOOP, 00 TO 63 MAX. 64 ADDRESSES PER DALI LOOP, 00 TO 63

DALI-11 DALI-13
00 01 02 EXIT 03 63 00 01 02 EXIT 03 63

PE PE

WALLPLATE & SENSORS WALLPLATE & SENSORS

11 12 1 11 12 1
10 2 10 2
BM2500-DALI 9
8 4
3 9
8 4
3 BM2500-DALI
7 6 5 7 6 5

TO MASTER OVERRIDE SWITCH

TO SECURITY/ACCESS CONTROL PANEL SWITCHBOARD

DALI-12 DALI-14
00 01 02 63 00 01 02 DALI- 63
EXIT 03 EXIT 03
AC
DALI EMG (61)
DALI SENSOR
PE

DALI WALLPLATE
DALI AREA CONTROLLER
WITH WALLPLATE & SENSORS

ETHERNET

RISER TO LOWER FLOORS

NOTES:
THE BM2500-DALI NETWORK CONTROLLER/GATEWAY MANAGES TWO DALI NETWORKS AND INCLUDES SCHEDULING, 16 INPUTS, 2 OUTPUTS AND AN RJ45 ETHERNET SOCKET FOR COMPUTER
MONITORING AND CONTROL. THE SWITCHBOARD CONTAINS BM2500-DALI CONTROLLER/GATEWAYS, DALI POWER SUPPLIES AND DALI INTERFACES.

Building Control Schematic


www.dalicontrol.com
DRG NO: DALI-1013 DATE: 30-JUN-2007 REV NO: B
MAX. 64 ADDRESSES PER DALI LOOP, MAX. 300m

DALI POWER SUPPLY P


250mA MAX S
DALI-02

01 02 EXIT

10
11 12 1
2
DALI EMG (04) DALI EMG (06)
9
8 4
3 PE
7 6 5

OPTIONAL ETHERNET DALI LIGHT SENSOR DALI SENSOR


CONTROLLER/GATEWAY
WITH RTC AND I/O..

DALI WALLPLATE DALI WALLPLATE

D/A DALI D/A MODULE


DALI RELAY MODULE RM DSI DALI DSI MODULE
00 1 to 10V 03 05

DIMMABLE ANALOG CHANNEL 1 TO 10V FIXED OUTPUT DIMMABLE DSI CHANNEL


CHANNEL

NOTES:
THE SCHEMATIC DIAGRAM SHOWS A DALI NETWORK (DALI-02) POWERED BY A DALI POWER SUPPLY.
THE DALI NETWORK INCLUDES 7 ADDRESSED DEVICES (00 TO 06) CONSISTING OF DALI LIGHT FITTINGS (01, 02), MONITORED DALI EMERGENCY FITTINGS (04, 06) AND DALI
MODULES (00, 03, 05) TO CONTROL HARD-WIRED CHANNELS OF LEGACY LIGHT FITTINGS.

A SINGLE DALI NETWORK CAN BE USED TO CONTROL UP TO 64 CHANNELS OF LEGACY FITTING S.

THE LIGHT FITTINGS ARE CONTROLLED BY DALI ECDs (ELECTRONIC CONTROL DEVICES) SUCH AS DALI WALLPLATES AND DALI SENSORS FROM ANY MANUFACTURER
INCLUDING DALI CONTROL'S DC100 SERIES OF DALI CONTROL DEVICES.

Legacy Fittings Control Schematic


www.dalicontrol.com
DRG NO: DALI-1014 DATE: 30-JUN-2007 REV NO: A
RISER TO CONTROL ROOM SWITCHBOARD DALI NETWORKS

DALI
-PS
NOTES:
THE BM2500-DALI NETWORK 00 01 02 EXIT 63 DALI-01
CONTROLLER/GATEWAY MANAGES
TWO DALI NETWORKS. EACH DALI-IF
BM2500-
WALLPLATE
BM2500-DALI INCLUDES DALI
DALI-IF
SCHEDULING, 16 INPUTS, 2 OUTPUTS
AND AN RJ45 ETHERNET SOCKET
FOR COMPUTER MONITORING AND
DALI
CONTROL. -PS

EACH DALI NETWORK REQUIRES A 00 01 02 EXIT 63 DALI-02


DALI-PS POWER SUPPLY AND A ETHERNET
SWITCH
DALI-IF INTERFACE. WALLPLATE

POWER SUPPLIES FOR THE BM2500-


DALI, AND ETHERNET SWITCH ARE DALI
-PS
NOT SHOWN IN THE SCHEMATIC
DIAGRAM. REFER TO WIRING 00 01 02 EXIT 63 DALI-03
DIAGRAMS FOR FULL DETAILS.
DALI-IF
BM2500-
BASE FITOUT WALLPLATE
DALI
DALI-IF
THE DIAGRAM SHOWS WALLPLATES
FOR A BAREBONES BASE FITOUT.
THE BM2500-DALI CONTROLLER/
GATEWAY IS PRECONFIGURED FOR DALI
-PS
AN 8-GANG WALLPLATE TO
CONTROL 8-GROUPS PER DALI 00 01 02 EXIT 63 DALI-04
NETWORK.
WALLPLATE
TENANCY FITOUT
FOR A TENANCY FITOUT THE
SYSTEM WOULD INCLUDE LIGHT DALI
FITTINGS, EMERGEMCY FITTINGS -PS
AND WALLPLATES AND SENSORS TO 00 01 02 EXIT 63 DALI-05
SUIT THE INSTALLATION.
DALI-IF
BM2500-
WALLPLATE
DALI
DALI-IF

DALI
-PS

00 01 02 EXIT 63 DALI-06

WALLPLATE

Typical Switchboard Schematic


www.dalicontrol.com
DRG NO: DALI-1015 DATE: 30-JUN-2007 REV NO: B
Any computer on the network can
be used to administer the system BUILDING
MONITOR ETHERNET
or to control llighting.
SWITCH
H G F E D C B A
D ETCE L ES
ENI L- NO

DB-6-1 DB-6-2 DB-6-3


LEVEL 6 BM-DALI BM-DALI BM-DALI
CONTROLLERS CONTROLLERS CONTROLLERS

DALI-6-1 DALI-6-3 DALI-6-5 DALI-6-7 DALI-6-8 DALI-6-10

DALI-6-2 DALI-6-4 DALI-6-6 DALI-6-9 DALI-6-11


RISER
CAT5E CABLE

DB-5-1 DB-5-2 DB-5-3 DB-5-4


LEVEL 5 BM-DALI BM-DALI BM-DALI BM-DALI
CONTROLLERS CONTROLLERS CONTROLLERS CONTROLLERS

DALI-5-1 DALI-5-3 DALI-5-5 DALI-5-7 DALI-5-8 DALI-5-11 DALI-5-14 DALI-5-17

DALI-5-2 DALI-5-4 DALI-5-6 DALI-5-9 DALI-5-12 DALI-5-15 DALI-5-18

DALI-5-10 DALI-5-13 DALI-5-16 DALI-5-19

DB-4-1 DB-4-2 DB-4-3


LEVEL 4 BM-DALI BM-DALI BM-DALI
CONTROLLERS CONTROLLERS CONTROLLERS

TO NEXT LEVEL
DALI-4-1 DALI-4-3 DALI-4-5 DALI-4-7 DALI-4-8 DALI-4-11

DALI-4-2 DALI-4-4 DALI-4-6 DALI-4-9 DALI-4-12

DALI-4-10

DALI Control Communications Overview


www.dalicontrol.com
DRG NO: DALI-1016 DATE: 14-NOV-2007 REV NO:
MAX. 64 ADDRESSES PER DALI LOOP, MAX. 300m

DALI POWER SUPPLY P


250mA MAX S
DALI-01

11 12 1
10 2
9 3
8 4
7 6 5

BM2500-DALI ETHERNET DALI SENSOR DALI SENSOR DALI SENSOR DALI SENSOR
CONTROLLER/GATEWAY
WITH RTC AND I/O.

DALI WALLPLATE DALI WALLPLATE DALI WALLPLATE DALI WALLPLATE

DALI DSI MODULE DSI-II DALI DSI MODULE DSI-II


2-CHANNELS 01 02 2-CHANNELS 05 06

DSI-II
03 04

DIMMABLE DSI CHANNEL DIMMABLE DSI CHANNEL DIMMABLE DSI CHANNEL DIMMABLE DSI CHANNEL

DIMMABLE DSI CHANNEL DIMMABLE DSI CHANNEL

NOTES:
THE SCHEMATIC DIAGRAM SHOWS A DALI NETWORK (DALI-01) POWERED BY A DALI POWER SUPPLY.
THE DALI NETWORK INCLUDES 6 ADDRESSED CHANNELS OF DSI LIGHT FITTING (01 TO 06).

A SINGLE DALI NETWORK CAN BE USED TO CONTROL UP TO 64 CHANNELS OF DSI FITTINGS.

THE LIGHT FITTINGS ARE CONTROLLED BY DALI ECDs (ELECTRONIC CONTROL DEVICES) SUCH AS WALLPLATES AND SENSORS AND DALI CONTROL'S BM-DALI SERIES OF
CONTROLLER/GATEWAYS.

DALI/DSI Control Schematic


www.dalicontrol.com
DRG NO: DALI-1017 DATE: 30-JUN-2007 REV NO: A