Introduction
This memo defines a portion of the Management Information Base (MIB)
for use with network management protocols in the Internet community.
In particular, it defines objects for managing uninterruptible power
supply (UPS) systems.
Case
[Page 1]
UPS MIB
RFC 1628
2.
May 1994
RFC 1442 which defines the SMI, the mechanisms used for
describing and naming objects for the purpose of management.
STD 17, RFC 1213 defines MIB-II, the core set of managed
objects for the Internet suite of protocols.
RFC 1448 which defines the protocol used for network access
to managed objects.
Object Definitions
Overview
This document defines the managed objects for Uninterruptible Power
Supplies which are to be manageable via the Simple Network Management
Protocol (SNMP).
Case
[Page 2]
UPS MIB
RFC 1628
4.
May 1994
Definitions
UPS-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
OBJECT-IDENTITY, Counter32, Gauge32, Integer32
FROM SNMPv2-SMI
DisplayString, TimeStamp, TimeInterval, TestAndIncr,
AutonomousType
FROM SNMPv2-TC
MODULE-COMPLIANCE, OBJECT-GROUP
FROM SNMPv2-CONF;
upsMIB MODULE-IDENTITY
LAST-UPDATED "9402230000Z"
ORGANIZATION "IETF UPS MIB Working Group"
CONTACT-INFO
"
Jeffrey D. Case
Postal: SNMP Research, Incorporated
3001 Kimberlin Heights Road
Knoxville, TN 37920
US
Tel: +1 615 573 1434
Fax: +1 615 573 9197
E-mail: [email protected]"
DESCRIPTION
"The MIB module to describe Uninterruptible Power
Supplies."
::= { mib-2 33 }
PositiveInteger ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS
current
DESCRIPTION
"This data type is a non-zero and non-negative value."
SYNTAX
INTEGER (1..2147483647)
NonNegativeInteger ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS
current
DESCRIPTION
"This data type is a non-negative value."
SYNTAX
INTEGER (0..2147483647)
Case
[Page 3]
RFC 1628
upsObjects
UPS MIB
May 1994
upsIdentManufacturer OBJECT-TYPE
SYNTAX
DisplayString (SIZE (0..31))
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The name of the UPS manufacturer."
::= { upsIdent 1 }
upsIdentModel OBJECT-TYPE
SYNTAX
DisplayString (SIZE (0..63))
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The UPS Model designation."
::= { upsIdent 2 }
upsIdentUPSSoftwareVersion OBJECT-TYPE
SYNTAX
DisplayString (SIZE (0..63))
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The UPS firmware/software version(s). This variable
may or may not have the same value as
upsIdentAgentSoftwareVersion in some implementations."
::= { upsIdent 3 }
upsIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX
DisplayString (SIZE (0..63))
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The UPS agent software version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations."
::= { upsIdent 4 }
Case
[Page 4]
RFC 1628
UPS MIB
upsIdentName OBJECT-TYPE
SYNTAX
DisplayString (SIZE(0..63))
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"A string identifying the UPS.
set by the administrator."
::= { upsIdent 5 }
May 1994
upsIdentAttachedDevices OBJECT-TYPE
SYNTAX
DisplayString (SIZE(0..63))
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator."
::= { upsIdent 6 }
upsBatteryStatus OBJECT-TYPE
SYNTAX
INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The indication of the capacity remaining in the UPS
systems batteries.
A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output)."
::= { upsBattery 1 }
Case
[Page 5]
RFC 1628
UPS MIB
May 1994
upsSecondsOnBattery OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"seconds"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power."
::= { upsBattery 2 }
upsEstimatedMinutesRemaining OBJECT-TYPE
SYNTAX
PositiveInteger
UNITS
"minutes"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off."
::= { upsBattery 3 }
upsEstimatedChargeRemaining OBJECT-TYPE
SYNTAX
INTEGER (0..100)
UNITS
"percent"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"An estimate of the battery charge remaining expressed
as a percent of full charge."
::= { upsBattery 4 }
upsBatteryVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 Volt DC"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The magnitude of the present battery voltage."
::= { upsBattery 5 }
upsBatteryCurrent OBJECT-TYPE
SYNTAX
Integer32
UNITS
"0.1 Amp DC"
MAX-ACCESS read-only
Case
[Page 6]
RFC 1628
UPS MIB
May 1994
STATUS
current
DESCRIPTION
"The present battery current."
::= { upsBattery 6 }
upsBatteryTemperature OBJECT-TYPE
SYNTAX
Integer32
UNITS
"degrees Centigrade"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The ambient temperature at or near the UPS Battery
casing."
::= { upsBattery 7 }
upsInputLineBads OBJECT-TYPE
SYNTAX
Counter32
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"A count of the number of times the input entered an
out-of-tolerance condition as defined by the
manufacturer. This count is incremented by one each
time the input transitions from zero out-of-tolerance
lines to one or more input lines out-of-tolerance."
::= { upsInput 1 }
upsInputNumLines OBJECT-TYPE
SYNTAX
NonNegativeInteger
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The number of input lines utilized in this device.
This variable indicates the number of rows in the
input table."
::= { upsInput 2 }
upsInputTable OBJECT-TYPE
SYNTAX
SEQUENCE OF UpsInputEntry
MAX-ACCESS not-accessible
Case
[Page 7]
RFC 1628
UPS MIB
May 1994
STATUS
current
DESCRIPTION
"A list of input table entries. The number of entries
is given by the value of upsInputNumLines."
::= { upsInput 3 }
upsInputEntry OBJECT-TYPE
SYNTAX
UpsInputEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"An entry containing information applicable to a
particular input line."
INDEX { upsInputLineIndex }
::= { upsInputTable 1 }
UpsInputEntry ::= SEQUENCE {
upsInputLineIndex
PositiveInteger,
upsInputFrequency
NonNegativeInteger,
upsInputVoltage
NonNegativeInteger,
upsInputCurrent
NonNegativeInteger,
upsInputTruePower
NonNegativeInteger
}
upsInputLineIndex OBJECT-TYPE
SYNTAX
PositiveInteger
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"The input line identifier."
::= { upsInputEntry 1 }
upsInputFrequency OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 Hertz"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present input frequency."
::= { upsInputEntry 2 }
upsInputVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The magnitude of the present input voltage."
Case
[Page 8]
UPS MIB
RFC 1628
May 1994
::= { upsInputEntry 3 }
upsInputCurrent OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 RMS Amp"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The magnitude of the present input current."
::= { upsInputEntry 4 }
upsInputTruePower OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"Watts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The magnitude of the present input true power."
::= { upsInputEntry 5 }
upsOutputSource OBJECT-TYPE
SYNTAX
INTEGER {
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7)
}
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker."
::= { upsOutput 1 }
upsOutputFrequency OBJECT-TYPE
SYNTAX
NonNegativeInteger
Case
[Page 9]
RFC 1628
UPS MIB
May 1994
UNITS
"0.1 Hertz"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present output frequency."
::= { upsOutput 2 }
upsOutputNumLines OBJECT-TYPE
SYNTAX
NonNegativeInteger
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table."
::= { upsOutput 3 }
upsOutputTable OBJECT-TYPE
SYNTAX
SEQUENCE OF UpsOutputEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"A list of output table entries. The number of
entries is given by the value of upsOutputNumLines."
::= { upsOutput 4 }
upsOutputEntry OBJECT-TYPE
SYNTAX
UpsOutputEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"An entry containing information applicable to a
particular output line."
INDEX { upsOutputLineIndex }
::= { upsOutputTable 1 }
UpsOutputEntry ::= SEQUENCE {
upsOutputLineIndex
PositiveInteger,
upsOutputVoltage
NonNegativeInteger,
upsOutputCurrent
NonNegativeInteger,
upsOutputPower
NonNegativeInteger,
upsOutputPercentLoad INTEGER
}
upsOutputLineIndex OBJECT-TYPE
SYNTAX
PositiveInteger
MAX-ACCESS not-accessible
STATUS
current
Case
[Page 10]
RFC 1628
UPS MIB
May 1994
DESCRIPTION
"The output line identifier."
::= { upsOutputEntry 1 }
upsOutputVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present output voltage."
::= { upsOutputEntry 2 }
upsOutputCurrent OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 RMS Amp"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present output current."
::= { upsOutputEntry 3 }
upsOutputPower OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"Watts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present output true power."
::= { upsOutputEntry 4 }
upsOutputPercentLoad OBJECT-TYPE
SYNTAX
INTEGER (0..200)
UNITS
"percent"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA."
::= { upsOutputEntry 5 }
Case
[Page 11]
RFC 1628
UPS MIB
May 1994
upsBypassFrequency OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 Hertz"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present bypass frequency."
::= { upsBypass 1 }
upsBypassNumLines OBJECT-TYPE
SYNTAX
NonNegativeInteger
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The number of bypass lines utilized in this device.
This entry indicates the number of rows in the bypass
table."
::= { upsBypass 2 }
upsBypassTable OBJECT-TYPE
SYNTAX
SEQUENCE OF UpsBypassEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"A list of bypass table entries. The number of
entries is given by the value of upsBypassNumLines."
::= { upsBypass 3 }
upsBypassEntry OBJECT-TYPE
SYNTAX
UpsBypassEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"An entry containing information applicable to a
particular bypass input."
INDEX { upsBypassLineIndex }
::= { upsBypassTable 1 }
UpsBypassEntry ::= SEQUENCE {
upsBypassLineIndex PositiveInteger,
upsBypassVoltage
NonNegativeInteger,
upsBypassCurrent
NonNegativeInteger,
Case
[Page 12]
UPS MIB
RFC 1628
upsBypassPower
May 1994
NonNegativeInteger
}
upsBypassLineIndex OBJECT-TYPE
SYNTAX
PositiveInteger
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"The bypass line identifier."
::= { upsBypassEntry 1 }
upsBypassVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present bypass voltage."
::= { upsBypassEntry 2 }
upsBypassCurrent OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 RMS Amp"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present bypass current."
::= { upsBypassEntry 3 }
upsBypassPower OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"Watts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The present true power conveyed by the bypass."
::= { upsBypassEntry 4 }
upsAlarmsPresent OBJECT-TYPE
SYNTAX
Gauge32
MAX-ACCESS read-only
Case
[Page 13]
RFC 1628
UPS MIB
May 1994
STATUS
current
DESCRIPTION
"The present number of active alarm conditions."
::= { upsAlarm 1 }
upsAlarmTable OBJECT-TYPE
SYNTAX
SEQUENCE OF UpsAlarmEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent."
::= { upsAlarm 2 }
upsAlarmEntry OBJECT-TYPE
SYNTAX
UpsAlarmEntry
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"An entry containing information applicable to a
Case
[Page 14]
RFC 1628
UPS MIB
May 1994
particular alarm."
INDEX { upsAlarmId }
::= { upsAlarmTable 1 }
UpsAlarmEntry ::= SEQUENCE {
upsAlarmId
PositiveInteger,
upsAlarmDescr
AutonomousType,
upsAlarmTime
TimeStamp
}
upsAlarmId OBJECT-TYPE
SYNTAX
PositiveInteger
MAX-ACCESS not-accessible
STATUS
current
DESCRIPTION
"A unique identifier for an alarm condition.
value must remain constant."
::= { upsAlarmEntry 1 }
This
upsAlarmDescr OBJECT-TYPE
SYNTAX
AutonomousType
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition."
::= { upsAlarmEntry 2 }
upsAlarmTime OBJECT-TYPE
SYNTAX
TimeStamp
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal
0."
::= { upsAlarmEntry 3 }
Case
[Page 15]
RFC 1628
UPS MIB
May 1994
upsAlarmBatteryBad OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"One or more batteries have been determined to require
replacement."
::= { upsWellKnownAlarms 1 }
upsAlarmOnBattery OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The UPS is drawing power from the batteries."
::= { upsWellKnownAlarms 2 }
upsAlarmLowBattery OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The remaining battery run-time is less than or equal
to upsConfigLowBattTime."
::= { upsWellKnownAlarms 3 }
upsAlarmDepletedBattery OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The UPS will be unable to sustain the present load
when and if the utility power is lost."
::= { upsWellKnownAlarms 4 }
upsAlarmTempBad OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"A temperature is out of tolerance."
::= { upsWellKnownAlarms 5 }
upsAlarmInputBad OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"An input condition is out of tolerance."
::= { upsWellKnownAlarms 6 }
upsAlarmOutputBad OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"An output condition (other than OutputOverload) is
out of tolerance."
::= { upsWellKnownAlarms 7 }
upsAlarmOutputOverload OBJECT-IDENTITY
Case
[Page 16]
RFC 1628
UPS MIB
May 1994
STATUS
current
DESCRIPTION
"The output load exceeds the UPS output capacity."
::= { upsWellKnownAlarms 8 }
upsAlarmOnBypass OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The Bypass is presently engaged on the UPS."
::= { upsWellKnownAlarms 9 }
upsAlarmBypassBad OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The Bypass is out of tolerance."
::= { upsWellKnownAlarms 10 }
upsAlarmOutputOffAsRequested OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The UPS has shutdown as requested, i.e., the output
is off."
::= { upsWellKnownAlarms 11 }
upsAlarmUpsOffAsRequested OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The entire UPS has shutdown as commanded."
::= { upsWellKnownAlarms 12 }
upsAlarmChargerFailed OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"An uncorrected problem has been detected within the
UPS charger subsystem."
::= { upsWellKnownAlarms 13 }
upsAlarmUpsOutputOff OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The output of the UPS is in the off state."
::= { upsWellKnownAlarms 14 }
upsAlarmUpsSystemOff OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The UPS system is in the off state."
::= { upsWellKnownAlarms 15 }
Case
[Page 17]
RFC 1628
UPS MIB
May 1994
upsAlarmFanFailure OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The failure of one or more fans in the UPS has been
detected."
::= { upsWellKnownAlarms 16 }
upsAlarmFuseFailure OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The failure of one or more fuses has been detected."
::= { upsWellKnownAlarms 17 }
upsAlarmGeneralFault OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"A general fault in the UPS has been detected."
::= { upsWellKnownAlarms 18 }
upsAlarmDiagnosticTestFailed OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The result of the last diagnostic test indicates a
failure."
::= { upsWellKnownAlarms 19 }
upsAlarmCommunicationsLost OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"A problem has been encountered in the communications
between the agent and the UPS."
::= { upsWellKnownAlarms 20 }
upsAlarmAwaitingPower OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The UPS output is off and the UPS is awaiting the
return of input power."
::= { upsWellKnownAlarms 21 }
upsAlarmShutdownPending OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"A upsShutdownAfterDelay countdown is underway."
::= { upsWellKnownAlarms 22 }
upsAlarmShutdownImminent OBJECT-IDENTITY
STATUS
current
Case
[Page 18]
UPS MIB
RFC 1628
May 1994
DESCRIPTION
"The UPS will turn off power to the load in less than
5 seconds; this may be either a timed shutdown or a
low battery shutdown."
::= { upsWellKnownAlarms 23 }
upsAlarmTestInProgress OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"A test is in progress, as initiated and indicated by
the Test Group. Tests initiated via other
implementation-specific mechanisms can indicate the
presence of the testing in the alarm table, if
desired, via a OBJECT-IDENTITY macro in the MIB
document specific to that implementation and are
outside the scope of this OBJECT-IDENTITY."
::= { upsWellKnownAlarms 24 }
upsTestId OBJECT-TYPE
SYNTAX
OBJECT IDENTIFIER
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The test is named by an OBJECT IDENTIFIER which
allows a standard mechanism for the initiation of
tests, including the well known tests identified in
this document as well as those introduced by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device.
Setting this variable initiates the named test. Sets
to this variable require the presence of
upsTestSpinLock in the same SNMP message.
The set request will be rejected with an appropriate
error message if the requested test cannot be
performed, including attempts to start a test when
another test is already in progress. The status of
the current or last test is maintained in
upsTestResultsSummary. Tests in progress may be
aborted by setting the upsTestId variable to
Case
[Page 19]
RFC 1628
UPS MIB
May 1994
upsTestAbortTestInProgress.
Read operations return the value of the name of the
test in progress if a test is in progress or the name
of the last test performed if no test is in progress,
unless no test has been run, in which case the well
known value upsTestNoTestsInitiated is returned."
::= { upsTest 1 }
-- see [6] for more information on the semantics of objects with
-- syntax of TestAndIncr
upsTestSpinLock OBJECT-TYPE
SYNTAX
TestAndIncr
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"A spin lock on the test subsystem.
used as follows.
The spinlock is
Case
[Page 20]
RFC 1628
UPS MIB
May 1994
upsTestResultsSummary */
get (upsTestSpinLock, upsTestResultsSummary,
upsTestResultsDetail)
while (upsTestResultsSummary == inProgress) {
short delay
get (upsTestSpinLock, upsTestResultsSummary,
upsTestResultsDetail)
}
/* when test completes, retrieve any additional
test results */
/* if upsTestSpinLock == lock_value + 1, then
these are our test */
/* results (as opposed to another managers */
The initial value of upsTestSpinLock at agent
initialization shall
be 1."
::= { upsTest 2 }
upsTestResultsSummary OBJECT-TYPE
SYNTAX
INTEGER {
donePass(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The results of the current or last UPS diagnostics
test performed. The values for donePass(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for nonvolatile storage of test results."
::= { upsTest 3 }
upsTestResultsDetail OBJECT-TYPE
SYNTAX
DisplayString (SIZE (0..255))
Case
[Page 21]
RFC 1628
UPS MIB
May 1994
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"Additional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned."
::= { upsTest 4 }
upsTestStartTime OBJECT-TYPE
SYNTAX
TimeStamp
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The value of sysUpTime at the
progress was initiated, or, if
the time the previous test was
value of upsTestResultsSummary
upsTestStartTime has the value
::= { upsTest 5 }
upsTestElapsedTime OBJECT-TYPE
SYNTAX
TimeInterval
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The amount of time, in TimeTicks, since the test in
progress was initiated, or, if no test is in progress,
the previous test took to complete. If the value of
upsTestResultsSummary is noTestsInitiated(6),
upsTestElapsedTime has the value 0."
::= { upsTest 6 }
--- Well known tests.
-upsWellKnownTests
upsTestNoTestsInitiated OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"No tests have been initiated and no test is in
progress."
::= { upsWellKnownTests 1 }
upsTestAbortTestInProgress OBJECT-IDENTITY
STATUS
current
Case
[Page 22]
RFC 1628
UPS MIB
May 1994
DESCRIPTION
"The test in progress is to be aborted / the test in
progress was aborted."
::= { upsWellKnownTests 2 }
upsTestGeneralSystemsTest OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The manufacturers standard test of UPS device
systems."
::= { upsWellKnownTests 3 }
upsTestQuickBatteryTest OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"A test that is sufficient to determine if the battery
needs replacement."
::= { upsWellKnownTests 4 }
upsTestDeepBatteryCalibration OBJECT-IDENTITY
STATUS
current
DESCRIPTION
"The system is placed on battery to a discharge level,
set by the manufacturer, sufficient to determine
battery replacement and battery run-time with a high
degree of confidence. WARNING: this test will leave
the battery in a low charge state and will require
time for recharging to a level sufficient to provide
normal battery duration for the protected load."
::= { upsWellKnownTests 5 }
upsShutdownType OBJECT-TYPE
SYNTAX
INTEGER {
output(1),
system(2)
}
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"This object determines the nature of the action to be
taken at the time when the countdown of the
Case
[Page 23]
RFC 1628
UPS MIB
May 1994
Case
[Page 24]
RFC 1628
UPS MIB
May 1994
Case
[Page 25]
UPS MIB
RFC 1628
May 1994
upsConfigInputVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2."
::= { upsConfig 1 }
upsConfigInputFreq OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 Hertz"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsConfig 2 }
Case
[Page 26]
RFC 1628
UPS MIB
May 1994
upsConfigOutputVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2."
::= { upsConfig 3 }
upsConfigOutputFreq OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"0.1 Hertz"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsConfig 4 }
upsConfigOutputVA OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"Volt-Amps"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The magnitude of the nominal Volt-Amp rating."
::= { upsConfig 5 }
upsConfigOutputPower OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"Watts"
MAX-ACCESS read-only
STATUS
current
DESCRIPTION
"The magnitude of the nominal true power rating."
::= { upsConfig 6 }
upsConfigLowBattTime OBJECT-TYPE
Case
[Page 27]
RFC 1628
UPS MIB
May 1994
SYNTAX
NonNegativeInteger
UNITS
"minutes"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round up to the next supported value. If
the requested value is larger than the largest
supported value, then the largest supported value
shall be selected."
::= { upsConfig 7 }
upsConfigAudibleStatus OBJECT-TYPE
SYNTAX
INTEGER {
disabled(1),
enabled(2),
muted(3)
}
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The requested state of the audible alarm. When in
the disabled state, the audible alarm should never
sound. The enabled state is self-describing. Setting
this object to muted(3) when the audible alarm is
sounding shall temporarily silence the alarm. It will
remain muted until it would normally stop sounding and
the value returned for read operations during this
period shall equal muted(3). At the end of this
period, the value shall revert to enabled(2). Writes
of the value muted(3) when the audible alarm is not
sounding shall be accepted but otherwise shall have no
effect."
::= { upsConfig 8 }
upsConfigLowVoltageTransferPoint OBJECT-TYPE
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The minimum input line voltage allowed before the UPS
system transfers to battery backup."
::= { upsConfig 9 }
upsConfigHighVoltageTransferPoint OBJECT-TYPE
Case
[Page 28]
RFC 1628
UPS MIB
May 1994
SYNTAX
NonNegativeInteger
UNITS
"RMS Volts"
MAX-ACCESS read-write
STATUS
current
DESCRIPTION
"The maximum line voltage allowed before the UPS
system transfers to battery backup."
::= { upsConfig 10 }
upsTrapOnBattery NOTIFICATION-TYPE
OBJECTS { upsEstimatedMinutesRemaining, upsSecondsOnBattery,
upsConfigLowBattTime }
STATUS current
DESCRIPTION
"The UPS is operating on battery power. This trap is
persistent and is resent at one minute intervals until
the UPS either turns off or is no longer running on
battery."
::= { upsTraps 1 }
upsTrapTestCompleted NOTIFICATION-TYPE
OBJECTS { upsTestId, upsTestSpinLock,
upsTestResultsSummary, upsTestResultsDetail,
upsTestStartTime, upsTestElapsedTime }
STATUS current
DESCRIPTION
"This trap is sent upon completion of a UPS diagnostic
test."
::= { upsTraps 2 }
upsTrapAlarmEntryAdded NOTIFICATION-TYPE
OBJECTS { upsAlarmId, upsAlarmDescr }
STATUS current
DESCRIPTION
"This trap is sent each time an alarm is inserted into
to the alarm table. It is sent on the insertion of
Case
[Page 29]
UPS MIB
RFC 1628
May 1994
Case
upsAlarmDescr
[Page 30]
RFC 1628
UPS MIB
May 1994
DESCRIPTION
"Support of all well known alarm types is not
required. The well known alarm types which must be
supported are: upsAlarmOnBattery, upsAlarmLowBattery,
upsAlarmInputBad, upsAlarmUpsOutputOff,
upsAlarmUpsSystemOff, and upsAlarmTestInProgress."
OBJECT
upsOutputSource
SYNTAX
INTEGER {
normal(2),
battery(4)
}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4),
booster(6) and reducer(7) is not required."
OBJECT
upsShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one shutdown type."
OBJECT
upsAutoRestart
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one restart type."
OBJECT
upsConfigInputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigInputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigOutputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigOutputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
Case
[Page 31]
UPS MIB
RFC 1628
May 1994
::= { upsCompliances 1 }
upsBasicCompliance MODULE-COMPLIANCE
STATUS
current
DESCRIPTION
"The compliance statement for UPSs that support
full-featured functions, such as control."
MODULE -- this module
MANDATORY-GROUPS { upsBasicIdentGroup,
upsBasicBatteryGroup, upsBasicInputGroup,
upsBasicOutputGroup, upsBasicAlarmGroup,
upsBasicTestGroup, upsBasicControlGroup,
upsBasicConfigGroup }
OBJECT
upsAlarmDescr
DESCRIPTION
"Support of all well known alarm types is not
required. The well known alarm types which must be
supported are: upsAlarmOnBattery, upsAlarmLowBattery,
upsAlarmDepletedBattery, upsAlarmTempBad,
upsAlarmInputBad, upsAlarmOutputOverload,
upsAlarmOnBypass, upsAlarmBypassBad,
upsAlarmOutputOffAsRequested,
upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
upsAlarmUpsSystemOff, upsAlarmGeneralFault,
upsAlarmDiagnosticTestFailed,
upsAlarmCommunicationsLost, upsAlarmShutdownPending,
and upsAlarmTestInProgress."
OBJECT
upsTestId
DESCRIPTION
"Support of all well known test types is not
required. If no tests are supported, then the only
well known test type which must be supported is
upsTestNoTestsInitiated."
OBJECT
upsOutputSource
SYNTAX
INTEGER {
normal(2),
battery(4)
}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4),
booster(6) and reducer(7) is not required."
GROUP upsBasicBypassGroup
Case
[Page 32]
RFC 1628
UPS MIB
May 1994
DESCRIPTION
"The upsBasicBypassGroup is only required for UPSs
that have a Bypass present."
OBJECT
upsShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one shutdown type."
OBJECT
upsAutoRestart
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one restart type."
OBJECT
upsConfigInputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigInputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigOutputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigOutputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT
upsConfigLowBattTime
DESCRIPTION
"Implementation of all possible values may be onerous
for some systems. Consequently, not all possible
values must be supported. However, at least two
different manufacturer-selected values must be
supported."
::= { upsCompliances 2 }
upsFullCompliance MODULE-COMPLIANCE
STATUS
current
DESCRIPTION
Case
[Page 33]
RFC 1628
UPS MIB
May 1994
Case
[Page 34]
UPS MIB
RFC 1628
May 1994
Case
subset
x
x
basic
x
x
adv
x
x
[Page 35]
RFC 1628
UPS MIB
--upsIdentUPSSoftwareVersion
--upsIdentAgentSoftwareVersion
--upsIdentName
--upsIdentAttachedDevices
---upsBatteryStatus
--upsSecondsOnBattery
--upsEstimatedMinutesRemaining
--upsEstimatedChargeRemaining
--upsBatteryVoltage
--upsBatteryCurrent
--upsBatteryTemperature
---upsInputLineBads
--upsInputNumLines
--upsInputFrequency
--upsInputVoltage
--upsInputCurrent
--upsInputTruePower
---upsOutputSource
--upsOutputFrequency
--upsOutputNumLines
--upsOutputVoltage
--upsOutputCurrent
--upsOutputPower
--upsOutputPercentLoad
----upsBypassFrequency
--upsBypassNumLines
--upsBypassVoltage
--upsBypassCurrent
--upsBypassPower
----upsAlarmsPresent
--upsAlarmDescr
--upsAlarmTime
---upsTestId
--upsTestSpinLock
--upsTestResultsSummary
--upsTestResultsDetail
--upsTestStartTime
--upsTestElapsedTime
---upsShutdownType
Case
May 1994
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
notes
x
x
x
x
x
x
notes
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
notes
notes
x
x
x
x
x
x
notes
notes
[Page 36]
RFC 1628
UPS MIB
--upsShutdownAfterDelay
--upsStartupAfterDelay
--upsRebootWithDuration
--upsAutoRestart
---upsConfigInputVoltage
--upsConfigInputFreq
--upsConfigOutputVoltage
--upsConfigOutputFreq
--upsConfigOutputVA
--upsConfigOutputPower
--upsConfigLowBattTime
--upsConfigAudibleStatus
--upsConfigLowVoltageTransferPoint
--upsConfigHighVoltageTransferPoint
May 1994
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
notes
notes
notes
notes
notes
notes
-- units of conformance
upsGroups
OBJECT IDENTIFIER ::= { upsConformance 2 }
upsSubsetGroups
upsSubsetIdentGroup OBJECT-GROUP
OBJECTS { upsIdentManufacturer, upsIdentModel,
upsIdentAgentSoftwareVersion, upsIdentName,
upsIdentAttachedDevices }
STATUS current
DESCRIPTION
"The upsSubsetIdentGroup defines objects which are
common across all UPSs which meet subset compliance.
Most devices which conform to the upsSubsetIdentGroup
will provide access to these objects via a proxy
agent. If the proxy agent is compatible with multiple
UPS types, configuration of the proxy agent will
require specifying some of these values, either
individually, or as a group (perhaps through a table
lookup mechanism based on the UPS model number)."
::= { upsSubsetGroups 1 }
upsSubsetBatteryGroup OBJECT-GROUP
OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
STATUS current
DESCRIPTION
"The upsSubsetBatteryGroup defines the objects that
are common to battery groups of two-contact UPSs."
::= { upsSubsetGroups 2 }
upsSubsetInputGroup OBJECT-GROUP
Case
[Page 37]
RFC 1628
UPS MIB
May 1994
OBJECTS { upsInputLineBads }
STATUS current
DESCRIPTION
"The upsSubsetInputGroup defines the objects that are
common to the Input groups of two-contact UPSs."
::= { upsSubsetGroups 3 }
upsSubsetOutputGroup OBJECT-GROUP
OBJECTS { upsOutputSource }
STATUS current
DESCRIPTION
"The upsSubsetOutputGroup defines the objects that are
common to the Output groups of two-contact UPSs."
::= { upsSubsetGroups 4 }
Case
[Page 38]
RFC 1628
upsBasicGroups
UPS MIB
May 1994
upsBasicIdentGroup OBJECT-GROUP
OBJECTS { upsIdentManufacturer, upsIdentModel,
upsIdentUPSSoftwareVersion,
upsIdentAgentSoftwareVersion, upsIdentName }
STATUS current
DESCRIPTION
"The upsBasicIdentGroup defines objects which are
common to the Ident group of compliant UPSs which
support basic functions."
::= { upsBasicGroups 1 }
upsBasicBatteryGroup OBJECT-GROUP
OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
STATUS current
DESCRIPTION
"The upsBasicBatteryGroup defines the objects that are
common to the battery groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 2 }
upsBasicInputGroup OBJECT-GROUP
OBJECTS { upsInputLineBads, upsInputNumLines,
upsInputFrequency, upsInputVoltage }
STATUS current
DESCRIPTION
"The upsBasicInputGroup defines the objects that are
common to the Input groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 3 }
upsBasicOutputGroup OBJECT-GROUP
OBJECTS { upsOutputSource, upsOutputFrequency,
upsOutputNumLines, upsOutputVoltage }
STATUS current
DESCRIPTION
"The upsBasicOutputGroup defines the objects that are
common to the Output groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 4 }
upsBasicBypassGroup OBJECT-GROUP
OBJECTS { upsBypassFrequency, upsBypassNumLines,
upsBypassVoltage }
STATUS current
DESCRIPTION
"The upsBasicBypassGroup defines the objects that are
Case
[Page 39]
RFC 1628
UPS MIB
May 1994
Case
[Page 40]
RFC 1628
upsFullGroups
UPS MIB
May 1994
upsFullIdentGroup OBJECT-GROUP
OBJECTS { upsIdentManufacturer, upsIdentModel,
upsIdentUPSSoftwareVersion,
upsIdentAgentSoftwareVersion, upsIdentName,
upsIdentAttachedDevices }
STATUS current
DESCRIPTION
"The upsFullIdentGroup defines objects which are
common to the Ident group of fully compliant UPSs."
::= { upsFullGroups 1 }
upsFullBatteryGroup OBJECT-GROUP
OBJECTS { upsBatteryStatus, upsSecondsOnBattery,
upsEstimatedMinutesRemaining,
upsEstimatedChargeRemaining }
STATUS current
DESCRIPTION
"The upsFullBatteryGroup defines the objects that are
common to the battery groups of fully compliant UPSs."
::= { upsFullGroups 2 }
upsFullInputGroup OBJECT-GROUP
OBJECTS { upsInputLineBads, upsInputNumLines,
upsInputFrequency, upsInputVoltage }
STATUS current
DESCRIPTION
"The upsFullInputGroup defines the objects that are
common to the Input groups of fully compliant UPSs."
::= { upsFullGroups 3 }
upsFullOutputGroup OBJECT-GROUP
OBJECTS { upsOutputSource, upsOutputFrequency,
upsOutputNumLines, upsOutputVoltage,
upsOutputCurrent, upsOutputPower,
upsOutputPercentLoad }
STATUS current
DESCRIPTION
"The upsFullOutputGroup defines the objects that are
common to the Output groups of fully compliant UPSs."
::= { upsFullGroups 4 }
upsFullBypassGroup OBJECT-GROUP
OBJECTS { upsBypassFrequency, upsBypassNumLines,
upsBypassVoltage }
STATUS current
DESCRIPTION
Case
[Page 41]
RFC 1628
UPS MIB
May 1994
Case
[Page 42]
UPS MIB
RFC 1628
5.
May 1994
Acknowledgements
The UPS MIB represents the combined work of the IETF UPS MIB Working
Group, with particular, substantial authorship contributions from:
Mike Davison
Fibercom, Inc.
Ray Wasson
Consultant
Roger Draper
Liebert Corporation
Ken Key
SNMP Research, Incorporated
Pete Yoest
American Power Conversion
Doug Rademacher
American Power Conversion
Ron Pitt
Network Security Systems, Inc
Terry Zumwalt
International Power Machines
Lawren Markle
Tripp Lite
Bill Elliot
ONEAC
Tom Brennan
Exide Electronics
Brian Young
Best Power Technology
Case
[Page 43]
RFC 1628
6.
UPS MIB
May 1994
References
[1] Case, J., Fedor, M., Schoffstall, M., and J. Davin, "Simple
Network Management Protocol", STD 15, RFC 1157, SNMP Research,
Inc., Performance Systems International, Performance Systems
International, MIT Laboratory for Computer Science, May 1990.
[2] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Protocol
Operations for Version 2 of the Simple Network Management
Protocol (SNMPv2)", RFC 1448, SNMP Research, Inc., Hughes LAN
Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April 1993.
[3] McCloghrie, K., and M. Rose, Editors, "Management Information
Base for Network Management of TCP/IP-based internets: MIB-II",
STD 17, RFC 1213, Hughes LAN Systems, Performance Systems
International, March 1991.
[4] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Structure
of Management Information for Version 2 of the Simple Network
Management Protocol (SNMPv2)", RFC 1442, SNMP Research, Inc.,
Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April 1993.
[5] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser,
"Conformance Statements for Version 2 of the Simple Network
Management Protocol (SNMPv2)", RFC 1444, SNMP Research, Inc.,
Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April, 1993.
[6] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Textual
Conventions for Version 2 of the Simple Network Management
Protocol (SNMPv2)", RFC 1443, SNMP Research, Inc., Hughes LAN
Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April 1993.
Case
[Page 44]
UPS MIB
RFC 1628
7.
May 1994
Security Considerations
Security issues are not discussed in this memo.